Tender Value
₹2.3 Cr
EMD Value
₹4.6 L
Closing Date
14 Aug 2026, 3:00 pm
Improvement of power supply distribution network in Central Gotanagar colony, replacement of overhead lines with underground cables.
DYCEE-PS-MLG-HQ-09-26-27
DYCEE-PS-MLG-HQ-09-26-27
Open
Works - General
180 Days
Kamrup Metro, Assam
₹0
₹4.6 L
23 Jul 2026
23 Jul 2026
31 Jul 2026
of overhead lines with underground cables.
Item- 1 Part A: Central Gotanagar North Side
S No. Item Description of Item Unit Qty Rate Amount
NFR HQ-ELECTRICAL/N F RLY
1 1 Design, supply , installation , testing and Set 2.00 374156.00 748312.00
commissioning of floor/ pedestal mounted outdoor
type double door LT Panel Board with canopy
confirming minimum IP-54 protection dust-vermin &
c o r r o s io n p r o o f , chemically treated chemically
treated , and Epoxy powder coated using Sheet
Steel of 2 mm having canopy at TOP & having 1 set
3 phase with neutral copper bus bar chamber
capacity 630 Amps comprising with the followings:-
A. 01 Nos. 630 Amps 4P on-load Change over switch
with proper connection to the panel., B. 02 Nos. 400
Amps , 4 pole, 36 KA microprocessor released based
MCCB suitable for mounting in the above LT panel
board, providing with necessary connection with
thepanel, C. 06 Nos. 200Amps 4P 36 KA
microprocessor released based MCCB suitable for
mounting in the above LT panel board, providing
with necessary connection with the panel, including
internal connection should be stranded copper strips
of suitable size from the bus bar to be provided as
per direction at site Engineer. The design of LV
Panel shall be verified for Internal Arc compliance of
minimum 80 kA for 0.5 sec as per IEC 61641. The LV
panel shall have provision for top/ bottom incoming
and bottom/ top outgoing respectively to suit site
conditions of cable entries (as per the site
requirements to be specified by the End User during
drawing approval) Minimum clearance between
phases /live parts shall be 25 mm and phases /live
parts/ neutral to ground shall be 19 mm except on
the equipment terminals. The busbars shall be
supported of regular intervals using SMC or DMC
insulators as per the tested design. It should have
minimum Comparative Tracking Index (CTI) of 600 V
as per IS 2824). The LV panel manufacturer
(Franchise) shall be ISO 9001/9002 certified. The
drawings of the LV Panels to be vetted with sign-
stamp by the Switchgear OEM. (Breaking capacity of
all MCCB's should be Ics=100% Icu with adjustable
magnetic settings.)
NFR HQ-ELECTRICAL/N F RLY
2 2 Design, supply , installation , testing and Set 4.00 195478.00 781912.00
commissioning of floor/ pedestal mounted outdoor
type double door LT Panel Board with canopy
confirming minimum IP-54 protection dust-vermin &
c o r r o s io n p r o o f , chemically treated chemically
treated , and Epoxy powder coated using Sheet
Steel of 2 mm having canopy at TOP & having 1 set
3 phase with neutral copper bus bar chamber
capacity 400 Amps comprising with the followings:-
A. 02 Nos. 200 Amps 4 pole, 36 KA microprocessor
released based MCCB suitable for mounting in the
above LT panel board, providing with necessary
connection with thepanel, B. 06 Nos. 125 Amps , 4
pole, 25 KA adjustable thermal and magnetic
released based MCCB suitable for mounting in the
above LT panel board, providing with necessary
connection with the panel, including internal
connection should be stranded copper strips of
suitable size from the bus bar to be provided as per
direction at site Engineer. The design of LV Panel
shall be verified for Internal Arc compliance of
minimum 80 kA for 0.5 sec as per IEC 61641. The LV
panel shall have provision for top/ bottom incoming
and bottom/ top outgoing respectively to suit site
conditions of cable entries (as per the site
requirements to be specified by the End User during
drawing approval) Minimum clearance between
phases /live parts shall be 25 mm and phases /live
parts/ neutral to ground shall be 19 mm except on
the equipment terminals. The busbars shall be
supported of regular intervals using SMC or DMC
insulators as per the tested design. It should have
minimum Comparative Tracking Index (CTI) of 600 V
as per IS 2824). The LV panel manufacturer
(Franchise) shall be ISO 9001/9002 certified. The
drawings of the LV Panels to be vetted with sign-
stamp by the Switchgear OEM. (Breaking capacity of
all MCCB's should be Ics=100% Icu with adjustable
magnetic settings.)
NFR HQ-ELECTRICAL/N F RLY
3 3 Design, supply , installation , testing and Set 7.00 167219.00 1170533.00
commissioning of floor/ pedestal mounted outdoor
type double door LT Panel Board with canopy
confirming minimum IP-54 protection dust-vermin &
c o r r o s io n p r o o f , chemically treated chemically
treated , and Epoxy powder coated using Sheet
Steel of 2 mm having canopy at TOP & having 1 set
3 phase with neutral copper bus bar chamber
capacity 250 Amps comprising with the followings:-
A. 02 Nos. 200 Amps 4 pole, 36 KA microprocessor
released based MCCB suitable for mounting in the
above LT panel board, providing with necessary
connection with the panel, B. 20 Nos. 63 Amps , 4
pole, B/C series 10kA MCB suitable for mounting in
the above LT panel board, providing with necessary
connection with the panel, including internal
connection should be stranded copper strips of
suitable size from the bus bar to be provided as per
direction at site Engineer. The design of LV Panel
shall be verified for Internal Arc compliance of
minimum 80 kA for 0.5 sec as per IEC 61641. The LV
panel shall have provision for top/ bottom incoming
and bottom/ top outgoing respectively to suit site
conditions of cable entries (as per the site
requirements to be specified by the End User during
drawing approval) Minimum clearance between
phases /live parts shall be 25 mm and phases /live
parts/ neutral to ground shall be 19 mm except on
the equipment terminals. The busbars shall be
supported of regular intervals using SMC or DMC
insulators as per the tested design. It should have
minimum Comparative Tracking Index (CTI) of 600 V
as per IS 2824). The LV panel manufacturer
(Franchise) shall be ISO 9001/9002 certified. The
drawings of the LV Panels to be vetted with sign-
stamp by the Switchgear OEM. (Breaking capacity of
all MCCB's should be Ics=100% Icu with adjustable
magnetic settings.)
4 4 Carrying, Laying, commissioning of various size Metre 6700.00 32.00 214400.00
Aluminium armoured LT cable partly along the pole
and partly through ground in cable trench with
suitable fixing arrangement. Loading, unloading &
carrying of cable to actual work site by contractor
own arrangement as per instruction of Engineer in-
charge at site. (Cable will be supplied by Railway)
5 5 Excavation for cable trenches in soft soil, depth upto Metre 600.00 622.00 373200.00
1.2 m including dressing of sides lift upto 1.5 m,
including getting out the excavated soil, refilling
with sand and or good soil after laying of cable/ pipe
etc in layers of 20 cm, ramming, watering and
disposal of surplus excavated soil as directed, within
a lead of 50 metres . As DSOR Item No. 14.4
6 6 Supply, installation, testing & commissioning of 40A Numbers 70.00 5055.00 353850.00
4P MCB, B/C SERIES with thermoplastic enclosure as
per direction of site engineer in-charge.
7 7 Supply, Carrying, laying, fitting, fixing & Metre 500.00 111.00 55500.00
commissioning of 63(OD) mm diameter Double wall
corrugated PN-6.0 Kgf/cm2 HDPE Pipe partly through
over ground , partly through underground with ISI
marked along with all accessories like socket, bend,
couplers etc. conforming to IS 14930, Part II
complete with fitting and cutting, jointing etc. as per
direction of site engineer in charge of Railway.
8 8 Supply, installation, testing, and commissioning of Set 6.00 47256.00 283536.00
an indoor busbar panel equipped with a 200A
busbar, comprising 4 nos of 40A, 4-pole, B/C-curve
MCBs, along with dedicated space and provisions for
the installation of 4 Nos of energy meters.
9 9 Dismantling of existing overhead LT lines with all Each 50.00 556.00 27800.00
accessories without damage from the work site and Span
handing over to concerned SSE office as per
instruction of site Engineer in-charge of railway.
NFR HQ-ELECTRICAL/N F RLY
10 10 Supply, erection of earthing set by 80 mm Dia GI Numbers 80.00 3323.00 265840.00
pipe 4 Mts. long including construction of earth pit
with cover and earth continuity by (25x3)mm GI
strip , GI nuts and bolts etc. as per direction at site
11 11 Supply & erection of GI tubular pole 9.5 Meter long Numbers 10.00 14139.00 141390.00
type410, SP -32 with suitable size step length,
section diameter and sectional thickness as per IS
2713 of 1980 including suitable size of base plate
and cap on top and digging of pit to 1/5th of the pole
height and supply and construction of CC foundation
in ratio 1:2:4 by cement, Sand and Ships of size 19
mm. The CC block will be 30 cm x 30 cm from
bottom of the pole up to 30cm above the GL.
12 12 Supply, fitting, fixing and testing of outdoor type 60 Numbers 60.00 3165.00 189900.00
watts LED street light fitting complete with LED
lamp, bend pipe and all other accessories including
connecting cable and provision of necessary hanging
arrangement etc. as per site requirement. Lumens
output should be greater than 100 Lumens/watt,
LED driver's efficiency should be minimum
90%,Power factor of complete fitting should be
greater than 0.90, Input operating voltage: 140V to
13 13 Excavation of horizontal boring manually for outside Metre 120.00 766.00 91920.00
of the Road/Railway track Embankment at a
minimum distance of 6 meters. From the
embankment GL and depth of 2.0 meters. Below
from G.L. with preparation of site for boring by
placing of pipes for electric cable protection through
contractor own arrangement as per direction of site
14 14 Supply, installation, and laying of G.I. pipe (medium Metre 50.00 2321.00 116050.00
class) of 150 mm (ID) with all necessary accessories
as per requirement at site.
15 15 Supply, installation, and laying of G.I. pipe (medium Metre 50.00 1488.00 74400.00
class) of 100 mm (ID) with all necessary accessories
as per requirement at site.
16 16 Supply, installation, and laying of G.I. pipe (medium Metre 70.00 635.00 44450.00
class) of 50 mm (ID) with all necessary accessories
as per requirement at site.
17 17 Supply, installation, testing and commissioning of Set 55.00 2979.00 163845.00
MS Junction box with 6 A MCB for street light pole
connection with all connecting accessories as per
requirement and direction of site engineer in-
NFR HQ-ELECTRICAL/N F RLY
18 18 Design, supply , installation , testing and Set 2.00 79941.00 159882.00
commissioning of floor/ pedestal mounted outdoor
type double door LT Panel Board with canopy
confirming minimum IP-54 protection dust-vermin &
c o r r o s io n p r o o f , chemically treated chemically
treated , and Epoxy powder coated using Sheet
Steel of 2 mm having canopy at TOP & having 1 set
3 phase with neutral copper bus bar chamber
capacity 250 Amps comprising with the followings:-
A. 02 Nos. 125 Amps 4 pole, thermal magnetic
based 25KA 4 pole MCCB,suitable for mounting in
the above LT panel board, providing with necessary
connection with the panel, B. 4 Nos 40 Amps , 2
pole, B/C series 10kA MCB suitable for mounting in
the above LT panel board, providing with necessary
connection with the panel, including internal
connection should be stranded copper strips of
suitable size from the bus bar to be provided as per
direction at site Engineer. The design of LV Panel
shall be verified for Internal Arc compliance of
minimum 80 kA for 0.5 sec as per IEC 61641. The LV
panel shall have provision for top/ bottom incoming
and bottom/ top outgoing respectively to suit site
conditions of cable entries (as per the site
requirements to be specified by the End User during
drawing approval) Minimum clearance between
phases /live parts shall be 25 mm and phases /live
parts/ neutral to ground shall be 19 mm except on
the equipment terminals. The busbars shall be
supported of regular intervals using SMC or DMC
insulators as per the tested design. It should have
minimum Comparative Tracking Index (CTI) of 600 V
as per IS 2824). The LV panel manufacturer
(Franchise) shall be ISO 9001/9002 certified. The
drawings of the LV Panels to be vetted with sign-
stamp by the Switchgear OEM. (Breaking capacity of
all MCCB's should be Ics=100% Icu with adjustable
magnetic settings.)
19 19 Supply and wiring of sub- main line concealed by RM 2000.00 180.00 360000.00
2x10 sq. mm. PVC insulated unsheathed and multi
stranded FRLS Copper Cable confirming to IS
694/1990 through suitable size of PVC conduit pipe
with 1sq. mm unsheathed copper cable as earth
continuity wire.
20 20 Supply, installation, testing and commissioning of a Numbers 46.00 242.00 11132.00
cable route marker consisting of a 10 cm x 10 cm x
5 mm thick galvanized iron (G.I.) plate with custom
inscription, securely bolted or welded to a 35 mm x
35 mm x 6 mm angle iron post (60 cm long),
including excavation and fixing the assembly firmly
in the ground as required.
Item- 2 Part B: Central Gotanagar South Side
S No. Item Description of Item Unit Qty Rate Amount
NFR HQ-ELECTRICAL/N F RLY
1 1 Design, supply , installation , testing and Set 2.00 374156.00 748312.00
commissioning of floor/ pedestal mounted outdoor
type double door LT Panel Board with canopy
confirming minimum IP-54 protection dust-vermin &
c o r r o s io n p r o o f , chemically treated chemically
treated , and Epoxy powder coated using Sheet
Steel of 2 mm having canopy at TOP & having 1 set
3 phase with neutral copper bus bar chamber
capacity 630 Amps comprising with the followings:-
A. 01 Nos. 630 Amps 4P on-load Change over switch
with proper connection to the panel., B. 02 Nos. 400
Amps , 4 pole, 36 KA microprocessor released based
MCCB suitable for mounting in the above LT panel
board, providing with necessary connection with
thepanel, C. 06 Nos. 200Amps 4P 36 KA
microprocessor released based MCCB suitable for
mounting in the above LT panel board, providing
with necessary connection with the panel, including
internal connection should be stranded copper strips
of suitable size from the bus bar to be provided as
per direction at site Engineer. The design of LV
Panel shall be verified for Internal Arc compliance of
minimum 80 kA for 0.5 sec as per IEC 61641. The LV
panel shall have provision for top/ bottom incoming
and bottom/ top outgoing respectively to suit site
conditions of cable entries (as per the site
requirements to be specified by the End User during
drawing approval) Minimum clearance between
phases /live parts shall be 25 mm and phases /live
parts/ neutral to ground shall be 19 mm except on
the equipment terminals. The busbars shall be
supported of regular intervals using SMC or DMC
insulators as per the tested design. It should have
minimum Comparative Tracking Index (CTI) of 600 V
as per IS 2824). The LV panel manufacturer
(Franchise) shall be ISO 9001/9002 certified. The
drawings of the LV Panels to be vetted with sign-
stamp by the Switchgear OEM. (Breaking capacity of
all MCCB's should be Ics=100% Icu with adjustable
magnetic settings.)
NFR HQ-ELECTRICAL/N F RLY
2 2 Design, supply , installation , testing and Set 3.00 195478.00 586434.00
commissioning of floor/ pedestal mounted outdoor
type double door LT Panel Board with canopy
confirming minimum IP-54 protection dust-vermin &
c o r r o s io n p r o o f , chemically treated chemically
treated , and Epoxy powder coated using Sheet
Steel of 2 mm having canopy at TOP & having 1 set
3 phase with neutral copper bus bar chamber
capacity 400 Amps comprising with the followings:-
A. 02 Nos. 200 Amps 4 pole, 36 KA microprocessor
released based MCCB suitable for mounting in the
above LT panel board, providing with necessary
connection with thepanel, B. 06 Nos. 125 Amps , 4
pole, 25 KA adjustable thermal and magnetic
released based MCCB suitable for mounting in the
above LT panel board, providing with necessary
connection with the panel, including internal
connection should be stranded copper strips of
suitable size from the bus bar to be provided as per
direction at site Engineer. The design of LV Panel
shall be verified for Internal Arc compliance of
minimum 80 kA for 0.5 sec as per IEC 61641. The LV
panel shall have provision for top/ bottom incoming
and bottom/ top outgoing respectively to suit site
conditions of cable entries (as per the site
requirements to be specified by the End User during
drawing approval) Minimum clearance between
phases /live parts shall be 25 mm and phases /live
parts/ neutral to ground shall be 19 mm except on
the equipment terminals. The busbars shall be
supported of regular intervals using SMC or DMC
insulators as per the tested design. It should have
minimum Comparative Tracking Index (CTI) of 600 V
as per IS 2824). The LV panel manufacturer
(Franchise) shall be ISO 9001/9002 certified. The
drawings of the LV Panels to be vetted with sign-
stamp by the Switchgear OEM. (Breaking capacity of
all MCCB's should be Ics=100% Icu with adjustable
magnetic settings.)
NFR HQ-ELECTRICAL/N F RLY
3 3 Design, supply , installation , testing and Set 7.00 167219.00 1170533.00
commissioning of floor/ pedestal mounted outdoor
type double door LT Panel Board with canopy
confirming minimum IP-54 protection dust-vermin &
c o r r o s io n p r o o f , chemically treated chemically
treated , and Epoxy powder coated using Sheet
Steel of 2 mm having canopy at TOP & having 1 set
3 phase with neutral copper bus bar chamber
capacity 250 Amps comprising with the followings:-
A. 02 Nos. 200 Amps 4 pole, 36 KA microprocessor
released based MCCB suitable for mounting in the
above LT panel board, providing with necessary
connection with the panel, B. 20 Nos. 63 Amps , 4
pole, B/C series 10kA MCB suitable for mounting in
the above LT panel board, providing with necessary
connection with the panel, including internal
connection should be stranded copper strips of
suitable size from the bus bar to be provided as per
direction at site Engineer. The design of LV Panel
shall be verified for Internal Arc compliance of
minimum 80 kA for 0.5 sec as per IEC 61641. The LV
panel shall have provision for top/ bottom incoming
and bottom/ top outgoing respectively to suit site
conditions of cable entries (as per the site
requirements to be specified by the End User during
drawing approval) Minimum clearance between
phases /live parts shall be 25 mm and phases /live
parts/ neutral to ground shall be 19 mm except on
the equipment terminals. The busbars shall be
supported of regular intervals using SMC or DMC
insulators as per the tested design. It should have
minimum Comparative Tracking Index (CTI) of 600 V
as per IS 2824). The LV panel manufacturer
(Franchise) shall be ISO 9001/9002 certified. The
drawings of the LV Panels to be vetted with sign-
stamp by the Switchgear OEM. (Breaking capacity of
all MCCB's should be Ics=100% Icu with adjustable
magnetic settings.)
4 4 Carrying, Laying, commissioning of various size Metre 6700.00 32.00 214400.00
Aluminium armoured LT cable partly along the pole
and partly through ground in cable trench with
suitable fixing arrangement. Loading, unloading &
carrying of cable to actual work site by contractor
own arrangement as per instruction of Engineer in-
charge at site. (Cable will be supplied by Railway)
5 5 Excavation for cable trenches in soft soil, depth upto Metre 600.00 622.00 373200.00
1.2 m including dressing of sides lift upto 1.5 m,
including getting out the excavated soil, refilling
with sand and or good soil after laying of cable/ pipe
etc in layers of 20 cm, ramming, watering and
disposal of surplus excavated soil as directed, within
a lead of 50 metres . As DSOR Item No. 14.4
6 6 Supply, installation, testing & commissioning of 40A Numbers 70.00 5055.00 353850.00
4P MCB, B/C SERIES with thermoplastic enclosure as
per direction of site engineer in-charge.
7 7 Supply, Carrying, laying, fitting, fixing & Metre 500.00 111.00 55500.00
commissioning of 63(OD) mm diameter Double wall
corrugated PN-6.0 Kgf/cm2 HDPE Pipe partly through
over ground , partly through underground with ISI
marked along with all accessories like socket, bend,
couplers etc. conforming to IS 14930, Part II
complete with fitting and cutting, jointing etc. as per
direction of site engineer in charge of Railway.
8 8 Supply, installation, testing, and commissioning of Set 4.00 47256.00 189024.00
an indoor busbar panel equipped with a 200A
busbar, comprising 4 nos of 40A, 4-pole, B/C-curve
MCBs, along with dedicated space and provisions for
the installation of 4 Nos of energy meters.
9 9 Dismantling of existing overhead LT lines with all Each 30.00 556.00 16680.00
accessories without damage from the work site and Span
handing over to concerned SSE office as per
instruction of site Engineer in-charge of railway.
NFR HQ-ELECTRICAL/N F RLY
10 10 Supply, erection of earthing set by 80 mm Dia GI Numbers 80.00 3323.00 265840.00
pipe 4 Mts. long including construction of earth pit
with cover and earth continuity by (25x3)mm GI
strip , GI nuts and bolts etc. as per direction at site
11 11 Supply & erection of GI tubular pole 9.5 Meter long Numbers 10.00 14139.00 141390.00
type410, SP -32 with suitable size step length,
section diameter and sectional thickness as per IS
2713 of 1980 including suitable size of base plate
and cap on top and digging of pit to 1/5th of the pole
height and supply and construction of CC foundation
in ratio 1:2:4 by cement, Sand and Ships of size 19
mm. The CC block will be 30 cm x 30 cm from
bottom of the pole up to 30cm above the GL.
12 12 Supply, fitting, fixing and testing of outdoor type 60 Numbers 60.00 3165.00 189900.00
watts LED street light fitting complete with LED
lamp, bend pipe and all other accessories including
connecting cable and provision of necessary hanging
arrangement etc. as per site requirement. Lumens
output should be greater than 100 Lumens/watt,
LED driver's efficiency should be minimum
90%,Power factor of complete fitting should be
greater than 0.90, Input operating voltage: 140V to
13 13 Excavation of horizontal boring manually for outside Metre 130.00 766.00 99580.00
of the Road/Railway track Embankment at a
minimum distance of 6 meters. From the
embankment GL and depth of 2.0 meters. Below
from G.L. with preparation of site for boring by
placing of pipes for electric cable protection through
contractor own arrangement as per direction of site
14 14 Supply, installation, and laying of G.I. pipe (medium Metre 60.00 2321.00 139260.00
class) of 150 mm (ID) with all necessary accessories
as per requirement at site.
15 15 Supply, installation, and laying of G.I. pipe (medium Metre 60.00 1488.00 89280.00
class) of 100 mm (ID) with all necessary accessories
as per requirement at site.
16 16 Supply, installation, and laying of G.I. pipe (medium Metre 80.00 635.00 50800.00
class) of 50 mm (ID) with all necessary accessories
as per requirement at site.
17 17 Supply, installation, testing and commissioning of Set 40.00 2979.00 119160.00
MS Junction box with 6 A MCB for street light pole
connection with all connecting accessories as per
requirement and direction of site engineer in-
NFR HQ-ELECTRICAL/N F RLY
18 18 Design, supply , installation , testing and Set 2.00 79941.00 159882.00
commissioning of floor/ pedestal mounted outdoor
type double door LT Panel Board with canopy
confirming minimum IP-54 protection dust-vermin &
c o r r o s io n p r o o f , chemically treated chemically
treated , and Epoxy powder coated using Sheet
Steel of 2 mm having canopy at TOP & having 1 set
3 phase with neutral copper bus bar chamber
capacity 250 Amps comprising with the followings:-
A. 02 Nos. 125 Amps 4 pole, thermal magnetic
based 25KA 4 pole MCCB,suitable for mounting in
the above LT panel board, providing with necessary
connection with the panel, B. 4 Nos 40 Amps , 2
pole, B/C series 10kA MCB suitable for mounting in
the above LT panel board, providing with necessary
connection with the panel, including internal
connection should be stranded copper strips of
suitable size from the bus bar to be provided as per
direction at site Engineer. The design of LV Panel
shall be verified for Internal Arc compliance of
minimum 80 kA for 0.5 sec as per IEC 61641. The LV
panel shall have provision for top/ bottom incoming
and bottom/ top outgoing respectively to suit site
conditions of cable entries (as per the site
requirements to be specified by the End User during
drawing approval) Minimum clearance between
phases /live parts shall be 25 mm and phases /live
parts/ neutral to ground shall be 19 mm except on
the equipment terminals. The busbars shall be
supported of regular intervals using SMC or DMC
insulators as per the tested design. It should have
minimum Comparative Tracking Index (CTI) of 600 V
as per IS 2824). The LV panel manufacturer
(Franchise) shall be ISO 9001/9002 certified. The
drawings of the LV Panels to be vetted with sign-
stamp by the Switchgear OEM. (Breaking capacity of
all MCCB's should be Ics=100% Icu with adjustable
magnetic settings.)
19 19 Supply and wiring of sub- main line concealed by RM 1950.00 180.00 351000.00
2x10 sq. mm. PVC insulated unsheathed and multi
stranded FRLS Copper Cable confirming to IS
694/1990 through suitable size of PVC conduit pipe
with 1sq. mm unsheathed copper cable as earth
continuity wire.
20 20 Supply, installation, testing and commissioning of a Numbers 40.00 242.00 9680.00
cable route marker consisting of a 10 cm x 10 cm x
5 mm thick galvanized iron (G.I.) plate with custom
inscription, securely bolted or welded to a 35 mm x
35 mm x 6 mm angle iron post (60 cm long),
including excavation and fixing the assembly firmly
in the ground as required.
Item- 3 Part C: Central Gotanagar East Side
S No. Item Description of Item Unit Qty Rate Amount
NFR HQ-ELECTRICAL/N F RLY
1 1 Design, supply , installation , testing and Set 1.00 1032413.00 1032413.00
commissioning of floor/ pedestal mounted outdoor
type double door LT Panel Board with canopy
confirming minimum IP-54 protection dust-vermin &
corrosion proof, chemically treated , colour of panel
shall be RAL 7035 structured finish , modular in
construction made of suitable size, using CRCA
Sheet Steel of 2mm thickness and are Epoxy powder
coating having 9 tank process having provision of
cable alley in both sides with 1 set 3 phase with
neutral (TPN) electrolytic grade 800A COPPER bus
bar and bus bar system shall have heat shrinkable
coloured PVC sleeve having 1. a) Supply & erection
of 1no. 4 pole microprocessor based manually
operated draw out (MDO) type 800A Air Circuit
Breaker with breaking capacity (Icu = Ics = Icw for 1
sec = 50KA) mechanical life = 20000 cycles,
Electrical life =20000 cycles, intrinsic degree of
protection of IP54 rating plug conforming to IS:
60947-II/IEC: 60947-II, operating voltage up to 690V,
Impulse withstand capacity =12KV. The ACB shall be
suitable for continuous operation at Ambient
Temperature of 50 degree Centigrade without any
duration. 4 pole ACBs should have 100% neutral
rating. The ACB should be fitted with proper wiring
in panel.ACB will have inbuilt - 2 NO+ 2 NC Aux.
contact, safety shutter assembly, racking handle,
door sealing frame, push-button cover & rating error
preventor. The ACB should conform the following
technical specification :- Rated current at 50°C:
1600 Ampere Type of Release: Microprocessor
based Rated operational voltage (V), 50/60Hz: 415
Volt Rated insulation voltage (V), 50/60Hz: 1000 Volt
Number of Poles: 4 Rated service short circuit
breaking capacity 50/60Hz (kA RMS): 50 KA Rated
impulse withstand voltage of main circuit (kV): 12
KV Typical opening time and closing time (ms): 40
ms and1 Typical opening time and closing time
(ms): 40 ms and 60 ms respectively. Electrical &
Mechanical life (operating cycles): 20000
Icu=Ics=Icw for 1 Second with Combined Test
Sequence Certification. Typical opening time and
closing time (ms): 40 ms and 60 ms respectively.
Electrical & Mechanical life (operating cycles): 20000
Icu=Ics=Icw for 1 Second with Combined Test
Sequence Certification. A) Supply, fitting, fixing,
testing & Commissioning of 01 No. 630A 4pole
microprocessor based 36 KA MCCB B)Supply, fitting,
fixing, testing & Commissioning of 12 Nos. 250Amp
4Pole 35ka Adjustable Thermal magnetic released
MCCB suitable for mounted in the above LT panel
board, connection of outgoing supply of copper bar
of suitable size from the bus bar as per instruction of
site Engineer. C)Supply, fitting, fixing, testing &
commissioning of 02 no Astronomical timer with 100
Amps 4 pole power contactor suitable for mounting
in the above LT panel board. Specification of Panel
as per Annexure-P(LV panel) of attached tender
document. (Breaking capacity of all MCCB's should
be Ics=100% Icu with adjustable magnetic settings
and MCCB's shall have a rated service voltage up to
690V and rated impulse withstand voltage shall not
be lesser than 8 KV)
NFR HQ-ELECTRICAL/N F RLY
2 2 Design, supply , installation , testing and Set 2.00 374156.00 748312.00
commissioning of floor/ pedestal mounted outdoor
type double door LT Panel Board with canopy
confirming minimum IP-54 protection dust-vermin &
c o r r o s io n p r o o f , chemically treated chemically
treated , and Epoxy powder coated using Sheet
Steel of 2 mm having canopy at TOP & having 1 set
3 phase with neutral copper bus bar chamber
capacity 630 Amps comprising with the followings:-
A. 01 Nos. 630 Amps 4P on-load Change over switch
with proper connection to the panel., B. 02 Nos. 400
Amps , 4 pole, 36 KA microprocessor released based
MCCB suitable for mounting in the above LT panel
board, providing with necessary connection with
thepanel, C. 06 Nos. 200Amps 4P 36 KA
microprocessor released based MCCB suitable for
mounting in the above LT panel board, providing
with necessary connection with the panel, including
internal connection should be stranded copper strips
of suitable size from the bus bar to be provided as
per direction at site Engineer. The design of LV
Panel shall be verified for Internal Arc compliance of
minimum 80 kA for 0.5 sec as per IEC 61641. The LV
panel shall have provision for top/ bottom incoming
and bottom/ top outgoing respectively to suit site
conditions of cable entries (as per the site
requirements to be specified by the End User during
drawing approval) Minimum clearance between
phases /live parts shall be 25 mm and phases /live
parts/ neutral to ground shall be 19 mm except on
the equipment terminals. The busbars shall be
supported of regular intervals using SMC or DMC
insulators as per the tested design. It should have
minimum Comparative Tracking Index (CTI) of 600 V
as per IS 2824). The LV panel manufacturer
(Franchise) shall be ISO 9001/9002 certified. The
drawings of the LV Panels to be vetted with sign-
stamp by the Switchgear OEM. (Breaking capacity of
all MCCB's should be Ics=100% Icu with adjustable
magnetic settings.)
NFR HQ-ELECTRICAL/N F RLY
3 3 Design, supply , installation , testing and Set 3.00 195478.00 586434.00
commissioning of floor/ pedestal mounted outdoor
type double door LT Panel Board as per IEC 61439 2
factory made totally enclosed weather and vermin
proof, suitable ventilated, 440 Volts, 50 HZ, AC
Supply, suitable for 3Phase/4P circuits , protection of
enclosure with pre-treatment and powder coating of
approved colour, with canopy confirming minimum
IP-54 protection , colour of panel shall be RAL 7035
structured finish , modular in construction made of
suitable size, using CRCA Sheet Steel of 2mm
thickness and are Epoxy powder coating having 9
tank process having provision of detachable cable
alleys units in both sides including suitable angle
iron/flat iron frame work supports with 1 set 3 phase
with neutral (TPN) electrolytic grade 400 A COPPER
bus bar and bus bar system shall have heat
shrinkable coloured PVC sleeve having RYB
indication lamp with digital Voltmeter with three row
display system VSS (AE/RISHAB), digital ammeter
with three row display system ASS (AE/RISHAB) CT
250/5A, CL-1.0, base plate, earthing studs, panel
locks, PCC work and making good disturbed surfaces
etc. necessary electrical connections with
new/existing cable complete all as specified and as
directed and comprising of the following
specifications:- A)Supply, fitting, fixing, testing &
Commissioning of 02 no. 200Amp, 4 pole, 36 KA
thermal magnetic based MCCB, suitable for
mounting in the above LT panel board, connection of
incoming supply of copper strips of suitable size
from the bus bar. B) Supply, fitting, fixing, testing &
Commissioning of 06 nos. 125A 4 pole, 25 KA
Adjustable Thermal magnetic releasedbased MCCB
suitable for mounting in the above LT panel board,
connection of incoming supply of copper strips of
suitable size from the bus bar. Specification of Panel
as per Annexure-P(LV panel) of attached tender
document. (Breaking capacity of all MCCB's should
be Ics=100% Icu with adjustable magnetic settings
and MCCB's shall have a rated service voltage up to
690V and rated impulse withstand voltage shall not
be lesser than 8 KV)
NFR HQ-ELECTRICAL/N F RLY
4 4 Design, supply , installation , testing and Set 7.00 167219.00 1170533.00
commissioning of floor/ pedestal mounted outdoor
type double door LT Panel Board with canopy
confirming minimum IP-54 protection dust-vermin &
c o r r o s io n p r o o f , chemically treated chemically
treated , and Epoxy powder coated using Sheet
Steel of 2 mm having canopy at TOP & having 1 set
3 phase with neutral copper bus bar chamber
capacity 250 Amps comprising with the followings:-
A. 02 Nos. 200 Amps 4 pole, 36 KA microprocessor
released based MCCB suitable for mounting in the
above LT panel board, providing with necessary
connection with the panel, B. 20 Nos. 63 Amps , 4
pole, B/C series 10kA MCB suitable for mounting in
the above LT panel board, providing with necessary
connection with the panel, including internal
connection should be stranded copper strips of
suitable size from the bus bar to be provided as per
direction at site Engineer. The design of LV Panel
shall be verified for Internal Arc compliance of
minimum 80 kA for 0.5 sec as per IEC 61641. The LV
panel shall have provision for top/ bottom incoming
and bottom/ top outgoing respectively to suit site
conditions of cable entries (as per the site
requirements to be specified by the End User during
drawing approval) Minimum clearance between
phases /live parts shall be 25 mm and phases /live
parts/ neutral to ground shall be 19 mm except on
the equipment terminals. The busbars shall be
supported of regular intervals using SMC or DMC
insulators as per the tested design. It should have
minimum Comparative Tracking Index (CTI) of 600 V
as per IS 2824). The LV panel manufacturer
(Franchise) shall be ISO 9001/9002 certified. The
drawings of the LV Panels to be vetted with sign-
stamp by the Switchgear OEM. (Breaking capacity of
all MCCB's should be Ics=100% Icu with adjustable
magnetic settings.)
5 5 Carrying, Laying, commissioning of various size Metre 4200.00 32.00 134400.00
Aluminium armoured LT cable partly along the pole
and partly through ground in cable trench with
suitable fixing arrangement. Loading, unloading &
carrying of cable to actual work site by contractor
own arrangement as per instruction of Engineer in-
charge at site. (Cable will be supplied by Railway)
6 6 Excavation for cable trenches in soft soil, depth upto Metre 600.00 622.00 373200.00
1.2 m including dressing of sides lift upto 1.5 m,
including getting out the excavated soil, refilling
with sand and or good soil after laying of cable/ pipe
etc in layers of 20 cm, ramming, watering and
disposal of surplus excavated soil as directed, within
a lead of 50 metres . As DSOR Item No. 14.4
7 7 Supply, installation, testing & commissioning of 40A Numbers 70.00 5055.00 353850.00
4P MCB, B/C SERIES with thermoplastic enclosure as
per direction of site engineer in-charge.
8 8 Supply, Carrying, laying, fitting, fixing & Metre 500.00 111.00 55500.00
commissioning of 63(OD) mm diameter Double wall
corrugated PN-6.0 Kgf/cm2 HDPE Pipe partly through
over ground , partly through underground with ISI
marked along with all accessories like socket, bend,
couplers etc. conforming to IS 14930, Part II
complete with fitting and cutting, jointing etc. as per
direction of site engineer in charge of Railway.
9 9 Supply, installation, testing, and commissioning of Set 7.00 47256.00 330792.00
an indoor busbar panel equipped with a 200A
busbar, comprising 4 nos of 40A, 4-pole, B/C-curve
MCBs, along with dedicated space and provisions for
the installation of 4 Nos of energy meters.
10 10 Dismantling of existing overhead LT lines with all Each 40.00 556.00 22240.00
accessories without damage from the work site and Span
handing over to concerned SSE office as per
instruction of site Engineer in-charge of railway.
NFR HQ-ELECTRICAL/N F RLY
11 11 Supply, erection of earthing set by 80 mm Dia GI Numbers 80.00 3323.00 265840.00
pipe 4 Mts. long including construction of earth pit
with cover and earth continuity by (25x3)mm GI
strip , GI nuts and bolts etc. as per direction at site
12 12 Supply & erection of GI tubular pole 9.5 Meter long Numbers 10.00 14139.00 141390.00
type410, SP -32 with suitable size step length,
section diameter and sectional thickness as per IS
2713 of 1980 including suitable size of base plate
and cap on top and digging of pit to 1/5th of the pole
height and supply and construction of CC foundation
in ratio 1:2:4 by cement, Sand and Ships of size 19
mm. The CC block will be 30 cm x 30 cm from
bottom of the pole up to 30cm above the GL.
13 13 Supply, fitting, fixing and testing of outdoor type 60 Numbers 60.00 3165.00 189900.00
watts LED street light fitting complete with LED
lamp, bend pipe and all other accessories including
connecting cable and provision of necessary hanging
arrangement etc. as per site requirement. Lumens
output should be greater than 100 Lumens/watt,
LED driver's efficiency should be minimum
90%,Power factor of complete fitting should be
greater than 0.90, Input operating voltage: 140V to
14 14 Excavation of horizontal boring manually for outside Metre 120.00 766.00 91920.00
of the Road/Railway track Embankment at a
minimum distance of 6 meters. From the
embankment GL and depth of 2.0 meters. Below
from G.L. with preparation of site for boring by
placing of pipes for electric cable protection through
contractor own arrangement as per direction of site
15 15 Supply, installation, and laying of G.I. pipe (medium Metre 40.00 2321.00 92840.00
class) of 150 mm (ID) with all necessary accessories
as per requirement at site.
16 16 Supply, installation, and laying of G.I. pipe (medium Metre 40.00 1488.00 59520.00
class) of 100 mm (ID) with all necessary accessories
as per requirement at site.
17 17 Supply, installation, and laying of G.I. pipe (medium Metre 65.00 635.00 41275.00
class) of 50 mm (ID) with all necessary accessories
as per requirement at site.
18 18 Supply, installation, testing and commissioning of Set 50.00 2979.00 148950.00
MS Junction box with 6 A MCB for street light pole
connection with all connecting accessories as per
requirement and direction of site engineer in-
NFR HQ-ELECTRICAL/N F RLY
19 19 Design, supply , installation , testing and Set 2.00 79941.00 159882.00
commissioning of floor/ pedestal mounted outdoor
type double door LT Panel Board with canopy
confirming minimum IP-54 protection dust-vermin &
c o r r o s io n p r o o f , chemically treated chemically
treated , and Epoxy powder coated using Sheet
Steel of 2 mm having canopy at TOP & having 1 set
3 phase with neutral copper bus bar chamber
capacity 250 Amps comprising with the followings:-
A. 02 Nos. 125 Amps 4 pole, thermal magnetic
based 25KA 4 pole MCCB,suitable for mounting in
the above LT panel board, providing with necessary
connection with the panel, B. 4 Nos 40 Amps , 2
pole, B/C series 10kA MCB suitable for mounting in
the above LT panel board, providing with necessary
connection with the panel, including internal
connection should be stranded copper strips of
suitable size from the bus bar to be provided as per
direction at site Engineer. The design of LV Panel
shall be verified for Internal Arc compliance of
minimum 80 kA for 0.5 sec as per IEC 61641. The LV
panel shall have provision for top/ bottom incoming
and bottom/ top outgoing respectively to suit site
conditions of cable entries (as per the site
requirements to be specified by the End User during
drawing approval) Minimum clearance between
phases /live parts shall be 25 mm and phases /live
parts/ neutral to ground shall be 19 mm except on
the equipment terminals. The busbars shall be
supported of regular intervals using SMC or DMC
insulators as per the tested design. It should have
minimum Comparative Tracking Index (CTI) of 600 V
as per IS 2824). The LV panel manufacturer
(Franchise) shall be ISO 9001/9002 certified. The
drawings of the LV Panels to be vetted with sign-
stamp by the Switchgear OEM. (Breaking capacity of
all MCCB's should be Ics=100% Icu with adjustable
magnetic settings.)
20 20 Supply and wiring of sub- main line concealed by RM 1850.00 180.00 333000.00
2x10 sq. mm. PVC insulated unsheathed and multi
stranded FRLS Copper Cable confirming to IS
694/1990 through suitable size of PVC conduit pipe
with 1sq. mm unsheathed copper cable as earth
continuity wire.
21 21 Supply, installation, testing and commissioning of a Numbers 38.00 242.00 9196.00
cable route marker consisting of a 10 cm x 10 cm x
5 mm thick galvanized iron (G.I.) plate with custom
inscription, securely bolted or welded to a 35 mm x
35 mm x 6 mm angle iron post (60 cm long),
including excavation and fixing the assembly firmly
in the ground as required.
Item- 4 Part D: Central Gotanagar West Side
S No. Item Description of Item Unit Qty Rate Amount
NFR HQ-ELECTRICAL/N F RLY
1 1 Design, supply , installation , testing and Set 3.00 374156.00 1122468.00
commissioning of floor/ pedestal mounted outdoor
type double door LT Panel Board with canopy
confirming minimum IP-54 protection dust-vermin &
c o r r o s io n p r o o f , chemically treated chemically
treated , and Epoxy powder coated using Sheet
Steel of 2 mm having canopy at TOP & having 1 set
3 phase with neutral copper bus bar chamber
capacity 630 Amps comprising with the followings:-
A. 01 Nos. 630 Amps 4P on-load Change over switch
with proper connection to the panel., B. 02 Nos. 400
Amps , 4 pole, 36 KA microprocessor released based
MCCB suitable for mounting in the above LT panel
board, providing with necessary connection with
thepanel, C. 06 Nos. 200Amps 4P 36 KA
microprocessor released based MCCB suitable for
mounting in the above LT panel board, providing
with necessary connection with the panel, including
internal connection should be stranded copper strips
of suitable size from the bus bar to be provided as
per direction at site Engineer. The design of LV
Panel shall be verified for Internal Arc compliance of
minimum 80 kA for 0.5 sec as per IEC 61641. The LV
panel shall have provision for top/ bottom incoming
and bottom/ top outgoing respectively to suit site
conditions of cable entries (as per the site
requirements to be specified by the End User during
drawing approval) Minimum clearance between
phases /live parts shall be 25 mm and phases /live
parts/ neutral to ground shall be 19 mm except on
the equipment terminals. The busbars shall be
supported of regular intervals using SMC or DMC
insulators as per the tested design. It should have
minimum Comparative Tracking Index (CTI) of 600 V
as per IS 2824). The LV panel manufacturer
(Franchise) shall be ISO 9001/9002 certified. The
drawings of the LV Panels to be vetted with sign-
stamp by the Switchgear OEM. (Breaking capacity of
all MCCB's should be Ics=100% Icu with adjustable
magnetic settings.)
NFR HQ-ELECTRICAL/N F RLY
2 2 Design, supply , installation , testing and Set 5.00 195478.00 977390.00
commissioning of floor/ pedestal mounted outdoor
type double door LT Panel Board as per IEC 61439 2
factory made totally enclosed weather and vermin
proof, suitable ventilated, 440 Volts, 50 HZ, AC
Supply, suitable for 3Phase/4P circuits , protection of
enclosure with pre-treatment and powder coating of
approved colour, with canopy confirming minimum
IP-54 protection , colour of panel shall be RAL 7035
structured finish , modular in construction made of
suitable size, using CRCA Sheet Steel of 2mm
thickness and are Epoxy powder coating having 9
tank process having provision of detachable cable
alleys units in both sides including suitable angle
iron/flat iron frame work supports with 1 set 3 phase
with neutral (TPN) electrolytic grade 400 A COPPER
bus bar and bus bar system shall have heat
shrinkable coloured PVC sleeve having RYB
indication lamp with digital Voltmeter with three row
display system VSS (AE/RISHAB), digital ammeter
with three row display system ASS (AE/RISHAB) CT
250/5A, CL-1.0, base plate, earthing studs, panel
locks, PCC work and making good disturbed surfaces
etc. necessary electrical connections with
new/existing cable complete all as specified and as
directed and comprising of the following
specifications:- A)Supply, fitting, fixing, testing &
Commissioning of 02 no. 200Amp, 4 pole, 36 KA
thermal magnetic based MCCB, suitable for
mounting in the above LT panel board, connection of
incoming supply of copper strips of suitable size
from the bus bar. B) Supply, fitting, fixing, testing &
Commissioning of 06 nos. 125A 4 pole, 25 KA
Adjustable Thermal magnetic releasedbased MCCB
suitable for mounting in the above LT panel board,
connection of incoming supply of copper strips of
suitable size from the bus bar. Specification of Panel
as per Annexure-P(LV panel) of attached tender
document. (Breaking capacity of all MCCB's should
be Ics=100% Icu with adjustable magnetic settings
and MCCB's shall have a rated service voltage up to
690V and rated impulse withstand voltage shall not
be lesser than 8 KV)
NFR HQ-ELECTRICAL/N F RLY
3 3 Design, supply , installation , testing and Set 7.00 167219.00 1170533.00
commissioning of floor/ pedestal mounted outdoor
type double door LT Panel Board as per IEC 61439 2
factory made totally enclosed weather and vermin
proof, suitable ventilated, 440 Volts, 50 HZ, AC
Supply, suitable for 3Phase/4P circuits , protection of
enclosure with pre-treatment and powder coating of
approved colour, with canopy confirming minimum
IP-54 protection , colour of panel shall be RAL 7035
structured finish , modular in construction made of
suitable size, using CRCA Sheet Steel of 2mm
thickness and are Epoxy powder coating having 9
tank process having provision of detachable cable
alleys units in both sides including suitable angle
iron/flat iron frame work supports with 1 set 3 phase
with neutral (TPN) electrolytic grade 400 A COPPER
bus bar and bus bar system shall have heat
shrinkable coloured PVC sleeve having RYB
indication lamp with digital Voltmeter with three row
display system VSS (AE/RISHAB), digital ammeter
with three row display system ASS (AE/RISHAB) CT
250/5A, CL-1.0, base plate, earthing studs, panel
locks, PCC work and making good disturbed surfaces
etc. necessary electrical connections with
new/existing cable complete all as specified and as
directed and comprising of the following
specifications:- A)Supply, fitting, fixing, testing &
Commissioning of 02 no. 200Amp, 4 pole, 36 KA
thermal magnetic based MCCB, suitable for
mounting in the above LT panel board, connection of
incoming supply of copper strips of suitable size
from the bus bar. B) Supply, fitting, fixing, testing &
Commissioning of 20 nos. 63A 4 pole, 16 KA B/C
series MCB suitable for mounting in the above LT
panel board, connection of incoming supply of
copper strips of suitable size from the bus bar.
Specification of Panel as per Annexure-P(LV panel)
of attached tender document. (Breaking capacity of
all MCCB's should be Ics=100% Icu with adjustable
magnetic settings and MCCB's shall have a rated
service voltage up to 690V and rated impulse
withstand voltage shall not be lesser than 8 KV)
4 4 Carrying, Laying, commissioning of various size Metre 3500.00 32.00 112000.00
Aluminium armoured LT cable partly along the pole
and partly through ground in cable trench with
suitable fixing arrangement. Loading, unloading &
carrying of cable to actual work site by contractor
own arrangement as per instruction of Engineer in-
charge at site. (Cable will be supplied by Railway)
5 5 Excavation for cable trenches in soft soil, depth upto Metre 600.00 622.00 373200.00
1.2 m including dressing of sides lift upto 1.5 m,
including getting out the excavated soil, refilling
with sand and or good soil after laying of cable/ pipe
etc in layers of 20 cm, ramming, watering and
disposal of surplus excavated soil as directed, within
a lead of 50 metres . As DSOR Item No. 14.4
6 6 Supply, installation, testing & commissioning of 40A Numbers 70.00 5055.00 353850.00
4P MCB, B/C SERIES with thermoplastic enclosure as
per direction of site engineer in-charge.
7 7 Supply, Carrying, laying, fitting, fixing & Metre 500.00 111.00 55500.00
commissioning of 63(OD) mm diameter Double wall
corrugated PN-6.0 Kgf/cm2 HDPE Pipe partly through
over ground , partly through underground with ISI
marked along with all accessories like socket, bend,
couplers etc. conforming to IS 14930, Part II
complete with fitting and cutting, jointing etc. as per
direction of site engineer in charge of Railway.
8 8 Supply, installation, testing, and commissioning of Set 4.00 47256.00 189024.00
an indoor busbar panel equipped with a 200A
busbar, comprising 4 nos of 40A, 4-pole, B/C-curve
MCBs, along with dedicated space and provisions for
the installation of 4 Nos of energy meters.
NFR HQ-ELECTRICAL/N F RLY
9 9 Dismantling of existing overhead LT lines with all Each 40.00 556.00 22240.00
accessories without damage from the work site and Span
handing over to concerned SSE office as per
instruction of site Engineer in-charge of railway.
10 10 Supply, erection of earthing set by 80 mm Dia GI Numbers 80.00 3323.00 265840.00
pipe 4 Mts. long including construction of earth pit
with cover and earth continuity by (25x3)mm GI
strip, GI nuts and bolts etc. as per direction at site
11 11 Supply & erection of GI tubular pole 9.5 Meter long Numbers 10.00 14139.00 141390.00
type410, SP -32 with suitable size step length,
section diameter and sectional thickness as per IS
2713 of 1980 including suitable size of base plate
and cap on top and digging of pit to 1/5th of the pole
height and supply and construction of CC foundation
in ratio 1:2:4 by cement, Sand and Ships of size 19
mm. The CC block will be 30 cm x 30 cm from
bottom of the pole up to 30cm above the GL.
12 12 Supply, fitting, fixing and testing of outdoor type 60 Numbers 40.00 3165.00 126600.00
watts LED street light fitting complete with LED
lamp, bend pipe and all other accessories including
connecting cable and provision of necessary hanging
arrangement etc. as per site requirement. Lumens
output should be greater than 100 Lumens/watt,
LED driver's efficiency should be minimum
90%,Power factor of complete fitting should be
greater than 0.90, Input operating voltage: 140V to
13 13 Excavation of horizontal boring manually for outside Metre 100.00 766.00 76600.00
of the Road/Railway track Embankment at a
minimum distance of 6 meters. From the
embankment GL and depth of 2.0 meters. Below
from G.L. with preparation of site for boring by
placing of pipes for electric cable protection through
contractor own arrangement as per direction of site
14 14 Supply, installation, and laying of G.I. pipe (medium Metre 50.00 2359.00 117950.00
class) of 150 mm (ID) with all necessary accessories
as per requirement at site.
15 15 Supply, installation, and laying of G.I. pipe (medium Metre 50.00 1512.00 75600.00
class) of 100 mm (ID) with all necessary accessories
as per requirement at site.
16 16 Supply, installation, and laying of G.I. pipe (medium Metre 85.00 646.00 54910.00
class) of 50 mm (ID) with all necessary accessories
as per requirement at site.
17 17 Supply, installation, testing and commissioning of Set 45.00 2979.00 134055.00
MS Junction box with 6 A MCB for street light pole
connection with all connecting accessories as per
requirement and direction of site engineer in-
NFR HQ-ELECTRICAL/N F RLY
18 18 Design, supply , installation , testing and Set 2.00 79941.00 159882.00
commissioning of floor/ pedestal mounted outdoor
type double door LT Panel Board with canopy
confirming minimum IP-54 protection dust-vermin &
c o r r o s io n p r o o f , chemically treated chemically
treated , and Epoxy powder coated using Sheet
Steel of 2 mm having canopy at TOP & having 1 set
3 phase with neutral copper bus bar chamber
capacity 250 Amps comprising with the followings:-
A. 02 Nos. 125 Amps 4 pole, thermal magnetic
based 25KA 4 pole MCCB,suitable for mounting in
the above LT panel board, providing with necessary
connection with the panel, B. 4 Nos 40 Amps , 2
pole, B/C series 10kA MCB suitable for mounting in
the above LT panel board, providing with necessary
connection with the panel, including internal
connection should be stranded copper strips of
suitable size from the bus bar to be provided as per
direction at site Engineer. The design of LV Panel
shall be verified for Internal Arc compliance of
minimum 80 kA for 0.5 sec as per IEC 61641. The LV
panel shall have provision for top/ bottom incoming
and bottom/ top outgoing respectively to suit site
conditions of cable entries (as per the site
requirements to be specified by the End User during
drawing approval) Minimum clearance between
phases /live parts shall be 25 mm and phases /live
parts/ neutral to ground shall be 19 mm except on
the equipment terminals. The busbars shall be
supported of regular intervals using SMC or DMC
insulators as per the tested design. It should have
minimum Comparative Tracking Index (CTI) of 600 V
as per IS 2824). The LV panel manufacturer
(Franchise) shall be ISO 9001/9002 certified. The
drawings of the LV Panels to be vetted with sign-
stamp by the Switchgear OEM. (Breaking capacity of
all MCCB's should be Ics=100% Icu with adjustable
magnetic settings.)
19 19 Supply and wiring of sub- main line concealed by RM 1580.00 180.00 284400.00
2x10 sq. mm. PVC insulated unsheathed and multi
stranded FRLS Copper Cable confirming to IS
694/1990 through suitable size of PVC conduit pipe
with 1sq. mm unsheathed copper cable as earth
continuity wire.
20 20 Supply, installation, testing and commissioning of a Numbers 32.00 242.00 7744.00
cable route marker consisting of a 10 cm x 10 cm x
5 mm thick galvanized iron (G.I.) plate with custom
inscription, securely bolted or welded to a 35 mm x
35 mm x 6 mm angle iron post (60 cm long),
including excavation and fixing the assembly firmly
in the ground as required.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
GCC-2022.pdf
ATTACHMENT
MicrosoftWord-ANNEXURES_August23to4thcorrectionslip.pdf
ATTACHMENT
correctionslip1to11compressed.pdf
ATTACHMENT
letterofcredit.pdf
ATTACHMENT
Tender doc
ATTACHMENT
09-documentofImprovementofpowersupplydistrutionnetworkinCentralGotanagarcolony_1.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].