| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.5 LAccepted-AOC | L1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹18.9 L+₹43,650 (2.36%)Rejected-AOC FLAT NO 1004 BUILDING NO L 11 KEDAR HOUSING SOCIETY 10TH FLOOR SECTOR NO 21 TALOJA PHASE 2 PANVEL RAIGAD NAVI MUMBAI 410208 | NAVI MUMBAI | RAIGAD | MAHARASHTRA | 410208 | L2 | Rejected-AOC NOT BEING LOWEST | |
| 3 | L3₹21.7 L+₹3.3 L (17.7%)Rejected-AOC | L3 | Rejected-AOC NOT BEING LOWEST | |
| 4 | L4₹21.9 L+₹3.4 L (18.5%)Rejected-AOC 205 PARSHAV VIHAR PLOT NO 50 1 P EXTN PATPARGANJ DELHI 110092 | DELHI | EAST DELHI | DELHI | 110092 | L4 | Rejected-AOC NOT BEING LOWEST | |
| 5 | L5₹22.0 L+₹3.5 L (18.9%)Rejected-AOC | L5 | Rejected-AOC NOT BEING LOWEST |
Tender Value
Refer Docs
EMD Value
₹48,600
Closing Date
7 Jan 2025, 6:00 pmClosed
COL MANOJ NEGI
CWE AF NORTH BANGALORE BELLARY ROAD JC NAGAR POST BANGALORE 560006
PROVN OF SMOKE DETECTOR AND FIRE ALARM SYSTEM CETAIN ROOMS AND LABS AT CHAF UNDER GE (AF) BANGALORE
2024_MES_687866_1
87470CWEAFNBAN
Open Tender
Civil Works
Item Rate
180 days
GE (AF) BANGALORE
AS PER NIT
7 documents required · 7 mandatory
₹500
GE (AF) BANGALORE
₹48,600
Yes
19 Feb 2025
10 Dec 2024
14 Jan 2025
11 Dec 2024
7 Jan 2025
24 Dec 2024
11 Dec 2024 - 18 Dec 2024
Amount
Supply, installation, commissioning and testing of Fire detectors complying with and type certified to EN 45 addressable type multisensor detector with heat and smoke combination photoelectric / optical base with self built intelligence as per IS:2175 complete all as specified and directed.
Supply, installation, commissioning and testing of Fire Alarm Control Panel complying with BS EN 54 single loop panel of capacity from 99 detectors and 99 modules upto 200 detectors and modules complete all as specified and directed.
S & F of fire Alarm sounder / siren, electronic type, horizontal single stage, continuous normal operation for atleast 50 minutes with sound level 65 DB to 120 DB measured from 1.5 mtr with sound output variation of +5 DB, 500 Mtrs range complete all as specified and directed.
Supply, installation, commissioning and testing of response indicator suitable for addressable fire alarm system including all accessories complete all as specified and directed.
Supply, installation, commissioning and testing of Manual Call Point for compliant with latest standards and is designed to interface with DIP switches provided for addressing of the call point. The RED blinking LED indicates normal operating condition. Activation of MCP is indicated by RED, steady LED including all accessories complete all as specified and directed.
Supply and Laying of Red coloured copper 2 core 1.5 sqmm electrical control cable. This PVC insulated and round sheathed wire features a bright annealed bare copper conductor and it supports voltage grade up to 1100 V easily, including all accessories, suitable for fire-alarm system control wiring complete all as specified and directed.
Supply and laying of 25 mm Steel rigid Conduit for surface area including Bends, Junction boxes, coupling Base, saddles screws etc complete all as specified and directed.
Supply, installation, commissioning and testing of Repeater Fire Alarm Panel, Active Repeater, Silence, Mute, Reset, Accept, Evacuate and Test Controls, DX control panels require 24 Vdc supply, ZX control panels require 24 Vdc supply and an RS485 card of size 165 x 254 x 50mm (H x W x D) complete all as specified and directed.
Supply, installation and testing of Beam Master detector with transmitter and receiver Bayblend FR110 Trim, Lexan Lens Cover, Noryl Blackbox, 1.77kg, 2mA @ 24Vdc, 200 x 230mm reflector complete all as specified and directed.
S & F CO2 Type 4.5 Kg Capacity Fire Extinguishers complete all as specified and directed.
S & F ABC Type 06 Kg Capacity Fire Extinguishers complete all as specified and directed.
M & L for removing and refixing of any type of false ceiling for the installation of sch items i.e fire detector wiring conduits etc including all necessary items and civil works complete all as specified and directed.
M & L for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the earth plate not less than 1.5 m below normal ground level, connected to galvanised iron wire 4 mm dia by means of bolts, nuts and washers of galvanised iron or steel connected to transformer, DG set, LT panel / DB/ earthing test point including PCC chamber, RCC cover 50mm thick with 8 mm dia bars, protection pipe, watering pipe 20 mm GI, funnel etc including excavation, earth work, disposal of surplus soil and earth strip protection pipe of GI 15 mm bore light grade upto 7.5 metre including testing on complete all as specified and directed. Note :- The rate is deemed to be inclusive of the cost of earth work, excavation on any type soil and removal of surplus soil to a distance of 50 Mtrs, earth lead protection GI pipe medium grade with suitable size from earth plate electrode to main switch, GI strip length up to 7.50M will be measured as one unit) including taking down of old unserviceable.
M/s ASPIRE ENGINEERING ENTERPRISES (BID ID -3203157)
B5BUILDING SOLUTIONS (BID ID -3207833)
SANJEEV ENTERPRISES (BID ID -3199986)
Hardik Engineers (BID ID -3201231)
Accurate Power Systems (BID ID -3208214)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .