SPECIAL REPAIR/REPLACEMENT OF TRANSFORMER AGAINST BER FOR MRS UNDER GE PANAGARH
2021_MES_461107_1
8706/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
PANAGARH
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
Yes
GE PANAGARH
₹98,500
Yes
6 Nov 2021
19 Jul 2021
1 Oct 2021
19 Jul 2021
29 Sept 2021
10 Aug 2021
Amount
Supply and install, testing and commissioning of step down outdoor type copper would Power transformer of capacity 3150 KVA complete (Plateform mounted) with standard, fitting HT 33000 V, 3 Phase, LT 11000 volts, 3 phase (33/11 KV Delta/Star, Vector Group DYn11) with off load change over switch on HT side to vary secondary voltage with range +7.5% to -7.5% with steps @ 2.5% all as per IS 2026 ,complete all as specified and as directed by Engrs-in-Charge. (i) No load Voltage Ratio (Normal Tap) - 33000/11000 V (ii) Number of phases : Three (iii) Frequency : 50 (iv) Type of Cooling : ONAN (v) Winding connections : The primary winding (HV) shall be connected in delta and secondary winding ( LV) shall be connected in star. (vi) Vector Group : Windings shall be connected as per Vector symbol : DYn11 (vii) Neutral Earthing : The neutral point of Secondary (LV) winding shall be brought out to a separate insulated terminal and shall be solidly earthed. (viii) Off Load Tap Changer of the transformer : Voltage tapping range on H.V. side will be (+7.5%) to (-7.5%) insteps of 2.5%. The tap changing switch shall be located in a convenient position so that it can be operated from ground level. The switch handle shall be provided with a locking arrangement along with tap position, enabling the switch to be locked in position. The tap position marking should increase in clockwise direction and there should be a back stopper in between tap position 1(+7.5%) & 7(-7.5%). (ix) The percentage impedance at 75 °C & 50 Hz refer to the (normal) principal Tapping shall be 6.25. (x) Losses : Standard losses will be as follows : (a) No load loss at 33/11 KV voltage ratio and 50 Hz frequency - 3.5 KW (Max) (b) Full load loss at 33/11 KV voltage ratio and 75 °C - 28 KW (Max)
Item No 1 Contd…. (xi) Terminals : (a) H.V.Bushing (33 KV Side) - 36KV Class Porcelain bushing with plain sheds for heavily polluted atmosphere (b) L.V.Bushing (11KV Side) - 12 KV Class Porcelain bushing with plain sheds for heavily polluted atmosphere. (c) Neutral Bushing - Neutral of L.V. winding shall be brought out through porcelain bushing similar to L.V. Bushing for connection with earth terminal in line with LV bushing. (xii) The following fittings and accessories shall be supplied with each Transformer : 1. Outdoor type bushing – HV - 3 Nos. and LV - 4 Nos. 2. Conservator with atmoseal and supporting bracket or structure as the case may be. 3. Isolating valve for conservator in between conservator and Buchholtz Relay and in between Buchholtz relay and main tank.. 4. Conservator valves for driven out air between air cell & wall of conservator & connection to breather. 5. Conservator drain valve. 6. Dial type oil level indicator complete with alarm contact. 7. Silica gel breather with oil seal and connecting pipe. The breather shall be accessible for inspection from ground. 8. Spring loaded setting type pressure relief Valve having suitable opening Port. Hole & provision of visual indication for opening of the valve & Alarm/Trip contact arrangement. 9. Access/inspection holes with bolted cover for access to inner ends of bushing. 10. Cover lifting eyes. 11. Lifting eyes for core frame with windings. 12. Tap changing arrangement with hand wheel for Off-Load tap-switch 13. Air release plug on top of cover or explosion vent will be provided. 14. Upper filter valve and bottom filter valve. 15. Drain valve.
Item No 1 Contd…. 16. Top and bottom oil sampling devices. Provision for oil sample collection during process of filtration should be made. 17. Lifting lugs. 18. Jacking pads with handling holes at four corners. 19. Transport lugs. 20. Under carriage base channel. 21. Tank earthing terminals – 2 Nos. 22. Bachholtz relay double float type with one set of alarm contacts, one set of trip contacts and testing pet cock. The contacts should be wired with a PVC armoured cable. 23. Dial thermometer for winding temperature with alarm contacts and Trip contacts. 24. Dial thermometer for oil temperature with alarm contacts and Trip Contacts. 25. An additional pocket for inserting thermometer for oil temperature indication. 26. Weather proof control cabinet for marshalling terminal connections from protective and indicative devices. The cabinet shall be provided with incandescent filament lighting, plugs etc. 27. Neutral Bushing 28. Rating plate, as per I.S.S. 29. Diagram Plate . Make: Schneider/ Seimens /BHEL
M/S ANANDA ENTERPRISE
MBS TRADING CO.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .