Superintending Engineer
office of the SE, CC, UPJNU, Prayagraj.
Dala Bazar Nagar Panchayat Water Supply Scheme Dist. Sonbhadra
2025_UPJNM_1093389_1
861/AMRUT2.0/322 Dt. 22.11.2025
Open Tender
Civil Works
Percentage
NP DALA BAZAR DIST-SONEBHADRA
Please refer Tender documents.
2 documents required · 2 mandatory
₹23,600
EE,CD UP JAL NIGAM URBAN MIRZAPUR
₹33.0 L
office of the SE, CC, UPJNU, Prayagraj.
7 Apr 2026
24 Nov 2025
16 Dec 2025
24 Nov 2025
15 Dec 2025
24 Nov 2025
29 Nov 2025
PUMP HOUSE - Survey, Investigation, Planning ,Drawing, Designing, Vetting of drwaing/ disign from IIT/ NIT/ Reputed engineering college,redesign, Construction, Commissioning of RCC frame stucture Pump houes Cum PLC Room of required size to accommodate required nos of pumps. For the construction of Pump House above CWR, minimum 6 m height is to be kept with suitable arrangements to install and dismantle VT/HSC pumps and installation of Fire Extinguishers, Power wiring & earthling system, rubber resistance sheets, spares for motors & switchgear, internal & external electrifications and adequate LED lighting, brickwork 1:4 (one cement and four sand), plasterwork 1:4 (one cement and four sand). Steel and cement to be used as per approved by Engineer-in charge / IS code. Reinforced Cement Concrete minimum M-20 to be used including fixing of doors, windows, shutters, glass panels with gantry girder arrangement with supply and fixing of suitable sizes o
f steel girder including acrylic painting two coat over one priming coat using approved Colour and shade and putty with primer three coat of ceiling of pump house and painting over new ironwork with one coat of primer and two coat of approved paint including cost of all arrangement of staircase, balcony with medium G.I pipe 20 mm size three row railing, shuttering, scaffolding and water with supply of all materials, labours T&P etc. required for proper completion of works as per direction of the Engineer.
Construction of Common CWR 100 KL under Zone-2 for Water Demand of Zone-2 & 3 - Survey, Investigation, Soil Testing( up to 30m depth), Planning,Drawing/ Designing, Vetting of drawing/ design from IIT/ NIT/REPUTED ENGINEERING COLLEGE, Construction, Commissioning of CWR of 100 KL. The Concrete in a minimum grade of M-30 and steel to be used as per IS code and approved by Employer. Seismic effects and wind load with earthquake resistance should be taken into account in the design. CWR should be provided with a ventilator, manhole of adequate size. An aluminium ladder minimum of 0.45 m wide in manhole should be provided. Ultrasonic water level indicator should be provided along with lighting conductor as per IS 2309. PCC of M-10 grade to be used in bed blocks. Inlet, Outlet, washout and Overflow arrangement with the supply & installation of pressure pipe of the suitable dia, for taking overflow water to a suitable low lying area. Painting of all steel and concrete pipes with 3 coats of approved cement plaster. internally side food grade epoxy painting ( 3 coat), outer side weather coat painting (3 coat)and anticorrosive paint including all labour, material, T & P etc., all required for proper completion of works as per the direction of the Engineer.
INSTALLATION OF " SCADA
Supply of all materials,labour, and T & P etc. and construct R.C.C.(M-25 grade) thrust blocks. Including mild steel works (1%) all complete as per design for following size and instructions of Engineer ‐in ‐ charge.
Supply of following sizes of CI D/F Sluice valves as per IS-780-1960 / CPHEEO MANUALS WITH LATEST AMENDMENTS tested to 10Kg / Cm2 fixing in pipelines trenches, jointing and testing etc. complete.
Investigation,design ,planing with supply installation ,testing of all material laboure etc.For 5.0 MLD WTP -Agitator,flash mixer, Air Blower, Dewatering system, Per /post chlorination system, back wash, sub station, recycle pump, filter media,filter nozzel, gates and valve with actuators, flowmeter, sludge thickner, pipe and fitting, PAC and Poly pump,Thickner feed pump,Sludge feed pump, Power and control cable, APFC panel, DG Set for wtp, Substation for wtp and main cwr, cable tray,electrical panel confirming to IEC 61439 for WTP and MCWR,LDB,CCTV setup, SCADA automation of WTP with analayzer,level switch,indicator with Master control Station for all zones, SCADA software for 24x7 water supply, MCWR and all pumping CWR, Indoor and out door lighting sytem, minimum 15 kw ongrid solar panel plant etc for 2.0 MLD WTP. with 3 month TRIAL & RUN.(incl. electicty expanses,other all consurmable item expanses etc. in trial & run period)
150 mm dia.
200 mm dia.
250 mm dia.
In Ordinary soil
Carting from store (upto 8 Km) the following sizes of D.I.Pipes (class K-9) and specials to the site of work, lowering them in to trenches and laying true to alignment and gradient and jointing etc. complete including testing of pipeline and cutting of pipes for making up the langth as required for proper completion of work (but excluding cost of trenching) upto the satisfaction of Engineer-In-Charge.
150 mm dia.
300 mm dia.
250 mm dia.
Carting of following sizes CI D/F Non Return valve from departmental store to site of work lowering the same into trenches and fixing in position and jointing the same with supply of all material and testing etc. complete.
150 mm dia.
200 mm dia.
250 mm dia.
Supply of all materials, labours T&P etc. and construction of masonary type sluice valve chamber.
Thrust Block
Dismantling of following type of road surface including stacking of serviciable material and disposal of unservicable material within the limit of npp upto 8km distance including supply of all labour T&P etc. required for proper completion of the work as per instructions o
300 mm (size 1.15m x 1.15m x 1.15m)
200 mm (size 0.85m x 0.85m x 0.85m)
150 mm (size 0.70m x 0.70m x 0.70m)
Bituminous Road
C.C. Road
Re-instatement of following type of road surface of PWD/ UPJN specifications including supply of all materials, labour, T&P etc. required for proper
completion of the work as per instructions of Engineer ‐in ‐charge.
Bituminous surface (20cm sand, 20cm GSB, 20cm WMM, 5 cm to 8 cm DBM, 3cm to 4 cm B.C.) payment made upto WMM- 50%, DBM- 30% and BC with testing in NABL aprooved lab/PWD- 20%
Bituminous surface (20cm sand, 20cm GSB, 20cm WMM, 5 cm to 8 cm DBM, 3cm to 4 cm B.C.) payment made upto WMM- 50%, DBM- 30% and BC with testing in NABL aprooved lab/PWD- 20%
f Engineer ‐in ‐charge.
100mm dia.
125mm dia.
For Zone-1 (550 KL/18 m stagging)
For Zone-2 (250 KL/20 m stagging)
Construction of OHT Survey,Investigation, Planning, engineering, drawing/ design ,vetting of IIT/ NIT/ REPUTED ENGINEERING COLLEGE, soil investigation ( up to 50 m depth Redesign and Supply of all materials labour T&P etc. for complete construction of R.C.C. (M30 Grade) Over Head Tank of following capatity and staging min 1.50m above ground level with main components, soil testing (up to 30m depth.) and assuming bearing capacity of soil as 8MT including cost of supply of design and drawings. all the water retaining components of OHT shall be casted in M-30 grade cement concrete with approved cement, coarse sand and stone grit as per I.S. 11682 and I.S. 456 seismic effects and wind load should be taken into consideration as per I.S. 1893 for earthquake resistance and I.S. 875 Part-III for wind load on structure and including 1M wide RCC doglegged staircase with separate columns, 1m wide R.C.C. M30 balcony, M.S. ladder made of 50x50x6mm angle section and 20mm plain M.S. bars with hand rails of 20mm medium class G.I. pipes, one aluminum ladder inside the tank from top dome to bottom dome, R.C.C. railling with 20mm dia medium class G.I.pipe (in 3 rows) on both sides of stair case, supported on 50x50x6mm M.S. angle section, spaced at intervals not more than 1.5m, proper ventilator at top dome in circular shape of 1.5m dia, Ultra Sonic Water Level Indicator fabricated with sensor connecting to automation, lightening conductor as per I.S.S. 2309 or its latest amendments of latest electricity rules, consisting of proper elecation rod with 5 or more fork points as prescribed in ISS 2309-1969 and ISS 3013-1966 C.I. manhole of min 60x60cm size with locking arrangement, supply, fixing, jointing of D.I.D/F Pipes of appropriate size with D.I.D/F specials conforming to IS 8329/2000 as vertical pipes for all required no of inlet (200mm OR as designed), all required no of outlet (250mm or as designed for each DMA), overflow and washout as per latest/relevant I.S. specification with all jointing materials for proper completion of work along with Sluice valves with actuator, construction of bed blocks in 1:2:4 PCC with cement, coarse sand and approved stone grit, construction of washout/ overflow chamber and chambers for sluice / butter fly valves as per departmental type design and drawings, supply of 300mm dia HDPE pipe PN-10) as per I.S.-4985/2000 for disposal of water from overflow and washout chamber to suitable point outside the water works compound, water container internal parts 3 coats food grade eppoxy painting, painting of all concrete surface and steel pipe works with three coats weather resist painting.
Provision for Crossing and laying of pipe line( up to 60 MTR) of both side at State/National Highway and payment to state/NHAI Authority for permission of National Highway crossing:- Survey site Investigation Planning , design Drawings,VETTING OF IIT/NIT/ REPUTED ENGINEERING COLLEGE, excavation, dismentaling, road restoration & other all utility restoration( as per required) as per NATIONAL HIGHWAY standard as per MORTH Road manual and vetting / checked from State Road/ NH DIV. PWD/NHAI/UPSHA/ PWD/ Divisional Office and taking NOC CHARGES.(incl. noc fees, licence fees, security amount) for trenchless crossing of National highway road , Road for required dia Rising main pipe / Distribution pipe with casing pipe as required for proper completion of work also including security money deposited to State Road department and Execution of all work in the present of State Road staff / Engineers including of supply of required dia MS carrier pipe and required size of MS casing pipe as per drawing and as per (IS:3589 & made from confining to IS:2062) with 750 Micron th. food grade coating internally and 750 MM TH. MICRONE anti corrosive bituminous paint externally by trenchless technology method at an average depth 3.60 mtr from normal ground level up to top of casing pipe including excavation & sand filling of Pit, Dewatering arrangement, Supporting system for soil, also including supply and fixing of 2 no Sluice valve ISI Mark, construction of sluice valve chamber etc. all complete work including supply & fixing specials in carrier pipe over main pipe, as per specification given in the bid documents including supply of all materials, labour T&P etc. for proper completion of work as per instruction of Engineer. and concerned department. (CASING- 600MM (id) MS PIPE 12 MM THICK & CARRIER PIPE- AS PER REQUIRED DESIGN) INCL.3M C/C SPACER
In Moorum /Kankar / Shingle etc. incl. replace of ordinary soil
In Soft/Medium rock. Incl. Replace of ordinary soil
Supply of following sizes of CI D/F Sluice valves as per IS-780-1960 / CPHEEO MANUALS WITH LATEST AMENDMENTS tested to 10Kg / Cm2 fixing in pipelines trenches, jointing and testing etc. complete.
Supply of all materials,labour, and T & P etc. and construct R.C.C.(M-25 grade) thrust blocks. Including mild steel works (1%) all complete as per design for following size and instructions of Engineer ‐in ‐ charge.
Provision for crossing of Nala/Culvert including making specials and supply of materials, encasing of concreting (M25) labour, t&P etc. complete. ( UP TO 6M LENGTH, 300 MM dia. Pipe)
INSTALLATION OF " SCADA
Earth work in ordinary soil, In Moorum /Kankar / Shingle, In Soft/Medium rock(incl. stacking & disposal). Etc. loam, clay or sand with lift upto 1.50M and lead upto 200m, filling watering and ramming of excavated earth into the trenches and disposal of surplus earth upto 8KM .
In Ordinary Soil
In Moorum /Kankar / Shingle etc & incl. replace of ordinary soil.
In Soft/Medium rock. & incl. replace of ordinary soil.
Carting of site of work, laying and jointing of DI pipes in trenches including lowering, testing and supply of all jointing materials etc. complete.
In Moorum /Kankar / Shingle etc. incl. replace of ordinary soil
In Soft/Medium rock. Incl. Replace of ordinary soil
Supply of following sizes of CI D/F Sluice valves as per IS-780-1960 / CPHEEO MANUALS WITH LATEST AMENDMENTS tested to 10Kg / Cm2 fixing in pipelines trenches, jointing and testing etc. complete.
Supply of all materials,labour, and T & P etc. and construct R.C.C.(M-25 grade) thrust blocks. Including mild steel works (1%) all complete as per design for following size and instructions of Engineer ‐in ‐ charge.
Provision for crossing of Nala/Culvert including making specials and supply of materials, encasing of concreting (M25) labour, t&P etc. complete. ( UP TO 6M LENGTH, 300 MM dia. Pipe)
INSTALLATION OF " SCADA
DI pipe Class K-7 (IS-8329/2000)
100 mm dia.
125 mm dia.
Supply of following sizes of CI D/F Sluice valves as per IS-780-1960 / CPHEEO MANUALS WITH LATEST AMENDMENTS tested to 10Kg / Cm2 fixing in pipelines trenches, jointing and testing etc. complete.
Supply of all materials,labour, and T & P etc. and construct R.C.C.(M-25 grade) thrust blocks. Including mild steel works (1%) all complete as per design for following size and instructions of Engineer ‐in ‐ charge.
Provision for crossing of Nala/Culvert including making specials and supply of materials, encasing of concreting (M25) labour, t&P etc. complete. ( UP TO 6M LENGTH, 300 MM dia. Pipe)
INSTALLATION OF " SCADA
Supply of following types of fittings including railway freight, cartage from store to site of work, all taxes and duties etc. complete. CI D/F Sluice Valves, Scour Valve Class-I as per IS 780 (1969) & CPHEEO MANUALS LATEST AMENDMENTS suitable for a working pressure of 10 Kg / Sq.Cm. ( without galondori)
Scour Valve 100mm dia
Fire Hydrant 80mm Dia
Carting of following sluice valves store to site of work, lowering, fixing and jointing of following fitting in trenches :
In Moorum /Kankar / Shingle etc. incl. replace of ordinary soil
In Soft/Medium rock. Incl. Replace of ordinary soil
Supply of following sizes of CI D/F Sluice valves as per IS-780-1960 / CPHEEO MANUALS WITH LATEST AMENDMENTS tested to 10Kg / Cm2 fixing in pipelines trenches, jointing and testing etc. complete.
Supply of all materials,labour, and T & P etc. and construct R.C.C.(M-25 grade) thrust blocks. Including mild steel works (1%) all complete as per design for following size and instructions of Engineer ‐in ‐ charge.
Provision for crossing of Nala/Culvert including making specials and supply of materials, encasing of concreting (M25) labour, t&P etc. complete. ( UP TO 6M LENGTH, 300 MM dia. Pipe)
INSTALLATION OF " SCADA
Supply of following types of fittings including railway freight, cartage from store to site of work, all taxes and duties etc. complete. CI D/F Sluice Valves, Scour Valve Class-I as per IS 780 (1969) & CPHEEO MANUALS LATEST AMENDMENTS suitable for a working pressure of 10 Kg / Sq.Cm. ( without galondori)
Scour Valve 100mm dia
Fire Hydrant 80mm Dia
Air Valve 25mm Dia
Supply of all types of materials and construct following chambers as per type design with supply of all labour, T&P etc. completed.
S.V. Chamber (Surface Box Type)
S.V. Chamber (Masonary Type)
Air Valve Chamber
Fire Hydrant Chamber
Bituminous Road
Dismantling of following type of road surface including stacking of serviciable material and disposal of unsericeable material within the limit of npp upto 8km distance including supply of all labour T&P etc. required for proper completion of the work as per instructions of Engineer ‐in ‐charge.
C.C. Road
BOE Road
Interlocking Road
Re-instatement of following type of road surface of PWD/ UPJN specifications including supply of all materials, labour, T&P etc. required for proper completion of the work as per instructions of Engineer ‐in ‐charge.
Bituminous surface (20cm sand, 20cm GSB, 20cm WMM, 5 cm to 8 cm DBM, 3cm to 4 cm B.C.) payment made upto WMM- 50%, DBM- 30% and BC with testing in NABL aprooved lab/PWD- 20%
C.C. Road in M25 grade, minimum thickness 15cm on 15cm sand & 20cm GSB filling base.
B.O.E. surface (50% new 1st class brick on 10cm thick sand base)
Interlocking Road (50% new Interlocking bricks M-30 grade, 80 mm thick on 10cm sand & 10cm GSB filling base)
Providing and laying of GSB for reinstatement of earthen road (Shoulder) including dressing, watering, ramming etc. complete. As per MORTH standard
Provision for crossing of square drain including all material, labour & T&P etc. complete. Up to 4 mtr span up to 200mm dia. Pipe
Provision for NALLA/CULVERT CROSSING UP TO 300MM DIA PIPE CROSSING 5M including all material, for casing etc. all complete work. With concereting casing M20 grade using
Provision for NALLA/CULVERT CROSSING UP TO 300MM DIA PIPE CROSSING 7M ncluding all material. all complete work. With With concereting casing M20 grade using
THRUST BLOCK
Supply of all materials,labour, and T & P etc. and construct R.C.C.(M-25 grade) thrust blocks. Including mild steel works(1%) all complete as per design for following size and instructions of Engineer ‐in ‐ charge.
100mm ( Size 0.55m x 0.55m x 0.55m)
125mm ( Size 0.60m x 0.60m x 0.60m)
150mm ( Size 0.70m x 0.70m x 0.70m)
200mm ( Size 0.85m x 0.85m x 0.85m)
250mm ( Size 1.00m x 1.00m x 1.00m)
Construction of electric power sub-station room- Survey, Investigation, Soil Testing, Planning, Designing,vetting of IIT/ NIT/ REPUTED ENGINEERING COLLEGE, redesign, Construction of electric power sub-station room (8.00m X 5.00m X 4.00m) of required size. Construction of RCC frame structure room including excavation of soil i.e. Kankar mixed morrom/soft/hard rock, PCC for bedding in lean concrete of minimum grade of M-15, R.C.C. in grade M-25 or above in footing, foundation, plinth beam, column, lintel beam, chajja, roof slab, brick work in CM 1:4 (1 cement & 4 sand) in walling, Internal plaster 12 mm thick for walls & celling in CM 1:4 (1 cement & 4 Sand), External plaster 20 mm thick in CM 1:4 (1 cement & 4 sand), providing laying hand cut polished kota stone flooring 25 mm to 30 mm thick on bed of CM 1:4 (1 cement & 4 sand) including cement float, filling jointing with neat cement slurry, curing polishing and cleaning, providing cable duct of required size, including fixing of rolling shutter, aluminium windows & ventilator with glass panels as per specifications, providing and applying white washing in two coat to new plaster surface, internal two coat snowcem painting including priming coat, external painting with apex ultima/equivalent paint including priming, painting over new iron work with one coat of primer and two coat oil paint of approved make including cost of all arrangement of shuttering, scaffolding including all materials, labours T&P etc. for proper completion of works as per direction of the Engineer.
300mm ( Size 1.15m x 1.15m x 1.15m)
Making House Connection should be done from distribution pipe line to outer wall of house or 2.0 m inside the boundary wall with provision of tap including supply of 7.0 m HDPE Pipe(is code 4984 with latest amendments) 20mm dia, PN- 12.5, PE-100, SDR-11 (0.6m depth below ground level), and 4.0m 15mm dia (ID) G.I. Pipe, Class-B and keeping the G.I. pipe atleast 1.0m in height above the G.L. as per department type design and Drowing including supply of specials, saddle, clamps etc. of suitable size, ISI mark 6mm BRASS FERRULE conforming to latest/relevant I.S. 2692/1989 or their latest amendments, BRASS Tap, all Materials, labours, T&P etc. complete, Dismentelling of all type of road surface, breaking of all type of floor, wall, and disposal of unserviceable materials up to 8km. Excavation pit/trench, cutting of pipe, Bailing out of water, carting and lowering them unto the already prepared trenches, fixing in position and jointing them with pipelines and testing etc, Grounting by CC 150mm x 150mm x 150mm size in M20, Restoration of pit, trench/Road (as site condition NON PAVED, BOE, CC, INTERLOCKING BRICKS, Bituminous road, RAMP, DRAIN, WALL, FLOOR etc.) as per PWD/UPJN SPECIFICATION and 3 nos GPS location colour photographs submitted after complition of work. Also including GIS Based Survey to collect all required data in projected area Nagar Panchayat Dala Bazar for proper complition of work as per drawing and. As per Instruction of Engineer in charge as per drawing. Payment make after completion of work up to household 50%, RETORATION & GROUTTING-30% and 20% submitted of photographs after Testing and Commisioning & handover to NP DALA BAZAR of all remaining work.
New Connections with New pipe line.
Provide all materials, labour T&P etc. and construct following single Room/Two Room staff quarter with bathroom, latrine & kitchen as per departmental specification and drawing Including excavation in foundation, PCC(M-15), Brick Work (1:6), 20mm thick DPC, RCC(M-20), 12mm thick plaster(1:4), Floring with tiles, Painting, Wiring / water supply & sanitary etc complete work. ( RCC FRAME STRUCTURE 3.6 M HEIGHT WTH PLINTH NOT LESS THAN 0.6 M)
Two Room Staff Quarter
One Room Staff Quarter
Constrution of Boundary Wall Construction of 1.5 m high and 115mm thick boundary wall (Intakewell Campus, Zone-1 , Zone-2, Zone-3 & Commen CWR Campus) with 230 mmx230 mm thick pillar made in RCC in 1:1.5:3 the spacing between two pillar should not be more than 2.0 m c/c and the depth of foundation should not be less than 0.60m below N.G.L. and plinth height should be kept 0.45m above N.G.L., Brick Work in 1:4 and 12mm thick plaster with cement and coarse sand in the ratio of 1:4, painting with weatherproof approved paint, at the site o
f water works as per departmental type design and drawing, as per specifications given in the bid document and pwd/upjn, including supply of all materials, labour T&P etc.for proper completion of the all work as per instructions of Engineer ‐in ‐ charge.
Supply and fixing of 3.6 m x 1.30 m MS gate including fabrication and supply of steel and construction of RCC pillars of size 1.5m x 0.23m x 0.23m in M25 grade with ornamental brick work 115mm thick around RCC pillers with elctrification and lighting arrangement, brick work in foundation 1:4 cement & fine sand upto plingth, as per departmental type design and drawing and as per specifications of pwd/upjn and laid down in the bid document, including supply of all material, labour,T&P etc.required for proper completion of the work as per instructions of Engineer‐in‐charge.
MS Gate (size 3.60 m X 1.30 m) minimum weight 1.60 Qtl
MS Wicket gate (size 1.20 m X 1.30 m) minimum weight 0.50 Qtl
Filling of earth at lower portion including leveling and dressing at water works. With proper compaction.
Provision for arboriculture/ greeneries/ plantation for development of water works ( REQUIRED all nonusing area) with pipe sprinkling arrengments. For ZONAL WATER WORKS
Construction of Cement Concrete USING 20 CM TH. M25 grade using concrete type & 30 cm GSB BASE approach road including supply of all materials, labour, tools and plants etc. complete.
Supply and Construction of roof top rain water & ground water harvesting system including all required materials, labour, tools and plants etc. complete. ( boring depth 2nd layer)
E&M Work
PUMPING PLANT AT INTAKE WELL Supply of vertical turbine forced clear water/oil lubricated raw water pump set along with V.H.S. squairal cage induction motor with shaft,35.0 meter column pipe,(tentative). it will be decided as per site required, thrust bearing,motor stool foundation bolt etc. suitable to operate 415 volt, 3 phase, 50Hz, AC Supply (2 W+ 1 S).(LPM - 1575 ,Head-60 M) (Both tantative)
CE/UL certified PLC/RTU with redudant CPU and power supply in IP 54 enclosure suitable to communicate with GSM based modem unit with redudant CPU and power supply with analog /digital parameter and features as specified for each zps/oht to store and trasmitt data on GSM backbone , RTU/PLC designed with logic to transfer data at multiple statins as specified in tender document
GSM/GPRS based wireless communication system for RTU capable to transfer and gather data from remote sites to control stations. All accessories included with signal enhancer, antennan etc.
Intelegent Energy meter with memory RTC and 2 serial parts integrated with RTU
Motor operated sluice valve with actuator complete in all respect
Electric motor operated sluice valve 150mm dia along with actuator for delivery pipe of pump.
Electric motor operated sluice valve 200mm dia along with actuator for common header.
Actuator panel having control of 3 no. actuator with sluice valve 100mm dia.
Actuator panel having control of 1 no. actuator with sluice valve 150mm dia. For commen header
Auto phase reversal unit/ automatic transformer suitable with inbuilt time delay & enclose of 100 Amp rating
Rador type level sensor for intake well level measurement with RTU communication.
Pressure Transmitter along with manual pressure gauge
Isolation transformer & surge arrestor.
CE/UL certifiedd 7 inch HMI touch screen suitable to communication with PLC/RTU for local display and control.
Security serveilliance camera IP with recorder
ELECTRO MAGNETIC FLOW METER
Provision of Electro magnetic flow meter suitable to measure the water discharge and to be fitted in common header of 200mm dia.
FLOW SENSOR
Type - Pulsed DC
End connection- Flanged of Carbon steel
Flange rating - PN 16 size 200 mm.
Electrode - SS 316
Lining Material - Hard rubber
Protection category - IP 68
Measuring Accuracy- + 5% of measured
Valve inclusive of linearity repeatability pressure effect and Hystrusues between 1 to 3 meter per second.
Sensor Housing - SS 304 with fully welded construction
Connection/ Junction Box - SS 304
Earthing only grounding rings required
FLOW TANSMITTER CONVERTOR
Type - Micro processor based modular desing
Display - 3 line back lit LDC for indication of actual flow rate forward reverse sum totolizer.
Protection category - IP 65
Enclosure - DI - Cast Aluminium with poly urethan with glass window.
Programming- Through three key pad as front facia.
Power Supply - 230 volt 50 HZ AC
Cable Gland - ½ NPT
Mounting - Wall mounted
Maximum Sepration - Upto 300 m between sensor and transmeter without any signal boosters.
Terminals - shock-Hazard-protected push lock terminal.
Error Indetification : 0.3, 6/22 MA
MAIN PIPING & VALVES INCLUDING COMMON HEADER :-
Size of Delivery of pump 150mm dia length as per site requirement
Size of Common header of 200mm dia. length as per site requirement
Supply of following
CI D/F Reflux Valve 150 mm dia -3 Nos.
CI D/F Tee 200x200x150 mm dia. -3 Nos.
D/F distance piece 150 mm dia. 1.00 m. long - as required
D/F distance piece 200 mm dia. 1.50 m. long -as required
D/F distance piece 200 mm dia. 3.00 m. long - as required
Dismantling joint 150 mm dia. - 3Nos.
Dismantling joint 200 mm dia for common header - 1 No.
Nut-bolts, rubber packing (as required)
Any other Item required for proper installation of above pumps. - 1 Job.
POWER WIRING CABLE FOR INCOMING PANEL & PUMPS :-
Supply of 1100 volt grade 120mm2 x 3½ core P.V.C. Armoured Alluminium conductor cable from outgoing of transformer to L.T. incoming Panel and for power wring of pumping plant.
HOT crane
Provision of H.O.T. crane of 5 Ton capacity along with gantry girder and chainpully block and geared trolly suitable for 8 meter dai and 12 meter clear lift complete in all respect for circular pump house, suitable for travelling length.
POWER WIRING :
Supply and laying of 1100 volt grade 25mm2 x 3½ core /suitable size P.V.C. Armoured Alluminium conductor cable from outgoing of transformer to L.T. incoming Panel and for power wring of pumping plant and also for power wiring of Pump set.
EARTHING :
Provision for double plate earthing for4 nos. of electric motors, starters, panels etc. excavation of earthing pit of required size supply and burrying of 600 mm x600 mm size 3mm thick copper earth plate vertically errected for earthing with its top at least 3 meter from ground level completed with 32 mm G.1. perforated pipes and funnel for watering, laying and fetting of earthing strip, CI boxes hinged cover masonary, laying alternate layers of characoal / coak and salt at least 150 mm thick each layer complete in all respect.
Earth work in ordinary soil, In Moorum /Kankar / Shingle, In Soft/Medium rock. Etc. loam, clay or sand with lift upto 1.50M and lead upto 200m, filling watering and ramming of excavated earth into the trenches and disposal of surplus earth upto 8KM.
Provision for painting of all the pumps set, main piping and valves, panels etc. installed in the pump house with three coats by enamel paint.
NSTALLATION OF " SCADA"
Installation of SCADA system, to controle the 3 set of pumping plant including testing and commissioning etc.
INSTALLATION AND COMMISSIONING
Installation of all 3 no.pumping plants along with L.T. panels distribution boards, switch gear control panels, starter etc laying & jointing of column pipes, delivery pipes, common header also commissiong of pumping plant.
Electrification for pump house and premises.
Electrification of pump house and campus with copper conductor wire concealed with the all material labour etc.
Fire Extinguisher capacity 4.5 Kg CO2
12.5 mm thick electric resistance rubber sheet as per BIS for LT Panels
Supply and fixing of exhaust fans of 18" size 1450rpm of GEC/equivalent make complete in all respect.
Servo Voltage Stabilizer suitable capacity
PUMPING PLANT AT INTAKE WELL Supply of Desilting pump set,nut bolt ,rubber packing etc. LPM - 250, Head - 40
Supply of stater panel suitable for abbove pump set
supply of 1100 volt grade copper submersible cable 3x16mm
MS column pipe 100mm Dai.
CI/DF Sluice valve 100mm Dai
CI/DF Reflex valve 100mm dai
CI/DF Bend 100 mm dai
SS guide pipe of 40mm dai.
Installation ,testing and commissioning of pumping plant.
E&M Work
Meter
CE/UL certified PLC/RTU with redudant CPU and power supply in IP 54 enclosure suitable to communicate with GSM based modem unit with redudant CPU and power supply with analog /digital parameter and features as specified for each zps/oht to store and trasmitt data on GSM backbone , RTU/PLC designed with logic to transfer data at multiple statins as specified in tender document
GSM/GPRS based wireless communication system for RTU capable to transfer and gather data from remote sites to control stations. All accessories included with signal enhancer, antennan etc.
PUMPING PLANT AT WTP C.W.R.to OHT zone 1 Supply of submersible pump set for clear water pump set to operate AC Supply 415 volt, 3 phase, 50Hz for pumping from WTP C.W.R.to OHT zone 1 (1W+1S). LPM - 1350, Head 50M (Both tentative)
SITC of SWITCH GEAR WITH AUTO MATION OF PUMPING PLANT Fully Automatic Air break manually ON/OFF/ Automatic ON/OFF soft starter of suitable capacity with G.S.M. based facility comprising of required electrical accessories complete in all respect-
Motor operated sluice valve with actuator complete in all respect
GSM/GPRS based wireless communication system for i RTU capable to transfer and gather data from remote sites to control stations. All accessories included with signal enhancer, antennan make for abbove ITRU.
Electric motor operated sluice valve 200mm dia along with actuator for common header.
Actuator panel having control of 3 no. actuator with sluice valve 100mm dia.
Motor operated sluice valve with actuator complete in all respect-
Auto phase reversal unit/ automatic transformer suitable with inbuilt time delay & enclose of 100 Amp rating
Pressure Transmitter along with manual pressure gauge
CE/UL certifiedd 7 inch HMI touch screen suitable to communication with PLC/RTU for local display and control.
Electric motor operated sluice valve 150mmdia along with actuator for delivery pipe of pump.
Rador type level sensor for intake well level measurement with RTU communication.
Isolation transformer & surge arrestor.
Security serveilliance camera IP with recorder
Rador type level sensor for level measurement with RTU communication.
ELECTRO MAGNETIC FLOW METER
Provision of Electro magnetic flow meter suitable to measure the water discharge and to be fitted in common header of 200mm dia.
FLOW SENSOR
CE/UL certifiedd rudder type lelvel transmitter for OHT
End connection- Flanged of Carbon steel
Flange rating - PN 16 size 200 mm.
Electrode - SS 316
Lining Material - Hard rubber
Measuring Accuracy- + 5% of measured
Valve inclusive of linearity repeatability pressure effect and Hystrusues between 1 to 3 meter per second.
Sensor Housing - SS 304 with fully welded construction
Connection/ Junction Box - SS 304
Earthing only grounding rings required
FLOW TANSMITTER CONVERTOR
Type - Micro processor based modular desing
Display - 3 line back lit LDC for indication of actual flow rate forward reverse sum totolizer.
Protection category - IP 65
Enclosure - DI - Cast Aluminium with poly urethan with glass window.
Programming- Through three key pad as front facia.
Power Supply - 230 volt 50 HZ AC
Cable Gland - ½ NPT
Mounting - Wall mounted
Maximum Sepration - Upto 300 m between sensor and transmeter without any signal boosters.
Terminals - shock-Hazard-protected push lock terminal.
Error Indetification : 0.3, 6/22 MA
Provision of Electro magnetic flow meter suitable to measure the water discharge and to be fetted in common header of 200mm dia having following specification
Size of Delivery of pump 150mm dia length as per site requirement
Flange rating - PN 16 size 150 mm.
Size of Delivery of pump 100mm dia Length as per site requirement.
Size of Common header of 150mm dia. Lengh as per site requirement
CI D/F Reflux Valve 100 mm dia - 2 Nos.
CI D/F Tee 150x150x100 mm dia. - 2 Nos.
D/F distance piece 100 mm dia. 1.00 m. long - 2 Nos.
D/F distance piece 150 mm dia. 1.50 m. long - 2 Nos.
Dismantling joint 150 mm dia. - 3Nos.
Dismantling joint 200 mm dia for common header - 1 No.
Nut-bolts, rubber packing (as required)
D/F distance piece 150 mm dia. 3.00 m. long - 2 Nos.
HOT crane
Provision of H.O.T. crane of 5 Ton capacity along with gantry girder and chainpully block and geared trolly suitable for 8 meter dai and 12 meter clear lift complete in all respect for circular pump house, suitable for travelling length.
POWER WIRING :
Dismantling joint 100 mm dia. - 2 Nos.
EARTHING :
Provision for double plate earthing for4 nos. of electric motors, starters, panels etc. excavation of earthing pit of required size supply and burrying of 600 mm x600 mm size 3mm thick copper earth plate vertically errected for earthing with its top at least 3 meter from ground level completed with 32 mm G.1. perforated pipes and funnel for watering, laying and fetting of earthing strip, CI boxes hinged cover masonary, laying alternate layers of characoal / coak and salt at least 150 mm thick each layer complete in all respect.
PAINTING
Dismantling joint 150 mm dia for common header - 1 No.
Supply of 1100 volt grade 35mm2 x 3½ core P.V.C. Armoured Alluminium conductor cable from outgoing of transformer to L.T. incoming Panel and for power wring of pumping plant.
Provision for double plate earthing for 2 nos. of electric motors, starters, panels etc. excavation of earthing pit of required size supply and burrying of 600 mm x600 mm size 3mm thick copper earth plate vertically errected for earthing with its top at least 3 meter from ground level completed with 32 mm G.1. perforated pipes and funnel for watering, laying and fetting of earthing strip, CI boxes hinged cover masonary, laying alternate layers of characoal / coak and salt at least 150 mm thick each layer complete in all respect.
Installation of SCADA system, to controle the 2 set of pumping plant including testing and commissioning etc.
Installation of all 2 pumping plants along with L.T. panels distribution boards, switch gear control panels, starter etc laying & jointing of column pipes, delivery pipes, common header also commissiong of pumping plant.
Servo vatage stabilizer of suitable Capacity
PUMPING PLANT AT WTP C.W.R. to CWR zone-2 Supply of Horizontal submersible pump set for clear water pump set to operate AC Supply 415 volt, 3 phase, 50Hz pumping At WTP C.W.R. to CWR zone-2(1W+1S) LPM - 1550, Head - 45 M (Both tentative)
SWITCH GEAR WITH AUTO MATION OF PUMPING PLANT
SITC of Fully Automatic Air break star delta/manually ON/OFF / Automatic ON/OFF soft starter of required capacity with G.S.M. based facility comprising of following electrical accessories complete in all respect-
Contractors of suitable ratings.
TOR of suitable ratings.
P.B Switches
Dual Amp & Voltmeter.
Toggle Switches
Indicating Lamps phase failure.
Phase reversal relay
Single Phase Preventer.
PUMPING PLANT AT WTP C.W.R.to OHT zone 1 Supply of submersible pump set for clear water pump set to operate AC Supply 415 volt, 3 phase, 50Hz for pumping from WTP C.W.R.to OHT zone 1 (1W+1S). LPM - 1350, Head 50M (Both tentative)
Capacitor of suitable ratings
GSM with water level indicator
SCADA compatible panel for star delta/manually ON/OFF/Automatic ON/OFF starter at requ
Electric motor operated sluice valve 150 mm dia along with actuator for delivery pipe of pump.
Electric motor operated sluice valve 200 mm dia along with actuator for common header.
Actuator panel having control of 2 no. actuator with sluice valve 150mm dia.
Security serveilliance camera IP with recorder
Actuator panel having control of 1 no. actuator with sluice valve 200mm dia. For commen header
ELECTRO MAGNETIC FLOW METER
Provision of Electro magnetic flow meter suitable to measure the water discharge and to be fitted in common header of 200mm dia.
FLOW SENSOR
CE/UL certifiedd rudder type lelvel transmitter for OHT
End connection- Flanged of Carbon steel
Flange rating - PN 16 size 200 mm.
Electrode - SS 316
Lining Material - Hard rubber
Protection category - IP 68
Measuring Accuracy- + 5% of measured
Valve inclusive of linearity repeatability pressure effect and Hystrusues between 1 to 3 meter per second.
Sensor Housing - SS 304 with fully welded construction
Connection/ Junction Box - SS 304
Earthing only grounding rings required
FLOW TANSMITTER CONVERTOR
Type - Micro processor based modular desing
Display - 3 line back lit LDC for indication of actual flow rate forward reverse sum totolizer.
Protection category - IP 65
Enclosure - DI - Cast Aluminium with poly urethan with glass window.
Programming- Through three key pad as front facia.
Power Supply - 230 volt 50 HZ AC
Cable Gland - ½ NPT
Mounting - Wall mounted
Maximum Sepration - Upto 300 m between sensor and transmeter without any signal boosters.
Terminals - shock-Hazard-protected push lock terminal.
Error Indetification : 0.3, 6/22 MA
Pressure Transmitter with manual pressure gauge.
Control cabling for scada including all power and control cable for all equipment (1.5sq mm, 10cx1sq mm, 2cx1sq mm other required items for pump set.
Size of Delivery of pump 150mm dia length as per site requirement
Provision of Electro magnetic flow meter suitable to measure the water discharge and to be fetted in common header of 200 mm dia. having following specification
Size of Delivery of pump 150mm dia length 6.0 Mtr / as per site requirement
Size of Common header of 200mm dia. Length 6.0 mtr/ as per site requirement
CI D/F Reflux Valve 150 mm dia as required
CI D/F Tee 200x200x150 mm dia. as required
D/F distance piece 150 mm dia. 1.00 m. long as required
D/F distance piece 200 mm dia. 1.50 m. long as required
D/F distance piece 200 mm dia. 3.00 m. long as required
Dismantling joint 200 mm dia for common header - 1 No.
Nut-bolts, rubber packing (as required)
Dismantling joint 150 mm dia.as required
HOT crane
Provision of H.O.T. crane of 5 Ton capacity along with gantry girder and chainpully block and geared trolly suitable for 8 meter dai and 12 meter clear lift complete in all respect for circular pump house, suitable for travelling length.
POWER WIRING :
Dismantling joint 100 mm dia. - 2 Nos.
EARTHING :
Provision for double plate earthing for4 nos. of electric motors, starters, panels etc. excavation of earthing pit of required size supply and burrying of 600 mm x600 mm size 3mm thick copper earth plate vertically errected for earthing with its top at least 3 meter from ground level completed with 32 mm G.1. perforated pipes and funnel for watering, laying and fetting of earthing strip, CI boxes hinged cover masonary, laying alternate layers of characoal / coak and salt at least 150 mm thick each layer complete in all respect.
Supply of 1100 volt grade 35mm2 x 3½ core P.V.C. Armoured Alluminium conductor cable from outgoing of transformer to L.T. incoming Panel and for power wring of pumping plant.
Dismantling joint 200 mm dia for common header - 1 No.Reflex valve 200mm dia as required.
Nut-bolts, Bend ,rubber packing (as required)
Installation of all 2 pumping plants along with L.T. panels distribution boards, switch gear control panels, starter etc laying & jointing of column pipes, delivery pipes, common header also commissiong of pumping plant.
Supply of 1100 volt grade 50.mm2 x 3½ core/ suitable size P.V.C. Armoured Alluminium conductor cable from outgoing of transformer to L.T. incoming Panel and for power wring of pumping plant.
PUMPING PLANT AT WTP C.W.R. to CWR zone-2 Supply of Horizontal submersible pump set for clear water pump set to operate AC Supply 415 volt, 3 phase, 50Hz pumping At WTP C.W.R. to CWR zone-2(1W+1S) LPM - 1550, Head - 45 M (Both tentative)
SWITCH GEAR WITH AUTO MATION OF PUMPING PLANT
SITC of Fully Automatic Air break star delta/manually ON/OFF / Automatic ON/OFF soft starter of required capacity with G.S.M. based facility comprising of following electrical accessories complete in all respect-
Contractors of suitable ratings.
TOR of suitable ratings.
P.B Switches
Dual Amp & Voltmeter.
Toggle Switches
Indicating Lamps phase failure.
Phase reversal relay
E&M Work
Servo vatage stabilizer of 40KVA/ suitable Capasity
PUMPING PLANT At CWR zone 2 to OHT Zone-2 Supply of submersible pump set for clear water pump set to operate AC Supply 415 volt, 3 phase, 50Hz for pumping Plant At CWR zone 2 to OHT Zone-2. ( 1 W+ 1 S). , LPM - 600, Head - 65 M (Both tentative)
CE/UL certified PLC/RTU with redudant CPU and power supply in IP 54 enclosure suitable to communicate with GSM based modem unit with redudant CPU and power supply with analog /digital parameter and features as specified for each zps/oht to store and trasmitt data on GSM backbone , RTU/PLC designed with logic to transfer data at multiple statins as specified in tender document
PUMPING PLANT AT WTP C.W.R.to OHT zone 1 Supply of submersible pump set for clear water pump set to operate AC Supply 415 volt, 3 phase, 50Hz for pumping from WTP C.W.R.to OHT zone 1 (1W+1S). LPM - 1350, Head 50M (Both tentative)
SITC of SWITCH GEAR WITH AUTO MATION OF PUMPING PLANT Fully Automatic Air break manually ON/OFF/ Automatic ON/OFF soft starter of suitable capacity with G.S.M. based facility comprising of required electrical accessories complete in all respect-
Motor operated sluice valve with actuator complete in all respect
Fully Automatic Air break star delta/manually ON/OFF / Automatic ON/OFF starter with G.S.M. based facility comprising of following electrical accessories complete in all respect-
GSM/GPRS based wireless communication system for iRTU capable to transfer and gather data from remote sites to control stations. All accessories included with signal enhancer, antenan for above iRTU.
Actuator panel having control of 3 no. actuator with sluice valve 100mm dia.
Motor operated sluice valve with actuator complete in all respect-
Electric motor operated sluice valve 200 mm dia along with actuator for common header.
Pressure Transmitter along with manual pressure gauge
Control panel with IP 54 protection, industrial grade fo rall equipment separate fo rcontrol (24v) and power equipment. SCADA compatible switch gear control panel for star delta/manually ON/OFF /Automatic ON/OFF starter of with suitable MCB and swich fuse unit for incoming power supply of uppcl .
Rador type level sensor for intake well level measurement with RTU communication.
Actuator panel having control of 2 no. actuator with sluice valve 100mm dia.
Actuator panel having control of 1 no. actuator with sluice valve 150mm dia. For commen header
Security serveilliance camera IP with recorder
Security serveilliance IP camera with recorder
ELECTRO MAGNETIC FLOW METER
Provision of Electro magnetic flow meter suitable to measure the water discharge and to be fitted in common header of 200mm dia.
FLOW SENSOR
CE/UL certifiedd rudder type lelvel transmitter for OHT
End connection- Flanged of Carbon steel
Flange rating - PN 16 size 200 mm.
Electrode - SS 316
Lining Material - Hard rubber
Protection category - IP 68
Measuring Accuracy- + 5% of measured
Valve inclusive of linearity repeatability pressure effect and Hystrusues between 1 to 3 meter per second.
Sensor Housing - SS 304 with fully welded construction
Connection/ Junction Box - SS 304
Earthing only grounding rings required
FLOW TANSMITTER CONVERTOR
Type - Micro processor based modular desing
Display - 3 line back lit LDC for indication of actual flow rate forward reverse sum totolizer.
Protection category - IP 65
Enclosure - DI - Cast Aluminium with poly urethan with glass window.
Programming- Through three key pad as front facia.
Power Supply - 230 volt 50 HZ AC
Cable Gland - ½ NPT
Mounting - Wall mounted
Maximum Sepration - Upto 300 m between sensor and transmeter without any signal boosters.
Terminals - shock-Hazard-protected push lock terminal.
Error Indetification : 0.3, 6/22 MA
Control cabling for Scada including all power and control cable for all equipment (1.5sq mm, 10cx1sq mm, 2cx1sq mm other required items for pump set.
CE/UL certified Radar type Level Transmitter for OHT
Size of Delivery of pump 150mm dia length as per site requirement
Provision of Electro magnetic flow meter suitable to measure the water and to be fetted
in common header of 200mm dia. having following specification
Size of Delivery of pump 100mm dia .Lenght for each pump.
Size of Common header of 150mm dia., length as per site requirement
CI D/F Reflux Valve 100 mm dia as per site requirement
CI D/F tee 150x150x100 mm dia. as per site requirement
D/F distance piece 100 mm dia. 1.00 m. long as per site requirement
D/F distance piece 150 mm dia. 1.50 m. long as per site requirement
Dismantling joint 200 mm dia for common header - 1 No.
D/F distance piece 150 mm dia. 3.00 m. long as per site requirement
Dismantling joint 100 mm dia. as per site requirement
Dismantling joint 150 mm dia. Reflex valve 150mm dia
Nut-bolts, bend,rubber packing ( as required)
TOOLS & PLANTS
For Pump house
One tool box of 33"x18"x12" fabricated from 18 gauge M.S. Sheet duly black painted comprising of of following tools.
Ring spanners (12 pcs.)
D/E spanners (12 pcs.)
Adjustable wrench (12")
Pipe wrench (14")
Crimpling tool(complete with die set)
heavy duty socket set 8mm to 50 mm size
Flow meter
Air release Valve
Fire extingushier cinfirming to BIS of 3 Kg Co2 gas type
Nut-bolts, rubber packing (as required)
12.5 mm thich electric resistance rubber sheet as per BIS for LT Panels
HOT crane
Provision of H.O.T. crane of 5 Ton capacity along with gantry girder and chainpully block and geared trolly suitable for 8 meter dai and 12 meter clear lift complete in all respect for circular pump house, suitable for travelling length.
POWER WIRING :
H.O.T CRANE
Installation of SCADA system, to controle the 3 set of pumping plant including testing and commissioning etc.
Electrification of pump house and campus with copper conductor wire concealed with the all material labour etc.
EARTHING :
Provision for double plate earthing for4 nos. of electric motors, starters, panels etc. excavation of earthing pit of required size supply and burrying of 600 mm x600 mm size 3mm thick copper earth plate vertically errected for earthing with its top at least 3 meter from ground level completed with 32 mm G.1. perforated pipes and funnel for watering, laying and fetting of earthing strip, CI boxes hinged cover masonary, laying alternate layers of characoal / coak and salt at least 150 mm thick each layer complete in all respect.
Provision of H.O.T. crane of 2 Ton capacity along with gantry girder and chainpully block and geared trolly suitable for 4 meter span and 12 meter clear lift complete in all respect for circular pump house, suitable for 6 meter travelling length.
Supply of 1100 volt grade 35mm2 x 3½ core P.V.C. Armoured Alluminium conductor cable from outgoing of transformer to L.T. incoming Panel and for power wring of pumping plant.
Supply of 1100 volt grade 25mm2 x 3½ core /suitable size P.V.C. Armoured Alluminium conductor cable from outgoing of transformer to L.T. incoming Panel and for power wring of pumping plant and also for power wiring of 3nos. Pump set.
Provision for double plate earthing fo2 nos. of electric motors, starters, panels etc. excavation of earthing pit of required size supply and burrying of 600 mm x600 mm size 3mm thick copper earth plate vertically errected for earthing with its top at least 3 meter from ground level completed with 32 mm G.1. perforated pipes and funnel for watering, laying and fetting of earthing strip, CI boxes hinged cover masonary, laying alternate layers of characoal / coak and salt at least 150 mm thick each layer complete in all respect.
Installation of all 2 pumping plants along with L.T. panels distribution boards, switch gear control panels, starter etc laying & jointing of column pipes, delivery pipes, common header also commissiong of pumping plant.
Electrification of pump house and campus with copper conductor wire concealed with the all material.
PUMPING PLANT AT WTP C.W.R. to CWR zone-2 Supply of Horizontal submersible pump set for clear water pump set to operate AC Supply 415 volt, 3 phase, 50Hz pumping At WTP C.W.R. to CWR zone-2(1W+1S) LPM - 1550, Head - 45 M (Both tentative)
SWITCH GEAR WITH AUTO MATION OF PUMPING PLANT
SITC of Fully Automatic Air break star delta/manually ON/OFF / Automatic ON/OFF soft starter of required capacity with G.S.M. based facility comprising of following electrical accessories complete in all respect-
Contractors of suitable ratings.
TOR of suitable ratings.
P.B Switches
Dual Amp & Voltmeter.
Toggle Switches
Indicating Lamps phase failure.
Phase reversal relay
Installation, testing and commissioning of complete SCADA system.
PUMPING PLANT AT WTP C.W.R.to OHT zone 1 Supply of submersible pump set for clear water pump set to operate AC Supply 415 volt, 3 phase, 50Hz for pumping from WTP C.W.R.to OHT zone 1 (1W+1S). LPM - 1350, Head 50M (Both tentative)
SITC of SWITCH GEAR WITH AUTO MATION OF PUMPING PLANT Fully Automatic Air break manually ON/OFF/ Automatic ON/OFF soft starter of suitable capacity with G.S.M. based facility comprising of required electrical accessories complete in all respect-
Motor operated sluice valve with actuator complete in all respect
Servo vatage stabilizer of suitable Capasity
PUMPING PLANT C.W.R. Zone -2 to O.H.T. zone 3 Supply of submersible pump set for clear water pump set to operate AC Supply 415 volt, 3 phase, 50Hz for pumping from C.W.R. Zone -2 to O.H.T. zone 3 (1W+1S). LPM - 950, Head - 60 M
Fully Automatic Air break star delta/manually ON/OFF / Automatic ON/OFF starter of 25 H.P. with G.S.M. based facility comprising of following electrical accessories complete in all respect-
Electric motor operated sluice valve 200 mm dia along with actuator for common header.
Security serveilliance camera IP with recorder
SCADA compatible panel for existing star delta/manually ON/OFF /Automatic ON/OFF starter of 25 H.P.
ELECTRO MAGNETIC FLOW METER
Provision of Electro magnetic flow meter suitable to measure the water discharge and to be fitted in common header of 200mm dia.
FLOW SENSOR
CE/UL certifiedd rudder type lelvel transmitter for OHT
End connection- Flanged of Carbon steel
Flange rating - PN 16 size 200 mm.
Electrode - SS 316
Lining Material - Hard rubber
Protection category - IP 68
Measuring Accuracy- + 5% of measured
Valve inclusive of linearity repeatability pressure effect and Hystrusues between 1 to 3 meter per second.
Sensor Housing - SS 304 with fully welded construction
Connection/ Junction Box - SS 304
Earthing only grounding rings required
FLOW TANSMITTER CONVERTOR
Type - Micro processor based modular desing
Display - 3 line back lit LDC for indication of actual flow rate forward reverse sum totolizer.
Protection category - IP 65
Enclosure - DI - Cast Aluminium with poly urethan with glass window.
Programming- Through three key pad as front facia.
Power Supply - 230 volt 50 HZ AC
Cable Gland - ½ NPT
Mounting - Wall mounted
Maximum Sepration - Upto 300 m between sensor and transmeter without any signal boosters.
Terminals - shock-Hazard-protected push lock terminal.
Error Indetification : 0.3, 6/22 MA
MAIN PIPING & VALVES INCLUDING COMMON HEADER :-
Size of Delivery of pump 150mm dia length as per site requirement
Actuator panel having control of 2 no. actuator with sluice valve 100mm dia.
Actuator panel having control of 1 no. actuator with sluice valve150mm dia. For commen header
CE/UL certified 7 inch HMI touch screen suitable to communication with PLC/RTU for local display and control.
Provision of Electro magnetic flow meter suitable to measure the water discharge up to 950 lpm and to be fetted in common header of 150 mm dia. having following specification
CI D/F Reflux Valve 100 mm dia
CI D/F Tee 150x150x100 mm dia.
D/F distance piece 100 mm dia. 1.00 m. long
D/F distance piece 150 mm dia. 1.50 m. long
Dismantling joint 200 mm dia for common header - 1 No.
Nut-bolts, rubber packing (as required)
D/F distance piece 150 mm dia. 3.00 m. long
HOT crane
Provision of H.O.T. crane of 5 Ton capacity along with gantry girder and chainpully block and geared trolly suitable for 8 meter dai and 12 meter clear lift complete in all respect for circular pump house, suitable for travelling length.
POWER WIRING :
Dismantling joint 100 mm dia. - 2 Nos.
EARTHING :
Provision for double plate earthing for4 nos. of electric motors, starters, panels etc. excavation of earthing pit of required size supply and burrying of 600 mm x600 mm size 3mm thick copper earth plate vertically errected for earthing with its top at least 3 meter from ground level completed with 32 mm G.1. perforated pipes and funnel for watering, laying and fetting of earthing strip, CI boxes hinged cover masonary, laying alternate layers of characoal / coak and salt at least 150 mm thick each layer complete in all respect.
Supply of 1100 volt grade 35mm2 x 3½ core P.V.C. Armoured Alluminium conductor cable from outgoing of transformer to L.T. incoming Panel and for power wring of pumping plant.
Supply of 1100 volt grade 25mm2 x 3½ core /suitable size P.V.C. Armoured Alluminium conductor cable from outgoing of transformer to L.T. incoming Panel and for power wring of pumping plant and also for power wiring of 3nos. Pump set.
Dismantling joint 100 mm dia.
Dismantling joint 100 mm dia for common header.,Reflex valve 150mm .
Nut-bolts, rubber ,bend ,packing (as required)
Supply of 1100 volt grade 50mm2 x 3½ / suitable size core P.V.C. Armoured Alluminium conductor cable from outgoing of transformer to L.T. incoming Panel and for power wring of pumping plant.
Chlorination plant at Zone 2 and Zone 3
SITC of suitable Capacity electromechanical type Bleaching Power solution upto 10 Kg/cm2 Pressure with Three phase electric motor with adequate capacity CGI tank complete in all respect for disinfecting the clear water. 1W+1S at Zone 2 and Zone 3 including all in all respect.
substation at Intakewell
HT Control Panel at Intakewell
2mm thick M.S. sheet fabricated factory wired dust and vermin proof cubical and floor mounting type control panel comprising with incomming VCB panel 1 nos and outgoing VCB panel 2 Nos of 11 KV/800 Amp. 3 Phase 3 wire 50 Hz.
Incoming panel
11 KV 3 Phase 3 wire 50 Hz. HT 1 Nos incoming VCB panel with a short circuit breaking current up to 18.4 KVA capacity in draw out version vaccum circuit breaker fitted with 3 Nos. single phase double core epoxy bar primary time current transformer of suitable ratio of class I accuracy and 5p 10 for protection core with burden of 15 VA per core., 1 no. 3 phase resin cast draw out type PT of ratio 11 KV/110 volt of class I accuracy and 100 VA burden, 1 set of closing & tripping coil suitable for 30 Volt DC., Mechanical indicator for ON/OFF., Emergency Mechanical tripping through push lever., Rear/Side entry cable box to accommodate suitable size cable., Energy Analyzer of measuring parameters such as voltage, current, KW, KWH, KVA & Power factor., Indicating lamp assembly for breaker ON/OFF trapping spring, charge., Over current and earth fault relay, C.D.G. 31 having elements for over current and one for earth fault etc., Incoming panel will be followed by a battery charge unit having specification as under AND The Cabinet of Suitable thickness shall be enclosed type to ensure the atmosphere is absolutely acid free. It shall be provided with cover for ventilation and shall have steel hinged doors equiped with battery & battery charger.
Outgoing panel
H.T. out going panels for feeding two transformers similar to incoming panel but without following accessories.
KWH meter with M.D.I.
Potential transformers
Outgoing battery charger
Provision for oil immersed natural air cooled step down transformer suitable for out door installation of 160 KVA or above as per requirement of site, 11/0, 4KV and as per I:S 2020/1972 with all accessories. The transformer should be provided with off load tap changer ± 7.5% voltage varialtion on L.T. side. These tapping should be connected by and externally separated tap changing switch. The temp side in oil by thermometer should not exceed 50oC and of winding by measuring resistance should not exceed 55oC over an ambient of 45oC maximum. The transformer should have cable box on HT/LT side for termination of cables.
Main L.T. Panel
2mm thick M.S. sheet fabricated factory wired dust and vermin proof cubical and floor mounting type control panel comprising of following items.
Incoming Panel
Reputed make cubical floor mounting extensible type panel complete with T.P. air insulated aluminum Bus bar of required capacity with neutral of reduced section, system voltage 415/440 volts 3 phase 4 wire 50 Hz indoor installation type and comprising of required nos suitable capacity breaker for incoming of transformer and D.G. set & required no of outgoing breakers for motors, lighting and other electrical equipments with minimum two nos of spare breakers, required nos of soft starter for motors and required capacity APFC panel housed in sheet steel cubical panel fitted with all accessories as per tender document. breaking capacity of all breakers should be as per IE rules and best engineering design. LT panel should comprise of required relays, multi function meter etc complete in all respect. fitted with following.
One set of Mechanical On/Off Indicator
One no. shunt trip oil
One set of T.P.I.D. M.T. Non-directional combined over current and earth fault relay having setting 50-200% for over current and 20-80% for earth fault or equivalent.
Two CTs of suitable ratio and class for protection and indication.
One no. neutral link
One no. 96 Sq.mm. Ammeter of and suitable range
One set of red green indicating lamp
Cable connection arrangments
Inter locking arrangements
Bus coupler
Bus coupler complete with internal wiring aluminium bus bar comprising of following.
Extensible type 1000 Amp. Capacity Aluminium bus bar arrangement for phase and neutical
600 Amp. 3 pole M.C.C.B. fitted with over load under voltage shunt trip short circuit release with safety shutter etc.
Electrical and mechanical inter locking arrangement
M.C.C.B On/Off indicating lamp.
HRC Fuses
Auxilliary contractors
Breaker control switch
Supply and laying of cable for Power Wiring and Earthing of 11 KV XLPE cable for suitable size 3 x 50mm sq.
Supply and laying of cable for Power Wiring and Earthing of 3.50 core 240 Sq.mm aluminium PVC cable 1100 V grade.
Supply of Jointing cable of HT Indoor joint
Supply of Jointing cable of HT outdoor joint
Supply of earthing materials and earthing arrangement.
Erection, testing and commissioning of Sub-Station including testing at work also.
Approval of electrical inspector, electric safety.
Foundation of Transformers
12.5 mm/25mm thich electric resistance rubber sheet as per BIS
Fencing work
Internal Electrification with concealed conduct wiring including all materials and labour complete in all respect of sump. Pump controlling room and staff Quarter.
DG SET at Intakewell
Suply Installation, Testing and commissioning of salient type 100 KVA or more with AMF panel as per site requirement DG set as per CPCB latest guide line powered with complete at Intake well
Power cable of 120 sqmm size/suitable size of 1100 volts grade 3½ core Alluminium armoured PVC seathed
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.63 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.84 MB
BOQ_2009619.xls
BOQ • 1.03 MB
DALABAZARBID861.pdf
Tender Documents • 11.36 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .