COL VIKAS KESARWANI
HQ CWE AF LOHEGAON
PROVISION OF VOLTAGE STABILIZER FOR AC PLANTS AT WSA PTT AND SIMULATOR UNDER GE (AF) LOHEGAON AT AIRFORCE STATION PUNE
2023_MES_579335_1
81871/E8
Open Tender
Civil Works
Item Rate
180 days
GE AF LOHEGAON
Please refer Tender documents.
6 documents required · 6 mandatory
₹1,000
GE AF LOHEGAON
₹1.1 L
Yes
3 Apr 2023
6 Feb 2023
13 Mar 2023
6 Feb 2023
6 Mar 2023
20 Feb 2023
Amount
Supply, Installation, commissioning & Testing of automatic out door type servo controlled voltage stablizer of capacity 500 KVA, IP 55 Protection, Three phase , 50 Hz Naturally Oil cooled type with minimum 980 ltrs oil BIS certified, unbalanced type, copper wound, metallic body duly power coated with lifting hooks, digital display, relay free smooth and silent operation with 1st filling of Transformer oil up to level, stablizer shall conform to BIS 9815 Pat 1 1994 and having following specifidation :- (a) Input voltage 340V-480V (b) Stablized Output voltage - Phase to PHase 415 V +- 1%, Phase to Neutral - 240V+-1% (c) Rated frequency 50 Hz (d) Zero distortion in wave form (e) Response time not to exceed 20 mille second (f) Sensitivity (+/-) 1% (g) Rate of correction not less than 6 volt/second between phase to Neutral (h) Efficiency more than 95% (i) Load Type : Suitable for three phase, unbalanced type Load (j) Digital Multi Functional Meter (k) Stablizer Shall be free from Hunting during Automatic Operation (l) NO Load loss shall not be more than 5% of rated output current.
Note: Protections (1) Over load, Short Circuit protections at Input End by Micropocessor Based ACB 800 Amps, Four Pole, 50 KA, 415 Volts, manual draw out type, manual spring charging type with copper bus link, copper cables, Under Voltage tripping Cool including CTs all as directed (2) High/Low voltage cut off (3) By pass arrangement - Providing 01 Nos Four Pole ON Load Change Over switch 800 Amps, 415 Volts. (4) Single phase sequence change protection
Note (Contd...): Acceptance Test- Testing of Servo Voltage Stablizer should be carried out as per BIS 9815 (Part1) in OEM factory in the presence of rep of accepting officer & Contractor/his represtative. Contractor shall give 45 days advance intimation with respect to date of testing. The following testing shall be carried out, (i) Physical Examination (ii) Insulation Resistance (iii) HIgh VOLtage Test (iv) Leakage Current Test (v) Out Put Voltage (vi) NO LOad Current (vii) Measurement of No Load Loss (viii) Induced Voltage Test Note : Before make & specification approval type test report of OEM as per BIS 9815(Part 1) should be produced by Contractor for the specified capacity/next higher capacity of any voltage range from Govt Lab/NABL Accredited lab.
Supply, Installation, commissioning & Testing of automatic out door type servo controlled voltage stablizer of capacity 400 KVA, IP 55 Protection, Three phase , 50 Hz Naturally Oil cooled type with minimum 900. ltrs oil BIS certified, unbalanced type, copper wound, metallic body duly power coated with lifting hooks, digital display, relay free smooth and silent operation with 1st filling of Transformer oil up to level, stablizer shall conform to BIS 9815 Pat 1 1994 and having following specifidation :- (a) Input voltage 340V-480V (b) Stablized Output voltage - Phase to PHase 415 V +- 1%, Phase to Neutral - 240V+-1% (c) Rated frequency 50 Hz (d) Zero distortion in wave form (e) Response time not to exceed 20 mille second (f) Sensitivity (+/-) 1% (g) Rate of correction not less than 6 volt/second between phase to Neutral (h) Efficiency more than 95% (i) Load Type : Suitable for three phase, unbalanced type Load (j) Digital Multi Functional Meter (k) Stablizer Shall be free from Hunting during Automatic Operation (l) NO Load loss shall not be more than 5% of rated out put current.
Note: Protections (1) Over load, Short Circuit protections at Input End by MCCB TP 630 Amps, 415 Volts Adjustable thermal Magnetic release type including CTs all as directed - 1 Set (2) High/Low voltage cut off (3) By pass arrangement - Providing 01 Nos Four Pole ON Load Change Over switch 630 Amps, 415 Volts. (4) Single phase sequence change protection
Note(Contd...): Acceptance Test- Testing of Servo Voltage Stablizer should be carried out as per BIS 9815 (Part1) in OEM factory in the presence of rep of accepting officer & Contractor/his represtative. Contractor shall give 45 days advance intimation with respect to date of testing, The following testing shall be carried out, (i) Physical Examination (ii) Insulation Resistance (iii) HIgh VOLtage Test (iv) Leakage Current Test (v) Out Put Voltage (vi) NO LOad Current (vii) Measurement of No Load Loss (viii) Induced Voltage Test Note : Before make & specification approval type test report of OEM as per BIS 9815(Part 1) should be produced by Contractor for the specified capacity/next higher capacity of any voltage range from Govt Lab/NABL Accredited lab.
Supply, Installation, commissioning & Testing of automatic out door type servo controlled voltage stablizer of capacity 300 KVA, Three phase, IP 55 Protection, 50 Hz Naturally Oil cooled type with minimum 800. ltrs oil BIS certified, unbalanced type, copper wound, metallic body duly power coated with lifting hooks, digital display, relay free smooth and silent operation with 1st filling of Transformer oil up to level, stablizer shall conform to BIS 9815 Pat 1 1994 and having following specifidation :- (a) Input voltage 340V-480V (b) Stablized Output voltage - Phase to PHase 415 V +- 1%, Phase to Neutral - 240V+-1% (c) Rated frequency 50 Hz (d) Zero distortion in wave form (e) Response time not to exceed 20 mille second (f) Sensitivity (+/-) 1% (g) Rate of correction not less than 6 volt/second between phase to Neutral (h) Efficiency more than 95% (i) Load Type : Suitable for three phase, unbalanced type Load (j) Digital Multi Functional Meter (k) Stablizer Shall be free from Hunting during Automatic Operation (l) NO Load loss shall not be more than 5% of rated out put current.
Note: Protections (1) Over load, Short Circuit protections at Input End by MCCB TP 630 Amps, 415 Volts Adjustable thermal Magnetic release type including CTs all as directed - 1 Set (2) High/Low voltage cut off (3) By pass arrangement - Providing 01 Nos Four Pole ON Load Change Over switch 630 Amps, 415 Volts. (4) Single phase sequence change protection
Note(Contd...): Acceptance Test- Testing of Servo Voltage Stablizer should be carried out as per BIS 9815 (Part1) in OEM factory in the presence of rep of accepting officer & Contractor/his represtative. Contractor shall give 45 days advance intimation with respect to date of testing, The following testing shall be carried out, (i) Physical Examination (ii) Insulation Resistance (iii) HIgh VOLtage Test (iv) Leakage Current Test (v) Out Put Voltage (vi) NO LOad Current (vii) Measurement of No Load Loss (viii) Induced Voltage Test Note : Before make & specification approval type test report of OEM as per BIS 9815(Part 1) should be produced by Contractor for the specified capacity/next higher capacity of any voltage range from Govt Lab/NABL Accredited lab.
Supply, Installation, commissioning & Testing of automatic out door type servo controlled voltage stablizer of capacity 200 KVA, Three phase, IP 55 Protection, 50 Hz Naturally Oil cooled type with minimum 450. ltrs oil BIS certified, unbalanced type, copper wound, metallic body duly power coated with lifting hooks, digital display, relay free smooth and silent operation with 1st filling of Transformer oil up to level, stablizer shall conform to BIS 9815 Pat 1-1994 and having following specifidation :- (a) Input voltage 340V-480V (b) Stablized Output voltage - Phase to PHase 415 V +- 1%, Phase to Neutral - 240V+-1% (c) Rated frequency 50 Hz (d) Zero distortion in wave form (e) Response time not to exceed 20 mille second (f) Sensitivity (+/-) 1% (g) Rate of correction not less than 6 volt/second between phase to Neutral (h) Efficiency more than 95% (i) Load Type : Suitable for three phase, unbalanced type Load (j) Digital Multi Functional Meter (k) Stablizer Shall be free from Hunting during Automatic Operation (l) NO Load loss shall not be more than 5% of rated out put current.
Note: Protections (1) Over load, Short Circuit protections at Input End by MCCB TP 400 Amps, 415 Volts Adjustable thermal Magnetic release type including CTs all as directed - 1 Set (2) High/Low voltage cut off (3) By pass arrangement - Providing 01 Nos Four Pole ON Load Change Over switch 400 Amps, 415 Volts. (4) Single phase sequence change protection
Note(Contd...): Acceptance Test- Testing of Servo Voltage Stablizer should be carried out as per BIS 9815 (Part1) in OEM factory in the presence of rep of accepting officer & Contractor/his represtative. Contractor shall give 45 days advance intimation with respect to date of testing, The following testing shall be carried out, (i) Physical Examination (ii) Insulation Resistance (iii) HIgh VOLtage Test (iv) Lekage Current Test (v) Out Put Voltage (vi) NO LOad Current (vii) Measurement of No Load Loss (viii) Induced Voltage Test Note : Before make & specification approval type test report of OEM as per BIS 9815(Part 1) should be produced by Contractor for the specified capacity/next higher capacity of any voltage range from Govt Lab/NABL Accredited lab.
Supply, laying, jointing, testing & commissioning LT under ground cable 1100 volts grade XLPE insulated armoured with galvanised round steel wire or steel strap, electric power cable heavy duty, with multi stranded aluminum conductor, laid in trenches, ducts fixed on wall/poles with proper size saddles and clamp laid under road/path/drain/culverts or enclosed in GI pipe/fix complete all as specified and directed for following size :
185 Sq mm x 3.5 core
240 Sq mm x 3.5 core
300 Sq mm x 3.5 core
Supply, install, testing and commissioning of in door type LT Panel (CPRI Approved ) Powder coated, free standing type compartmentalized in construction factory fabricated from makes as specified and made out of 2 mm thick CRCA sheet & suitable size as apporved by GE to accomodate all accessories / fittings, MCCB, MCB, Contactors and TPN Copper bus bars having rating cap of 600 A. The TPN bus bars shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator. The bus bar shall have copper extension links for connecting with out going MCCB. The Out Going MCCB of rating greater than 600 amps shall have copper extension link & copper bus bar for connecting the cables. The cubicle shall have a bottom channel & free standing frame made of angle iron of size not less than 50 mm X 50mm X 6mm & detachable predrilled gland plateof thickness not less than 3 mm thick powder coated should be used at the bottom for entry of armoured cable of adequate size with glands.The above panel shall be front & Back openable lockable /openable by key from both sides.
Note: The panel shall be Dust, vermin proof and powder coated of approved thickness complete including CTs, control wiring by 1.5Sqmm Wire and consisting the following, including taking down of old unsv panel after disconnecting Existing cables, & Reconnecting the cables to new panels, replacing of cable glands, lungs and including PCC foundation, excevation, foundation bolts. The Panel shall comprise of following switchgears & acessories (a) MCCB FP 400 Amp 35 KA -01 Nos (For Main incoming) (b) MCCB TP 200 Amps 25 KA -02 Nos (d) MCCB TP 100 Amps, 25 KA-06 Nos (e) S&F Indicating Lamp RYB (LED) Type-01 Set Note : Layout diagram of panel shall be submitted by the Contractor for the approval of GE.
Supply install, test and commissioning of in door type LT Panel (CPRI Approved) Powder coated, free standing type compartmentalized in construction factory fabricated from makes as specified and made out of 2 mm thick CRCA sheet & suitable size as apporved by GE to accomodate all accessories / fittings, MCCB, MCB, Contactors and TPN Copper bus bars having rating cap of 600 A. The TPN bus bars shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator. The bus bar shall have copper extension links for connecting with out going MCCB. The Out Going MCCB of rating greater than 600 amps shall have copper extension link & copper bus bar for connecting the cables. The cubicle shall have a bottom channel & free standing frame made of angle iron of size not less than 50 mm X 50mm X 6mm & detachable predrilled gland plateof thickness not less than 3 mm thick powder coated should be used at the bottom for entry of armoured cable of adequate size with glands.The above panel shall be front & Back openable lockable /openable by key from both sides.
Note: The panel shall be Dust, vermin proof and powder coated of approved thickness complete including CTs, control wiring by 1.5Sqmm Wire and consisting the following, including taking down of old unsv panel after disconnecting Existing cables, & Reconnecting the cables to new panels, replacing of cable glands, lungs and including PCC foundation, excevation, foundation bolts. The Panel shall comprise of following switchgears & acessories (a) S&F MCCB FP 400 Amp 35 KA -01 Nos (For Main incoming) (b) S&F MCCB TP 200 Amps 25 KA -03 Nos (d) S&F MCCB TP 100 Amps, 25 KA-02 Nos (e) S&F Indicating Lamp RYB (LED) Type-01 Set Note : Layout diagram of panel shall be submitted by the Contractor for the approval of GE.
Supply install, test and commissioning of in door type LT Panel (CPR Approved) Powder coated, free standing type compartmentalized in construction factory fabricated from makes as specified and made out of 2 mm thick CRCA sheet & suitable size as apporved by GE to accomodate all accessories / fittings, MCCB, MCB, Contactors and TPN Copper bus bars having rating cap of 600 A . The TPN bus bars shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator. The bus bar shall have copper extension links for connecting with out going MCCB. The Out Going MCCB of rating greater than 125 amps shall have copper extension link & copper bus bar for connecting the cables. The cubicle shall have a bottom channel & free standing frame made of angle iron of size not less than 50 mm X 50mm X 6mm & detachable predrilled gland plateof thickness not less than 3 mm thick powder coated should be used at the bottom for entry of armoured cable of adequate size with glands.The above panel shall be front & Back openable lockable /openable by key from both sides.
Note: The panel shall be Dust, vermin proof and powder coated of approved thickness complete including CTs, control wiring by 1.5Sqmm Wire and consisting the following, including taking down of old unsv panel after disconnecting Existing cables, & Reconnecting the cables to new panels, replacing of cable glands, lungs and including PCC foundation, excevation, foundation bolts. The Panel shall comprise of following switchgears & acessories (a) S&F MCCB FP 400 Amp 35 KA -01 Nos (For Main incoming) (b) S&F MCCB TP 100 Amps 25 KA -04 Nos (d) S&F MCCB TP 63 Amps, 25 KA -02 Nos (e) S&F Indicating Lamp RYB (LED) Type-01 Set Note : Layout diagram of panel shall be submitted by the Contractor for the approval of GE.
Supply install, test and commissioning of out door type LT Panel (CPRA Approved) Powder coated, free standing type compartmentalized in construction center openable double door type with canopy factory fabricated from makes as specified and made out of 3 mm thick CRCA sheet & suitable size as apporved by GE to accomodate all accessories / fittings, MCCB, MCB, Contactors and TPN Copper bus bars having rating cap of 400 A. The TPN bus bars shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator. The bus bar shall have copper extension links for connecting with out going MCCB. The Out Going MCCB of rating greater than 125 amps shall have copper extension link & copper bus bar for connecting the cables. The cubicle shall have a bottom channel & free standing frame made of angle iron of size not less than 50 mm X 50mm X 6mm & detachable predrilled gland plateof thickness not less than 3 mm thick powder coated should be used at the bottom for entry of armoured cable of adequate size with glands.The above panel shall be front & Back openable lockable /openable by key from both sides.
Note: The panel shall be Dust, vermin proof and powder coated of approved thickness complete including CTs, control wiring by 1.5Sqmm Wire and consisting the following, including taking down of old unsv panel after disconnecting Existing cables, & Reconnecting the cables to new panels, replacing of cable glands, lungs and including PCC foundation, excevation, foundation bolts. The Panel shall comprise of following switchgears & acessories (a) S&F MCCB FP 200 Amp 25 KA -01 Nos (For Main incoming) (b) S&F MCCB TP 100 Amps 16 KA -04 Nos (d) S&F MCCB TP 63 Amps, 16 KA -03 Nos (e) S&F Indicating Lamp RYB (LED) Type-01 Set Note : Layout diagram of panel shall be submitted by the Contractor for the approval of GE.
Supply install, test and commissioning of out door type LT Panel (CPRI Approved) Powder coated, free standing type compartmentalized in construction center openable double door type with canopy factory fabricated from makes as specified and made out of 3 mm thick CRCA sheet & suitable size as apporved by GE to accomodate all accessories / fittings, MCCB, MCB, Contactors and TPN Copper bus bars having rating cap of 800 A. The TPN bus bars shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator. The bus bar shall have copper extension links for connecting with out going MCCB. The Out Going MCCB of rating greater than 125 amps shall have copper extension link & copper bus bar for connecting the cables. The cubicle shall have a bottom channel & free standing frame made of angle iron of size not less than 50 mm X 50mm X 6mm & detachable predrilled gland plateof thickness not less than 3 mm thick powder coated should be used at the bottom for entry of armoured cable of adequate size with glands.The above panel shall be front & Back openable lockable /openable by key from both sides.
Note: The panel shall be Dust, vermin proof and powder coated of approved thickness complete including CTs, control wiring by 1.5Sqmm Wire and consisting the following, including taking down of old unsv panel after disconnecting Existing cables, & Reconnecting the cables to new panels, replacing of cable glands, lungs and including PCC foundation, excevation, foundation bolts. The Panel shall comprise of following switchgears & acessories (a) MCCB FP 500 Amp 50 KA -01 Nos (For Main incoming) (b) MCCB TP 400 Amps 35 KA -01 Nos (c) MCCB TP 100 Amps, 16 KA -03 Nos (d) MCCB TP 63 Amps, 16 KA -02 Nos (e) Indicating Lamp RYB (LED) Type-01 Set Note : Layout diagram of panel shall be submitted by the Contractor for the approval of GE.
Material & labour for earthing complete with copper plate electrode (98 percent conductivity when annealed)of size 60 cm x 60cm x 3.15 mm thick burried directly in ground vertically to a depth not less than 2.25 mtr deep below ground level with top edge of earth plate at a depth not less than 1.5 mtr below ground level connected to and including copper strip(98 percent conductivity when annealed) 20x3 mm upto 7.5 mtr long by means of copper/brass bolt, nut, check nuts and washers besides brazing at all joints with GI protection pipe of 40mm bore medium grade up to 7.5 metre and connected to earthing test point all as shown in electrical plate No.3 of SSR part-I and as specified or indicated and testing on completion including excavation & eartwork in any type of soil, PCC (1:3:6) type C-1 chamber, precast slab 50mm thick in cement concrete (1:2:4) type B1 (reinforced with welded steel wire fabric (XPM) of weight not less than 4 Kg/Sqm), with frame, funnel with 20mm bore GI pipe medium grade watering pipe, wire mesh and lugs test point etc including taking out old unsv copper plate with connected items NOTE : (i) Item includes the cost of 7.5 metre length GI pipe for protection of earth lead and earth lead . (ii) On testing, if the earth resistance less than specified is not obtained, earthing will be regenerated at no extra cost till the desired earth resistance is obtained.
M&L for earthing complete with GI earth plate electrode 60cmx60cmx6.3mm thick buried directly in ground vertically at a depth not less than 2.25m below normal ground level with top level of earth plate at depth not less than 1.5m below normal ground level surrounded form all sides by 15cm thick and packed layer of charcoal dust and common salt filling in alternate layers and electrode connection by using GI strip 25mmx4mm by means of bolts, nuts, check nuts and washers of galvanized iron and protected by GI pipe light grade 50mm bore connected to main switch board or main control board and GI pipe light grade 20mm bore for watering and including funnel, wire mesh, 80mm thick pre-cast RCC 1:2:4, type B-1 cover reinforced with hard drawn steel wire fabric weighing not less than 4 Kg/sqm in lieu of CI cover, PCC 1:3:6 type C2 pit/chamber including all necessary excavation; and earth work, disposal of surplus soil to a distance not exceeding 50m all as specified and as shown in Electrical Plate No 3 of MES Schedule Part-I.
S&F earth continuity conductor tied to walls or burried in ground or drawn in pipe of size 25x4 mm galvanised iron strip complete all as specified and directed
S&F copper earth continuity conductor or main earthing lead of size 20x3 mm fixed to wall on batten or recess or chases or burried in ground or drawn in conduit /pipe or any other indicated suitation for earting etc as required complete all as specified and as directed.
Excavating in post holes (or similar holes) each n exc 0.5 cu.m, getting out, returning filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25cm, watering, and removing surplus soil to a distance n exc 50m and making good surface of hard / dense soil.
S & F Rolled mild steel in Compound girders and stanchions, lattice girders, posts, staging for water tanks and the like including caps, bases, splices etc. builtup from two or more beam or channel sections or angles with plates, including all lattice bars, stiffeners, gusset plates,etc. conforming to FE-410 - W(grade E-250) quality 'A' all as directed and specified.
S & F Plates (Plain or Corrugated) channels,square cut or notched (ordinary or counter sunk) forming holes with out any attachment conforming to FE-410 - W(grade E-250) quality 'A' all as directed and specified.
S & F rolled sections as in main and cross beams, hip and jack rafters, purlins where connected to common rafters and running rails and guides for sliding doors, fixed with angle cleats or other connecting plates conforming to FE-410 - W(grade E-250) quality 'A' all as directed and specified.
S&F 0.63 mm thick Galvanised corrugated mild steel sheeting with two corrugations side lap,fixed with coach screws and washers in roofs walls etc. with grade of zinc coating 275.
S&F 0.80 mm thick plain galvanised mild steel sheeting as in ridges hips, valley gutters drip and straight flashings (length and girth as fixed) with L or J hooks or coach screws with grade of zinc coating 275 complete all as specified and as directed.
M&L Hand rails, half round or other steel section or core for wooden hand-rail straight portion, drilled and counter sunk for balusters running bars, for doors,balusters,nosing to steps including embeding in concrete and screwing etc. wind ties for roof ,Brackets for Valley gutters ,including securing bolts; posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe 410-0 or FE 310-0
M & L for preparation of new steel surfaces over 10 cm width or girth and applying two coats of synthetic enamel paint over a coat of red oxide, zinc chrome primer all as directed and specified.
M&L applying two coats of Camouflage pattern synthetic enamel painting to new surfaces steel/ CGI sheet surface exc. 10 cm width/girth over a coat of mordant solution including preparation of surfaces by removal of galvanisation if reqd, washing and cleaning,including filling with filler where reqd all as specified and directed
Surface excavation n.exc (not exceeding) 30 cm deep and averaging 15cm deep and getting out in soft/ loose soil
M&L for Hardcore with boken stone of gauge n exc 63 mm, deposited, spread and levelled and layer n exc 15 cm thick, water and rolled /rammed to a true surface
M&L for 100 mm thick using PCC (1:4:8) type D-2 (using 40 mm graded stone agg) sub base complete all as specified and directed
M&L for 75mm thick PCC (1:3:6) type C-2 (using 20mm graded stone agg) sub base complete all as specified and directed
M&L for 40 mm thick PCC (1:2:4), type B0 (using 12.5mm graded stone aggregate) as in floor finished even and smooth including spike rolling using extra cement complete all as directed by Engr-in-charge.
Supply only for Metallic floor hardener complete all as specified and directed
Supply and fixing 38 mm wide glass dividing strips of 3mm thick in concrete floor topping all as specified and directed by Engr-in- charge
Excavation in trenches n.exc 1.50m wide and n.exc 1.50m in depth and getting out in Hard/dense soil;
M&l for PCC (1:4:8) type D-2 using 40mm graded crushed aggregate as mass concrete and filling of foundation
M&L pre-cast cement concrete (1:3:6) type C-1 as in block masonry (20mm graded crushed stone aggregate) with solid blocks,exc.10cm in width and setting in cement mortar 1:6 complete all as specified and directed
M & L Cement concrete (1:2:4) type B2 (using 40 mm graded stone aggregate) in foundations, filling and mass concrete
M&L for 10mm thick rendering on fair faces of brick works finished even and fair without using extra cement in cement mortar 1: 4 complete all as specified and as directed
Returning,filling in ,including spreading,levelling ,watering and well ramming in layers not exe 25cm in hard/dense soil.
Removing excavated material n, exe 50m and depositing where directedat a level n, exc 1.5 m above the starting point complete all as spfd
GRACE CONSTRUCTIONS
somnath engineering corporation
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .