Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance VILLAGE DINAK P O KANAID TEHSIL SUNDERNAGAR | BILASPUR | HIMACHAL PRADESH | 174001 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance SHOP NO 5 BACHAT BHAWAN UNA TEHSIL UNA HP 174303 | UNA | UNA | HP | 174303 | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹32,700
Closing Date
13 Jul 2021, 5:00 pmClosed
XEN Electrical division No. 1 Shimla-9
The Executive Engineer Electrical Division No-1 HPPWD Shimla-9
Providing 125 KVA D G set for Isolation ward in the Old Ayurvedic Hospital Building at Nahan Distt Sirmour H P
2021_PWD_49452_1
Electrical Div.No1PWD Shimla 021-22-1338-42 dt.30-
Open Tender
Electrical Works
Item Rate
30 days
SHIMLA
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
E.E.Electrical Division No-I Shimla-9
₹32,700
17 Jul 2021
5 Jul 2021
14 Jul 2021
5 Jul 2021
13 Jul 2021
5 Jul 2021
Amount
Supply, installation, testing and commissioning of 125 KVA/100 KW Diesel engine, 6 cylinders, 4 stroke cycle, radiated cooled, turbocharged Charged Aircooled, developing 159 BHP at 1500 RPM under NTP conditions of BS:5514. The engine shall be provided with electrical starting `arrangement & shall give the electrical output of 125KVA/ 100 KW at 0.8 power factor, 415Volts at the alternator terminal with AMF panel
DIESEL ENGINE : 6 cylinders, 4 stroke cycle, radiated cooled, turbocharged Charged Aircooled , developing 159 BHP at 1500 RPM under NTP conditions of BS:5514. The engine shall be provided with electrical starting `arrangement & shall give the electrical output of 125KVA/ 100 KW at 0.8 power factor, 415Volts at the alternator terminal with AMF panel
Specifications:
6 cylinders, 4 stroke cycle, radiated cooled, turbocharged Charged
Radiator cooled, Engine mounted Water pump, Thermostats, Coolant, Self-contained piping.
High pressure common rail fuel system, Spin on type Fuel filters, Self contained piping.
Lub Oil pump, Spin on type lub oil filter ,Self contained piping
Dry type replaceable paper element air filter, Air intake manifold with necessary connections, Turbo charger.
Exhaust manifold, Flexible piping, Silencer – Hospital Grade.
P1.1 controller with PS0500 Features
Starter, 24V, DC, Battery charging Alternator, With in-built Regulator .
Flywheel, Flywheel housing.
GENSET CONTROLLER -Genset controller shall be a microprocessor based generator set monitoring and control system. The control provides a simple operator interface to the generator set, manual and remote start/ stop control, shutdown fault indication, and an LCD hour counter. The integration of all functions into a single control system provides enhanced reliability and performance compared to conventional generator set control systems. The control has been designed and tested to meet harsh environment in which gensets are typically applied.
Alternator:- Alternator shall be suitable for continuous operation generating 125 KVA at 1500 RPM, 415Volts, 0.8 power factor suitable for 50 Hz, 3 phase system. The alternator shall be in SP-DP enclosure, self excited, self regulated, foot mounted with ball and/ or roller bearings on end shields. The alternator confirms to IS/IEC 60034-1 & shall be suitable for operation in tropical conditions.The alternator shall be of self-excited, self regulated, self ventilated in brushless design, provided with suitable automatic voltage regulator and shall conform to BS:2613 or BS : 5000 and shall give rated output at NTP conditions.
CONTROL PANEL FOR DG SET :
The Generator control shall be indoor type, floor mounted, dust and vermin proof in sheet steel construction. The panel shall have doors at the front and back for proper maintenance. The panel shall have steel channel fabricated kick-plate and bolted type cable gland plate fitted at the bottom. The panel shall be constructed from 2 mm thick steel sheet. All the joint shall have proper gasket.
Monitoring and control devices shall be housed on the front door. Generally the construction of the panel will be such that various equipments for application will be housed in compartment. All incoming and out going power and control cables shall be from the bottom.
The panel will be equipped as follows :-
Incomer - 1 no. 3-pole, 200 Amp MCCB, Set of CTs for metering.
Indication Lamps :- Genset Running, Set on Load, Phase Indication.
SOUND ATTENUATED SYSTEM
Thickness of sheet - 16 - G
The Sound Attenuated DG sets are designed and engineered by the CAD/CAM experts conforming to international standards and mandatory noise level norms achieving Noise level of 75 dB(A) at a distance of 1 Metres. in open environment.The system is made of high-class sheet metal fabricated panels of 16G thickness having modular construction with multi-fold sheet channels & ISMC section for ease of assembly and dismantling, and high quality Fireproof Acoustic material i.e. Rock Wool (50-100 mm thick having 64-96 kg/m3 density).
ACCOUSTIC MATERIALS :-
Acoustic enclosure ismade of CRCA sheets in munsel green shde and a structural/sheet metal base frame painted in black and fire retardant grade acoustic insulation material (P.U .Foam.) complying to IS 8183
VENTILATION
Acoustic enclosure is designed in such a way that there are no hot pockets around engine and it is provided with suitable designed engine radiator which does not allow the temperature to rise more than 70C above ambient temperature.To achieve optimal output and minimum sound level from the DG set, suitable openings are provide for increasing the inflow of air required for combustion & forced ventilation. Air intake system as per the recommendations and engine requirement are provided.
SILENCER
Specially designed low noise silencer with rain cap suitably optimised to meet stringent niose emission standards laid down by MoEF/CPCB
VIBRATION ISOLATION:-
To avoid transfer of vibration from genset to enclosure & surrounding specially designed vibration isolators are used.
Warranty: - Standard 2 years comprehensive warranty on Engine & Alternator, from the date of dispatch or 5000 Hrs. of operation from the date of commissioning, whichever is earlier against any manufacturing defect. 5 Critical Parts of Engine (Cylinder Head, Cylinder Block, Camshaft, Crankshaft, Connecting rod) shall be warranted for 5 Years or 5000 Hrs. of operation whichever is earlier from the date of dispatch against manufacturing defect.
Complete rate of DG Set including, Price of DG set, Price of AMF Panel, Installation charges Cable connection etc. completes in all respects.Makes:- Cummins /equivalent models from Catepillar / Volvo/Kirloskar
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick includingaccessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut,bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
Providin and filling fuel (Diesel) for testing of D.G set
Excavation in foundation, trenches etc. in earth work, lift upto 1.50 meters stacking the excavated soil not more than 3 meters clear from the edge of excavation and then returning the stacked soil in 15 cm and laying cement concrete 1:3:6(1 cement:3 sand:6 graded stone aggregate 20mm nominal size) and curing complete.Foundation size 5.00m*2.00m*0.80m(0.20m above ground level and 0.60m below ground level).
Providing & Laying of one number aluminium conductor, PVC insulated and PVC sheathed armoured/ XLPE power cable, 1.1 KV grade of following sizes on wall surface as required.
Armoured cable 95 sq. mm (3.5 core)
Haminder Pal
KUMAR ELECTRONICS CO.
Bhardwaj Electrical Co.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .