Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.0 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹11.7 L+₹29,910 (2.62%)Rejected-Finance | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹11.8 L+₹37,090 (3.25%)Rejected-Finance INDEX NO E 29 CWE JRC 352 3 GURU NANAK PURA EAST JALANDHAR CITY PIN 144001 | JALANDHAR CITY | JALANDHAR | PUNJAB | 144001 | L3 | Rejected-Finance Other than L1 | |
| 4 | L4₹13.4 L+₹2.0 L (17.4%)Rejected-Finance | L4 | Rejected-Finance Other than L1 | |
| 5 | L5₹13.5 L+₹2.1 L (18.6%)Rejected-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L5 | Rejected-Finance Other than L1 |
Tender Value
₹21 L
EMD Value
₹42,000
Closing Date
8 Dec 2020, 6:00 pmClosed
CWE Amritsar
CWE Amritsar Old Cantt Amritsar
SPECIAL REPAIR TO HT DISTRIBUTION SYSTEM AT OLD CANTT UNDER GE AMRITSAR
2020_MES_391438_1
CWE/ASR-65/2020-21
Open Tender
Civil Works
Item Rate
180 days
Amritsar
Class E
Categoray b ii
8 documents required · 8 mandatory
₹500
GE Amritsar
₹42,000
31 Dec 2020
31 Oct 2020
10 Dec 2020
31 Oct 2020
8 Dec 2020
25 Nov 2020
Amount
Supply, laying, jointing and testing HT XLPE cable cross section area 95 Sqmm, 3 core, 11000 V screened, PVC 'E' grade insulated bedded, galvanised steel (heavy duty ) strip or wire armoured with alluminium conductor 11 KV pressure earthed system conforming to IS 7098 (Part-1 ) 1977 and Part-II of 1985 laid in pipes /ducts/ trenches,under floor and roads or fixed to wall etc incl taking out old unsv cable any type complete all as specified and directed.
Supply, laying, jointing and testing HT XLPE cable cross section area 120 Sqmm, 3 core, 11000 V screened, PVC 'E' grade insulated bedded, galvanised steel (heavy duty ) strip or wire armoured with alluminium conductor 11 KV pressure earthed system conforming to IS 7098 (Part-1 ) 1977 and Part-II of 1985 laid in pipes /ducts/ trenches,under floor and roads or fixed to wall etc complete all as specified and directed. NOTE ITEM NO 1 & 2 :- a. Pre-dispatch factory inspection of cable shall be shall be done by the representative of Accepting Officer. Contractor shall intimate in this regard well in advance so as to avoid delay. b. In case of restrictions on movemnent of inspecting officer on account of Covid pandemic or any other reason, the Accepting Officer may waive off the factory inspection. In such circumstances, the saving to contractor on account of waival of factory ispection ie 1% of cost of Item No 1 & 2 shall be recovered from his payments. c. In case of any dispute, the decision of Accepting Officer shall be final and binding. No claim of the contractor whatsoever in this regard shalll be entertained later.
M&L indoor type cable end terminatrion kit, heat shirnkable jointing material and accessary complete suitable for 11 KV HT XLPE underground cable size 95 to 120 sqmm 3 core including testing after jointing complete all as specified and directed.
M&L oudoor type cable end terminatrion kit, heat shirnkable jointing material and accessary complete suitable for 11 KV HT XLPE underground cable size 95 to 120 sqmm 3 core including testing after jointing complete all as specified and directed.
M&L cable straight through joint box type suitable for 11 KV U/G XLPE screened PVC bedded GI Strip or wire armoured cable size 50 to 95 Sqmm 3 core heat shrinkable, , termination kit jointing material connected to electrical system with and including cable pieces of suitable size length, and the tap vice type compelete all as specified and directed.
M&L cable straight through joint box type suitable for 11 KV U/G XLPE screened PVC bedded GI Strip or wire armoured cable size 120 to 185 Sqmm 3 core , heat shrinkable, , termination kit jointing material connected to electrical system with and including cable pieces of suitable size length, and the tap vice type compelete all as specified and directed.
Excavation in trenches not exc. 1.50 m wide and not exc. 1.50 m in depth for foundation etc. or for laying of pipes and fittings, cables, HT / LT poles, stay assembly etc including forming bottom surfaces to required level and slope and getting out in hard / dense soil complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm thick in each layer as in hard / dense soil complete all as specified and directed.
Removing surplus excavated material (SOIL) to distance not exc. 50 m and depositing where directed at a level not exc. 1.50 m above the starting point complete all as specified and directed.
M & L for sand filling in trenches for cable protection including necessary punning and consolidation as required complete all as specified and directed. NOTE:- Punned thickness only will be considering for payment.
Supplying and laying un-reinforced precast concrete cable cover, class HVP, type 1 with peak, size 300mm x 180mm x 40mm
Supply and fixing HT cable route indicator of cast iron not less than 100mm dia fixed through welding angle iron support of size 35 mm x 35 mm x 5 mm thick, 50 cm long including two coats of synthetic enamel paint over a coat of red oxide primer along HT trench including planting in ground with PCC (1:3:6) type C1 of size 30 cm x 30 cm x 60 cm complete all as specified and directed by Engineer-in-Charge.
S & F 80 mm bore light grade galvanised iron tubing with all necessary GI fittings as in protection pipe of cable, fixed to pole or laid under floor / ground / under road crossings for protection of cable complete all as specified and directed.
Supply, installation, commissioning and testing of switch Air break, Gang operated with 12 insulator switch Triple pole mechanicaly operated, mounted on insulator and steel frame, with mechanism worked from ground level, for current rating 200 Amp operating Voltage 11 KV out door type vertical mounted type complete with locking arrengement,assembly with fuse mount carrier and fuse element of required capacity and isolate suitable for 11 KV including necessary electric connection and 11 KV fuse (drop out type) of capacity 10 Amp.complete with DO fuses assambly with one No. operating Rod of 25 mm dia bore grade GI pipe of suitable length worked out from ground level and handle complete with lock and two Nos keys incl flat iron clamp 50mm x 6mm MS channel of suitable size & length for fixing GOD incl nut,bolt, washers including taking down existing set all as directed by Engineer-in-charge.
M&L for MS cross arms bracing, supports, clamps and back plate, fabricated from structural steel section including nuts, bolts and washers, welding, bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint complete all as specified and directed.
Material and labour for boring hole under road/path/floor etc for laying of XLPE cables any size and type all as specified and directed at site by Engineer-in-Charge.
Supply and errecting in true vertical position steel tubuler poles 11 meter long complete with M S base plate , MS pole cap, bolts nuts & screw as specified type 410 SP-55 with and including painting of poles with black bitumenous paint throughout the length internally and outside upto planting depth and remaining portion with two coats of aluminium paint over a coat of red oxide primer, including painting of 05 Nos. bands / strips of 30 cm wide each with two coats of synthetic enamel paint (black & yellow) at a distance of 30 cm from plinth block upto 1500 mm height and marking / sign writing of pole number and feeders locations of pole with thick synthetic enamel paint (white) complete all as specified and directed. complete all as specified and directed.
Dismantling /taking out old unserviceable ACSR/aluminium conductors any size from existing overhead lines including disconnecting complete all as specified and directed.
Dismantling of cross arms, fabricated from MS structural section of any type and size, duly bolted from existing position and keeping at side for repair/replacement complete all as specified and directed by Engineer in charge
Dismantling of insulators of any type or any size complete from the HT poles including removing the binding wire complete all as specified and directed.
PCC 1:4:8 type D-2, using stone aggregate 40mm graded as in foundation for electric poles including necessary form work where required and fair finish to the exposed surfaces all as specified & directed by Engr-in-charge.
All as per srl item No 21 here-in-before but PCC 1:3:6 type C-2 as in foundation of stays and coping of poles
Re-stretching/stringing only existing ACSR of any size on LT pole including binding the ACSR with insulator, aluminium binding wire complete all as specified and as directed. Note :- One running metre shall be measured for complete 4 to 6 conductors & GI wire.
Kaul Enterprises
Northern cable fault locatoers
BHARAT ENGINEERS
R D Bansal
dinesh enterprises
GULSHAN SINGH GHAI AND SON
Raman Electric Trading Co
UNITED ENGINEERING CORPORATION
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .