Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹74.7 CrAccepted-AOC | ₹74.7 Cr Quoted ₹78.6 Cr | L1 | Accepted-AOC Accept |
| 2 | Rejected-Technical | - | - | Rejected-Technical Disqualified |
| 3 | Rejected-Technical | - | - | Rejected-Technical Disqualified |
| 4 | Rejected-Technical N A | FARIDABAD | HARYANA | 121004 | - | - | Rejected-Technical Disqualified |
| 5 | Rejected-Technical MATERE HOUSE SEC NO 14 PRADHIKARAN PUNE MAHARASHTRA INDIA 412105 | PUNE | MAHARASHTRA | 412105 | - | - | Rejected-Technical Disqualified |
Tender Value
₹72.1 Cr
EMD Value
₹36.1 L
Closing Date
15 Jul 2024, 6:00 pmClosed
Executive Engineer
Executive Engineer, P. W. Bldg Division, Pune at Govt. Milk Scheme Campus
Construction of Sahakar Sankul building of Basement 1 2 G 10 floors for Sahakar Department at mouje Yerwada sr. no. 191 A P, Pune 06 Currently proposed Construction of Sahakar Sankul building of Basement 1 L.G. U.G. 4 floors for Sahakar Dep
2024_PWDRP_1041466_1
E-Tender Notice No. 1 for 2024-25 IInd Call
Open Tender
Civil Works
730 days
Shivajinagar Pune
Please refer Tender documents.
3 documents required · 3 mandatory
₹11,800
₹36.1 L
2 Dec 2024
18 Jun 2024
18 Jul 2024
18 Jun 2024
15 Jul 2024
18 Jun 2024
Amount
Excavation for foundation in earth, soil of all types, sand, gravel and soft murum, including removing the excavated material up to a distance of 50 m. beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift upto 1.5 m.) By Mechanical Means
Excavation for foundation in earth, soils of all types, sand,gravel and soft murum, including removing the excavated material upto a distance of 50 metres beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift from 1.5m to 3.0m) By Mechanical Means
Excavation for foundation in hard murum including removing the excavated material upto distance of 50 metres beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift upto 1.50 m) By Mechanical Means
Excavation for foundation in Hard murum including removing the excavated material upto a distance of 50 metres beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift from 1.5 to 3.0m.) By Mechanical Means
Excavation for foundation in hard murum and boulders including removing the excavated material up to a distance 50 metres, beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift upto 1.5m.) By Mechanical Means
Excavation for foundation in Hard murum and boulders including removing the excavated material upto a distance of 50 metres, beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift from 1.5 m to 3.0 m.) By Mechanical Means
Excavation for foundation in Hard murum and boulders including removing the excavated material upto a distance of 50 metres, beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift from 3 m to 4.5 m.) By Mechanical Means Increase Rate by 20% ( as per SSR guidline pg no 6 )
Excavation for foundation in Soft rock and old cement or lime masonry foundations including removing the excavated material upto a distance of 50 metres beyond the building area and stacking as directed, including dewatering, preparing the bed for the foundation and necessary back filling with available earth/murum, ramming ,watering including shoring and strutting etc. complete. (Lift from 1.5m To 3.0 m.) By Mechanical Means
Excavation for foundation in Soft rock and old cement or lime masonry foundations including removing the excavated material upto a distance of 50 metres beyond the building area and stacking as directed, including dewatering, preparing the bed for the foundation and necessary back filling with available earth/murum, ramming ,watering including shoring and strutting etc. complete. (Lift from 3m To 4.5 m.) By Mechanical Means Increase Rate by 20% ( as per SSR guidline pg no 6 )
Excavation for foundation in Soft rock and old cement or lime masonry foundations including removing the excavated material upto a distance of 50 metres beyond the building area and stacking as directed, including dewatering, preparing the bed for the foundation and necessary back filling with available earth/murum, ramming ,watering including shoring and strutting etc. complete. (Lift from 4.5m To 6.0 m.) By Mechanical Means Increase Rate by 30% ( as per SSR guidline pg no 6 )
Excavation for foundation in Hard rock by chiselling, wedging, line drilling, etc. including trimming and levelling the bed, removing the excavated material upto a distance of 50 metres beyond the building area stacking as directed, dewatering and back filling with available earth/ murum watering, ramming etc. complete. (Lift from 1.5m To 3 m.). By Mechanical Means Increase Rate by 10% ( as per SSR guidline pg no 6 )
Excavation for foundation in Hard rock by chiselling, wedging, line drilling, etc. including trimming and levelling the bed, removing the excavated material upto a distance of 50 metres beyond the building area stacking as directed, dewatering and back filling with available earth/ murum watering, ramming etc. complete. (Lift from 3m To 4.5 m.). By Mechanical Means Increase Rate by 20% ( as per SSR guidline pg no 6 )
Excavation for foundation in Hard rock by chiselling, wedging, line drilling, etc. including trimming and levelling the bed, removing the excavated material upto a distance of 50 metres beyond the building area stacking as directed, dewatering and back filling with available earth/ murum watering, ramming etc. complete. (Lift from 4.5m To 6.0 m.). By Mechanical Means Increase Rate by 30% ( as per SSR guidline pg no 6 )
Disposing the excess excavated material Murum, Earth obtained from the items of excavation and disposing the same off the site and at dumping place approved by the governing authority including loading, unloading and all leads and lifts complete.
Dewatering on BHP basis by using water pump including diversion of stream, providing cofferdams, earthern bunds etc. as may be necessary for foundation and other parts of the the works and pumping out water during and after excavation as may be required by using 3.0 BHP pump etc. complete. (prior approval of Superintending Engineer will be necessary)
Providing preconstructional antitermite treatment as per I.S. 6313 (Part-II) by treating the top surface of plinth filling at the rate of 5 litres of emulsion concentrate at 1.0 percent of clorophyrifos per One Square Metre of surface area covering ten years guarantee on bond paper.
Providing preconstructional antitermite treatment as per I.S. 6313 (Part-I) to the soil along the external face of building by punching holes of 1.2 of 1.5 C.M. diametre about 30 -60 cm deep at 15 cm c/c as close to the wall as possible and to inject 0.5 percent of aldrin or clorophyrifos at the rate of 7.5 litres per hole and sealing the same with proper filling and covering 10 years guarantee on bond paper.
Filling in plinth and floors with approved excavated material in 15cm. to 20cm. Layers including watering and compacting etc. complete.
Providing dry/ trap/ granite/ quartzite/ gneiss rubble stone soling 15 cm to 20 cm thick including hand packing and compacting etc. complete.
Providing and laying Cast in situ/Ready Mix cement concrete in M10 of trap/ granite/quartzite/gneiss metal for foundation and bedding / steps including steel centering, formwork, laying/pumping, compacting, roughening them if special finish is to be provided, finishing uneven and honeycombed surface and curing etc. complete. The Cement Mortar 1:3 plaster is considered for rendering uneven and honeycombed surface, only. Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etc. (Wooden centering will not be allowed.),with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
Providing and fixing 20 to 25 mm thick rough shahabad box type waterproofing for basement or underground floor on a base of Cement concrete 1:3:6, including sub base of 2.50 centimeter thick Cement mortar 1:3 with conceal, secrete (RMW), Algae proof or other alike waterproofing liquids, raking of joints upto 35 mm depth, filling the joints with 6 mm size crushed metal, hand grouting with cement slurry, curing and cleaning, with 7 years guarantee on court fee stamp of Rs. 100/- with ponding test etc complete. (excluding Cement concrete 1:3:6 base concrete )
Providing and fixing 20 to 25 mm thick rough shahabad box type waterproofing treatment to vertical outside faces of Reinforced Cement concrete walls of basement or underground floor including filling the gap of 25 mm between rough shahabad and R.C.C. walls with cement grout mixed with water proofing liquid Algae proof or other alike with one tile lift method, brushing the joints horizontally with cement slurry mixed with water proofing liquid for width 30 to 35 mm and sloping coping over topmost tile with cement mortar 1:3, butting the bottom most with Cement concrete 1:2:4 mixed with water proofing liquid, curing, with 7 years guarantee on court fee stamp of Rs.100/- with ponding test etc complete. (excluding Cement concrete 1:3:6 base concrete)
Providing and laying jointless Polydee-LM, a highly flexible elastometric coating for RCC / cementitious surface for terrace waterproofing on B.B. Coba / R.C.C, after application of TP- 42 Primer on perfectly clean surface (free from loose dust and foreign matter) application of 1st coat of Polydee-LM @ 700 gms/ One Square Metre and applying 2nd coat of Polydee-LM @ 700 gms/ One Square Metre and finishing the same with sprinkling the AG-10 granules on the wet coating. (After finishing covering the treatment with 25mm cement plaster for protection with fibrillated 6mm Plyplast fibre @ 125 gms/ One Square Metre to be paid in separate item.) covering 7 years guarantee on Court Fee Stamp Paper of Rs. 100/- etc. Complete. Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and laying Cast in situ/Ready Mix cement concrete M-30 of trap / granite/quartzite/ gneiss metal for R.C.C. work in foundations like raft, strip foundations, grillage and footings of R.C.C. columns and steel stanchions etc. columns as per detailed designs and drawing or as directed including Steel centering formwork, cover blocks laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete. (Excluding reinforcement and structural steel). with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
Providing and laying Cast in situ/Ready Mix cement concrete M-40 of trap / granite/quartzite/ gneiss metal for R.C.C. columns as per detailed designs and drawing or as directed including steel centering, formwork, cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete,(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Providing and laying Cast in situ/Ready Mix cement concrete in M-30 of trap/ granite/ quartzite/ gneiss metal for R.C.C. pardi of required thickness including steel centering, formwork, cover blocks, laying/pumping, compacting and roughening them if special finish is to be provided and curing complete. (Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Providing and laying Cast in situ/Ready Mix cement concrete M-30 of trap / granite/quartzite/ gneiss metal for R.C.C. beams and lintels as per detailed designs and drawings or as directed including steel centering, formwork, cover blocks, laying/pumping, compactionand roughening the surface if special finish is to be provided and curing etc. complete. (Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Providing and laying Cast in situ/Ready Mix cement concrete M-40 of trap / granite/quartzite/ gneiss metal for R.C.C. beams and lintels as per detailed designs and drawings or as directed including steel centering, formwork, cover blocks, laying/pumping, compactionand roughening the surface if special finish is to be provided and curing etc. complete. (Excluding reinforcement and structural steel). with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and laying Cast in situ/Ready Mix cement concrete M-30 of trap/ granite/ quartzite/ gneiss metal for R.C.C. slabs and landings as per detailed designs and drawings including steel centering, formwork, cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete,(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Providing and laying Cast in situ/Ready Mix cement concrete M-40 of trap/ granite / quartzite/ gneiss metal for R.C.C. slabs and landings as per detailed designs and drawings including steel centering, formwork, cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete,(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and laying Cast in situ/Ready Mix cement concrete in M-30 of trap / quartzite/granite /gneiss metal for R.C.C. Waist slab, and steps of staircases as per detailed design and drawings or as directed including steel centering, plywood/ steel formwork, steel props, laying/pumping, compaction, finishing uneven and honeycombed surface with C.M. 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening the surface if special finish is to be provided and curing etc. complete. (Excluding einforcement, including cover block).(Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etc.) with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and laying Cast in situ/Ready Mixcement concrete M-30 of trap/ granite/ quartzite/ gneiss metal for R.C.C. chajja as per detailed design and drawings including steel centering, formwork, cover blocks, laying/pumping, compacting and roughening the surface if special finish is to be provided and curing complete. (Excluding reinforcement and structural steel). with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing in position TMT - FE - 500 bar reinforcement of various diameters for R.C.C. pile caps, footings, foundations, slabs, beams columns, canopies, staircase, newels, chajjas, lintels pardis, copings, fins, arches etc. as per detailed designs, drawings and schedules. including cutting, bending, hooking the bars, binding with wires or tack welding and supporting as required complete. Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Providing and fixing in position to the exact profile and prestressing the high tensile strands to specified ultimate strength, standard end anchorages, cable ducts, grouting ducts after prestressing and bearing plates with wedges as per detailed drawings including necessary plant and machinery for prestressing etc. Complete. Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing fly ash brick masonry with conventional / I.S. type fly ash bricks in C.M. 1:6 in foundation and plinth including bailing out water manually striking joints, racking out joints watering and scaffolding etc. complete.
Providing fly ash brick masonry with conventional/ I.S. type bricks in cement mortar 1:6 in superstructure including striking joints, raking out joints, watering and scaffolding etc. Complete Lower Ground Floor
Terrace Floor
Providing Autoclaved Aerated Concrete Block masonary of conforming to IS:2185 (Part 3) - 1984 in extra fine jointing mortar of fixoblock of UltraTech or equivalent in superstructure including striking joints, raking out joints and scaffolding etc. Complete. (The test shall be carried out conforming to IS:6441 (Part I) – 1972) Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Providing Autoclaved Aerated Concrete Block masonary of conforming to IS:2185 (Part 3) - 1984 in extra fine jointing mortar of fixoblock of UltraTech or equivalent in Half brick thick wall including striking joints, raking out joints and scaffolding etc. Complete. (The test shall be carried out conforming to IS:6441 (Part I) – 1972) Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing chicken mesh of 22 gauge, with about 30 cm. width at the junction of R.C.C members and brick work, of approved quality including fixing mesh in position by necessary drilling in concrete /B.B.masonry and or tying by binding wire etc. Complete. Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Providing internal cement plaster 12mm thick in single coat in cement mortar 1:3 without neeru finish to concrete or brick surfaces, in all position including scaffolding and curing etc. Complete. Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Providing sand faced plaster externally in cement mortar using approved screened sand, in all positions including base coat of 15 mm thick in cement mortar 1:4 using waterproofing compound at 1Kilogramper cement bag curing the same for not less than 2 days and keeping the surface of the base coat rough to receive the sand faced treatment 6 to 8 mm thick in cement mortar 1:4 finishing the surface by taking out grains and curing for fourteen days scaffolding etc.complete. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Providing and applying gypsum plaster ( with Gypsum material ) with finishing with gypsum material in 10 to 13 millimeter thickness to previously plastered surface / or on newly brick surface ( Excluding rough cast plaster ) in all position including preparing and Finishing the surface scaffolding etc.complete. Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Providing and applying Two coats of wall care Putty on plastered surface and Ceiling and Walls to prepare surface even and smooth of approved make, etc complete. Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Providing cement based water proofing treatment to terraces (Indian water proofing or alike) with brick bats laid in required slope to drain the water for any span after cleaning the base surface. Applying a coat of cement slurry admixed with approved water proofing compound and laying the brick bats on bottom layer in C.M.1:5 admixed with approved water proofing compound filling up to half depth of brick bats, curing this layer for 3 days, applying cement slurry over this layer joints of brick bats with C.M.1:3 admixed with approved water proofing compound and finally top finishing with average 20 mm. thick layers of same mortar added with jute fiber at 1Kilogramper bag including finishing the surface smooth with cement slurry admixed with approved water proofing compound. Marking finished surface with false squares of 300mm x 300 mm. making the junctions at the parapet rounded and tapered top for required height, with drip mould at the junction of plaster and parapet and curing and covering 10 years Guarantee against leakproofness on Court fee stamp paper of Rs. 500/- including ponding test etc. Complete. Basement Floor
1st Floor
2nd Floor
4th Floor
Terrace Floor
Providing internal cement plaster 12mm thick in single coat in cement mortar 1:4 with fine cement finish 1.5 mm thick without neeru finish to concrete or brick surfaces, in all positions including scaffolding and curing etc. Complete. Basement Floor
Terrace Floor
Providing and applying a base coat comprising of 1Kilogram Polydee-MC and 1Kilogram fresh cement after wetting the surface followed by drying the surface for 2 days, apply primer coat of TP-40 and after drying, applying Polydee-11 two component (mixing ratio 2 A : 1 B) ) Antibacterial food grade coating inside drinking water tank in two coats with time interval of minimum 8 hrs. covering 7 years guarantee on Court Fee Stamp Paper of Rs. 100/- etc. Complete. Basement Floor
Terrace Floor
Providing and laying cement concrete flooring 50mm thick with M20 cement concrete laid to proper level and slope in alternate bays including compaction, filling joints, marking lines to give the appearance of tiles of 30cm x 30cm or other size laid diagonally/ square etc. finishing smooth (with extra cement) in any colour as directed and curing etc. complete.with Crushed sand VSI Grade Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and laying vitrified mirror / glossy finish tiles decorative type having size 590 mm to 605 mm x 590 mm to 605 mm of 8 to 10 mm thickness and confirming to IS. 15622-2006 ( group Bla) of approved make, shade and pattern for flooring in required position laid on a bed of 1:4 cement mortar including neat cement float, filling joints, curing and clearing etc. Complete. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and laying vitrified mirror / glossy finish tiles having size 590 mm to 605 mm x 590 mm to 605 mm of 8 to 10 mm thickness and confirming to IS. 15622-2006 ( group Bla) of approved make, shade and pattern for dado and skirting in required position fixed in 1:4 cement mortar including neat cement float, filling joints, curing and clearing etc. Complete Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and laying vitrified matt fininsh tiles having size 590 mm to 605 mm x to 605 mm of 8 to 10 mm thickness and confirming IS. 15622-2006 (Group Bla) of approved make, shade and pattern for flooring in required position laid on a bed of 1:4 cement morar including neat cement float, filling joints, curing and cleaning etc. Complete. 4th Floor
Providing and laying vitrified matt finish tiles having size 590 mm to 605 mm x to 605 mm of 8 to 10 mm thickness and confirming IS. 15622-2006 (Group Bla) of approved make, shade and pattern for dado and skirting in required position fixed in 1:4 cement mortar including neat cement float, filling joints, curing and cleaning etc. Complete. 4th Floor
Providing and laying Vitrified tlles (Matt and Antiskid finish) In floor in 800milimeter x 1200milimeter sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to 1S: 15622, of approved brand and manufacturer, in all colours and shade, lald on 20 millmeter thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slury @3.3 kg/sgm including grouting the joints with white cement and matching pigments excetra The tiles must be cut with the zero chipping diametermond cutter only Laying of tiles will be done with the notch trowel, plier, wedge clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily.as directed by engineer-in- Charge. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and laying matt finish ceramic tiles of having size 30 cm x 30 cm confirming to I.S.15622/2006 (group D II-A) and 7 to 8 mm thick for flooring in required position laid on a bed of 1:4 cement mortar including cement float, filling joint with white/colour cement slurry cleaning curing etc. Complete. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and laying ceramic tiles having size 30 cm. x 60 cm. confirming to corresponding I.S. for dado and skirting in required position with readymade adhesive mortar of approved quality on plaster of 1:2 cement mortar including joint filling with white/ colour cement slurry cleaning curing etc. Complete. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and laying telephone black / Amba White / Cadburybrown / Ruby red / Ocean Brown granite stone of 18 to 20 mm thick for door frame/ dado/ window boxing etc. On C.M. 1:6 including filling joints with polymer base filler nosing/moulding the sharp edges wherever necessary, curing, etc. Complete. Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing sills of required material 20mm to 25mm thick, on a bed of cement mortar 1:4 including cement float, filling joints with neat cement slurry, curing, moulding edges, polishing,cleaning complete. b) Granite Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and laying in position flooring of telephone black / Amba White / Cat bary brown / Ruby red / Ocean Brown granite stone of approved shade and size 18 mm to 20 mm thick on bed 1:6 cement mortar including cement floats striking joints, pointing in C.M. 1:3 curing and cleaning etc. Complete. Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing machine cut machine polished 18 mm to 20 mm thick telephone black / Amba White / Cat bary brown / RBI red / Ocean Brown granite stone for treads and risers of steps and staircases of approved colour and shade with full moulding and three grooved line for the treads on bed of 1:4 Cement mortar including float filling joints with neat cement slurry curing polishing and cleaning etc. Complete. Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and laying machine cut machine Polished Kota stone flooring 25mm to 30mm thick and required width in plain/ diamond pattern on bed of 1:6 C. M. including cement float, filling joints with neat cement slurry, curing, polishing and cleaning etc. Complete. Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and laying machine cut machine polished machine cut Kota stone slabs 20 to 25 mm thick for treads and risers of steps and staircases, with rounded nosing for the treads on a bed of 1:4 cement mortar including cement float, filling joints with neat cement slurry, curing, polishing and cleaning etc. Complete. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing in required position skirting or dado of polished Kotah Stone slab 25 mm to 30 mm thick fixed on base on plaster of cement mortar 1:4 including cement float, filling joints with cement slurry, curing rubbing, polishing and cleaning complete. Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing leather finished polishing to Granite Stone slab by continuous grinding in 4 coats of different bits to receive rough and matt finish including buffing process before laying and fixing of stone as per drawing and design, including cleaning, washing and finishing etc. Complete. Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and constructing granite kitchen platform with fixing of stainless steel sink 600 mm x 450 mm size as per detailed drawing including vertical both side polished kadappah stone 25 to 30 mm thick supports with kadappah top 35 to 40 mm thick and polished granite 16 to 20 mm top with side strips of granite at front and both sides of platform raised with two vertical granite supports 15 cm height and top granite of 75 x 40 cm including cutting, opening for sink of required size in kadappah as well as granite etc. complete. (Platform top size 5.00 m x 0.60 m and height is 0.75 m) Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and laying in situ cement concrete M20 with tremix treatment for 100 mm thickness for flooring with groove cutting of 4mm wide and 20mm deep with necessary refilling with bitumen etc. Complete. Basement Floor
Lower Ground Floor
Upper Ground Floor
Providing and applying Texture plaster with finishing with texture material of approved make in 3 to 4 millimeter thickness on previously plastered surface, including Plaster Groove 6mm thickness or Tape Grooves 35 to 45 mm thickness or as required, in all position including preparing the surface, scaffolding etc. Complete. Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and applying 2 Coats of 100% Pure acrylic low VOC water based paint with to withstand for period of atleast 5 years of approved make. Paint should provide durable long lasting silk finish with high resistance to UV and resistance to spreading of flame. Paint should protect against concrete carbonation with R value of minimum 600 and ability to built cracks upto min 0.7mm. The paint has to be applied on High quality water based acrylic copolymer primer with good alkali resistance properties. With all leads and lifts at all levels etc. complete, as directed by Engineer in charge. Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Providing and applying antipeel paint of approved make & approved brand exterior Emulsion paint of approved quality, colour and shade to old and new surface in two coats, including exterior acrylic primer coat, scaffolding, preparing the surface etc. complete (Heat Reflective Paint). Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Providing and applying one coat of seal cement primer of approved manufacture and shed including scaffolding preparing the surface by cleaning dirt and other foreign matters, scrapping if necessary including scaffolding etc. Complete. Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Providing and applying two coats of water proof cement paint of approved manufacture and of approved colour to old plastered surfaces including scaffolding if necessary, cleaning and preparing the surface, watering for two days etc. Complete. Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Providing and applying priming coat on concrete/ masonary/ Asbestos Cement plastered surfaces including scaffolding if necessary, preparing the surface by thoroughly cleaning oil, grease, dirt and other foreign matter and sand papering as required etc. Complete. Basement Floor
Lower Ground Floor
Providing and applying washable oil-bound distemper of approved colour and shade to old and new surfaces in two coats including scaffolding, preparing the surfaces. (excluding the primer coat.) etc. Complete. Basement Floor
Lower Ground Floor
Providing and applying two coats of High Albedo paint having minimum Solar Reflective Index (SRI) 108 (with solar reflectance & thermal emittance tested as per ASTM) C 1549 and ASTM C 1371 respectively, VOC less than 10 cc/gm. The coating thickness and the methodology of application shall strctly as per manufacturer's specifitions and as approved by engineer in charge. Surface preparation includes cleaning with metal wire brush to remove all dust, fungus etc, washing with water all complete.The contractor shall give guarantee for the performance of SRI and also the durabitity of coating, all complete as per direction of Engineer - in- incharge. Terrace Floor
Providing and fixing frame with / without ventilator of size as specified with Country cut teak wood for doors and windows including chamfering, rounding, rebating, iron holdfast of size 300mm x 40mm x 5mm with oil painting, etc. Complete Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Solid Core Flush door Single leaf Providing and fixing factory made solid core flush door in single leaf 35 mm thick, decorative types, of exterior grade, as per detailed drawings, conforming to I.S.:2202 - 1962 (Revised) with approved face Laminates on both faces with/without glazing and venetians in the positions shown on the drawings or as directed, all necessary beads, moulding and lipping, holdfasts, mat finish stainless steel fixtures fastenings , finishing with french-polish/ waxing complete. (without door frame). (Sample to be got approved from Ex.Engineer before use) Commercial Hard Wood shutter Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing & Flxing 44-MM thick both side LAMINATED DOOR (WITHOUT GLASS) made up of 18mm thick COMMERTIOL ( 1S1-303) plywood frame covered with 12mm thick COMMERTIOL ( 1SI-303) plywood both side of the frame to get required thickness as per architectural design & drawing with both side Cover with 1.00mm thick LAMINATE confirming to (1S1 2046) Premium quality with grove, edges finish with 50 X 10mm BTC lipping as per drawing is fitted by BTC 22 X 10mm moulding [including all materials brass screw, brass hinges (125 X 12mm,) mortice lock, door stopper, antitermite treatment to plywood, two coats melamine pollish to moulding and lipping, labour charges as directed by engineer Incharge etc Complete. Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing & Fixing 44 MM thick both side LAMINATED DOOR (WITH GLASS) made up S.* of 18mm thick COMMERTIOL ( IS1-303) plywood frame covered with 12mm thick COMMERTIOL ( \$1-303) plywood both side of the frame to get required thickness as per architectural design & drawing & Covered with both side 1.00mm thick LAMINATE confirming to (1S1 2046) grove, edges finish with 50 X 10mm BTC lipping and 8mm flot glass strip as per drawing is fitted by BTC 22 X 10mm moulding including all matarials brass scruw, brass hinges (125 X 12mm,) mortilse lock, door stopper, antitarmite treatment to plywood, two coat melamine pollish to moulding and lipping, labour charges etc. Complete. Lower Ground Floor
2 Hour Insulated, Flame, Smoke Radiation check Lead Lined Fire Door 57mm 2HR FRL (120/120) 3 Criteria - INTEGRITY / INSULATION/ STABILITY WOODEN DOOR - Fire Door Tested in accordance to IS: 3614 Part 2. with prior approval of concerned Superitending Engineer Providing of 120 min Fire rated lead lined doors system duly tested for 3 criteria - Integrity, Insulation and Stability Criteria as per the IS: 3614 Part 2 and BS: 476 part 22 with standard heating conditions as specified in IS:3614 Part II 1992 and BS: 476 part 20 & 22 1987 to achieve the required integrity, insulation and stability (i.e. to restrict the heat radiation, temperature rise on the non fire side to the maximum of 140° C above the ambient temperature on the exposed surface of the shutter. The fire doors are tested with NCBN technology ("Non Combustible by Nature"). Lead lined to check radiation. Code No; 2 Hour Insulated, Flame, Smoke Radiation check Lead Lined Fire Door 57mm 2HR FRL (120/120) 3 Criteria - INTEGRITY / INSULATION/ STABILITY WOODEN DOOR - Fire Door Tested in accordance to IS: 3614 Part 2. a) Door Frame: Providing Frames for Lead Lined Fire resistant door shutters 1st class Malaysian Hardwood Frame densified and pressure treated with fire retardant chemicals in vacuum impregnation vessel under 160 PSI pressure as per IS:401and kiln seasoned to moisture below 15% as per IS:1141 of section 140 X 70 mm with 45mm thick two layered 3mm Lead Line Sheets with 10mm overlap from either side & spray quoted with 2 coats of In tumescent paint of minimum 200 micron, with 1 row of Brush- Type Astroflame® intumescent strip (imported) of size 10mmx4mm concealed in the groove of the Frame for fire and hot and cold smoke sealing, etc. complete as per direction of Engineer in Charge Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
b) Shutter: Providing of 57mm thick asbestos free composite, 'TUFWUD' brand - 3 criteria - fire, heat and smoke check Lead Lined Door Shutter with flame guard of 120 minutes IS3614 part -II comprising of 2x9mm Calcium Silicate boards, Chemical treated internal timber with Fire retardant chemicals in pressure impregnation vessels under 160 PSI pressure as per IS:401and kiln seasoned to moisture below 15% as per IS:1141 frame work of 100x30 mm with 30mm thick infill of ceramic fibre (density 128 Kilograms/CMT) vermiculite mix, 3mm thick Lead Sheet on one side faced & 3mm Fire retardant High Density Fibreboard, internally lipped with hardwood beading, and pasted in Hydraulic Press under 50 tonnes pressure, spray quoted with 2 coats of Intumescent paint of minimum 300 micron, and with 1 row of Brush- Type Astroflame® intumescent strip (imported) of size 10mmx4mm concealed for fire and smoke sealing in the grooves in the shutter on all edges except bottom, without any external lipping. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
c) Vision Panel: 2 HR rated E Class clear high stress fire rated glass is pre fabricated strategically inside the shutter structure with 10 mm inside the shutter on all sides with U- glazing. An additional insulated powdercoated 'Z' channel of 16 swg MS sheet to be fixed for reinforcement of the joints. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Panic Bar: (For 2 Hr fire Rated single Panic bar) Supplying, fitting & fixing Surface mounted Crash Bar/ panic Bar of touch pad style ,made of heavy duty cast iron/ steel body & latches with SS ,BHMA certified & conforming to ANSI A 156.3 for grade-1 ( 3 hours fire rated ) and suitable for surface mounting to wooden/hollow metal/ Al framed door,with maximum operating force 8Kilogram for unlocking easily & outwardly during emergency,complete in all respect as per direction & satisfaction of Engineer-in charge including all taxes & incidental charges. (Note: To be installed at "FIRE EXIT"only under location specific instruction of Eingineer-in -Charge.) Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Door Closure: (For 2 Hr fire Rated EN-3 Door Closure) Supplying, fitting & fixing Surface mounted overhead Door Closer for 2 hour fire rated doors of different size (e.g size -EN-3 for leaf width upto 900mm) CE certified, marked & conforming to EN - 1154 of approved quality (Internationally reputed brand like Dorma, Geze, Hafele, Assabloy & Magnum etc.) fitted and fixed Complete as per direction & satisfaction of Engineer -in Charge including all taxes & incidental charges. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
12"SS Handle: (For 2 Hr fire Rated 12"SS Handle) Supplying, fitting & fixing Stainless Steel 'D' or 'H' type of size 300 mm x 19 mm tubular Handle with Grade 304, CE certified, marked & conforming to EN - 1154 of approved quality (Internationally reputed brand like Dorma, Geze, Hafele, Assabloy & Magnum etc.)as per direction of Eingineer -in Charge fitted and fixed complete including all taxes & incidental charges. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Aluminium System Color Anodized Partly Fixed/ partly openable system Window :- Providing and fixing aluminium system color anodized partly fixed/ partly openable window various sizes. Casement will be made from Geeta/ Malwin/Lexi/Brandson, 40mm series or equivalent system. Windows will be of specially extruded aluminium section Joints will be of 45 degrre joints, joints will be fixed with specially developed clits. Track frame will be fixed to the masonry opening of windows with S S 202 wood screws. Fixed glass casement will be made from specially extruded aluminium section, glass considered is 5mm clear toughned glass. All shutter will be having 45 degree joints, joints will be fixed with specially developed clits from uniform hairline. All fixing screws will be SS 202. Window will be sealed with weather sealant from outer periphery. Etc complete as per architecture drawing and the direction of the engineer-in-charge. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Two Track Two Glass Shutter Window :- Providing and fixing aluminium system color anodized sliding window of various sizes. Window will be made from Geeta/ Malwin/Lexi/Brandson, 25 to 27 mm slim series or equivalent system. Windows will be of specially extruded aluminium 2Track – 2 Glass shutter , track joint will be of 45 degree joints, joints will be fixed with specially developed clits. Track frame will be fixed to the masonry opening of window qith SS 202 screws. Glass shutter will be made from specially extruded aluminium section, glass considered is 5 mm clear toughened glass. All shutter will be having 45 drgree joints, joints will be fixed with specially developed clits to form uniform hairline joint. All shutter will be fixed to the main frame with necessary double roller to have smooth and easy mevment of the shutter. Shutter will have single point self pressing lock. All fixing screws will be of SS 202. Windows will be sealed with weather sealant from outer periphery . Etc. Complete. Lower Ground Floor
Upper Ground Floor
1st Floor
4th Floor
Three Track Three Glass Shutter Window :- Providing and fixing aluminium system color anodized sliding window of various sizes. Window will be made from Geeta/ Malwin/Lexi/Brandson, 25 to 27 mm slim series or equivalent system. Windows will be of specially extruded aluminium 3Track – 3 Glass shutter , track joint will be of 45 degree joints, joints will be fixed with specially developed clits. Track frame will be fixed to the masonry opening of window qith SS 202 screws. Glass shutter will be made from specially extruded aluminium section, glass considered is 5 mm clesr toughened glass. All shutter will be having 45 drgree joints, joints will be fixed with specially developed clits to form uniform hairline joint. All shutter will be fixed to the main frame with necessary double roller to have smooth and easy mevment of the shutter. Shutter will have single point self pressing lock. All fixing screws will be of SS 202. Windows will be sealed with weather sealant from outer periphery . Etc. Complete. Lower Ground Floor
Upper Ground Floor
1st Floor
Providing and fixing in position powder coated aluminium louvered windows / ventilator of various sizes with powder coating as per detailed drawing and specifications including aluminium frames 80 x 38 mm x 1.22 mm box type, 5 mm thick sheet glass louvers, of approved quality etc. Complete. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing 900mm high S.S.304 Grade Stainless steel railing with 40mm diameter and 1.5mm thick at top, 40mm diameter and 1.5mm thick vertical supports spaced at 1.5m center to center and 8mm thick toughened glass including fabricating , fixtures, errecting , necessary welding , grinding , finishing, buffing to stainless steel pipe etc. Complete Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing 40mm diameter and 1.5 mm thick Stainless steel hand railing in S.S.304 Grade including fabricating, fixtures, errecting, necessary welding, grinding, finishing, buffing to stainless steel pipe etc. Complete Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing stainless steel (Grade 304) railing made of hollow tubes, channels, plates etc. including welding grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories and stainless steel dash fasteners, stainless steel bolts, etc. of the required size on the top of the floor of the side of waiste slab with suitable arrangement as per approval of engineer in charge (for payment purpose, only the weight of the stainless steel members shall be considered excluding fixing accessories such as nut bolts, fasteners etc.). 50mm dia. pipe, 1.5mm thickness and weight 1.92Kilogram/ r. Metre Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing mild steel grill work for windows, ventilators, etc. 15 Kilogram/ One Square Metre as per drawing including fixtures necessary welding and painting with one coat of anticorrosive paint and two coats of oil painting complete. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing rolling shutter fabricated from steel laths of minimum thickness 0.9 mm with lock plate of 3.15 mm thickness reinforced with 35 x 35 x 5 mm angle section fitted with sliding bolts and handles for both sides, deep M.S. channel section of depth and thickness not less than 65 mm and 3.15 mm respectively with hold fast arrangements, M.S. Bracket plate 300 x 300 x 3.15 mm minimum size and shape with square bar, suspension shaft of minimum 32 mm diameter, hood cover of M.S. sheet not less than 0.9 mm thickness and of any size at top and safety devices including mechanical gear operation arrangement consisting of worm gear wheels and worms of high grade cast iron or mild steel and one coat of red lead primer etc. complete. (I.S. 62481979) (With mechanical gear) Basement Floor
Providing and fixing collapsible steel gate in one / two leaves with hot rolled vertical channels of 18 x 9 x 3 mm minimum size, crossings of M.S. flats of size 18 x 5 mm T or E section for runner of minimum 40 x 6 mm size for flange, M.S. flat for top runner of minimum size 40 x 12 mm with roller wheels confirming to grade F.G. 150 fitted with snap headed rivets of minimum size 6 mm max. spacing of vertical channels be 100 mm enclosed gate position and clear space of 150 mm between two sets of crossings with hold fasts, stoppers, spaces, handles, locking arrangement and one coat of red lead primer and oil painting etc. complete. (I.S. 105211983). Lower Ground Floor
Providing and fixing M.S. grill door 24 Kilogram/ One Square Metre of various size as per detailed drawings without hot dip coating, iron fixtures and fastenings and 3 coats of oil painting etc Terrace Floor
Providing, fabricating and erecting at site of work the tubular steel structure (shed) as per standard design and specifications having various spans in between trusses and in multiples of standard length of bays as specified as per standard specifications, inclusive of cost of steel tubular trusses, tubular columns purlins, tie runners, foundation bolts, base plates, nuts and bolts, welding wherever required etc. as per detailed drawing inclusive of one coat of anticorrosive paint and two coats of oil painting of approved quality and shade etc. complete. Spec. One Number : As directed by Engineer-in-charge. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Supply and installation of ZMS (Nylon) cubicles of width and depth as per specifications/ site drawings. Cubicle height will be 2003 mm. ZMS Series Cubicles: Std Sizes (W x D x H): 900 mm x 1550 mm x 2003 mm, (Height is including 150 mm gap from bottom) Door Width- 600 mmITEM DESCRIPTION Made from solid grade compact high pressure laminate as per IS:2046 and EN-438 manufactured under high specific pressure > 5 MPa and temperature >120°C. All doors will be of single colour and made of 12 mm thick HPL compact panel. All pilasters will be made of 12 mm thick HPL compact panel. All intermediate partitions or dividers will be made of 12 mm thick HPL compact laminate panels. Size of panels to be as per drawing. HARDWARE & ACCESSORIES are Semi-spherical (Top) head frame structure for surface protection. Size to be 50x32x1.6T. Corner joinery section, Size to be 40x16.5x1.8T.U-Channel Wall joinery section, Size to be 22x16x1.6T.Door stopper section, Size to be 21x12.5x1.6T. Stainless steel grade 304 screws, Anti-rotation Nylon polyamide grade-6 expandable wall plugs, The Work shall complete as per drawing , under supervision of engineer in charge, etc complete. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Supply and Installation of translucent roof with DPI Flux standing seam multicell polycarbonate panel system. The system with complete assembly of co extruded UV protected multicell panels incorporated into a complete system. Co-extruded UV protected polycarbonate panel system of min 12 mm thick of 900 mm (min.) width with angular daylighting concept. Panels shall have minimum six layers with truss bridge design for higher flexibility & strength. Panels with all fixing accessories to ensure best performance for wind uplift, vibration, oil canning and visual appearance. Panels shall be manufactured with vertical standing seam at both sides of the panel. Panels shall be fixed on Purlin with snap on connectors with double tooth grip lock locking mechanism and will be secured on MS structure (will be paid Separately) with 3 One Numbers self-drilling screws & trapezoid SS fasteners holding the base of the standing seam offering best stability having a pull-out load of min. 7000N (7KN) tested as per ISO 6892:1998 and IS 1608: 2005, as per design requirement. Panels must satisfy Dart drop impact test as per IS 14443-97 shall show no sign of breakage on Polycarbonate sheets which have been exposed to UV for a min. of 500 Hours as per ASTM G 155. Panels shall not have Yellowness Index as per ASTM D 1925 of 15 units when tested on a sample exposed to UV for 500 Hours as per ASTM G 155. U value shall not be more than 1.6 W/m2K as per EN ISO 10077-2:2018. Panel shall be with additional End cap/Aluminium U/F profile/ Glazing Bar for ends as required. Panel shall be fixed over MS structural steel/MS purlin (paid separately) conforming to the detail technical specifications as per approved architectural drawings. Trained and factory authorized labour with supervision to complete the entire panel installation as per drawing & direction of the engineering in charge. Colour: As per Approval. Approved Make: FLUX by DPI Daylighting or approved equivalent The 12mm thick panels shall be used for a roofing height of upto 15 mtrs. Terrace Floor
Providing and Fixing of GI Lay in Plain metal ceiling consisting of 600x600mm Lay in tiles of pre coated galvanized steel in 0.5 mm thickness in Global white color tile to be laid on grid systems with 15mm wide T - section flanges color white having rotary stitching on the Main Runner, 1200 mm and 600 mm Cross Tees.Providing and Fixing of GI Lay in Plain metal ceiling consisting of 600x600mm Lay in tiles of pre coated galvanized steel in 0.5 mm thickness in Global white color tile to be laid on grid systems with 15mm wide T - section flanges color white having rotary stitching on the Main Runner, 1200 mm and 600 mm Cross Tees.products approved as per GRIHA and BS 476 etc. Complete. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing Modular false ceiling of 600 x 600 mm center to center and 13 mm thick square mineral fiber board to be fixed on frame work of alluminium sections for suspended false ceiling consisting of alluminium T 2”x1 ½” (50 mm x 40 mm) weighing 0.39 Kilogram/m at 60 cms center center and fixed with ½” x ½” (15 x 15 mm) flanges weighing 0.19 Kilogram/m suspended on 6 mm dia mild steel rod weighing 0.22 Kilogram/m, fixed on wall and beams including rounding of the edges with alluinium T of 2” x 1 ½” (50 mm x 40 mm) weighing 0.39 Kilogram/m etc. (all alluminium sections shall be anodized) including all labour, material, lifts etc. Complete. Lower Ground Floor
Upper Ground Floor
Providing and fixing in position Gypsum board false ceiling with 12.5 mm thick Gypsum boards, screwed/fixed to the under structure of suspended G.I. Grid constructed and suspended from the main ceiling consisting of ceiling sections of size 25 x 50 mm maximum center to center distance of 600 milimetre perimeter channel and intermediate channels at maximum center to center distance 1200 milimetre galvanized grid should be fixed to reinforced cement concrete slab. The gypsum board should be fixed to galvanized iron grid with necessary screws. The boards should be taped and filled from underside to give smooth, seamless ceiling. The rate should include necessary additional ceiling sections and intermediate channels. Additional intermediate channels should be fixed to strap hangers for additional support to prevent strapping at every 1200 milimetre item to be completed in all respect including necessary sleeves for ducts finishing of joints cut outs, painting including labour, material, lifts etc. all complete. Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Aluminum laser cut Jali :- Providing and fixing aluminium laser cut jali of 2mm thickness with pure polyester Matt finish exterior grade UV resistant powder coating / anodizing. The jali to be fixed to the sub framing using self drilling screws which shall not be visible in the elevation. The sub framing to be anchored to the main building using Anchor fasteners. Test report to be submitted for structural stability of the system for its self weight and wind load of 120kmpl. Required detailed shop drawing and sample is needs to get approved from the project Architect before execution on site. Work shall be carried our including all lead and lift etc. As directed by Engineer-in-charge. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Aluminum Louvers :- Providing and fixing in position powder coated Aluminum louvers with 15 Gauge Aluminum vertical box louvers 300x100 mm as louvers including cutting, bending as per profile, screwing, including all Necessary Fittings & Fixtures , lead, lift scaffolding etc completed. 3rd Floor
4th Floor
Aluminum Louvers :- Providing and fixing in position powder coated Aluminum louvers with 15 Gauge Aluminum vertical box louvers 100x75 mm with as louvers including cutting, bending as per profile, screwing, including all Necessary Fittings & Fixtures , lead, lift scaffolding etc completed. 4th Floor
Providing & Fixing double shutter glass door of required size of 12mm thick toughen glass frosting and edge polish as shown in the drawing or as direction, including all necessary fittings like hydraulic patch fitting , top patch fitting, Top pivot, door handele, door lock, door stoper, door soft central 180 weather seal for door edges etc. All complete as per architectural drawing and the direction of the engineers-in-charge with all necessary fasteners and accessories complete. Lower Ground Floor
Upper Ground Floor
Providing & Fixing 12mm thick toughen glass and edge polish as shown in the drawings or as directed, including all necessary fitting like Upper glazing profile, bottom locking, glazing profile, standard gasket for profile, locking gasket 12mm, door soft central 180 weather seal for glass edges as per drawings having glass fixing sections at all sides concealed in partitions etc. Complete as direction by Engineer-in-charge. Gaps between glass panesls should be filled by color silicon weather proofing sealent, EPDM gasket, handles all necessary fasteners and accessories complete. 2nd Floor
Structural Glazing : Providing structural glezing using min.6mm thick saint-gobain make reflective glass in any shade as per requirement.it includes aluminium framework of rectangular aluminium tube of size 64mm X 58mm and electro coloured to 15 microns .the aluminium extrusions is manufactured asper IS 63400. dow corning 995 silicone Structural Glazing sealant is to be used for fixing glass with aluminium frame.high quality expansion bolts with good load bearing capacity is to be used for fixing aluminium frame to wall.it also includes scaffolding and other necessary fittings. Lower Ground Floor
Upper Ground Floor
1st Floor
3rd Floor
4th Floor
Providing and fixing 90 cm x 60 cm Granite plate engraving 10 cm. Height letter, figures including painting the lefters/figures with approved colour and shade complete
Providing and fixing in position anodised (as per IS 1868/1982) Aluminium fixed staggered ( Z Type) Ventilator with aluminium rectangular pipe 63 mm x 38.10 mm x 1.22 mm at weight 0.650 Kilogram/One Running Metre, Aluminium angle of size 15 mm x 15 mm x 1 mm,aluminium channel of 9 mm sizes, S.S.mosquito net of 304 Grade,4 mm thick float glass per detailed drawing and as directed by Engineer in charge etc.complete. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Plumbing Works :- Providing and fixing Ivory european type wall-hung, Size 360mm x 360mm x 575 mm with flush valve having flow rate up to 6.0 Litr/Full Flush, 3Litr/Half Flush of Jaquar/Cera/Hindware /Perryware or equivalent make including PVC soil pipe, vent pipe upto outside face of wall, 100mm dia PVC plug bend inlet pipe all fittings,cutting & making good walls, floors etc as directed by Engineer in charge.( Make shall conform to manufacturer's Green product and shall got approved from the Engineer In Charge. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing C.P. 2 Way BIB cock (6LMP) with wall flange of approved make including necessary sockets/ union nut etc. complete as directed by Engineer in charge Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
C.P.Handshower (health faucet) 1m.PVC tube with wall hook jaquar make (Cat. No. ALD 563 ) Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing stainless steel sink of size 600 x 510 x 200 mm incluidng coupling, outlet pipe, elbow and other necessary fitting, finishing etc. Complete Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing sink cock (6LPM) with regular swinging spout (Wall / floor Mounted Model) with wall flange having flow rate up to 6.0 Litr/Minute of Jaquar/Cera/Hindware /Perryware or equivalent make incluidng other necessary fitting, etc. complete as directed by Engineer in charge.( Make shall conform to manufacturer's Green product and shall got approved from the Engineer In Charge.) Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing Autoclosing pillar cock (6LPM) of pressmatic tap of approved make or equivalent including all fixtures, fittings etc. Complete Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing oval type under counter wash hand basin of 16 inch x 22 inch size and of special colour shade having telephonic black / coloured granite of 180 mm thick stone black kadappa framework including chromium plated coupling Bottle-Trap using CERA company or equivalent oval typa wash basin model no 3448 as per detailed drawing or as directed by engg incharge etc complete. (Counter size 1.20 m X 0.60 m ) Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing C.P. Angular stop clock with wall flange of approved make continental including necessary sockets/union nut etc. Complete. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing Ivory glazed urinal with Pressmatic auto closing valve having flow rate up to 4.0 Litr/Flush of Jaquar/Cera/Hindware /Perryware or equivalent make with P.V.C. waste pipe with fitting arrangement etc.complete as directed by Engineer in charge.( Make shall conform to manufacturer's Green product and shall got approved from the Engineer In Charge.) Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing 450mm x 550mm size superior type Belgium mirror with 16mm dia. nickel plated towel rod etc. complete.Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing P.V.C. Rain water pipes of 160mm outer diameter and having wall thickness of 2.2 to 2.7 mm confirming to I.S. 13592-1992 including proper rainwater receiving recess with P.V.C. plug, bend, necessary fittings, such as, offsets, shoes, inluding fixing the pipe on wall using approved wooden cleats projecting 25mm to 40mm from face of wall a fixing with clips of approved quality and One No. ,filing the joint using rubber gasket with solvent cement and properly resting the shoe of pipes on C.C. or masonry blocks, including necessary scaffolding and maintenance for 3 yrs for any leakages or dislocations of pipes. All the P.V.C. fittings and additional 2 piece socket clips shall be got approved from engineer in charge etc. Complete. Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Providing and fixing ISI 1729/2002 grade 75 mm dia Cast Iron Waste Water Pipe with lugs necessary fittings such as bends, tees, single junction, double junction, slotted vent, offsets on wall or into the ground including filling joints with cement mortar 1:2 proportion fixing on wall by means by galvanised Mild Steel bracket of 30 x 5 mm plate and 8 mm square rod with Galvanised Iron clamp with washer as per design drawing and as directed to keep pipe 50 mm away from wall including necessary scaffolding and painting the exposed faces with one coat of red lead oil paint and two coats of gray oil paint including removing the existing pipe if necessary and conveying and stacking in PWD Chowky or as directed by Engineer-in-Charge. Lower Ground Floor
Providing and fixing ISI 1729/2002 grade 100 mm dia Cast Iron Soil Pipes With lugs including plug bend necessary fittings such as bends, tees, single junction, double junction, slotted vent, offsets on wall or into the ground including filling joints with cement mortar 1:2 proportion fixing on wall by means of galvanised Mild Steel bracket of 30 x 5 mm plate and 8 mm square rod with Galvanised Iron clamp with washer as per design, drawing and as directed to keep pipe 50 mm away from wall including necessary scaffolding and painting the exposed faces with one coat of red lead oil paint and two coats of white oil paint including removing the existing pipe if necessary and conveying and stacking in PWD Chowky or as directed by Engineer-in-Charge. Lower Ground Floor
Providing and fixing on walls/ ceiling/ floor 15 mm dia. CPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. Complete Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing on walls/ ceiling/ floor 20 mm dia. CPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. Complete Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing on walls/ ceiling/ floor 25 mm dia. CPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. Complete Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing on walls/ ceiling/ floor 32 mm dia. CPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. Complete Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing on walls/ceiling/floor 15 mm dia. uPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. Complete. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing on walls/ceiling/floor 20 mm dia. uPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. Complete. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing on walls/ceiling/floor 25 mm dia. uPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. Complete. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing on walls/ceiling/floor 32 mm dia. uPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. Complete. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing on walls/ceiling/floor 40 mm dia. uPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. Complete. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing on walls/ceiling/floor 50 mm dia. uPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. Complete. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and laying in trenches 50 mm dia. medium grade having embossed as ISI Mark galvanised iron pipes of 12.43 Kilogram/meter necessary fitting remaking good the demolished portion with filling trenches and with primer of anticorrosive oil paint , 2 coats Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. Complete. Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and laying in trenches 80 mm dia. medium grade having embossed as ISI Mark galvanised iron pipes of 12.43 Kilogram/meter necessary fitting remaking good the demolished portion with filling trenches and with primer of anticorrosive oil paint , 2 coats Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. Complete. Terrace Floor
Providing and laying in trenches 100 mm dia. medium grade having embossed as ISI Mark galvanised iron pipes of 12.43 Kilogram/meter necessary fitting remaking good the demolished portion with filling trenches and with primer of anticorrosive oil paint , 2 coats Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. Complete. Terrace Floor
Providing and fixing screw down 15 mm dia. wheeled stop tap of brass including necessary sockets/union nut complete 1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing screw down 20 mm dia. wheeled stop tap of brass including necessary sockets/union nut complete Lower Ground Floor
2nd Floor
3rd Floor
Providing and fixing screw down 32 mm dia. wheeled stop tap of brass including necessary sockets/union nut complete Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Providing and fixing screw down 40 mm dia. wheeled stop tap of brass including necessary sockets/union nut complete Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
Terrace Floor
Providing and fixing screw down 50 mm dia. wheeled stop tap of brass including necessary sockets/union nut complete Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Providing and fixing in position UPVC ultra violet stabilized 110 mm outer diameter cowl dome confirming to I.S.-4985 including making joints with solvent cement etc. Complete Terrace Floor
Providing and fixing 45 cm wide mild steel ladder of 40mm x 6 mm mild steel flat stringers and steps of 18 mm dia. mild steel bar for water tank including fixing it in (1:2:4) M-15 cement concrete block 60cm x 30cm x 30cm and painting the ladder complete. (Anti-Corossive Paint) Terrace Floor
Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete as per specification no. FF-FFA/ARV Terrace Floor
Providing fixing, testing and commissioning in position 160 mm dia minerally reinforced polypropylene high density low noise pipe ring fit conforming to BS EN 1451, Fire resistancy DIN 4102, B2, Tensile strength: 13 N/mm2, waste water between pH 2 and pH 12, Density: 1.9 g/cm3 3 DIN 53479 with all the engineered support as per detail technical specification, including all fittings such as bends, junctions, inspection doors, offsets, cowl, access pieces/plugs etc. including cutting holes in walls, slab and making good the same wherever required as per direction of Engineer in Charge. (Suspended Soil, Waste & Rain water Pipe at Basement Ceiling Level) Basement Floor
Lower Ground Floor
Upper Ground Floor
Providing fixing, testing and commissioning in position 75 mm dia minerally reinforced polypropylene high density low noise pipe ring fit conforming to BS EN 1451, Fire resistancy DIN 4102, B2, Tensile strength: 13 N/mm2, waste water between pH 2 and pH 12, Density: 1.9 g/cm3 3 DIN 53479 with all the engineered support as per detail technical specification, including all fittings such as bends, junctions, inspection doors, offsets, cowl, access pieces/plugs etc. including cutting holes in walls, slab and making good the same wherever required as per direction of Engineer in Charge. (Suspended Soil, Waste & Rain water Pipe at Basement Ceiling Level) Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing fixing, testing and commissioning in position 110 mm dia minerally reinforced polypropylene high density low noise pipe ring fit conforming to BS EN 1451, Fire resistancy DIN 4102, B2, Tensile strength: 13 N/mm2, waste water between pH 2 and pH 12, Density: 1.9 g/cm3 3 DIN 53479 with all the engineered support as per detail technical specification, including all fittings such as bends, junctions, inspection doors, offsets, cowl, access pieces/plugs etc. including cutting holes in walls, slab and making good the same wherever required as per direction of Engineer in Charge. (Suspended Soil, Waste & Rain water Pipe at Basement Ceiling Level) Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and fixing 10 cm PVC nahani trap with grating etc. Complete. R.A. Unit : 1 / Per No Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and laying concrete pipes of I.S.NP. class of 225mm diameter in proper line, level and slope including necessary collars, excavation, laying, fixing with collars in cement mortar 1:1 and refilling the trench complete
Providing and laying concrete pipes of I.S.NP. class of 300mm diameter in proper line, level and slope including necessary collars, excavation, laying, fixing with collars in cement mortar 1:1 and refilling the trench complete.
Providing and constructing Brick Masonry Inspection Chamber 90cm x 45cm With R.C.C. raft in B.C. soil area including cost of reinforcement, 1:2:4 cement concrete channels half round G.S.W. pipes, Brick Masonry, plastering from inside and airtight with 75 mm thick R.C.C. cover medium duty 140 Kilogram etc. Complete. (Sewer chamber + Storm Chamber+ Electrical(2nos))
Providing and constructing Brick Masonry inspection trap Chamber 90cm x 45cm including 1:4:8 C.C foundation, 1:2:4 C.C.channels/half round glazed stoneware pipe channel, salt glazed stone-ware intercepting trap with rodding pipe set in 1:4:8 cement concrete block, brick masonry plastering inside and Outside, fixed in cement concrete with R.C.C. Cover medium duty 140 Kilogram. etc complete (Sewer Trap)
RWH - Recharge Pit Providing and constructing recharge pit of 2.0m deep and 1.0m dia of pre-cast RCC rings with 6.5" dia x 25m deep borewell at the floor of recharge pit including installation of combination of solid/perforated PVC casing pipe wrapped around with netlon mesh including 300mm thick sidefilling around outside of RCC rings (annular space) with 40mm size boulders including filling of recharge pit up to 0.5m depth with 25-75mm clean washed gravels from bottom up followed by 0.5m depth of 10-25mm of clean washed stones followed by 0.5m of washed river fine aggregate (natural sand/crushed sand VSI grade finely washed etc.) including netlon mesh between each gravel/fine aggregate (natural sand/crushed sand VSI grade finely washed etc.) media layer including covering with RCC slab, manhole frame & cover, PVC rungs, PVC end caps, fittings etc. including arrangement for inlet & outlet pipe excavation & backfilling as shown in the drawing.The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, taxes, including all leads, lifts at all levels. All material should be of approved make. All works complete as per the drawing, technical specification and direction of the Engineer in charge.
Providing and fixing 40 mm. dia Ball cock medium type with PVC float including sockets and necessary fittings and tested as per municipal requirements etc. complete.
Providing and laying in trenches 40 mm dia. heavy grade having embossed as ISI Mark galvanised iron pipes of 4.49 Kilogram/metre necessary fitting remaking good the demolished portion with filling trenches and with primer of anti-corrosive oil paint ,2 coats complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete.
Providing and laying in trenches 80 mm dia. heavy grade having embossed as ISI Mark galvanised iron pipes of 10.15 Kilogram/metre necessary fitting remaking good the demolished portion with filling trenches and with primer of anti-corrosive oil paint , 2 coats complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete
Providing and fixing 40mm diameter water meter with non-return valve including strainer,sockets/ union nut and including water meter box making locking arrangements and lock. [Withoutchamber].
Providing and fixing 80mm diameter water meter with non-return valve including strainer, sockets/ union nut and including water meter box making locking arrangement and lock.[Without chamber]
Providing & Fixing 65 mm dia butterfly valve (Body : Grey Cast Iron, Shaft : SS, Disc : SG Iron (Rilson coated), Liner : HT - EPDM) (upto 150mm dia with hand lever operation & above with gear box operation). Tested to a pressure not less than 15 Kg/Sq.cm. Including rubber gasket, flanges, nuts, bolts, washers & painting complete as required.
Providing & Fixing 75-80 mm dia butterfly valve (Body : Grey Cast Iron, Shaft : SS, Disc : SG Iron (Rilson coated), Liner : HT - EPDM) (upto 150mm dia with hand lever operation & above with gear box operation). Tested to a pressure not less than 15 Kg/Sq.cm. Including rubber gasket, flanges, nuts, bolts, washers & painting complete as required.
Providing & Fixing 100 mm dia butterfly valve (Body : Grey Cast Iron, Shaft : SS, Disc : SG Iron (Rilson coated), Liner : HT - EPDM) (upto 150mm dia with hand lever operation & above with gear box operation). Tested to a pressure not less than 15 Kg/Sq.cm. Including rubber gasket, flanges, nuts, bolts, washers & painting complete as required.
Providing & fixing gun metal 40mm dia, horizontal wafer type non return valve conforming to IS 778 and tested to a pressure not less than 15 Kg/Sq.cm, Including rubber gasket, flanges, union, nuts, bolts & washers complete as required., for all leads and lifts, testing etc. complete. (Prior approval of sample and brand by Ex.Engineer is necessary before use.)
Providing and fixing H.D.P container one piece moulded water tank made out of low density polythyler and built corrugation including of delivery up to destination hoisting and fixing of accessories such as inlet, outlet overflow of all tanks capacity above 1000 to 20,000 litres
Constructing brick masonry circular manhole 1.22 m internal dia at bottom and 0.56 m dia at top in cement mortar 1:4 (1 cement :4 coarse sand) inside cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement foundation concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement, all complete as per standard design :
Constructing brick masonry circular manhole 1.22 m internal dia at bottom and 0.56 m dia at top in cement mortar 1:4 (1 cement :4 coarse sand) inside cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement foundation concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement, all complete as per standard design : Extra depth for circular type manhole 1.22 m internal dia (at bottom) beyond 1.68 m to 2.29 m :
Supplying and erecting 75/80 mm dia Cast Iron end line strainer of T-Pot type flanged end pattern, PN16 pressure rating, SS screen, end connection with flanged, for positive suction complete as per specification no. FF-VL/ELS
Supplying and erecting 100 mm dia Cast Iron end line strainer of T-Pot type flanged end pattern, PN16 pressure rating, screen of SS and end connection with flanged, for positive suction complete
Supplying & fixing in position galvanised iron puddle flanges of 60 cm length with flange on one / both ends and welded to mild steel plate (5mm thick) in the centre etc. complete as directed by engineer-in-charge. Flange on Both Ends 1- 100 mm dia puddle
Supplying & fixing in position galvanised iron puddle flanges of 60 cm length with flange on one / both ends and welded to mild steel plate (5mm thick) in the centre etc. complete as directed by engineer-in-charge. Flange on One End 3 - 80 mm dia puddle
Supplying & fixing in position galvanised iron puddle flanges of 60 cm length with flange on one / both ends and welded to mild steel plate (5mm thick) in the centre etc. complete as directed by engineer-in-charge. Flange on One End 1 - 50 mm dia puddle
Providing and fixing 24" dia. FRP Cover for Overhead Water tank
Providing and fixing 36" dia. FRP Cover for Underground Water tank
Providing and fixing Ductile iron Man Hole Covers/ Strom Water Grating and Grating with frame of Various sizes, weight and types and load bearing capacity as per EN-124, equivalent NECO with prior approval of concerned Superitending Engineer.
Providing and Fixing toilet set for differently Abled persons consist of Floor Mounted white vitreous china water Closet including 6 litre capacity white vitreous china flushing Cistern with raised soft-push button, white vitreous china wash basin of size 46 x 36 cm and one no SS 304 hinged rail 76 cms & three no SS 304of (Grab Bar) 60 cms all including cutting and making good the walls and floors wherever required ,seat cover, cistern & wash basin fittings,nuts, bolts and gasket etc complete as per the direction of Engineer-In-charge Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Providing and laying Cast in situ/Ready Mix cement concrete M-35 of trap / granite/quartzite/ gneiss metal for R.C.C. columns as per detailed designs and drawing or as directed including steel centering, formwork, cover blocks, laying /pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete,(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)Basement Floor
Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Providing and laying Cast in situ/Ready Mix cement concrete in M-20 of trap/ granite/ quartzite/ gneiss metal for R.C.C. coping to plinth or parapet and sill of doors and windows moulded as per detailed drawings or chamfered as approved by the Engineer including steel centering, formwork, cover blocks, laying/pumping, compacting, curing, finishing and roughening them if special finish is to be provided and curing complete. (Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Terrace Floor
Painting Line, Dashes, Arrows etc on Roads in two coats on new work with ready mixed road marking paint confirming to I.S. 164 on Bituminous surface including cleaning the surface of all dirt, dust and other foreign matter, demarcation at site and traffic control (Over/Upto __cm wide) (MORTH-803) – a) SurfaceOver 10cm Wide On New SurfaceBasement Floor
Lower Ground Floor
Upper Ground Floor
CORE CUTTING Carried out core cutting work as per instruction given by department and structural consultant ( bar locator test carried out prior to core and location got finalized by structural Consultant ) 125mm Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
CORE CUTTING Carried out core cutting work as per instruction given by department and structural consultant ( bar locator test carried out prior to core and location got finalized by structural Consultant ) 75mm Lower Ground Floor
Upper Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
Demolition Works :- Dismantling brick masonry in lime or cement mortar and stacking the materils as directed with all leads, lifts etc.
Dismantling the R.C.C. Work 1:2:4 and sorting out the materials such as steel etc. as directed and stacking them within the specified lead as directed etc. complete.
Removing rich mix cement concrete including stacking the spoils as directed with all leads, lifts etc, complete
Structural Steel Dismantling- Dismantling Existing Structural Steel framing of Tubes, Chanels, Tees, Angles, Pipes, beams etc. As per Direction from PWD Department /Engineer In Charge, Item includes, cutting, removing, stacking the same as per place given within site premises as per direction from Engineer In Charge includes all leads lifts etc. Complete.
Removing Np-2 and Np-3 class pipes including stacking at road side as directed by the Engineer in charge. Upto 900mm dia. etc complete.
Removing Np-2 and Np-3 class pipes including stacking at road side as directed by the Engineer in charge. Upto 900mm dia and above. etc complete.
Removing urinal pans or wash hand basins with frame including disconnecting the sanitary and water supply connections, removing the same carefully and stacking the serviceable materials as and where directed including throwing the unserviceable materials
Removing W.C. pans including disconnecting the sanitary and water supply connections, removing and breaking flooring and bed con-crete around pan removing the same carefully and stacking the serviceable materials as adn where directed including throwing t
Subwork-1 Estimate no : 111072 of 2023-2024 Providing External E.I , Internal E.I, Fire Fighting System Work, Fire alarm System Work, PA system Work, Lift Work, CCTV Work, HVAC Work etc. Supplying and erecting PVC insulated PVC round sheathed 2.5 sq.mm (50 no. X 0.25 mm dia.) 3 core flexible multi stranded copper Industrial cable for voltage grade up to 1.1 kV
Supplying and erecting integrated LED street light fitting 70-75W IP65 & IK08 class having single piece pressure die-cast aluminium housing, having system lumens output of Min. 7700 Lumens, min. efficacy of 110 lumen/W, CRI>70, CCT upto 6500K,THD<10%, p.f. >0.95, operating range of 140-270V, inbuilt surge protection of 10 kV, Life class of 50,000 Hrs. at L70B50, including driver complete with 3 Years warranty as per specification No FG-ODF/FLS2.
Supplying and erecting integrated LED street light fitting 85-90W IP65 & IK08 class having single piece pressure die-cast aluminium housing, having system lumens output of Min. 9300 Lumens, min. efficacy of 110 lumen/W, CRI>70, CCT upto 6500K, THD<10%, p.f. >0.95, operating range of 140-270V, inbuilt surge protection of 10 kV, Life class of 50,000 Hrs. at L70B50, including driver complete with 3 Years warranty as per specification No FG-ODF/FLS2.
Supplying, erecting & marking SPMCB 6A to 32A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying, installing, testing and commissioning SF 6 Insulated 22kV, 630A, 16kA/3sec, 4 way outdoor, extensible motorised SCADA compatible RMU, internal arc tested as per electric supply company specification consisting of 2 nos. feeder with 2 LBS and 2 nos. feeder with 2 VCB compliant to IEC 62271 - 100, 200 and 102, as per specification no. SW-HTS/RMU SCADA
Supplying, erecting, testing and commissioning 22KV HT metering cubical (compact type) approved by MSEDCL / licensee fabricated with 2 mm (14 SWG) M.S. sheets with supporting angle, painted with powder coating / epoxy paint of required shade, copper bus bar size 25 x 6 mm, heavy duty mechanical lock, with counter meter for measuring no. of times the opening of meter door, top side cover (CT, PT cover) interlock with meter door, epoxy casted 3 nos. CT having required ratio between 25/5A to 200/5A, VA 10 or 15, Class 0.2S, epoxy casted 3 nos. PT having ratio 22000/V3/110/V3 VA 50, Class 0.2 suitable for provided trivector meter, and provision for incoming and outgoing cables complete duly tested by licensee with necessary test certificates and erected on provided plinth/ cc foundation.
Supplying and erecting 250 kVAr, 440 V 3 phase, 50 Hz., Contactor Logic & Intelligent Relay micro APFC passive filter panel, consisting of suitable steps of APP/MPP type capacitor units with Detuned (harmonic filter) reactors of suitable rating , APFC panel shall be compliance to IEC 61439 and power quality IEC 61921 standard as per specification no CP-ED/APFC
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 25 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 50 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 185 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½core 240 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 300 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 10 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL provided trench/ pipe as per specification no. CB-LT/CU
Supplying , erecting & terminating XLPE insulated, galvanised steel formed wire armoured (strip) cable 22 kV(E), 3 x 300 sq. mm. aluminium conductor laid in provided trench / pipe as per specification no. CB-HT(Round Armoured Note-2- Add 31%)
Providing and erecting Heat shrinkable indoor termination kit for 11 kV (UE)/ 22 kV ( E ) XLPE HT cable 3x240 to 400 sq. mm. with necessary material as per specification no. CB-JT/HT
Providing and erecting Heat shrinkable outdoor termination kit for 11 kV (UE)/ 22 kV ( E ) XLPE HT cable 3x240 to 400 sq. mm. with necessary material as per specification no. CB-JT/HT
Supplying and laying (including excavation of suitable width & depth up to 90 cm) 50 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, to required depth complete.
Providing & erecting 6 m high (clear height) galvanised octagonal pole with foundation bolts having bottom of 130 mm A/F, top 70 mm A/F on provided foundation as per specification no. OH-PL/OPL
Providing & erecting 7 m high (clear height) galvanised octagonal pole with foundation bolts having bottom of 130 mm A/F, top 70 mm A/F on provided foundation as per specification no. OH-PL/OPL
Providing and erecting galvanised 1000mm single arm sword type bracket with FRP dome and ball as per specification no. OH-PL/PBKT
Providing and erecting galvanised 1000mm double arm sword type bracket with FRP dome and ball as per specification no. OH-PL/PBKT
Providing pipe type earthing with 40mm. dia. G.I. pipe or 20 mm dia. G.I. Rod complete with all materials testing and recording the results as per specification no. EA-EP
Supplying, installation and testing of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25 kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete, and recording the results Specification no. EA-MOBI
Providing earthing with copper earth plate size 60 x 60 x 0.315 cm with funnel with a wire mesh for watering and brick masonry block C.l. cover with minimum 25 kg Carbon based environment friendly back fill Ground Enhancing compound complete with all materials, testing & recording the results as per specification no ESE -LA
Supplying and erecting copper strip of high purity required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with bituminous paint with joints required. As per specification no. EAEP.
Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP.
Supplying and erecting GI wire of high purity of required sizes used for earthing or any other purposes on wall with necessary G. I. Clamps fixed on wall/cable/conduit with screws complete.
Supplying, installing, testing & commissioning 3 phase, 22/0.433 kV, 50 Hz., 800 kVA, Mineral oil immersed and naturally cooled outdoor type, Copper wound ,without gas cushioning ,hermetically Sealed transformer, delta/star connected with additional neutral brought out on load side, temperature rise should not exceed 45℃ by thermometer in oil and 50℃ by the resistance method in winding at full load rating, using type A winding insulation (kraft paper) with HV tapping (with on load tap changer) on load +5 to -15 in steps of 2.5%, with standard accessories complete with test certificate with losses below 2401 Watts at 50% load, 6723 Watts at 100% load as per IS:1180 (part 1) : 2014 with necessary permissions of Electrical Inspector, as per specification no SS- TRSL.
Providing printed instruction chart for treating persons suffering from electric shock, printed in English & Marathi and duly laminated complete.
Providing pair of duly tested rubber hand gloves as per IS :47705 suitable for working up to 22 kV supply complete.
Supplying standard first aid box with necessary antiseptic cream, medicine for use on wounds due burn, crepe bandage, gauge bandage, medicated ready to use bandage (Band-Aid) adhesive tape for medicinal use, scissors,anti-septic solution,etc. (All above contents shall be of standard makes)
Supplying and fixing PVC synthetic elastomer electrically insulating mat with class C insulation conforming to IS: 15652 – 2006 tested having 3mm thickness up to 33 Kv
Supplying shock proof leather safety shoes of electrical grade of standard size as IS :11226, 14544 duly tested, with necessary test certificate from manufacturer.
Supplying, erecting, testing and commissioning of diesel generating set with alternator of 380/400 kVA output continuous rating, 3 Phase, 415 V, 50c/s 0.8 p. f. A.C supply, a totally enclosed air cooled / liquid cooled multi-cylinder diesel engine developing suitable BHP at 1500 rpm with 10% overload for 1 hour in 12 hours, along with standard accessories, self-excited, self-regulated, screen protected alternator with static excitation system running at 1500 RPM as per IS 4722-2001 with voltage regulation +/- 5 %, with performance class G2 and maximum fuel consumption 65.5 Ltr/hr @75% loading. Both the engine and alternator direct coupled on a common fabricated steel base frame and mounted on anti-vibrating pads with standard control panel comprising meters, switchgears, indicators connected with suitable wires/cables, the complete set enclosed in composite Acoustic enclosure as fully assembled integral unit made of 16 SWG CRCA Sheet, sound absorbing material to restrict sound level up to 75 dB at 1.0 m, provided with first filling of oil, diesel not less than 450 Ltr etc. on provided M20 Grade CC Foundation and obtaining necessary approval from Electrical Inspector as per specification no. GEN-DG
Making M- 20 grade reinforced cement concrete foundation by considering the safe soil bearing capacity at site as 10 T/sq.m at 1.5 m depth including supply of steel, concrete, excavation and fixing provided nut bolts with the help of template, duly plastered as per design complete (for 6m to 8m high octagonal/conical GI pole).
Supply, installation, testing & commissioning of DG SYNCHRONISING PANEL (FORM 4B TYPE 6) including AMF for all DG sets [NON CSR] The panel shall be compartmental type with Aluminium busbar and separate cable and busbar chambers. The cable chambers shall be free from any live open connections. The panel shall be comprising of following & IEC 61439 OEM DESIGN & BMS COMPATIBLE& BMS COMPATIBLE Indication lamps for all incoming feeders for phase identifications and for indication of Switch status. I/C ACB should have Following accessories; 1) Protection - LSIG , 2) Ready to Close signaling contact, 3) Auxillary contacts - 4 NO + 4 NC, 4) Position Signal Switch, 5) UV Release, 6) ICU = ICS = 65 KA, 7) Microprocessor based, 8) Trip Signal Switch, 9) ACB should be capable to remotely switch ON, OFF, Trip status for BMS compatible @ RS 485 system. MCCB should have Following accessories; 1) Protection - LSIG -Adjustable Overload & Adjustable Shortcircuit, 2) ON/OFF - Auxilary Switch, 3) Trip - Fault Signaling contacts 4) Microprocessor based, 5) ICU = ICS =36 KA, 6) Spreaders, 7) Rotary operating handle, 8) Phase Barriers. INCOMER-1 Incomer-1= 415V , 630A, 4P, MCCB of 35KA - 1No Incomer-2= 415V , 630A, 4P, MCCB of 35KA - 1No sychronizing controller for each DG set Incomer OUTGOING FEEDERS FROM INCOMING SOURCE -1 415V , 1250A, 4P, ACB of 50 KA - 1No-To Main Changeover panel incomer 415V , 1250A, 4P, ACB of 50 KA - 1No-SPARE 415V, 1300A, 3Ph, 4wire 50Hz, Aluminium busbars (91E electrical grade) having withstand ability symmetrical fault level of 65 KA for 1 Sec.(WITH 100% NEUTRAL).
Subwork 2 Estimate no : 111072 of 2023-2024 Providing Internal EI Work(Point wiring, Mains & Submains Wire , Conduit, MCB's, DB's, Main Panel, LT cabling) Supplying and erecting HMS PVC conduit FRLS grade 25 mm dia. With necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC.
Supplying and laying HMS PVC conduit FRLS grade 25 mm dia with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC.
Supplying and erecting mains with 3x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW(1Rx1.5 Sq.mm Earth Wire Considered)
Supplying and erecting mains with 3x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW(1R x 2.5 Sq.mm Earth Wire Considered)
Supplying and erecting modular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type switch 16A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type switch 16 / 20 A with indicator, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type 3 pin 6A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete
Supplying and erecting modular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type telephone socket two gang with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and fixing tool-less IO (Ethernet) flush/surface type in provided modular box as per specification no. WG-NAS/IO
Supplying and erecting modular type (two module) electronic step regulator for fan, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type blanking plate one module, duly erected on provided plate & box.
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 1 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 2 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 3 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 6 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Point wiring for light/bell concealed type in min 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm. (2+1E) FRLSH grade copper wires, modular type switch, earthing and required accessories as per specification No: WGPW/CW
Point wiring for ceiling fan concealed type in min 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm. (2+1E) FRLSH grade copper wires, modular type switch, earthing and required accessories as per specification No: WGPW/CW
Secondary point wiring for additional light/ bell point, concealed type in min 20 mm FRLS grade PVC conduit with 1.5 sq.mm. (2+1E) FRLSH grade copper wires with required accessories as per specification No: WG-PW/CW
Wiring for plug on board with Switch socket surface/concealed type, copper wiring and earthing and with modular accessories as per specification No: WGPW/CW
Supplying & erecting 2 pair telephone copper cable 0.5 mm dia. with high density polyethylene insulation, polyester taped, Nylon Rip Cord & grey colour sheathed with FR PVC, conforming to ITD specification S/WS 113C laid in provided PVC casing capping/conduit as per specification No. WG-TW
Supplying & erecting 50 pair, 0.5 mm dia. jelly filled armoured telephone copper cable with poly-al laminate moisture barrier, polythene sheathed, G.S.Tape armoured polythene jacketed having laid in provided trench as per specification No. WG-TW
Supplying & erecting 100 pair, 0.5 mm dia. jelly filled armoured telephone copper cable with poly-al laminate moisture barrier, polythene sheathed, G.S.Tape armoured polythene jacketed having laid in provided trench as per specification No. WG-TW
Supplying, erecting & commissioning MDF Box 50x50 pairs made from min. 1.5mm thick MS sheet as per specification no. WG-TW
Supplying, erecting & commissioning MDF Box 200x200 pairs made from min. 1.5mm thick MS sheet as per specification no. WG-TW
Supplying, erecting & commissioning 10 pair module for connection & disconnection of telephone cable as per specification no. WG-TW
Supplying and installing, testing & commissioning of digital (hybrid) type EPABX of 6 x 32 extensions suitable upto 96 extensions complete.
Supplying, installing, testing & commissioning IP telephone instrument as per specification complete.
Supplying, installing, testing & commissioning analogue type 1+1 basic twin instrument telephone set without display complete
Supplying & installing expansion cabinet for extension of digital hybrid EPABX to expand system by 32 ports with programming and configuration of extensions and Direct lines with required accessories complete.
Supplying and installing enhanced cat-6 cable with 4-connector channel, performance test report as per ANSI/TIA-568.2-D suitable for networking complete as per specification.
Supplying and erecting LSZH armoured multimode optical fibre cable with 6 fibres, core dia 50/125 µm (OM3), suitable upto 10 GBPS, ethernet distance at 850 nm of wavelength, on wall/ceiling or laid in provided pipe/trench as per specification no. WG-COC/OFC LSZH
Supplying and fixing 1 m UTP patch cord of Cat 6 type in position as per specification No. WG-COC/PC
Supplying, fixing, and configuring 20 (1G-RJ45) ports + 4 combo 1G ports + 4 Supplying, fixing, and configuring 20 Ports + 4 SFP combo, Layer 2, GB managed ethernet switch, with web view/CLI erected in provided rack complete
Supplying, fixing, and configuring 24 ports with 4 (SFP+) port, ethernet managed switch with web view/CLI, 6KV surge protection on ethernet port and console port for management in provided rack as per specification no. WGNWC/GBS
Supplying and fixing 24 port patch panel with tool-less keystone jacks in provided U Rack complete as per specification no. WG-NAS/PP
Supplying and fixing 24 ports light guide unloaded interconnect unit, rack mounted type, with adapter panel for termination of optical fibre cables in provided U rack complete as per specification no. WG-NAS/ LIU
Supplying and fixing SC/LC type multimode duplex adapter to couple two connectors between OFC & Fibre switch/Fibre module as per specification no. WG-NAS/MMA
Supplying and fixing SC/LC type multimode pigtails (OM3) for LIU to terminate OFC in LIU as per specification No. WG-NAS/LIU2
Supplying and fixing 6U wall mount rack (Dimension-DxWxH – 500x600x367mm) as per specification No. WG-NAS/RAK
Supplying and fixing 17U floor mount rack (Dimension-DxWxH – 800x600x954mm) as per specification No. WG-NAS/RAK
Supplying and erecting LED square / circular Max. 18 W down lighter/ Panel Light having pressure die-cast aluminium housing, polystyrene diffuser having system lumens output of Min. 2000 Lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50, including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty.
Supplying and erecting LED square / circular Max. 25 W down lighter/ Panel Light having pressure die-cast aluminium housing, polystyrene diffuser having system lumens output of Min. 2750 Lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50, including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty.
Supplying and erecting LED Panel Light(600mm X 600mm) Max. 35 W having CRCA powder coated housing, polystyrene diffuser having system lumens output of Min 4200 Lumens, min. efficacy of 120 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50 including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty.
Supplying and erecting rectangular shaped LED Panel Light(1200mm X 300mm) Max. 35 W having CRCA powder coated housing, polystyrene diffuser having system lumens output of Min. 4200 Lumens, min. efficacy of 120 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50, including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty.
Supplying and erecting bulk head LED fitting max. 10W with high transitivity diffuser with system lumens output of min. 1100 lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., THD<10%, p.f. >0.95, operating range of 140-260V, in built surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50, including driver, IP66, IK09 rated on provided PVC block / wooden board with 3 years warranty.
Supplying and erecting CRCA powder coated corridor / passage light LED fitting (4 feet) Max. 33W with high transitivity diffuser with system lumens output of Min. 4000 lumens , min. efficacy of 120 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., Ripple<5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 4 kV, Life class of 50,000 Hrs. at L70B50, including driver, with end caps on provided PVC Block / wooden board with 3 years warrant
Supplying & erecting 18W, 230V integral type LED Lamp suitable for B-22 / E27 base.
Supplying & erecting Aviation obstruction light consisting of yellow painted diecast aluminium alloy housing with Integral LED aviation light comprising of aluminium housing with polycarbonate enclosure complete.
Supplying and erecting energy saving ceiling fan 230 V A.C. 50 cycles 1200 mm complete erected in position as per specification no. FG-FN/CF
Supplying, erecting, testing and commissioning of 10kVA capacity online pure sine wave, with backup time of 30 hrs. PWM & IGBT based UPS with 0.9 to unity output pf, 3 phase input & 3 phase output complete with all protections as per specification no. AP-UPS
Supplying, erecting, testing and commissioning of 20kVA capacity online pure sine wave, with backup time of 30 hrs. PWM & IGBT based UPS with 0.9 to unity output pf, 3 phase input and 3 phase output complete with all protections as per specification no. AP-UPS
Supplying and erecting 12 V/65Ah SMF battery with battery terminal wire, duly charged complete with 24 months warranty complete
Supplying, erecting & marking SPMCB 6A to 32A, C-series with rated short -circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting & marking SPMCB 6A to 32A, B-series with rated short -circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting & marking TPMCB 6A to 32A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting & marking TPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting & marking FPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying & erecting triple pole and neutral distribution board (TPNDB), SPMCB of 4 ways/phase (12 poles), with door, 1.2mm thickness, surface/flush mounted, IP 43 protection on iron/GI frame (horizontal busbar type) as per specification no. SW-SWR/MCBDB
Supplying & erecting triple pole and neutral distribution board (TPNDB), SPMCB of 8 ways / phase (24 poles), with door, 1.2mm thickness surface/ flush mounted, IP 43 Protection on iron/GI frame (horizontal busbar type) as per specification no. SW-SWR/MCBDB
Supplying & erecting triple pole and neutral distribution board (TPNDB), SPMCB of 12 ways /phase (36 poles), with door, 1.2mm thickness surface/flush mounted, IP 43 Protection on iron/GI frame (horizontal busbar type) as per specification no. SW-SWR/MCBDB
Supplying & erecting CRCA sheet metal one way enclosures of 1.2mm thickness suitable for DP MCB /TP MCB/FP MCB/RCCB/RCBO complete erected on angle iron/GI frame.
Supplying & erecting triple pole and neutral distribution board (TPNDB),SP/TP MCBs total 4 ways /12 Poles, with door, 1.2mm thickness surface/flush mounted, IP 43 Protection on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB
Supplying & erecting triple pole and neutral distribution board (TPNDB), 3 pole/ 4 pole MCCB as incomer & outgoing SP MCB (12 poles) or TP MCB of 4 ways (12 poles), with door, 1.2mm thickness, surface/flush mounted, on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB1
Providing & erecting 3 Pole MCCB, 415 V, 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB
Providing & erecting 4 Pole MCCB, 415 V, 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB(For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB.)
Providing & erecting 4 Pole MCCB, 415V, 200A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, With insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB(For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB.)
Providing & erecting 4 Pole MCCB 415V, 630A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB(For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB.)
Supplying, fixing and commissioning 4 pole RCBO 32/40A, with overcurrent, rated short-circuit breaking capacity (10 kA) and earth leakage protection, with 30/100/300 mA sensitivity and short circuit and earth leakage trip indication as per specification no SW-RCCB/RCBO
Supplying, fixing and commissioning 4 pole RCBO 63A, with overcurrent, rated short-circuit breaking capacity (10 kA) and earth leakage protection, with 30/100/300 mA sensitivity and short circuit and earth leakage trip indication as per specification no SW-RCCB/RCBO
Providing & erecting prewired meter module suitable for MCCB panel board with CTs and emfs VIF meter.
Supplying and erecting terminal spreaders suitable for 4 pole, above 400A up to 630A MCCB (Set of 8)
Supplying and erecting extended rotary handle for MCCB with adjustable telescopic rod suitable for up to 250A MCCB.
Supplying and erecting iron work, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority.
Supplying and erecting of any size electrolyte aluminium patti or bar in bus bar chamber / in panel or any other purpose, 500 V with require capacity 99.9% aluminium purity with E91E Grade as per IS 5082 & Current Density 0.8 A per sq. mm. with fixing arrangement (like lug or bottle type lug) to both the end with high grade polyolefin insulation sleeve complete as per specification no. BCPBB
Supplying & erecting LED type indicating pilot lamp with LED colours red /yellow / green, 230 / 250V on provided box / panel with necessary material,wiring & connections etc.
Supplying & erecting LED type indicating pilot lamp with LED colour blue, 230 / 250 V on provided box / panel with necessary material, wiring & connections etc.
Supplying, installation & marking of surge arrestor/ surge protection device at the sub main distribution board after the incoming breaker of type 2 tested for Imax 40 kA for three phase and neutral with compliance to IEC 61643-11 as per specification no. CP-SPD
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 25 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 70 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 6 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 10 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no.CB-LT/CU
Providing & erecting hot dipped galvanised cover suitable for perforated type Cable tray manufactured from 18 SWG (1.2 mm thick) GI sheet of 300 mm width & 20 mm height complete with necessary hardware.
Providing & erecting hot dipped galvanised cover suitable for perforated type Cable tray manufactured from 18 SWG (1.2 mm thick) GI sheet of 500 mm width & 20 mm height complete with necessary hardware.
Subwork-3 Estimate no : 111072 of 2023-2024 Providing Fire Fighting,Water Pumps,WTP, Installation Work Carrying out core cutting of size 3" to 5" dia x 15" length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original.
Supplying & erecting Fully Automatic Star/delta starter suitable for 12.5 H.P to 15 H.P. for 3 phase squirrel cage motor totally enclosed with overload and no volt relay complete erected on provided angle iron frame.
Supplying & erecting flat flexible 3 core 1.5 sq.mm PVC sheathed submersible type copper cable suitably clamped at fixed intervals with column pipe assembly complete.
Supplying, installation, testing and commissioning of main fire pump (MFP /EP) suitable for water discharge of 2280 to 2850 LPM at 90 to 70 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 55kW or of suitable kW capacity for manual/automatic operation and consisting of following : (a) Horizontal type, single stage, centrifugal/split casing pump of cast iron body & bronze impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plasteredwith anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/SSC/EP
Supplying, installation, testing and commissioning of jockey fire pump (JP) suitable for water discharge of 180 to 240 LPM at 140 to 110 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 15 kW or of suitable kW capacity for manual/automatic operation and consisting of following: (a) Horizontal/vertical type, multi stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade), mechanical seal conforming to IS 1520. (b) Suitable kW Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003)complete, as per specification no. FF-MFP/JP
Supplying, installation, testing and commissioning of booster fire pump [BP] suitable for water discharge of 900 LPM at 35 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 7.5 kW or of suitable kW capacity for manual/automatic operation and consisting of following : (a) Horizontal/vertical type, single/multi stage, centrifugal casing pump of cast iron body & bronze/CI impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d)Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/BP
Supplying, installation, testing and commissioning of main fire pump (MFP/DP) suitable for water discharge of 2280 to 2850 LPM at 90 to 60 m head driven by 76 HP or suitable HP capacity diesel engine at required working speed suitable for manual/automatic operation and consisting of following : (a) Horizontal type, single stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade), mechanical seal conforming to IS 1520. (b) Water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12/24 volts DC electric starting equipment with battery of required AH capacity with necessary charger suitable to work on 230v, 50Hz AC supply, diesel tank of minimum 150ltr capacity with first filling of diesel up to 100% level with necessary piping with valves up to engine ,exhaust pipe extended up to 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications etc. as required. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with engine assembly and accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/SSC/DP
Supplying and erecting G.I. pipe ‘C’ class ERW 25 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 50 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 65 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 75/80 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 100 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 150 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 200 mm dia with necessary fittings complete as per specification no. FF-PP
Providing coating of bitumen paint & 4mm thick wrapping for underground 150 mm ring main of fire fighting system.
Supplying and erecting 150 mm dia cast iron foot valve ball type/flap type with strainer for negative suction complete as per specification no. FF-VL/FV
Supplying and erecting 100 mm dia Cast Iron end line strainer of Y-type flanged end pattern, PN16 pressure rating, SS screen, end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) for positive suction complete as per specification no. FF-VL/ELS
Supplying and erecting 200 mm dia Cast Iron end line strainer of T-Pot type flanged end pattern, PN16 pressure rating, screen of SS and end connection with flanged, for positive suction complete as per specification no. FF-VL/ELS
Supplying and erecting 200 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV
Supplying and erecting 50 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying and erecting 100 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying and erecting 150 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying and erecting 100 mm dia cast iron double flange NRV complete with PN16 pressure rating, as per specification no. FF-VL/NRV
Supplying and erecting 150 mm dia cast iron double flange NRV complete with PN16 pressure rating, as per specification no. FF-VL/NRV
Supplying and erecting 200 mm dia cast iron double flange NRV complete with PN16 pressure rating, as per specification no. FF-VL/NRV
Supplying and erecting 50 mm dia gun metal gate valve complete with PN16 pressure rating, as per specification no. FF-VL/GV
Supplying and erecting gun metal single outlet hydrant valve fitted with necessary accessories complete as per specification no. FF-VL/HV
Supplying and installing wall mounting swinging hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene (Polyhose) along with necessary accessories complete as per specification no. FF-FFA/HV
Supplying and erecting 63mm dia, reinforced rubber lined (R.R.L.) hose pipe, 15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/RRL
Supplying and erecting 19 mm dia high pressure poly propylene hose pipe complete as per specification no. FF-FFA/HOP
Supplying and erecting gun metal branch pipe of 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as per specification no. FFFFA/NZ
Supplying and erecting 19 mm dia gun metal chrome plated nozzle complete as per specification no. FF-FFA/NZ
Supplying and erecting fire brigade header ( Siamese connection )of 150 mm dia, for supplying water in fire tank complete as per specification no. FF FA/FMC
Supplying and erecting 300 mm dia 1.5m in height air vessel / tank fabricated from min 5mm thick M.S. sheet complete as per specification no. FF-FFA/ACT
Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete as per specification no. FF-FFA/ARV
Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, erected with provided G.I. pipe, elbow etc. complete as per specification no. FF-FFA/PG
Supplying and erecting 12/15 mm dia pressure switch with provided isolation valve, G.I. nipple, elbow, etc complete as per specification no. FF-FFA/PS
Supplying and erecting M.S./CRCA cabinet for housing single hydrant valve of size ( 400 x 400 x 400)mm or hose pipe box of size ( 600 x 600 x 200)mm made from min. 1.5 mm thick CRCA sheet with angle iron work of min. of size (25 x 25 x 4) mm having front doors with viewing glass of size (200x150) mm and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5)
Supplying and erecting M.S./CRCA cabinet for housing Floor Hydrant valve, hose pipe, hose reel and branch pipe (size 1000 x 736 x 736 mm.) made from 16 SWG sheet and angle iron 25 x 25 x 4 mm. having front doors with viewing glass (8"x6") and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5)
Supplying, erecting, testing and commissioning of quartzoid bulb sprinkler, 15 mm (½") dia. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FFSPR.
Supplying, erecting, testing and commissioning vane type water flow detector 150 mm dia. with 1) Visual switch activation 2) Rugged switch assembly 3) Heavy duty aluminium pipe saddles 4)Durable metal enclosure 5) Steel U bolts for secure mounting 6) Two SPDT ( Single pole double track ) synchronised switches 7) serviceable without draining pipes.
Supplying and erecting fire resistant mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30-2011 suitable to seal the openings of all kinds of cables, pipes and cable support system in steel, aluminium and plastic profiles ( except hollow core conductors). The residual openings shall be closed with filler, as per specification no FF-FRM.
Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed in wall complete.
Supplying and erecting ISI mark GI pipe 32 mm. dia ‘C” class at position with accessories complete. Specification no. CW-PLB/GP.
Supplying and erecting ISI mark GI pipe 40 mm. dia ‘C” class at position with accessories complete. Specification no. CW-PLB/GP.
Supplying and fixing ISI grade approved 9 Ltrs. capacity galvanised round bottomed Fire Buckets, as per IS 2546, fully filled with dry yellow sand, painted Red and lettered 'FIRE' each with one stand with brackets to hang three buckets on each MS post as directed. (at meter rooms, substation, panel room)
Supplying and fixing resilient rubber neoprene lined Double arch vibration eliminators (water bellows) suitable for working pressure 13 kg/sq cm. and test pressure 20 kg/sq cm.
Supply erection of emergency start / stop push button station weather proof type for Booster pump at Reception.
Sprinkler Flexible drop 1000 mm long - UL Listed pipes made of Corrugated SS Tubing to with stand 16 Bar pressure with welded reducer on one end to directly accommodate sprinkler & female check-nut on the other end to connect to the branch pipe with supports complete.
Inspector test valve assembly with watch glass arrangement PN16, With Drain Ball Valve, 50mm dia
Supply & fixing of approved type Rosette Plates ( Recessed type, in two piece) for Sprinklers below false ceiling area. The Rosette shall be fabricated by M.S. plate, 2mm thick, powder coated of color approved by architects / client.
Supplying and fixing 150 mm Mechanical Gong Control Valve with 24 V hooter, bronze seat clapper, clapper arm, hydraulically driven mechanical gong bell to sound continuous alarm when wet riser / sprinkler system activates, clock valve, pressure gauge, emergency release, strainer, with drain pipe leading to drain, bypass, test control box, ball valves, orifice plate, gaskets, cabling, pressure & flow switches, Bell etc. Complete. (For sprinkler system)
150mm dia Victaulic / Mechanical Grooved Coupler, FM approved, ASTM F1476 compliant, grooved coupler with EPDM rubber gasket to take water pressure of 20 bar, and capable to accommodate a displacement of 6 to 9 mm for thermal movement in pipes, including SS bolts, nuts etc complete
Supplying and erecting ABC powder type fire extinguisher as per IS : 13849 of 4 kg capacity with necessary clamp for erection on Wall.
Supplying & erecting Carbon Dioxide (CO2) Trolley mounted Fire Extinguisher with 45 kg capacity, cartridge type conform to IS 2878, gas confirming to 15222, cylinder confirming to IS 7285, PESO approved complete.
Automatic Modular Extinguisher, Gas based (clean agent as per NFPA 2000) based sprinkler with MS vessel, ceiling mounted with necessary bracket, fasteners etc complete. (5 kg weight) (For Meter Rooms, Panel Rooms, Equipment Rooms etc)
Supplying and erecting PVC insulated PVC round sheathed 1 sq.mm (32 no. x 0.20mm dia.) 3 core flexible multi stranded copper Industrial cable for voltage grade up to 1.1 kV
Supplying, erecting, testing and commissioning self contained water cooler 230/250V 50Hz nominal cooling capacity of 40 litres per hour and storage capacity 80 litres with partially stainless steel body As per specification no. APWCR/ WC
Supplying & erecting Fully Automatic Star/delta starter suitable for 12.5 H.P to 15 H.P. for 3 phase squirrel cage motor totally enclosed with overload and no volt relay complete erected on provided angle iron frame.
Supplying & erecting Float sensor switch for water level controller working on 250V & rated current 8A, with 2 mtr. wire & High quality of wire & plastic body.
Supplying & erecting Dewatering Monoblock pump set 415V, 3 phase, 50C/s, A.C. supply of 5.5KW/ 7.5 H.P., of 21 to 36 m head with 910 to 190 LPM discharge, 14.5mm Solid Handling Capacity, non-clogging minimised abrasive wear, large impeller clearance & maintenance free pump set with water proof cable duly sealed with epoxy material built in protection to prevent the motor from burn out due to abnormal operation. specially designed high efficiency motor with F class insulation & the pump mechanically sealed in the oil chamber,. etc. complete as per specification no. DWP- SMP
WTP - 5cu./hr including Carbon, Sand filter, Chlorine dsinfection system, feedpumps ncluding all necessary piping in UPVC SCH80, valves etc complete
Hydro-pneumatic pumps set for pumping water from UGWT to multiple OHTs, including dry run protection, PLC panel, cabling, sensors, Pressure transmitters all related piping in SS 316, Brass valves like ball valves, NRV etc with vibration dampers, skid mounted assembly etc complete. (For Flushing water supply from GWT to OHT). Pump = Vertical inline monoblock centrifugal System Discharge ( Q ) = 200 LPM (Working) Individual Pump Discharge = 100 LPM Approximate Head in m ( H ) = 50 m Pump Qty – 2 working + 1 Supporting Maximum starts & Stops per Hrs. - 30 nos Approx. System Electrical Requirement = 4 HP (Working) Approx. Individual Pump Electrical Requirement = 2 HP Diaphragm type pressure tank Capacity in lit : 50 ltr. Working Pumps on VFD
Hydro-pneumatic pumps set for pumping water from UGWT to multiple OHTs, including dry run protection, PLC panel, cabling, sensors, Pressure transmitters all related piping in SS 316, Brass valves like ball valves, NRV etc with vibration dampers, skid mounted assembly etc complete. (For Domestic water supply from GWT to OHT) Pump = Vertical inline monoblock centrifugal System Discharge ( Q ) = 300 LPM (Working) Individual Pump Discharge = 150 LPM Approximate Head in m ( H ) = 50 m Pump Qty – 2 working + 1 Supporting Maximum starts & Stops per Hrs. - 30 nos Approx. System Electrical Requirement = 8 HP (Working) Approx. Individual Pump Electrical Requirement = 4 HP Diaphragm type pressure tank Capacity in lit : 50 ltr. Working Pumps on VFD
Supplying, installing, testing, and commissioning of Deluge valve of 100mm dia comprising of a main gate valve, in and pressure guage, water motor gong, test connection of adequate size with valve and other accessories complete as per NFPA standard including relevent trimkits and solenoid valve with mating flanges suitable to be activated by the Flow Switches including power and control wiring upto panel & ON/OFF arrangement and associated works.
Providing, installation, testing & commissioning of water curtain nozzle, UL Listed, 15mm dia at connection, PN16 nickel chrome plated brass, BSPT, K-32 or K-factor as per design consideration complete as required and coverage of 2.5 meter either side.
Supplying and erecting HMS PVC conduit FRLS grade 25 mm dia. With necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC
Supplying and laying HMS PVC conduit FRLS grade 25 mm dia with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC.
Supplying and erecting PVC box trunking of size 100x50 mm. with accessories on wall/ceiling as per specification No: WG-MA/BOX .
Supplying, installing, testing and commissioning remote response indicators suitable to operate on 5 - 28 V dc supply having FR Polymer ABS Housing complete as per specification no. FF-FAAS/RRI
Supplying, installing, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the 8 loop capacity and capable of supporting upto 250 devices and detectors per loop, with on-board LCD display with min 16 lines of text, operating at 230 V 50HZ - AC with inbuilt Battery Backup of a minimum 24 hours in normal condition and 30 min in alarm condition, suitable provision for network connectivity,interfacing with third party equipment via a MODBUS/ OPC/ L-ON interfaceetc. conforming to IS 15908:2021, IS 2189: 2008, EN 54 & VDS / FM/ UL 864 (10th edition) with 3 years replacement warranty FF-AFAS/CP
Supplying, installing, testing and commissioning of repeater panel with suitable battery backup of a minimum of 24 hours in normal condition and 30 min in alarm condition, 80 backlit alphanumeric LCD display with inbuilt buzzer to indicate fault/fire alarm, manual control keys for silence/mute and to reset the FACP from the repeater station. Panel size shall not more than 175 x 275 x 65 mm conforming to EN 54 or UL approved with 3 years equipment replacement warranty FF-AFAS/RP
Supplying, installing, testing and commissioning of addressable optical smoke detector, single/twin LED’s with 360 degree view, suitable for low voltage 15 to 32 V DC two wires supply, in-built locking mechanism to check the removal and pilferage of the detector, in built isolation mode, start up current 300µA and alarm condition current shall be maximum 6.5 mA, operating temperature 0°C to 50°C, humidity 0-95% RH, IP 41, conforming to IS 2189: 2008, 11360_1985_Reff2020 EN 54 or UL Approved with 3 years equipment replacement warranty FFAFAS/SD .
Supplying, installing, testing and commissioning of intelligent addressable thermal/heat detector with rate of rise cum fixed temperature thermistor complete with base as required, suitable for temperature variations from -20°C to 38°C for fixed-heat and rate-of-rise type detectors and 0°C to 66°C for high heat type detectors, in built isolation mode, suitable for offices/ceiling cable trenches/less ventilation area's etc. with 3 years equipment replacement warrantyIS : 2175 - 1988 reaffirmed 2000, IS 15908:2021 standards FF-AFAS/SD.
Supplying, installing, testing and commissioning of addressable manual call points ( break glass type/pull station type), made of addressable break glass plastic square in shape surface/flush mounted with "Break Glass" massage embedded on the glass, complete erected with mounting base and required accessories conforming to EN 54 or UL listed with 3 years equipment replacement warranty FF-AFAS/MCP.
Supplying, installing, testing and commissioning of addressable fire control/relay module complete as required, with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 reed relays, EN 54 or UL Listed FF-AFAS/CRM
(New) Supplying, installing, testing and commissioning of addressable fire monitor module complete as required. EN 54 or UL Listed with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/MM
Supplying, installing, testing and commissioning of addressable fire isolator module complete as required. EN 54 /FM or UL Listed with 3 years equipment replacement warranty conforming to IS 5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/ISM
Supplying, installing, testing and commissioning of addressable horn cum strobe sound/ hooter, output frequency 500 to 1000 Hz with dB as per Chart given in IS 15908:2021, with flashing at 1 Hz over the strobe’s entire operating voltage range EN 54, conforming to IS 2189: 2008, IS 15908:2021 standards with 3 years equipment replacement warranty FF-AFAS/SSH.
Supplying, erecting, testing and commissioning 120 W amplifier suitable to operate on 230 Volts A.C. / 12 Volts D.C. supply complete as per specification no. FF-PA/AFR
Supplying, erecting, testing and commissioning of 2 core shielded cable complete as per specification no. FF-PA/MCC
Supplying, erecting, testing and commissioning of 1.0 sq. mm speaker wire complete.
Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required.
Supplying, installation, testing & commissioning of 2-Way Fire Fighting Telephone Jack for communication.
Supplying, installation, testing & commissioning of Fire Fighting Telephone Headset.
Subwork-4 Estimate no : 111072 of 2023-2024 Providing Lift Installation Work(Total - 6 Lifts)For Proposed Construction of Sahakar Sankul Building(B.F+L.G.F+U.G.F+4 Floors+Terrace) SITC of Electric Traction Passenger Lift with 1386712 Rated capacity :- 13 Passenger/884Kg · Floors :- BF+LGF+UGFG+4 floor (7 Stops/7 Landings) .Travel :- 3 to 24 mtrs. Location of Lift Machine:- MR/MRL · Rated speed :- 1.0mps VS · Car/Landing door clear opening of 900/1000 mm wide x 2000 mm high · Clear Car size of 2000 mm wide x 1100 mm deep x 2250 mm high . Lift shaft available having clear size of 2550 mm wide x 1950 mm deep, 2000 mm Pit depth, 2600 mm Overhead. Doors type :- COPO/TOPO Doors with frame made from SS 304 grade solid(non-cladded) sheet of 1.5mm thick in hairline finish for car and all landing doors with SS door architraves/frames The lift doors shall have minimum 1 hour fire rating (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory). ·Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. The lift car interior design shall be done as per the directions of engineer in charge. · COP with SS face plate having metallic push buttons with Braille code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with / without attendant key switch, OWD with audio-visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor. ·LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings. ·Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port. The controller shall have necessary protections such as overcurrent, overvoltage, over speed, overheat for all devices including lift motor and travel direction protection, protection for phase loss at input or output etc. various operation modes such as maintenance, change direction by attendant, full load bypass, VIP call operation, self levelling operation, call cancel facility, auto return to home landing, fireman evacuation operation, earthquake operation, door open/close operation from COP etc. The system can record information for minimum 30 latest faults, with real-time clock management and handheld keypad with LCD screen for view and setting of parameters, The control panel duly wired with proper size & strength, copper wire for power & control circuit, with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class. .ARD complete with necessary SMF VRLA batteries. Fireman controller having fireman switch at fire Landing. CCTV surveillance system comprises of 2 nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for min. 90 days with min. 18” FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge. Lift Machine of Gearless PMSM of suitable kW with duty cycle of minimum 120 starts/hr (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory), with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength. Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work.Minor civil work such as alteration work if any necessary for erection of landing door frames and it's accessories e.g. sill, header, hole pass etc complete with plaster finish, civil work for erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails, providing and fixing steel girders/RCC work having adequate strength for mounting and hoisting lift machine etc. complete as per specification no. LFT. General: - Job includes entire procedure of obtaining all necessary erection permissions & "License to Work the Lift" from Electrical Inspector(Lifts) with submission to the Engineer In Charge. The above rate includes Fully Comprehensive AMC for one year from the date of commissioning. ADD ON- ADD ON NOTE A1-3 For Lift having 900mm wide x 2000mm high clear entrance in 1.5mm thick SS 304 grade solid(non-cladded) landing door [Two panel], this includes all necessary accessories like LOP's with UP/DN buttons-arrows-indicators, extension of guide rails, shaft wiring with trunking, travelling cables, main hoisting ropes/belts, & OSG rope landing doors with all accessories etc. necessary for the normal safe functioning of lift installation complete.
SITC of Electric Traction Passenger Lift with · Rated capacity :- 16 Passenger/1088Kg · Floors :-BF+LGF+UGF+4 floor+Terrace (7 Stops/7 Landings) · Travel :- 21 to 29.4 mtrs · Location of Lift Machine:- MR/MRL · Rated speed :- 1.5mps VS · Car/Landing door clear opening of 1000mm wide x 2250 mm high · Clear Car size of 1600 mm wide x 1600 mm deep x 2250 mm high · Lift shaft available having clear size of 2400 mm wide x 2300 mm deep, 1500 mm Pit depth, 2550 mm Overhead. Doors type :- COPO/TOPO Doors with frame made from SS 304 grade solid(non-cladded) sheet of 1.5mm thick in hairline finish for car and all landing doors with SS door architraves/frames The lift doors shall have minimum 1 hour fire rating (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory) ·Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. The lift car interior design shall be done as per the directions of engineer in charge. COP with SS face plate having metallic push buttons with Braille code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with / without attendant key switch, OWD with audio-visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor. LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings. Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port. The controller shall have necessary protections such as overcurrent, overvoltage, over speed, overheat for all devices including lift motor and travel direction protection, protection for phase loss at input or output etc. various operation modes such as maintenance, change direction by attendant, full load bypass, VIP call operation, self levelling operation, call cancel facility, auto return to home landing, fireman evacuation operation, earthquake operation, door open/close operation from COP etc. The system can record information for minimum 30 latest faults, with real-time clock management and handheld keypad with LCD screen for view and setting of parameters, The control panel duly wired with proper size & strength, copper wire for power & control circuit, with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class. · ARD complete with necessary SMF VRLA batteries. Fireman controller having fireman switch at fire Landing. CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for min. 90 days with min. 20" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge. Lift Machine of Gearless PMSM of suitable kW with duty cycle of minimum 120 starts/hr (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory), with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength. Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work. Minor civil work such as alteration work if any necessary for erection of landing door frames and it's accessories e.g. sill, header, hole pass etc complete with plaster finish, civil work for erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails, providing and fixing steel girders/RCC work having adequate strength for mounting and hoisting lift machine etc. complete as per specification no. LFT. General: - Job includes entire procedure of obtaining all necessary erection permissions & "License to Work the Lift" from Electrical Inspector(Lifts) with submission to the Engineer In Charge. The above rate includes Fully Comprehensive AMC for one year from the date of commissioning. Add On Note- For Lift having 1000mm wide x 2000mm high clear entrance in 1.5mm thick SS 304 grade solid(non-cladded) landing door [Two panel], this includes all necessary accessories like LOP's with UP/DN buttons-arrows-indicators, extension of guide rails, shaft wiring with trunking, travelling cables, main hoisting ropes/belts, & OSG rope landing doors with all accessories etc. necessary for the normal safe functioning of lift installation complete.
SITC of Triplex Lift control system for three nos. microprocessor/PLC based simplex lift controllers along with necessary software with programming and hardware e.g. logic board, necessary communication/control/data cabling laying in rigid PVC conduits/trunking etc. complete.
Subwork-5 Estimate no : 111072 of 2023-2024 Providing CCTV Installation Work For Proposed Construction of Sahakar Sankul Building(B.F+L.G.F+U.G.F+4 Floors+Terrace) Supplying and erecting HMS PVC conduit FRLS grade 25 mm dia. With necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC.
Supplying and laying HMS PVC conduit FRLS grade 25 mm dia with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC.
Supplying and installing enhanced cat-6 cable with 4-connector channel, performance test report as per ANSI/TIA-568.2-D suitable for networking complete as per specification.
Supplying and erecting LSZH armoured multimode optical fibre cable with 6 fibres, core dia 50/125 µm (OM3), suitable upto 10 GBPS, ethernet distance at 850 nm of wavelength, on wall/ceiling or laid in provided pipe/trench as per specification no. WG-COC/OFC LSZH
Supplying and fixing 1 m UTP patch cord of Cat 6 type in position as per specification No. WG-COC/PC
Supplying, fixing, and configuring 24 ports, POE switch in provided rack as per specification No. WG-NWC/ENS
Supplying and fixing 24 port patch panel with tool-less keystone jacks in provided U Rack complete as per specification no. WG-NAS/PP
Supplying and fixing 24 ports light guide unloaded interconnect unit, rack mounted type, with adapter panel for termination of optical fibre cables in provided U rack complete as per specification no. WG-NAS/ LIU
Supplying and fixing SC/LC type multimode duplex adapter to couple two connectors between OFC & Fibre switch/Fibre module as per specification no. WG-NAS/MMA
Supplying and fixing 6U wall mount rack (Dimension-DxWxH – 500x600x367 mm) as per specification No. WG-NAS/RAK
Supplying and fixing 12U wall mount rack (Dimension-DxWxH – 500x600x635 mm) as per specification No. WG-NAS/RAK
Supplying & erecting of High definition 4/5 Megapixel IP IR Bullet Camera with following features Image Sensor : minimum 1/2.8" Progressive Scan CMOS, Video Resolution : minimum 2592 x 1520 Video Compression : H.264, H.265 or higher, at least Three individually configurable stream, Frame rate : minimum 25 fps at all resolutions,WDR : minimum 120 dB Wide Dynamic Range,ONVIF profile conformant, minimum IR distance : 50m, Lens Type : 2.8/4/6 mm Lens, fixed focal, Field of View : 2.8 mm, horizontal FOV 107°, vertical FOV 57°, diagonal FOV 129° 4 mm, horizontal FOV 86°, vertical FOV 47°, diagonal FOV 102° 6 mm, horizontal FOV 55°, vertical FOV 29°, diagonal FOV 65° Lux sensitivity - minimum 0.2 Lux at color, minimum 0.05 Lux at Black & White, 0.0 Lux (IR) Night Vision Distance minimum IR - 50m. Camera minimum Adjustment Angles - Pan : 350°, Tilt : 72°, Rotate : 350°. Power Supply : Support 12VDC & PoE, IP67, IK10 - Vandal Resistant. Built in micro SD/SDHC/SDXC card slot of minimum 128 GB, Built in microphone. minimum Input/Output - Audio in × 1, Audio Out × 1, Alarm in × 1, Alarm Out × 1. Image Settings : Rotate mode, saturation, brightness, contrast, sharpness, gain, white balance. Image Enhancements : Day/Night-Auto (ICR)/Color/Black & White, 3D Digital Noise Reduction, Automatic White Balance, Automatic Gain Control, Backlight Compensation, Highlight Compensation. Events : Privacy Masking, Motion detection, Scene change detection, Face capture, Video tampering, audio exception detection, Region entrance detection, Region exiting detection. Operating temperature ( -30 to 60° C ) . Security - User account and password protection, HTTPS, IP filter, IEEE 802.1X, digest authentication, user access log, TLS1.2, AES - 256, SSH/Telnet closed, FTP disabled. Protocol - DHCP, UDP, HTTP, HTTPS, NTP, DNS, RTP, RTSP, SMTP, SSL/TLS, TCP/IP, Secure Real-Time Transport Protocol (SRTP), Bonjour, SNMP and Secure shell (SSH) supported protocol. RoHS, WEEE, ISO-14001 and REACH compliant, UL/EN OR equivalent BIS/TECH/STQC or any indian standards as applicable, CE, FCC certified. duly erected in position on wall/ceiling/false ceiling/provided pole (mounting height not more than 5 meter) etc with all accessories etc complete as per specification no. CCTV-CAM
Supplying & erecting of High definition 4/5 Megapixel IP IR Dome Camera with following features Image Sensor : minimum 1/2.8" Progressive Scan CMOS, Video Resolution : minimum 2592 x 1520 Video Compression : H.264, H.265 or higher, at least Three individually configurable stream, Frame rate : minimum 25 fps at all resolutions, WDR : minimum 120 dB Wide Dynamic Range, ONVIF profile conformant, minimum IR distance : 50m, Lens Type : 2.8/4/6 mm Lens, fixed focal, Field of View :2.8 mm, horizontal FOV 107°, vertical FOV 57°, diagonal FOV 129° 4 mm, horizontal FOV 86°, vertical FOV 47°, diagonal FOV 102° 6 mm, horizontal FOV 55°, vertical FOV 29°, diagonal FOV 65° Lux sensitivity - minimum 0.2 Lux at color, minimum 0.05 Lux at Black & White, 0.0 Lux (IR) Night Vision Distance minimum IR - 50m. Camera minimum Adjustment Angles - Pan : 350°, Tilt : 72°, Rotate : 350°. Power Supply : Support 12VDC & PoE, IP67, IK10 - Vandal Resistant. Built in micro SD/SDHC/SDXC card slot of minimum 128 GB, Built in microphone. minimum Input/Output - Audio in × 1, Audio Out × 1, Alarm in × 1, Alarm Out × 1. Image Settings : Rotate mode, saturation, brightness, contrast, sharpness, gain, white balance. Image Enhancements : Day/Night-Auto (ICR)/Color/Black & White, 3D Digital Noise Reduction, Automatic White Balance, Automatic Gain Control, Backlight Compensation, Highlight Compensation. Events : Privacy Masking, Motion detection, Scene change detection, Face capture, Video tampering, audio exception detection, Region entrance detection, Region exiting detection. Operating temperature ( -30 to 60° C ) . Security - User account and password protection, HTTPS, IP filter, IEEE 802.1X, digest authentication, user access log, TLS1.2, AES - 256, SSH/Telnet closed, FTP disabled. Protocol - DHCP, UDP, HTTP, HTTPS, NTP, DNS, RTP, RTSP, SMTP, SSL/TLS, TCP/IP, Secure Real-Time Transport Protocol (SRTP), Bonjour, SNMP and Secure shell (SSH) supported protocol. RoHS, WEEE, ISO-14001 and REACH compliant, UL/EN OR equivalent BIS/TECH/STQC or any indian standards as applicable, CE, FCC certified. duly erected in position on wall/ceiling/false ceiling/provided pole (mounting height not more than 5 meter) etc with all accessories etc complete as per specification no. CCTV-CAM.
Supplying & erecting of High definition 4/5 Megapixel IP IR PTZ Camerawith following features Image Sensor : minimum 1/2.8" Progressive Scan CMOS Video Resolution: minimum 2880 x 1620 Video Compression : H.264, H.265 or higher, at least Three individually configurable stream, Frame Rate : minimum 30 fps at all resolutions, WDR : minimum 120 dB Wide Dynamic Range,ONVIF profile conformant. Auto Tracking, Pre-set Tour Settings, Pan : 360° endless, Tilt : From -15° to 90° (auto-flip 180°), minimum Pan Speed - from 0.1°/s to 160°/s, minimum Preset Speed: 240°/s, minimum Tilt Speed - from 0.1°/s to 120°/s, minimum Preset Speed : 200°/s, Min Presets- 250, Min IR distance :150m Lens Type : minimum 4.3 - 12.5mm Lens min 16 x digital zoom, min 30 x optical Zoom. Focus Mode : Auto/Zooming/One Push Manual, Lux sensitivity- minimum 0.2 Lux at color, minimum 0.05 Lux at Black & White,0.0 Lux (IR) Night Vision Distance Min IR- 150m, Power Supply : support 12/24 VDC, 24 VAC & PoE, IP67/IP66, IK10, built in micro SD/SDHC/SDXC card slot minimum 256 GB, built in microphone.minimum Input/Output : Audio in × 1, Audio Out × 1, Alarm in× 1, Alarm Out × 1. Image Settings : Rotate mode, saturation, brightness, contrast, sharpness, gain,white balance Image Enhancements : Day/Night-Auto (ICR)/Color/Black & White, 3D Digital Noise Reduction, Automatic White Balance, Automatic Gain Control, Backlight Compensation, Highlight Compensation. Events : Privacy Masking, Motion detection, Scene change detection, Face capture, Video tampering, audio exception detection, Region entrance detection, Region exiting detection. Operating temperature ( -30 to 60° C ) .Security : User account and password protection, HTTPS, IP filter, IEEE 802.1X, digest authentication, user access log, TLS1.2, AES-256, SSH/Telnet closed, FTP disabled. Protocol-DHCP, UDP, HTTP, HTTPS, NTP, DNS, RTP, RTSP, SMTP, SSL/TLS, TCP/IP, Secure Real-Time Transport Protocol (SRTP),Bonjour,SNMP and Secure shell (SSH) supported protocol.RoHS, WEEE, ISO-14001 and REACH compliant, UL/EN OR equivalent BIS/TECH/STQC or any indian standards as applicable, CE, FCC certified.duly erected in position on wall/ceiling/false ceiling/provided pole (mounting height not more than 5 meter) etc with all accessories etc complete as per specification no CCTV-CAM.
Supplying, installing, testing & commissioning of 64/80 Ch Network Video Recorder (NVR), suitable connect Min. 64 IP Cameras, up to 5 Megapixel Resolution, with HDMI 1/VGA 1 and HDMI 2/VGA 2 outputs provided, Atleast one HDMI output of 4K resolution, atleast one VGA output with output up to 1920 × 1080, Support H.265 or higher, H.264, MJPEG, Supports Redundant Dual Power,Incoming Bandwidth 320 Mbps with minimum 8 SATA Hard Disks, ANR Technology,8 SATA interfaces for 8 HDDs and capacity of each HDD up to 8TB, minimum 02 USB port, Alarm I/O 16/4, RJ-45 10/100/ 1000 Mbps selfadaptive Ethernet interface,support multi brand network Cameras, ONVIF conformance, Multiple network monitoring: Web viewer . support protocol TCP/IP, DHCP, DNS, DDNS, NTP, SADP, SMTP, NFS, iSCSI, UPnP™, HTTPS. RoHS, UL, CE, FCC certified. duly erected in provided U Rack with wiring connections, tagging and programming etc. complete as per specificationss no. CCTV-NVR
Supplying & erecting 8 TB internal Surveillance HDD suitable for SATA Port of NVR, interface transfer rate 6 GB/S, maximum sustained transfer rate 210 MB/Sec to 213 MB/S. Drive bay supported 08+, Cameras supported up to 64, Cache (MB) 256, Load/Unload Cycle -3000000, Work Load Rating per Year 180TB, MTBF 1000000 Hrs. HTTPS. RoHS, UL, CE certified, duly erected in position in provided NVR as per specification no. CCTV-HDD
Supplying & erecting 55" professional LED display with 1920 *1080 ( Full HD) Display, suitable for 32/64 channel NVR and following features Brightness: minimum 500 Cd/m2 Contrast Ratio: minimum 1000:1 Viewing angle: 178/178 deg. Response time: maximum 8 ms Inputs: HDMI, VGA, BNC,USB, Audio In, Built-in speakers maximum 10 W, Suitable to operate on 100-240 V 50 Hz AC supply and 24/7 Duty Cycle duly erected on wall or table top with standard accessories like wall mount stand and wiring connections etc. complete as per specifications no. CCTV-MON
Subwork-6 Estimate no : 111072 of 2023-2024 Providing HVAC System For Proposed Construction of Sahakar Sankul Building(B.F+L.G.F+U.G.F+4 Floors+Terrace) Supplying and erecting mains with 3x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting PVC insulated PVC round sheathed 1.5 sq.mm (30 no. x 0.25 mm dia.) 3 core flexible multi stranded copper Industrial cable for voltage grade up to 1.1 Kv
Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles 225mm. 1400 RPM rust proof body & blades, wire mesh, duly erected, complete.
Supplying and erecting exhaust fan heavy duty 230 V A.C. 50 cycles 450 mm.1400 RPM complete erected in position as per specification no. FG-FN/EXF
Supplying, erecting, testing and commissioning of 22HP, VRF/VRV air conditioning system outdoor unit (ODU) complies type-IV OEM standards working on HFC refrigerant R410A or other required/suitable green equivalent refrigerant, for minimum cooling capacity as delivering 100% capacity at 47° C, non stop cooling even at 56° C and coefficient of performance (COP) 3.00 to 4.00, modular type vertical hot air discharge suitable for longer piping range upto 1000 metre operation in cooling mode with inverter/ digital VRF/VRV technology microprocessor based control compressor starter/control panel with scroll compressor, air cooled copper condenser coil of suitable shape for increasing maximum heat transfer area, rain protection cover, built in oil separator, accumulator and oil receiver, copper tube aluminium fin air cooled condenser, condenser fan with motor suitable for 415V±10%, 50 Hz, 3 phase power supply (all suitable for high ambient conditions), internal copper refrigerant piping, internal wiring and refrigerant, etc. all housed in powder coated weather proof cabinet complete.
Supplying, erecting, testing and commissioning of 24HP, VRF/VRV air conditioning system outdoor unit (ODU) complies type-IV OEM standards working on HFC refrigerant R410A or other required/suitable green equivalent refrigerant, for minimum cooling capacity as delivering 100% capacity at 47° C, non stop cooling even at 56° C and coefficient of performance (COP) 3.00 to 4.00, modular type vertical hot air discharge suitable for longer piping range upto 1000 metre operation in cooling mode with inverter/digital VRF/VRV technology microprocessor based control compressor starter/control panel with scroll compressor, air cooled copper condenser coil of suitable shape for increasing maximum heat transfer area, rain protection cover, built in oil separator, accumulator and oil receiver, copper tube aluminium fin air cooled condenser, condenser fan with motor suitable for 415V±10%, 50 Hz, 3 phase power supply (all suitable for high ambient conditions), internal copper refrigerant piping, internal wiring and refrigerant, etc. all housed in powder coated weather proof cabinet complete.
Supplying, erecting, testing and commissioning of 26HP, VRF/VRV air conditioning system outdoor unit (ODU) complies type-IV OEM standards working on HFC refrigerant R410A or other required/suitable green equivalent refrigerant, for minimum cooling capacity as delivering 100% capacity at 47° C, non stop cooling even at 56° C and coefficient of performance (COP) 3.00 to 4.00, modular type vertical hot air discharge suitable for longer piping range upto 1000 metre operation in cooling mode with inverter/digital VRF/VRV technology microprocessor based control compressor starter/control panel with scroll compressor, air cooled copper condenser coil of suitable shape for increasing maximum heat transfer area, rain protection cover, built in oil separator, accumulator and oil receiver, copper tube aluminium fin air cooled condenser, condenser fan with motor suitable for 415V±10%, 50 Hz, 3 phase power supply (all suitable for high ambient conditions), internal copper refrigerant piping, internal wiring and refrigerant, etc. all housed in powder coated weather proof cabinet complete.
Supplying, erecting, testing and commissioning of 28HP, VRF/VRV air conditioning system outdoor unit (ODU) complies type-IV OEM standards working on HFC refrigerant R410A or other required/suitable green equivalent refrigerant, for minimum cooling capacity as delivering 100% capacity at 47° C, non stop cooling even at 56° C and coefficient of performance (COP) 3.00 to 4.00, modular type vertical hot air discharge suitable for longer piping range upto 1000 metre operation in cooling mode with inverter/digital VRF/VRV technology microprocessor based control compressor starter/control panel with scroll compressor, air cooled copper condenser coil of suitable shape for increasing maximum heat transfer area, rain protection cover, built in oil separator, accumulator and oil receiver, copper tube aluminium fin air cooled condenser, condenser fan with motor suitable for 415V±10%, 50 Hz, 3 phase power supply (all suitable for high ambient conditions), internal copper refrigerant piping, internal wiring and refrigerant, etc. all housed in powder coated weather proof cabinet complete.
Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette room/indoor unit (IDU-compact/standard size) of nominal cooling capacity 1.0TR ( 441 cfm ) to 1.3TR (512 cfm ) having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. IDU with drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anti corrosive coating suitable for coastal area in all respects suitable to operate on 1-phase, 230V, 50Hz, AC supply complete. The unit consisting with any additional refrigerant and oil charge as per requirement during installation.
Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette room/indoor unit (IDU-compact/standard size) of nominal cooling capacity 1.5TR (512 cfm) to 1.8TR (618 cfm) having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. IDU with drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anti corrosive coating suitable for coastal area in all respects suitable to operate on 1-phase, 230V, 50Hz, AC supply complete. The unit consisting with any additional refrigerant and oil charge as per requirement during installation.
Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette room/indoor unit (IDU-compact/standard size) of nominal cooling capacity 2.0TR (618 cfm) to 2.3TR (671 cfm) having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. IDU with drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anti corrosive coating suitable for coastal area in all respects suitable to operate on 1-phase, 230V, 50Hz, AC supply complete. The unit consisting with any additional refrigerant and oil charge as per requirement during installation.
Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette room/indoor unit (IDU-compact / standard size) of nominal cooling capacity 2.6TR (918 cfm) to 2.8TR ( 1100 cfm ) having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. IDU with drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anti corrosive coating suitable for coastal area in all respects suitable to operate on 1-phase, 230V, 50Hz, AC supply complete. The unit consisting with any additional refrigerant and oil charge as per requirement during installation.
Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette room/indoor unit (IDU-compact / standard size) of nominal cooling capacity 3.0TR (1100 cfm) to 3.2TR (1165 cfm) having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. IDU with drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anti corrosive coating suitable for coastal area in all respects suitable to operate on 1-phase, 230V, 50Hz, AC supply complete. The unit consisting with any additional refrigerant and oil charge as per requirement during installation.
Supply, installation, testing and commissioning of manually operated, opposed blade, duct mounted, flanged volume control dampers of required sizes in GI construction with operating mechanism, mounting arrangement, etc.
Supply, fabrication, installation and testing of flexible canvas connections constructed between ductable unit/AHU /FAN of suitable size with fire resist flexible double canvas sleeve complete.
Providing adhesive thermal insulation for supply / return air duct with 19mm nitrile rubber insulation having R-value as per the prevailing provisions in ECBC2017
Providing and applying of acoustic insulation for air ducts with 15mm thick, 48 kg/cu.m class 'O' nitrile rubber with necessary accessories.
Supplying & erecting tile type modular diffuser made from aluminium sheet with powder coated matching to the ceiling shade for provided supply and return air complete.
Supplying and installation of high pressure grade required size copper connection Y or T- Joints/refnet complete erected on wall/ceiling with supports/raceways, Nitrile rubber insulation, painting etc. with brazing and testing for leakages confirming the normal operation of the VRV/VRF air conditioning system.
Supplying and installing of collar damper of galvanised iron material of upto 120 microns for anti corrosive resistance for supply air grill / diffuser of suitable size.
Supplying, laying/fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 41.3mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete.
Supplying, laying/fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 34.9mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete.
supplying, laying/fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 28.6mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete.
supplying, laying/fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 22.2mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultraviolet radiation with OEM standards of VRV/VRF air conditioning system complete.
supplying, laying/fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 19.1mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19 mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultraviolet radiations with OEM standards of VRV/VRF air conditioning system complete.
supplying, laying/fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 15.9 mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultraviolet radiations with OEM standards of VRV/VRF air conditioning system complete.
supplying, laying/fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 12.7mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultraviolet radiations with OEM standards of VRV/VRF air conditioning system complete.
supplying, laying/fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 9.5 mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultraviolet radiations with OEM standards of VRV/VRF air conditioning system complete.
supplying, laying/fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 6.4mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultraviolet radiations with OEM standards of VRV/VRF air conditioning system complete.
Supplying and erecting 25/32 mm (ID/OD) Chlorinated polyvinyl chloride pipe (CPVC), thickness 3.2 mm conforming to IS 15778 (CTS Series) with necessary CPVC fittings and solvent cement for AC System as per specification No. ESD-HWP/CPVC Note : For Chlorinated Polyvinyl Chloride pipe, additional insulation of maximum 6 mm thickness to be considered on pipe.
Supplying and erecting 32/40 mm (ID/OD) Chlorinated polyvinyl chloridepipe (CPVC), thickness 3.8 mm conforming to IS 15778 (CTS Series) with necessary CPVC fittings and solvent cement for AC System as per specification No. ESD-HWP/CPVC Note : For Chlorinated Polyvinyl Chloride pipe, additional insulation of maximum 6 mm thickness to be considered on pipe.
Supplying and erecting 40/50 mm (ID/OD) Chlorinated polyvinyl chloride pipe (CPVC), thickness 3.8 mm conforming to IS 15778 (CTS Series) with necessary CPVC fittings and solvent cement for AC System as per specification No. ESD-HWP/CPVC Note : For Chlorinated Polyvinyl Chloride pipe, additional insulation of maximum 6 mm thickness to be considered on pipe.
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3 core 2.5 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 4 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 10 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal as per IS-277 (120 GSM both sides & confirming to Class VIII) for GS Sheets and Smacna Standards rectangular/round ducting complete with RTV duct Sealant ,neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approve drawings and specifications of following sheet thickness complete as required .Thickness 0.63 mm sheet (24 Guage)
Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal as per IS-277 (120 GSM both sides & confirming to Class VIII) for GS Sheets and Smacna Standards rectangular/round ducting complete with RTV duct Sealant ,neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approve drawings and specifications of following sheet thickness complete as required .Thickness 0.80 mm sheet (22 Guage)
Supplying, fixing acoustic lining on wall and ceiling of AHU rooms with 50mm thick, density 32 kg/cu.m resin bonded glass fiber insulation friction fixed in 610mm x 610 mm frame work made of 25X50X50X50X25 mm made out of 0.6mm thick GI sheet U shaped channel and covered with reinforced fiber glass tissue and finished with 0.80 mm perforated aluminium sheet etc. complete as required and as per specifications.
Supplying, installing, testing and commissioning of smoke spill single speed (VFD)compatible axial fans. Fan, casing, motor, drive shall be suitable for smoke exhaust application & thermally rated for 250ºC for 2 hours as per [BS-7346 Part-2 : 1090] Class-H. Motors shall be High Temperature resistance smoke venting type suitable for 415+10% volts, 50 cycles , 3 phase AC supply with IP 55 protection, static pressure shall be as indicated. Each fan shall be with TEFC squirrel cage induction motors, all fan shall be with flexible fire proof connection at inlet and outlet. Suitable spring isolators to provided along with the fans. Spring mount Isolater to have Efficiency of above 90%. Quoted price to include MS structural work required for mounting the fans as indicated in the drawing.These fans shall operate during Normal as well as fire mode.All fans should be interlock with the fire alarm control panel in case of fire emergency operation. CFM: 32000 @20mm WG Exhaust Air Fan
Supplying, installing, testing and commissioning of smoke spill single speed axial fans. Fan, casing, motor, drive shall be suitable for fresh air application & thermally rated for 250ºC for 2 hours as per [BS-7346 Part-2 : 1090] Class-H. Motors shall be High Temperature resistance smoke venting type suitable for 415+10% volts, 50 cycles , 3 phase AC supply with IP 55 protection, static pressure shall be as indicated. Each fan shall be with TEFC squirrel cage induction motors, all fan shall be with flexible fire proof connection at inlet and outlet. Suitable spring isolators to provided along with the fans. Spring mount Isolater to have Efficiency of above 90%. Quoted price to include MS structural work required for mounting the fans as indicated in the drawing. These fans shall operate during Normal as well as fire mode. All fans should be interlock with the fire alarm control panel in case of fire emergency operation. CFM: 32000 @20mm WG Fresh Air Fan
SITC of Centrifugal backward curved Jet fans with bottom suction. Fan shall be AMCA certified for Air & Sound performance. Fan shall be complete with GSS casing with two mounting brackets ( 220 GSM ), Aluminium impeller, Motor Class H and totally enclosed non-ventilated (TENV) high temperature rated motor certified for 250 Deg C for 2 Hrs - 415/3P/50Hz. Inlet & outlet attenuators , inlet & outlet protection net. Complete assembly shall be certified for 250 Deg C for 2 Hrs. fire rating as per BS EN 12101-3:2002 F200, F300 & F400, certified by TUV SUD PSB & the copy of the Fire-test report has to be submitted for the approval.The Locations of the jet fans has to be done in such a way that the Air velocity at any point on the plane of 1m from the ground level should not be less than 0.25m/s during the normal mode.[NON CSR]
SITC of carbon Monoxide sensor are designed for environment monitoring and controlling in industrial and commercial buildings.High performance semiconductor sensors and circuits, ensure accurate measurement and temperature compensation.Digital technology applied, multiple output optional, over voltage and reverse polarity protection, high reliability and interference. Sensor : Digital Semiconductor Range : 0~100/250/500 ppm (Jumper Settable) Output : 4~20mA / 2~10VDC; Jumper Settable Communication: 4~20mA / 2~10VDC; Jumper Settable Accuracy: ±5% of F.S Response time: <60 seconds; T90 in 45 seconds Sampling Time: 1s Power: 24V AC / DC Output Load: 500Ω (current), >2KΩ (voltage) Housing : Fireproof ABS Enclosure; UL94V0 Display : Analog Display Area Of Coverage : 500 m2 Agency Approval : CE
SITC of Control panel Fully compartmentalised comprising of incoming MCCB / MCB, Amp metering, outgoing feeders with MCB, DOL / star delta stater comprising of contactors, relays, pushbutton station, facility for remote operation through push buttons, Auto manual switches and safety devices. The panels shall be incorporate PLCs to run basement ventilation fans at a particular logic taking signals from CO sensosr & fire alarm systems. The necessory control circuits & equipments shall be considered in MCC cost. Incomer- 160A FP MCCB, Outgoing Feeder - 63A TP MCB+Starter-6 Nos, 25 TP MCB+Starter-16 Nos, 160 A Alu. Busbar.The PLC panel shall operate the main exhaust fans(VFD) (normal & fire mode) based on the signal from CO sensor. During a CO SENSOR signal for 30-90 ppm (i.e polution mode) in normal mode fans shall operate and at 100 ppm and above and fire mode or during emergency in fire mode exhaust fans shall operate along with the normal mode fans and Jet fans . The PLC panel should have the provision of hooking up the panel with the fire alarm / fire fighting panel in case of emergecny. The PLC panel should have the provision for monitoring the whole system through BMS. The PLC panel should have the provision for zone wise operation.PLC Panel to include the starter panel for all the jet fans & axial fans with DOL/Star Delta starter of required capacity for the respective ventilation zone, incoming switch gear, overload relay , control accessories like Elmex connectors, ferrules etc. with ON/OFF push button & indicating lamps (ON/OFF/TRIP), facility of control wiring for remote operation. Also potential free contacts to be provided for BMS. The panels to be designed considering 'Type 2' coordination.
Supply, installation, testing and comissiong of starter panel (IP 54 rated for indoor installation and IP 65 rated for outdoor installation) with DOL/Star Delta starter of required capacity incoming switch gear (MPCB), overload relay, control accessories like Elmex connectors, ferrules etc. with ON/OFF push button & indicating lamps (ON/OFF/TRIP), facility of control wiring for remote operation. The panels to be designed considering 'Type 2' coordination.Phase Reversal. 5.5 kW each fan (For Staircase,Liftwell Pressurization fan)[NON CSR]
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid