Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.3 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹9.8 L+₹1.2 L (14.1%)Rejected-Finance | L2 | Rejected-Finance Other than L1 |
Tender Value
₹9.9 L
EMD Value
₹20,000
Closing Date
3 Nov 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE NO 2 DELHI CANTT-10
HQ CWE NO 2 DELHI CANTT-10
REPAIR/REPLACEMENT OF HT EXTERNAL NETWORK AND OTHER CONNECTED ITEMS AT DGBR AND SALARIA OFFICERS ENCLAVE UNDER GE WEST DELHI CANTT-10
2022_MES_550924_2
CWE/WEST-27/2022-23
Open Tender
Civil Works
Item Rate
180 days
GE WEST DELHI CANTT
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE WEST DELHI CANTT-10
₹20,000
Yes
11 Jan 2023
13 Oct 2022
5 Nov 2022
13 Oct 2022
3 Nov 2022
21 Oct 2022
Amount
Maintenance,Servicing,cleaning,Vaccum circuit breaker unit 11KV of capacity 630A, make CG,racking out from panel / opening of the VCB for servicing / overhauling, taking out and removing unserviceable/defective parts including cleaning & servicing ,greasing, oiling of the parts etc and replacement of unserviceable parts with new one, reassembling the VCB after overhauling / servicing and Calibration and testing of 11KV VCBs indoor type along with control panel and control wiring,protection system and Calibration of relays by injecting high voltage/ current in primary / secondary side as required for check the triping mechanism complete including rectification of defects noticed complete all as specified and directed by Engineer-in-Charge. (Note :- The quoted rates of the contractor includes for fixing the serviceable parts in position and replacement of unserviceable parts with new parts. The new replaced parts shall be measured and paid for separately under appropriate item of Sch `A’ as `supply only.)
Supply only in repairs following spare parts for 11 KV VCB, upto 630 Amps capacity indoor type of Make:Crompton Greaves Closing coil assy of 11 KV VCB's matching with the existing system complete.
Spring charging motor & gear assy of 230 volts 0.25 HP of 11 KV VCB's type VE -12, matching with the existing VCB system complete.
Supply only Vacuum Interrupter bottle type with brash, connecting parts suitable for 11 KV VCB Panel as per site requirement complete all as specified and directed.(Make:CG)
Isolating contact assembly 630 Amps suitable for 11 KV VCB Panel make CG complete all as specified and directed.
Indicator lamp LED type of different colour as per exiting size, 30/110 volts
Bus bar spoute bushing suitable for HT 11 KV VCB panel board complete all as specified and directed.
Tripping Coil assembly 30 Volts DC suitable for 11 KV VCB Panel complete all as specified and directed.
Maintenance,Servicing,cleaning,Oil circuit breaker unit 11KV of capacity 400A, make CG,racking out from panel / opening of the OCB for servicing / overhauling, taking out and removing unserviceable/defective parts including cleaning & servicing ,greasing, oiling of the parts etc and replacement of unserviceable parts with new one, reassembling the OCB after overhauling / servicing and Calibration and testing of 11KV OCBs indoor type along with control panel and control wiring,protection system complete including rectification of defects noticed complete all as specified and directed by Engineer-in-Charge. (Note :- The quoted rates of the contractor includes for fixing the serviceable parts in position and replacement of unserviceable parts with new parts. The new replaced parts shall be measured and paid for separately under appropriate item of Sch `A’ as `supply only.)
Supply only in repairs following spare parts for 11 KV OCB, upto 400 Amps capacity indoor type of Make:Crompton Greaves Closing coil assy of 11 KV OCB's matching with the existing system complete.
Spring charging motor & gear assy of 230 volts 0.25 HP, of 11 KV OCB's 30 volts matching with the existing OCB system complete.
Tripping Coil assembly 30 Volts DC suitable for 11 KV OCB Panel complete all as specified and directed.
Periodical servicing to 11KV HT RMU (3 ways) any type make- Crompton Greaves model Sabre complete including the following:- (a) Disconnecting the 11 KV line from RMU. (c) Opening the RMU and replacmenet the unserviceable part as required at site. (b) Checking of mechanical system for proper functioning of upward/downward or clock wise and anty clock wise movement of breaker. (d) Cleaning & servicing the fixed/ moving contact, busbar,cable boots with the CTC solution and greasing/oiling the parts where requied or as directed. (e) Tighting the all loose parts and testing complete as directed by EIC. (f) Repair the door/lock incl welding and painting and replacement of lock/handle
Note- (i) Replacing new items shall be measured and paid seperately as a supply only. (ii) Other part which is not included but requierd for functioning of equipment is included in the quoated rate. (iii) Remove the moisture from RMU by heating (iv) The above job to be carried out by engineer of authorised dealer/service centre of concerned manufacturer. (vii) Painting with the approved coloure after preperationg of old surface as directed.
Supply only terminal protector 11 KV, up to 630 Amp as per sample.
Supply only Bus bar obround Bushing Set of three
Supply and filling SF-6 gas to maintain required pressure in RMU complete all as directed.
Supply only Stainless steel/Cast iron RMU on/off handle
Supply only operating mechanism assembly for RMU 3 Way,11kV,630 Amp
Dehydration/filtration of transformer oil by means centrifuging machine electrically operated at site of installation of transformer in running condition including testing of transformer oil before and after filtration by means of oil testing machine, keeping the electrodes at 2.5 mm gap and to achieve die electric strength of filtered oil 50 KV and above complete all as specified and directed.
Supply and topping up/replaced transformer oil conforming to IS : 335 and withstand dielectric strength of 60 KV (when tested with 2.5 Gap electrode) complete all as specified and directed.
S&F in replacement with new HT Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm to 300 sqmm complete all as specified and directed.
Supplying, laying and commissioning of HT XLPE cables, insulated, screened, PVC bedded, galvanized steel strip armoured, earthed, electric power cable with Aluminium conductor, 11 KV grade, 3 Core, 240 Sq.mm cross sectional area laid in trenches / fixed on poles including taking up/down old cables complete all as specified and as directed by the Engineer - in - Charge. Note: Earth work,excavation,cable covers and sand cushioning shall be measured and paid separately.
Material and labour for locating UG cable fault through high voltage UG cable testing van or any authorised service provider in HT cables of any size or distance complete all as specified and directed to the entire satisfaction of Engr-inCharge.
Supplying and laying synthetic Rubber insulated mats 2.5 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m.
M & L Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20cm size
M & L for Locating electrical faults and repair work in HT-LT side of the transformer/VCB/OCB/RMU whenever any fault arises at Salaria officers Enclave area OR HQ DGBR area making complete supply system functional dully rectifying the system fault and repair work complete all as specified and directed. Note: (a) Whenever any breakdown reported the Contractor will have to take immeadiate action and send skilled Technecian immediately on site. (b) Any parts required to be replaced during repair work shall be measured and paid for separately.
S & F in repair Perforated Cable Tray made out of steel with galvanized coating 3 mm thick suitable for mounting on wall/Floor with suitable size/Nos of fastners complete all as specified and directed.
M&L for Taking down existing unserviceable Lightning Arrestors and S & F HT Lightning arrestor Metal Oxide Type (Gap less) heavy duty single pole suitable for system voltage of 11 KV and working rated arrestor voltage 10 KV with normal discharge current of 10 KA, all as per IEC 99.4 effectively earthed complete all as specified and directed.
M & L for Dismentaling,Taking down existing unserviceable GOAB switch and S&F in repair new Switch 9 insulator air break gang operated (Swing out expulsion ruse insulators with voice connector in GOAB coller), tripple pole mechnical operated from ground level mounted on insulator and Mild steel frame out door type suitable for vertical installation single break provided with locking arrangement consisting of MS channel HT post top insulator with drop out fuses operating rod 20mm dia GI medium grade pipe worked from ground levelconfirming of IS 1818 of 1972 and continuous current rating upto 400 amp, 9 Insulator and volt 11 KV, complete all as specified and as directed.
M & L in repair straight through cable jointing kit 11 kv for cable sizes 240 to 400 Sqmm, 3 core complete all as specified and directed.
M&L for excavation in trenches in soft soil n.exc 1.5 Mtr wide and n.exc 1.5 meter in depth for laying of cables/pole etc setting out trimming the site forming bottom surface to required level complete all as specified and directed by Engr-in-Charge.
M&L for returning filling in-trenches including spreading leveling watering and well ramming in layers with soft/loose/dense soil n.exc 25 cm thick in each layer of soil complete all as specified and directed by Engr-in-Charge.
M&L for removing/excavated soil to a distance n.exc 50 Mtr and depositing where directed at a level not exc 1.5 Mtr above the starting point complete all as specified and as directed by Engr-in-Charge.
M&L for sand cushioning with a layer of sand Jamuna 23 cm thick (8 cm under and 15 cm above the cable) in trenches complete all as specified and as directed by Engr-in-Charge
M&L for Laying old serviciable un-reinforced precast concrete cable covers for cable protection of class LV type 1 flat of size 250 x150 x 40 mm.
Supply and laying un-reinforced precast concrete cable covers for cable protection of class LV type 1 flat of size 250 x150 x 40 mm.
Earthing complete with GI earth plate electrode of size 600mm x 600mm x 6mm thick buried directly to ground vertically to a depth not less than 2.25 Mtr below the ground level with top edge of earth plate not less than 1.65 Mtr below normal ground level connected to GI strip 32 x 6 mm size and earthing lead protected with 50 mm bore GI pipe, light grade, filling around with charcoal dust and salt including excavation, returning, filling of earth and disposal of surplus soil to a distance not exceeding 50 mtr and connected to GI strip by means of GI nuts, bolts and washers strip connected to earth plate including chamber PCC 1:3:6 type C-1 using 20mm graded crushed stone aggregate in concrete pit pre-cast RCC 40 mm thick reinforced with 6 mm dia round at 75 mm C/C both way with 12 mm dia mild steel plain bar lifting handle 2 Nos funnel with wire mesh 20 mm dia GI pipe light grade watering pipe and frame work complete all as shown in electrical plate No. 3 of SSR Part-I 2009 including testing on completion complete all as specified and as directed.
M&L earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/ pipe or fixed to pole or any other indicated situation using GI strip 32 x 6 mm as earthing lead complete all as directed including taking down the old unserviceable complete all as specified and directed.
Material and labour for disconnecting electrical connection removing the defective transformer loading and transporting to workshop from site and vice-versa including disconnecting and rewinding of 11/0.433KV, 630 KVA, Three Phase, Four Wire, 50Hz make-Transtron/GEC transformer with paper insulated copper winding wire as per original data complete rewinding of HV/LV on three limbs providing insulation material like spares, wooden blocks, cotton tape etc. and re-conditioning three limbs complete opening, replacement of cock sheet packing, vent diaphragm replacement of LT terminal plate, filling of new transformer oil for top up with existing oil after proper filtration of 50 KV dielectric strength and testing of transformer at factory and at site after connecting all electrical connection in full load all Complete all as directed.Note: Topping Transformer Oil/Parts will be measured and paid seperately.
Notes :- 1. Spares required will be measured and paid separately under appropriate item. 2. The Quoted Rate shall be deemed to include transportation, electrical connections, Testing & Commissioning. 3. Necessary test certificate from authorised workshop after repair shall be submitted by the contractor to the Engrin-Charge.
Supply only following Items / Spares required for transformers :-
HT coil of suitable gauge of paper insulated copper winding wire for any capacity of transformer
LT coils of suitable guage of paper insulated copper winding wire for any capacity of transformer
Gasket for Transformer
630 KVA transformer LT bushing assembly complete all as specified and directed.
630 KVA transformer HT bushing assembly complete all as specified and directed.
M & L in repair 250 KVA transformer LT bushing assembly complete all as specified and directed.
M & L in repair 250 KVA transformer HT bushing assembly complete all as specified and directed.
UNIQUE BUILDERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .