| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹13.7 LAccepted-AOC | L-1 | Accepted-AOC Lowest bidder for the subject work. | |
| 2 | L-2₹15.9 L+₹1.9 L (13.9%)Rejected-Finance | L-2 | Rejected-Finance other than the lowest bidder |
| Sl No | Description | Qty | Unit | KIRTIMAN ENTERPRISES L1 | KIRTIMAN TRADERS L2 |
|---|---|---|---|---|---|
| 1.00 | Disconnecting existing incoming & outgoing connections and servicing, overhauling and maintenance of VCB, 11 kV, vertical or horizontal isolation, installed with receiving, distribution system and capacitor bank including checking of different functional parts and setting/ calibration of VCB installations including the followings: -
(a) checking the protection system calibration of triple pole overload/earth fault relay with all three phase, trip supervision relay, lock out under voltage relay & outgoing.
(b) checking the alarm system with hooter and reset push button system and auxiliary alarm cancellation relay system.
(d) checking the metering system and replace the same if required as site requirement for ammeter & voltmeter with selector switch, frequency meter, indicator LED lamps for ON / OFF flushed with front of panel on incoming & out going sides.
(e) checking the operation of manual charging of the system button for ON/OFF.
(f) checking motor operated spring stored energy trip and closing coil system.
(g) checking auxiliary switching system for manual charging & all metering equipments.
(h) checking the CT coils & replace the same if required for proper functioning.
(i) checking the potential transformer fitted on top of the VCB along with metering equipments and functioning and reconnect the same with as per site requirements.
(j) checking the DC wiring system & battery bank and repair and replace the same as per site requirement.
(k) Dusting/cleaning by smooth brushing or dry cotton and lubricating of movable mechanism suitably with oil/grease and painting with enameled paint by scrapping the rusted surface and replacement of unserviceable/ burnt out/worn out spare parts with new one as per existing make including taking down/ dismantling of existing unserviceable spares parts of VCB/Capacitor Banks all as directed by Engineer-in-charge.
(l) Testing after repair/ maintenance as per OEM's instructions.
Note: -
(i) The quoted rate shall be inclusive of required T & P for including servicing, overhauling, calibration and testing etc.
(ii) The new spare parts required for replacement excluding wiring, nuts, bolts, washers, gasket etc. shall be paid and measured separately as as S & F in repairs.
(iii) Servicing, overhauling, calibration and testing etc. shall be carried out as per the Manufacturer’s instructions/ guideline and by the authorised of the manufacturer and the necessary literature shall be made available to the department. The quoted rate shall be inclusive of these aspects. | 16 | Each | 9,000 ₹1,44,000 Lowest | 12,000 ₹1,92,000 |
| 2.00 | Supply & Fix in repair Bushing SPOUT Set vertical type of epoxy resin with brass buss, colour red epoxy including connected of alluminium bus bar as per size - 03 Nos, for current capacity upto 630A, 11 KV VCB Switch, etc. with connetion including taking out old unsv complete all as specified and directed. | 4 | Each set of three | 7,000 ₹28,000 Lowest | 8,500 ₹34,000 |
| 3.00 | S&F in repair Current Transformer (CT) Ratio 100/50/5+5A of 11 KV, 15VA, Core 1, type Class - 0.5 accuracy including taking out old unsv complete all as specified and directed. | 4 | Each set of three | 8,000 ₹32,000 Lowest | 9,500 ₹38,000 |
| 4.00 | S&F in repair Potential transformer (PT) Ratio 11 KV/110 Volts dry type resin cast, type Class 0.5 accuracy including taking out old unsv complete all as specified and directed. | 4 | Each set of three | 9,000 ₹36,000 Lowest | 9,500 ₹38,000 |
| 5.00 | S&F in repair Auxillary switches provide remote electrical indication if the circuit breaker is open or closed they are provided two -switch combinations, with a maximum of two switch combinations for the NF frame and six two switch combinations for the RF frame complete all as per existing pattern including taking out old unsv complete all as specified and directed. | 4 | Each Set | 8,000 ₹32,000 Lowest | 8,000 ₹32,000 Lowest |
| 6.00 | Supply and fixing in repair Jaw Cluster contact rating upto 800 Amp, copper 99.9% electrolytic silver plated for VCB complete including taking out old unsv complete all as specified and directed. | 4 | Each Set of three | 15,000 ₹60,000 Lowest | 18,000 ₹72,000 |
| 7.00 | Supply & Fixing in repair CLOSING coil assembly voltage rating 110 V, DC of existing specification complete including taking out old unsv complete all as specified and directed. | 6 | Each | 3,000 ₹18,000 Lowest | 3,500 ₹21,000 |
| 8.00 | Supply & Fixing in repair TRIPING coil assembly voltage rating 110 V, DC of existing specification complete including taking out old unsv complete all as specified and directed. | 6 | Each | 2,000 ₹12,000 Lowest | 2,050 ₹12,300 |
| 9.00 | Supply & Fixing in repair Digital Multifunction meter having V,A,F,PF etc. Accuracy class 0.5 complete as per existing model including taking out old unsv complete all as specified and directed. | 6 | Each | 13,500 ₹81,000 Lowest | 15,000 ₹90,000 |
| 10.00 | Supply & Fixing in repair Amp meter selector switch 3 phase complete including taking out old unsv complete all as specified and directed. | 4 | Each | 3,000 ₹12,000 Lowest | 3,500 ₹14,000 |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
2 Oct 2025, 6:00 pmClosed
Col Pawan Kumar, CWE
Headquarters, Commander Works Engineer, Bhopal, Military Engineer Services, SI Line, Bhopal, Pin Code - 462001 (Madhya Pradesh)
REPAIR AND MAINT OF HT OVER HEAD, UG CABLES TRANSFORMERS VCBS AND CONNECTED WORKS NASIRABAD AND AJMER MIL STATION UNDER GE NAISRABAD
2025_MES_728679_1
84075/E8
Open Tender
Civil Works
Item Rate
180 days
Nasirabad
AS PER NIT CONDITION
7 documents required · 7 mandatory
₹500
Yes
GE Nasirabad
₹30,000
Yes
11 Oct 2025
1 Sept 2025
4 Oct 2025
1 Sept 2025
2 Oct 2025
15 Sept 2025
1 Sept 2025 - 15 Sept 2025
Amount
Supply & Fix in repair Bushing SPOUT Set vertical type of epoxy resin with brass buss, colour red epoxy including connected of alluminium bus bar as per size - 03 Nos, for current capacity upto 630A, 11 KV VCB Switch, etc. with connetion including taking out old unsv complete all as specified and directed.
S&F in repair Current Transformer (CT) Ratio 100/50/5+5A of 11 KV, 15VA, Core 1, type Class - 0.5 accuracy including taking out old unsv complete all as specified and directed.
S&F in repair Potential transformer (PT) Ratio 11 KV/110 Volts dry type resin cast, type Class 0.5 accuracy including taking out old unsv complete all as specified and directed.
S&F in repair Auxillary switches provide remote electrical indication if the circuit breaker is open or closed they are provided two -switch combinations, with a maximum of two switch combinations for the NF frame and six two switch combinations for the RF frame complete all as per existing pattern including taking out old unsv complete all as specified and directed.
Supply and fixing in repair Jaw Cluster contact rating upto 800 Amp, copper 99.9% electrolytic silver plated for VCB complete including taking out old unsv complete all as specified and directed.
Supply & Fixing in repair CLOSING coil assembly voltage rating 110 V, DC of existing specification complete including taking out old unsv complete all as specified and directed.
Supply & Fixing in repair TRIPING coil assembly voltage rating 110 V, DC of existing specification complete including taking out old unsv complete all as specified and directed.
Supply & Fixing in repair Digital Multifunction meter having V,A,F,PF etc. Accuracy class 0.5 complete as per existing model including taking out old unsv complete all as specified and directed.
Supply & Fixing in repair Master Trip Relay, 110 Volt DC Supply complete as per existing model including taking out old unsv complete all as specified and directed.
Supply & Fixing in repair Ammeter as per existing model size & capacity complete including taking out old unsv complete all as specified and directed.
Supply & Fixing in repair TNC Switch, three position switch, as per existing size complete including taking out old unsv complete all as specified and directed.
Supply & Fixing in repair Segment gear for 11KV Mechanism Assembly, as per existing size complete including taking out old unsv complete all as specified and directed.
Supply & Fixing in repair Z type switch, Micro limit, 11KV Windsor as per existing size complete including taking out old unsv complete all as specified and directed.
Supply only Vacuum Interrupter type as per existing model suitable for 11KV VCB Panel complete including taking out old unsv complete all as specified and directed.
Supply & Fixing in repair Numeric Relay with IDMT characteristics for overcurrent and earth fault protection, 110 Volt DC Supply with as setting range of 200% to 2000% Instantaneous Overcurrent /Short circuit protection and Earth fault protection in range of 1A to 5A in steps of 0.1A complete as per existing model including taking out old unsv complete all as specified and directed.
Supply & Fixing in repair LED type indication lamps as per existing Colour code for status - (ON/OF/TRIP/TCH/SPRING CHARGER), for breaker position (Test/Service), for aux supply availability (AC healthy/DC healthy) etc. capacity as per existing make and model complete including taking out old unsv complete all as specified and directed.
Supply and fixing in repair HRC(High Rupturing Capacity) Fuses suitable for 11KV, VCB, 630 Amp panel complete including taking out old unsv complete all as specified and directed.
Supply and fixing in repair space heater suitable for 11KV VCB panel as per existing wattage capacity complete including taking out old unsv complete all as specified and directed.
Supply and fix VCB Power Pack operating voltage 24 Volt - 110 Volt DC of existing capacity and make including taking out old one complete all as specified and directed.
S&F in repair spring charging motor 220V AC/110V DC complete including taking out old unsv complete all as specified and directed.
M&L for HT self fusing insulation tapes (without compound) of size 38 x 0.76 mm, 5 m long for VCB Bus bar insulation complete including taking down old to disposal off complete all as specified and directed.
Taking down old unserviceable control cable of any type and any size for taking credit complete all as specified and directed.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated control cable for working voltages of 1100 V, PVC sheathed, armoured, 12 core, nominal cross sectional area of main conductor 2.5 sqmm, stranded copper conductor, conforming to IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated control cable for working voltages of 1100 V, PVC sheathed, armoured, 6 core, nominal cross sectional area of main conductor 2.5 sqmm, stranded copper conductor, conforming to IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated control cable for working voltages of 1100 V, PVC sheathed, armoured, 4 core, nominal cross sectional area of main conductor 2.5 sqmm, stranded copper conductor, conforming to IS 7098 (Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
M&L Earthing complete with GI strip as earth lead and MS galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate is not less than 1.5 mtr below normal ground level connected to galvanized iron strips 32 x 6 mm with GI pipe, nuts, bolts and washers complete upto and including test point made out of 40 x 3mm GI flat, PCC pit of required size in PCC 1:2:4 type B1 and RCC cover with frame including plastering and white wash, charcoal, common salt 15cm at round the earth plate, watering pipe 20mm med grade/galvanized and 40mm dia GI pipe medium grade for GI strip protection with GI funnel including dismantling old earthing complete all as specified and directed as shown in electrical plate No 3 of SSR Part-I 2009. Notes: (i) The unit rate includes for 40mm diam medium grade protection pipe and earth lead upto 7.50 meter. (ii) Any variation in length of earth lead and protection pipe beyond 7.5 m shall be measured & paid seperately separately. (iii) PCC pit shall be provided at least 500mm away from the pit and not on the earth pit itself and the extra cost of additional height of watering pipe, bends, elbow etc shall be deemed to be included in the unit rate.
Supply and replace 32mm x 6 mm GI strip as in earth continuity conductor fixed to wall or pole or recess or chases or burried in ground or drawn in conduit pipe or any other indicated situation for loop earthing etc as required complete all as specified and directed.
Supplying and laying synthetic Rubber insulated mats 2.5 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m including taking out old unserviceable rubber matting and removing from site of work complete all as specified and directed.
KIRTIMAN TRADERS (BID ID -3439807)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .