Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.0 LAccepted-AOC GROUND FLOOR THAKUR COMPLEX BASANTPUR | BASANTPUR | SHIMLA | HIMACHAL PRADESH | 171018 | L1 | Accepted-AOC Being L1 | |
| 2 | Rejected-Technical | - | Rejected-Technical L2 |
Tender Value
₹28.9 L
EMD Value
₹58,000
Closing Date
20 Jul 2021, 5:00 pmClosed
XEN Elect Divn No II HPPWD Shimla-2
XEN Elect Divn No II HPPWD Shimla-2
Providing electrical installation
2021_PWD_49643_1
ED.II.GA.Tender/21-22-2435-36 dated 06.07.2021
Open Tender
Electrical Works
Item Rate
365 days
Shimla
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
EE Elect Division No II
₹58,000
30 Jul 2021
9 Jul 2021
21 Jul 2021
9 Jul 2021
20 Jul 2021
9 Jul 2021
Amount
Wiring for light point / fan point / exhaust fan / call bell point with 1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit and earthing the light point with 1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable as required. Group C.
Light Point
Wiring for power plug with 2x4 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 1 No.4 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable for earthing as required.
Wiring for power plug with 4x4 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 2 No.4 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable for earthing as required.
Wiring for circuit/sub-main with following size PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 1 No.HRFRLS/PVC insulated single core copper conductor cable of same size for earthing as required.
2x1.5 Sq. mm.
Supplying and laying unarmoured 3 core 1.5 sq. mm cable on existing tray/on surface as required complete in all respects
Supplying and fixing MS angle slotted cable tray of size 200 mmx54 mm L&T make as required complete in all respects
Supplying and fixing G.I. Modular box of (140mmx78mmx50mm) size with modular plate and cover in recess including providing and fixing 5 pin 5/6 amps modular socket outlet and 5/6 amps, modular switch, connections etc. as required.
Supplying and fixing G.I. Modular box of (140mmx78mmx50mm) size with modular plate and cover in recess including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps, modular switch, connections etc. as required.
Supplying and fixing sheet metal bus-bar chamber suitable for 100 Amp. 415 volts capacity with 4 No. copper strip bus-bars each of length 300mm & cross-sectional area (25.4mmx3.17mm), enclosure made from 1.6 mm thick M.S. sheet having overall dimensions (380mmx400mmx150mm) nominal with all accessories including connections, earthing the body etc. as required:-
Providing and fixing following rating and breaking capacity MCCB in the existing cubical panel board including drilling holes in the cubicle panel, making connections, etc. as required.
100 Amp. -10 KA
Supplying and erection of 6 amps. to 32 amps. rating, 10 KA breaking capacity, 240 volts, 'C' curves, miniature circuit breaker of following poles in the existing MCB DB complete with connections etc. as required:-
Single pole. Cat-A.
Supplying and erection of 40/50/63 amps rating, 10 KA breaking capacity, 240 volts, 'C' curves, miniature circuit breaker of following poles in the existing MCB DB complete with connections etc. as required:-
Double pole. Cat-A.
Triple pole & Neutral. Cat-A.
Supplying and fixing following rating, double pole (single phase & neutral) 240 volts, residual current circuit breaker (RCCB), having a sensitivity current up to 300 miliampers in the existing MCB DB complete with connections, testing and commissioning etc. as required.
63 Amps. Cat-A.
Supplying and fixing following rating, four pole (three phase & neutral) 415 volts, residual current circuit breaker (RCCB), having a sensitivity current up to 300 miliampers in the existing MCB DB complete with connections, testing and commissioning etc. as required.
25 Amps. Cat-A.
Supplying and fixing of following way, single pole and neutral sheet steel MCB distribution board, 240 volts, on surface / recess, complete with tinned copper bus- bar, wire-set, neutral link, earth bar, din-bar, detachable gland plate, blanking plate, cable, identification labels interconnections, phosphatized and powder painted, including earthing etc. as required:-
Double door-8 way
Supplying and fixing of following way triple pole and neutral, sheet steel MCB distribution board, 415 volts, on surface / recess, with provision for 4-pole MCB/Isolator/RCCB/RCBO as incomer and SP MCBs as outgoing, complete with tinned copper bus- bar, wire-set, neutral link, earth bar, din-bar, detachable gland plate, cable, identification labels interconnections, phosphatized and powder painted, including earthing etc. as required:-
Single door-6 way (8+18), horizontal type
Single door-8 way (8+24), horizontal type
Single door-12 way (8+36), horizontal type
Earthing with copper earth plate 600mm x 600mm x 3mm thick, including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) complete as required.
Extra for using salt and coke for G.I. or copper plate earth electrode complete as required.
Providing and fixing 25mm x 5mm copper strip on surface or in recess for earth connections etc. as required.
Providing and fixing 8 SWG (4 mm dia.) copper wire on surface or in recess for loop earthing as required.
Providing and fixing of lightning conductor finial, made of 25 mm dia. 300 mm longGI tube, having single prong at top, with 85 mm dia 3 mm thick copper base plate including holes etc. complete as required.
Supplying and fixing G.I. tape 20mmx3mm thick on parapet or surface of wall for lightning conductor as required ( for horizontal run)
Fixing of copper/G.I. tape 20mmx3mm thick on parapet or surface of wall for lightning conductor as required ( for vertical run)
Earthing with G.I. earth plate 600 mmx600 mmx 6 mm thick, including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) complete as required.
Providing, laying and fixing of one No. aluminium conductor, PVC insulated and PVC sheathed, armoured/XLPE power cable, working voltage 1100 volts grade on surface etc. of the required size:-
Armoured cable 16 sq. mm (4 core)
Armoured cable70 sq. mm (3.5 core)
Armoured cable 10 sq. mm (twin core)
Armoured cable 6 sq. mm (twin core)
Armoured cable240sq. mm (3.5 core)
Providing and fixing SS Enclosure for DU / DH MCCBs, suitable for 4-Pole MCCBs etc. as required. Make: L&T, Schneider, Siemens, ABB, C&S etc.
D.S Ranta Electrical Contractor
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.PDF
finance_74291.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .