Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹19.7 LAdmitted-Finance | -26.99% | ₹19.7 L | L1 | Admitted-Finance |
| 2 | L2₹23.8 L+₹4.0 L (20.5%)Admitted-Finance | -12.00% | ₹23.8 L+₹4.0 L (20.5%) | L2 | Admitted-Finance |
| 3 | L3₹24.0 L+₹4.3 L (21.6%)Admitted-Finance | -11.21% | ₹24.0 L+₹4.3 L (21.6%) | L3 | Admitted-Finance |
Tender Value
₹27.0 L
EMD Value
₹54,021
Closing Date
25 Jun 2026, 3:00 pmClosed
EE,ELD-9,DDA
EE,ELD-9,DDA
Providing, installation, testing and commissioning of semi-high mast poles and gate lights alongwith maintenance at water bodies of Nithari, Kirari and Madanpur Dabas in Rohini.
2026_DDA_912429_1
11/EE/ELD-9/DDA/NIT/ 2026-27
Open Tender
Electrical Works
Works
365 days
Rohini
Please refer Tender documents.
13 documents required · 13 mandatory
₹0
₹54,021
9 Jul 2026
10 Jun 2026
26 Jun 2026
10 Jun 2026
25 Jun 2026
10 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supplying, installation, testing and commissioning of hot dip galvanized octagonal steel pole of 9 Mtr. height and made of 3 mm thick sheet, having bottom 155 mm OAF & top 70 mm OAF, hot dip galvanized M.S base plate of size 260 mm x 260 mm x 16 mm thick, on existing RCC foundation with GI bolt and nuts, making connections, interconnections with suitable size of copper wire with thimble/lugs in the connector box, earthing, marking/ numbering of pole etc. complete as per drawing & technical specifications attached including following accessories with mounted inbuilt control box having flush cover with 2 nos mounting strips with tapped holes:-
(a) 6 mm thick phenolic laminated / bakelite sheet inside the window mounted on the existing mounting strips inside the flush door.
(b) 4 nos. 40 Amp terminal block suitable for following conductor / cable, fixed on DIN channels i/c providing and fixing DIN channel of suitable length – on the existing phenolic laminated / bakelite sheet.
(i) 16 sq mm conductor – 4 nos and short links 5-nos.
(ii)Terminal suitable for 6 SWG GI wire / 1.5 sq mm wire.
(c) 6 Amp SP MCB,10 kA ‘C’ Series-1 nos. including mountings on DIN channel, Earth stud 2 Nos. welded at suitable height i/c washers, springs washers & nuts etc.
(d) Suitable arrangement for saddling of incoming / outgoing cables i/c lugs thimbles etc as required. | - | Each | 18,785 | - |
| 2 | Providing and laying in position, M25 reinforced cement concrete foundation of size 500mm long x 500mm wide and 1400 mm deep i/c excavation of earth, refilling, providing cutting, bending and placing in position reinforcement of cold twisted bar of 12 mm dia. 1500 mm long (approx.)-8 Nos. and reinforcement ring of cold twisted bar of 8 mm dia. 2000 mm long (approx.)-8 Nos. (With approx. 150 mm spacing) i/c centering & shuttering as required, positioning of foundation bolts 4 nos. M-24x750mm long foundation bolt of L Type (100 mm bend & 750 mm straight), 150 mm top threaded portion of bolt shall be galvanized and rest portion shall be coated with Red oxide to avoid corrosion & G.I nuts (EN 8-grade) with 3 Nos. and 2 Nos. washer, along with 2 Nos. templates/Anchor plate of size 260 mm x 260 mm x 3 mm thick shall be supplied manufactured from the original pole manufacturing company only for casting of foundations and providing 63 mm (OD) 2 Nos. DWC pipe 1 mtr long approx. each for cable entry and exit etc complete as required. | - | Each | 10,304 | - |
| 3 | Supplying and installation of hot dip galvanized circular ring having inner diameter 1000 mm made out of 48 mm dia MS pipe B-class and having 4 nos. arms of length approximate 400mm long each made out of 40mm dia MS pipe B- class i/c mounting arrangement at the top of the pole i/c marking holes for installation of flood light luminaries and wire entries with movable cap at the top with fixing arrangement. Complete as required. | - | Each | 7,293 | - |
| 4 | 100 W LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥120 and <135 lm/Watt) Supplying, installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -5 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection,EMI-EMC as per CISPR-15,lenses for beam angle 30 deg-120deg as per the application and the project requirementdeg, suitable tilt able fitting, life time (LED,Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K /4000°K / 5700°K /6500°K (As per ANSI Bin),SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). | - | Each | 2,467 | - |
| 5 | Rate as per quotation of M/s RISHA Dated 07.08.2025
Supplying, installation, testing and commissioning of floor mounted feeder panel duly compartmentalized (outdoor type) double door cubicle panel board of Suitable size made out of 2mm thick CRCA MS sheet having hinged gasketed cover and screw type knob with double locking arrangement and rain protection cover mounted on MS angle iron base frame made out of 40 mm X 40 mm X 5 mm angle iron with 1 mtr. Long leg grouted with 1:3:6 foundation and should be as per drawing approved by Engineer-In-Charge. Legs should be covered with brick wall, connection, interconnection with painting after applying a coat of primer, i/c connection inter connection of the accessories mounted there on with suitable size of copper wire with thimble/lugs, earthing the body of the feeder panel i/c supplying & fixing of the following items :
INCOMER
a) 63A 4 pole 25 kA MCCB - 1 No
b) Ammeter with selector switch (0-25 A) - 1 No
c) Voltmeter with selector switch (0-500 V) - 1 No
d) Indication Lamp (RYB) with control HRC fuse with fuse fitting- 1 set.
BUS BAR
100 A TPN Al. Bus Bar (suitable size) - 1 Set
OUTGOING
a) 16 A TP&N 10 kA MCB - 4 Nos.
b) Power contactor - 1 No.
c) Astronomical Timer switch – 1 No.
d) Auto/Manual toggle switch – 1 No.
e) Compartment having space for DISCOM energy meter with 6mm thick Bakelite sheet for mounting energy meter.
f) Danger Notice plate – 1 No.
g) Lightning inside the feeder pillar
Note: Foundation dully plastered and finished shall be made as per site requirement for which nothing extra shall be paid. | - | Set | 78,740 | - |
| 6 | Supplying fabrication and installation of wire mesh protection cover guard for main feeder pillar made out of 8 SWG wire mesh of suitable size with MS angle iron base frame 40 mm X 40 mm X 5 mm and 0.5 Mtr. long leg spot and MS strip with support size 40 mm X 6 mm as per drawing approved by Engineer-in-Charge i/c providing door of suitable size with S/F of godown lock, locking arrangement, painting and grouting of angle iron frame in CC 1:2:4 etc. complete as required. | - | Mtr. | 18,060 | - |
| 7 | Providing, laying, testing & commissioning of 'B' class heavy duty G.I. pipe conforming to IS 1239 including welding, fittings like elbows, tees, flanges, tapers, nuts,bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :65 mm | - | Mtr. | 1,076 | - |
| 8 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
Upto 35 sq. mm (clamped with 1mm thick saddle) | - | Metre | 64 | - |
| 9Supplying of following sizes of PVC insulated and PVC sheathed/XLPE aluminium conductor armoured power cable of 1.1 KV grade i/c connection & testing etc. as required and as per technical specification enclosed. | |||||
| 9.01 | 4 x 16 Sq.mm | - | Mtr. | 380 | - |
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.33 MB
BOQ_958896.xls
BOQ • 0.32 MB
NIT11.pdf
Tender Documents • 1.67 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .