Loading…
Loading…
Tender Value
₹4.7 L
EMD Value
₹9,433
Closing Date
22 Jun 2026, 3:00 pm2d left
Similar tender results from the same govt authority in the past 3 years.
AGM (EM)
FCI RO Bhubaneswar
Electrical ARMO works at FSD Jagannathpur for the FY 2026-27
2026_FCI_912577_1
EM/Engg./2026-27/01
Open Tender
Electrical Works
65 days
Jagannathpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹9,433
11 Jun 2026
11 Jun 2026
23 Jun 2026
11 Jun 2026
22 Jun 2026
11 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount | Item Code |
|---|---|---|---|---|---|---|
| 1 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
(a) 20 mm | 165 | Metre | 254 | ₹41,910 | BI01010001010000000000000515BI0100001113 |
| 2 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
(a) 3 x 4 sq. mm | 165 | Metre | 222 | ₹36,630 | BI01010001010000000000000515BI0100001114 |
| 3 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.
(a) Group A | 9 | Each | 1,189 | ₹10,701 | BI01010001010000000000000515BI0100001115 |
| 4 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
(a) 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire | 65 | Metre | 311 | ₹20,215 | BI01010001010000000000000515BI0100001116 |
| 5 | Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required. (a) 5/6 amps switch | 60 | Each | 63 | ₹3,780 | BI01010001010000000000000515BI0100001117 |
| 6 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts "C" curve DP MCB complete with connections, testing and commissioning etc. as required. | 3 | Each | 1,258 | ₹3,774 | BI01010001010000000000000515BI0100001118 |
| 7 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy >135 lm/Watt). Supplying, Installation, Testing & Commissioning of Street light LED fixture, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in allrespect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).
(a) 45 watt | 6 | Each | 1,966 | ₹11,796 | BI01010001010000000000000515BI0100001119 |
| 8 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. | 90 | Metre | 313 | ₹28,170 | BI01010001010000000000000515BI0100001120 |
| 9 | Supplying and fixing of 32 mm dia X 2.00 metres long G.I. pipe (medium class) bracket for mounting of fluorescent / HPMV / HPSV street light fitting on pole including bending the pipe to the required shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts, bolts and washer, painting the flat iron with primer and finish paint etc. as required. | 2 | Each | 1,647 | ₹3,294 | BI01010001010000000000000515BI0100001121 |
| 10 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required
(a) 8 Module (125mmX125mm) | 13 | Each | 517 | ₹6,721 | BI01010001010000000000000515BI0100001122 |