Loading…
Loading…
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
Refer Docs
EMD Value
₹2,000
Closing Date
13 Oct 2026, 12:00 pm3d left
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Executive Engineer
Office of The Executive Engineer, ETD-II, Gorakhpur.
ATTENDING AND RECTIFICATION OF SF-6 GAS LEAKAGE FROM 145KV SF-6 CB OF ABB MAKE 40 MVA TF-II BAY CB AT 132KV SS BARAHALGANJ AND 40 MVA TF BAY CB AT 132KV SS KAURIRAM UNDER ETD-II GORAKHPUR.
2026_UPTCL_1189875_1
14-ETD-II(G)/2026-27
Open Tender
Electrical Works
Item Rate
90 days
132KV Barahalganj and 132KV Kauriram
Please refer Tender Documents.
2 documents required · 2 mandatory
₹590
AC No.-10887544323, IFSC-SBIN0001494
₹2,000
25 Sept 2026
25 Sept 2026
13 Oct 2026
25 Sept 2026
13 Oct 2026
25 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Detecting & Attending of SF-6 Gas leakage from 145 KV SF-6 CB of ABB make at: 132 KV 40 MVA T/F-II Bay CB at 132 KV S/S Barahalganj 132 KV 40 MVA T/F Bay CB at 132 KV S/S Kauriram. | |||||
| 1.01 | Inspection and rectification of gas leakage of 132 KV SF-6 Circuit Breaker (ABB make). The job includes opening of assembly from upper & lower terminal flanges, cleaning of all grooves of flanges and porcelains with petrol, scrubber pad and acrylic solution, replacement of all O-ring of the pole and gas pipe fitting by applying anabond adhesive. Reassembly of pipe then evacuation of pipe upto 760 mm.Ilg. After testing of vacuum for 12 hrs and satisfactory result, refilling of SF-6-gas upto required level. Checking of proper operation of circuit breaker from local and remote. This work also includes of timing CO Test after overhauling of CB. All material, T&P except SF-6 gas required for execution of work will be arranged by the contractor at his own cost. | 2 | Job | - | - |
| 1.02 | Replacement of main NRV with pipeline (if Required) work consist of dismantling of main NRV with pipeline and replace it with new-one and fitting at its original place in CB. SF-6 gas filling in all poles at desired level for satisfactorily completion of work. SPF-6 Gas will be provided by firm on its own cost. | 2 | Job | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.11 MB
BOQ_2242186.xls
BOQ • 0.23 MB
Technical14.pdf
Tender Documents • 0.79 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .