| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.5 LAccepted-AOC H NO 90 VILLAGE REWLA KHANPUR PO NAJAFGARH NEW DELHI 110043 | NEW DELHI | WEST DELHI | DELHI | 110043 | L1 | Accepted-AOC Accepted due to lowest rate quoted | |
| 2 | L2₹27.0 L+₹1.7 L (6.61%)Rejected-Finance | L2 | Rejected-Finance Rejected due to highest rate quoted |
Tender Value
₹41 L
EMD Value
₹82,000
Closing Date
21 Oct 2024, 6:00 pmClosed
GE (AF) GURGAON
GE (AF) GURGAON
REPAIR/REPLACEMENT OF SEWAGE LINES MANHOLES SEPTIC TANK BRICK DRAIN AND CERTAIN MISC B/R WORKS AT AF STN ARJANGARH AND REPAIR/MAINT OF EXTERNAL WATER SUPPLY LINES GATE VALVES PERIODICAL MAINT AND SERVICING OF RO PLANT ACS AND MAINT OF DG SET AT AF
2024_MES_676162_1
GE/GUR-/NIT-35/2024-25
Open Tender
Civil Works
Item Rate
240 days
GE (AF) GURGAON
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (AF) GURGAON
₹82,000
10 Dec 2024
23 Sept 2024
23 Oct 2024
23 Sept 2024
21 Oct 2024
7 Oct 2024
Amount
M&L for Carrying out the 'B' Check from authorised rep of service engineer from the manufaturer of the DG Set of Cummins/Kirloskar/Sudhir 320 KVA capacity replacing the unserviceable spares (including the cost of repairs) for Engine as described herein after under para (a) to (f) and as per manufacturers instructions complete all as specified and as directed. (a) S&F lubricating oil filter including taking down old filter. (b) S&F bypass filter including taking down old filter. (c) S&F Air filter including taking down old filter. (d) Checking of Mechanical Governor (e) Checking & topping up of coolant SK 802 OIC make Valvoline SERVO Hindustan as required level. (f) Any other checks as per manufacturesrs instructions. Note :- Coolants/oil will be measured and paid in relevent items.
All as per item No. 01 above but 125 KVA capacity DG Set.
All as per item No. 01 above but 30 KVA capacity DG Set.
All as per item No. 01 above but 20KVA capacity DG Set.
Supply only coolant SK 802 of Make: OIC Servo Hindustan
Supply only Engine oil 20W40 of the specified grade as per OEM complete all as specified and as directed.
S&F Fan belt suitable for 320 KVA DG Set of Make Sudhir including dismantling existing fan belt complete all as specified and as directed.
S&F Fan belt suitable for125 KVA DG Set of Make Sudhir including dismantling existing fan belt complete all as specified and as directed.
S&F Fan belt suitable for 20/30 KVA DG Set of Make Sudhir including dismantling existing fan belt complete all as specified and as directed.
Rewinding of armature of self starter dismantling the old coil cleaning thoroughly and wound with super enamelled copper conductor of existing size and gauge varnishing drying and fixing to self starter properly testing and commissioning for 320 KVA DG set complete all as specified and as directed.
All as per above item No. 10 but for 30 KVA DG Set complete all as specified and as directed.
M&L for preperation of old painted surface of installation by removing all dirt, dust, grease oil etc and painting complete of Diesel engine generator set including accessories with two coat of synthetic enamel paint of approved colour for 125 KVA capacity at MPH, CPH. complete all as specified and as directed.
All as per above item No. 12 but for 30 KVA DG Set complete all as specified and as directed.
Supply and fixing in replacement of AVR S/F VARIABLE SPEED DCDG suitable for DG set with input voltage range 415 Volt AC with neutral & Out put DC voltage 6 Amp 95 Volt DC suitable for DG set 320 KVA complete all as specified and as directed.
Supply & fixing Battery terminal, lug, bolts type suitable for heavy duty battery complete all as specified and as directed.
Supply & fixing Battery leads for copper conductor multiwired 16 Sqmm. 1.5 mtrs long complete all as specified and as directed.
Dismantling/Taking out of radiator assembly to work shop for cleaning with compressed air ,pointing out leaking places and soldering carefully and refix in position after making it serviceable of DG 320 KVA complete all as specified and as directed.
All as per item No. 17 above but 30 KVA capacity DG Set complete all as specified and as directed.
S&F Fuel hose pipe from fuel filter to fuel pump for DG set upto 31.25 KVA, complete all as specified and as directed.
S&F Fuel pipe from fuel tank to fuel filter (transparent) for DG set upto 320 KVA, complete all as specified and as directed.
All as per item No. 20 above but 125 KVA capacity DG Set complete all as specified and as directed.
All as per item No. 20 above but 30 KVA capacity DG Set complete all as specified and as directed.
S&F fuel feed pump suitable size as required on site for DG set of capacity upto 30 KVA, complete all as specified and as directed.
Supply and fixing of Fuse (HRC type) 63 amps, for DG sets of capacity up to 320 KVA complete all as specified and as directed.
Supply and fixing battery 12 volts 80 AH ,ISI mark, complete all as specified and as directed.
Taking down and dismantling HPSV/ LED type street light fitting for 45/ 70/150/250 watt capacity of any make/type from pole/GI pipe unserviceable items to be kept in safe custody and taken as credit complete all as specified and as directed.
Supply and fixing LED Steet light fitting 70 Watt Pressure die cast aluminium housing with pre-wired grey Tray with LED and driver, heat resistant flat glass suitably gasketed for IP66 protection comlete with all accessories prewired fixed on Pole/ wall bracket and connected complete all as specified and as directed.
S & F LED floodlight luminaire with secondary optics made in pressure die cast housing and heat sink in aluminium extrusion with IP66, Turbo LED series ,120Watt & accessories and connecting up to looping box with PVC insulated multi stranded copper conductor cable 1.5 sqmm twin Core all as specified and as directed. Note for Items Ser No 28 & 29: (a) Driver and luminaries shall be of same make. (b) LM - 79 report of fixtures shall be produced by contractor. ( c) CRI of the luminaries should be more than 80. (d) THD of the luninaries shall be less than 20. (e) PF of the luminaries shall be more than 0.9 (f) System efficacy shall not be less than 90 lumen/ watt.
S & F LED floodlight luminaire with secondary optics made in pressure die cast housing and heat sink in aluminium extrusion with IP66, Turbo LED series ,80Watt & accessories and connecting up to looping box with PVC insulated multi stranded copper conductor cable 1.5 sqmm twin Core complete all as specified and as directed.
M&L for defect rectification LTcable laid in trenches by locating fault with the help of electronic fault locating machine comprising of surge generator pulse, ECHO fault locator with high frequency distance calculator etc. including and additional excavation in normal alluvial strata required for exposing the cable fault, removal of deteriorated portion of cable treating of cable and keeping the same ready for jointing work for cable of any size complete all as specified and as directed. The fault locating equipments will be brought to site within the hours of instruction from Engr-in-Charge.
Supply and jointing straight through cold shrink joint suitable for LT 415 Volt XLPE cable of size 70 to 120 Sq mm 3.5 core complete all as specified and as directed.
Supply and jointing straight through joint cold shrink suitable for LT 415 Volt XLPE cable of size 25 to 50 Sq mm 3.5/4 core complete all as specified and as directed.
S & F in replacement of Aluminium Cable lugs/Thimbles upto size 16 to 25 sqmm complete all as specified and as directed.
S & F in replacement of Aluminium Cable lugs/Thimbles of size 35 to 50 sqmm complete all as specified and as directed.
S & F in replacement of Aluminium Cable lugs/Thimbles of size 70 to 120 sqmm complete all as specified and as directed.
Supply and fix in replacement of automatic timer switch pole mounted enclosure consisting of ON/OFF switch based on LUX level power contactor 40 Amps, 10KA 'C' series 4 pole, MCB 40 Amps, TP - 03 Nos, enclosure made of rust proof, shock proof, conforming to IP -54 complete all as specified and as directed. Note: (i) Inlet/outlet connecting cable PVC insulated aluminium stranded conductor 6 Sqmm, 4 single core for incoming & outgoing up to 8 Mtr deemed to be included in the unit rate. (ii) Provn of glands and lugs shall be deemed to be included in the quoted rate.
Supply and fix in replacement Electronic Water level indicator having 10 Levels (form 1 to 10), sensor system should be with LED display with 6 Volt Battery (Rechargeable type), consisting of ON/OFF switch,suitable for 230 Volt, ISI Marked, including necessary wiring, sensor or necessary items as dircted by company manufacturer for fully functional of level indicator complete all as specified and as directed.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.50m deep for laying of water pipe lines/taking out pipe lines and getting out in soft/lose soil including forming bottom surface to required level and slope complete all as specified and as directed.
Returing ,fiiling including spreading ,leveling ,watering and well ramming in layers not exe. 25 cm soil complete all as specified and as directed.
Removal of surplus soil to a distance not exceeding 50 m and doepositing where directed at a level not exceeding 1.5 m above the strarting point complete all as specified and as directed.
Taking out unserviceable rusted steel water tubing and connection including cleaning for refixing or removal from site complete all as specified and as directed of the following sizes:-
(a) 20 mm bore .
(b ) 25 mm bore.
(c) 40 mm bore.
(d) 50 mm bore.
(e) 80 mm bore.
Supply and laying in trenches/wall/floors GI tubing medium grade including all required fittings as required at site complete all as specified and as directed of following sizes:
(a) 20 mm bore .
(b ) 25 mm bore.
(c) 40 mm bore.
(d) 50 mm bore.
(e) 80 mm bore.
Taking down old unserviceable CPVC/ Flexible PVC Pipe line 25 mm dia any type form Solar water heater system complete all as specified and as directed.
Supplying and laying of CPVC pipes SDR 11 & Plain CPVC SDR 11 fittings on walls/ceiling or laying in floors complete all as specified and as directed. Note: Cost of Fittings such as Elbow, Bend, Tee, socket, Reducer, Clamp, nut, bolt and washers etc to be included in quoted rate.
Supplying and Fixing 25 mm dia CPVC Ball valve suitable for SDR 11 & Plain CPVC SDR Pipe line complete all as specified and as directed.
Taking out existing cast iron water mains (including all fittings) with spigot and socket ends and lead joints including burning out joints and recovering lead and Supply, laying ,connection and testing CI pipes with spigot and socket ends centrifugally cast,class 'LA' in any length, laid in trenches complete all as specified and as directed of sizes 150 mm bore.
M&L CI specials such as bends (any type,radius, tapers) and any type (straight,bend, increasing, decreasing,or double socket ect). Tee pieces single branch 'Y' junction double branch,cross (all sockets or socket and spigot), collars caps and plugs ect for upto 250mm bore as in repair including complete all as specified and as directed.
Taking down existing non- return valve and S&F 80 mm more CI non return valve, flanged type ISI marked with by pass arrangement complete all as specified and as directed.
Taking down existing sluice valve and supply and fix in position sluice valve (ISI marked) flanged and drill both ends cast iron body, heavy duty brass spindle type PN 1.6 with and including jointing rubber gasket,nut,bolts including taking out existing CI sluice valve complete all as specified and as directed of following sizes:-
(a) 150 mm bore.
(b) 100 mm bore.
(c) 80 mm bore.
Drilling and tapping cast iron water mains for branch connection of the internal dia 20mm including clamp piece and nuts and bolts complete all as specified and as directed.
M&L for run lead joints for following sizes of CI spun pipes /fittings complete all as specified and as directed of the following bore pipe:-
Taking down existing Foot valve and S&F Cast Iron Body, ISI Marked Foot valve suitable for 80mm dia pipe line including all fittings complete all as specified and as directed.
Taking out old unserviceable Gate vale, S & F of 20 mm bore gunmetal globe or gate valve, with iron wheel head, screwed both ends for iron pipe confirming to latest relevant IS with and including necessary excavation and earthwork as required at site complete all as specified and as directed.
Taking out old unserviceable Gate vale, S & F of 25 mm bore gunmetal globe or gate valve, with iron wheel head, screwed both ends for iron pipe confirming to latest relevant IS with and including necessary excavation and earthwork as required at site complete all as specified and as directed.
Supply and fixing pig lead complete all as specified and as directed.
Supply and fixing lead wool complete all as specified and as directed.
Taking out burnout existing gland packing, S&F gland packing (Superior quality) and Greasing in 10/7.5 HP pump set complete all as specified and as directed.
Material and labour for bacteriological and chemical analysis of water sample of Govt approved lab/ISO certified lab, the water sample to be carried every month or as directed by Engr -in- charge in sterilized bottle/watercan which will be the responsibility of the contractor. Cost of testing charges including conveyance and water test certificate to be submitted in Duplicate to Engineer-in-charge. Note: sample to be collected from sump and pump house as directed by Engr -in- charge.
M&L for Lifting of submersible pump set any description from borewell including column pipe and submersible cable and lowering of pump in bore well after development of borewell including refixing of coloumn pipes complete all as specified and as directed. Note: cost of disconnecting pipe from header / cables from panel shall be deemed to be included in the quoted rate.
M&L for repairs & Servicing of defective submersible pump of capacity up to10 HP by dismantling the pump & removing unserviceable parts , assemble the pump properly after replacements of unserviceable parts complete all as specified and as directed . Note:- (a) The rates are inclusive of transporting the pump from bore well site to repair work shop & back to site. (b) The rate are inclusive of turning / finishing work for fixing of parts properly. (c) The replacement of unserviceable parts will be measured and paid separately under respective item of this schedule.
M&L for rewinding of Submersible motor by taking out burnt copper winding, cleaning the casing & slots with wire brush & washing with pressure water & shall be dried , rewinding the motor using required gauge of super enameled copper winding wire. Making the winding leak proof & taking out the electric connection with suitable size of submersible cable up to 03 Meter, Capacity of motor 10 HP complete all as specified and as directed .
Supply and fix parts of submersible pump set of capacity 10 HP complete all as specified and as directed:-
i) Bearing bush Gun Metal.
ii) Bearing bush SS with rubber.
iii) Oil seal.
iv) Thrust plate/thrust bearing set.
v) Sand Guard.
vi) CI Thrust Casing.
vii) CI stage casing.
viii). GM Bush.
ix) Mild steel key for impeller.
x) SS Studs with nuts.
xi) CI Intermediate section.
xii) SS coupling bush common for pump & motor with key.
xiii) High Tensile steel shaft.
M& L for servicing of RO plant( Acqua gurad type) of capacity 15 to 40 ltrs per hour incl replacement of following items :-
i) Carbon filter .
ii) Sediment filter .
iii) Membrane.
iv) R O Pump.
(v) Complete set of Pipe (fresh Water pipe line and Waste water Pipe).
M& L for taking out pump motor set vertical cap 10 HP,dismantling pump and motor separately , rewinding of electric motor with super enamelled copper wire of existing gauge after cleaning the slots properly and assembling and refixing in position and testing complete all as specified and as directed.
Cleaning of RCC underground sump of Size 10X10X10CFT complete by removing all scales, dirts, mud, chemical deposit etc from inner and outer chamber of tank as well as from the mouth of all circulating pipes connected with sump including scrapping out and throughly cleaning of internal surface/floor by using bleaching powder, soda ash etc complete all as specified and as directed.
Cleaning of RCC under ground sump of 50000 Gallon capacity complete by removing all scales, dirts, mud, chemical deposit etc from inside the tank as well as from the mouth of all circulating pipes connected with RCC tank including scrapping out and throughly cleaning of internal surface/floor by using bleaching powder, soda ash etc complete all as specified and as directed. Note Proper care should be taken during cleaning so that no scales/dirts/deposits enters the supply/delivery line .
Cleaning of RCC over head reservoir of 50000 Gallon capacity complete by removing all scales, dirts, mud, chemical deposit etc from inner& outer chamber of tank as well as from the mouth of all circulating pipes connected with RCC tank including scrapping out and throughly cleaning of internal surface/floor by using bleaching powder, soda ash etc complete all as specified and as directed. Note Proper care should be taken during cleaning so that no scales/dirts/deposits enters the supply/delivery line
Attending Complaints by deploying sufficeient labour for rectification of leakage of UG water pipe lines of size 80 to 100 mm Bore of any description such as CI/GI pipe line at any location including necessary excavation, earth work, dewatering, cutting existing pipe lines including repairs with suitable flanges, Joints or any other material complete all as specified and as directed.
.All as per Items Ser No 68 but for upto 50mm dia pipe line complete all as specified and as directed. Note for Item Ser No 68 & 69:-(i) Complaint will be notified to contractor on mobile phone at any time between 0800 hrs to 2200 hrs and will be rectified within 12 hours after notification, failing which double of quoted rate per day per complaint will be recovered. (ii) Completion report of the complaint shall be given in writing and recorded in the register. (iii) Rates quoted shall be deemed to include the cost of T&P required. Pipes and Jointing material shall be measured and paid under relevant items of schedule.
M&L for Servicing, Oiling, Greasing and Cleaning of split type AC with high pressure pump of any capacity, checking of defects/ leaking and adjusting setting to work and testing and writing of MES No . complete all as specified and as directed.
M & L for cutting of suction line and discharge line tubing of AC, front scaled unit de-scaling, flushing out condenser and cooling coil thoroughly and reconnecting with the seal unit and charging of gas with required qty of refrigerant for 1.5 ton Split type AC complete all as specified and as directed.
All as per item No 71 described here-in-before but 2 ton capacity split type AC complete all as specified and as directed.
Repair to voltage stabilizer of capacity 5 KVA including replacement of burnt out transformer and S&F new transformer of complete all as specified and as directed.
M&L for replacement running capacitor of existing makes and capacity duly ISI marked for and split type AC 1.5/2 Ton capacity complete all as specified and as directed.
M&L for replacement of starting relay of existing makes and capacity duly ISI marked for split type AC 1.5/2 Ton capacity complete all as specified and as directed.
M&L for replacement starting capacitor of existing make and capacity duly ISI marked for window type A/C 1.5 ton and split type AC 1.5/2 ton capacity complete all as specified and as directed.
S&F in replacement of Electronic control (PCB) of existing makes and capacity duly ISI marked for split type AC 1.5/2 Ton capacity complete all as specified and as directed.
M&L for Repair to compressor off size of existing makes and capacity for split type AC 1.5/2 Ton capacity complete all as specified and as directed.
S&F Filter pad of existing makes and capacity duly ISI marked for split type AC 1.5/2 Ton capacity complete all as specified and as directed.
S&F in replacement of Thermostat switch of existing makes and capacity duly ISI marked for split type AC 1.5/2 Ton capacity complete all as specified and as directed.
M&L for Rewinding of blower motor of capacity 1.5/2.0 Ton complete all as specified and as directed.
S&F in replacement of new rotary type AC compressor of split AC with reconditioned & repaired compressor from authorized dealers of company in exchange including gas charging of capacity 1.5Ton capacity complete all as specified and as directed.
S&F in replacement of new reciprocating type, AC compressor of split AC with reconditioned & repaired compressor from authorized dealers of company in exchange including gas charging of capacity 2.0 Ton capacity complete all as specified and as directed.
S&F in replacement of Evaporator coil complete all as specified and as directed.
S&F in replacement of Suction/Discharge valve complete all as specified and as directed.
S&F in replacement of Copper tube for 1.5 /2.0 Ton split AC 1/4 complete all as specified and as directed.
S&F in replacement of Copper tube for 1.5 /2.00 Ton split AC 1/2 complete all as specified and as directed.
M& L for detection/ rectification of leakage of gas in the system and gas charging in the system with appropriate qty of gas incl uding testing for smooth functioning of water of capacity 60/80/120 ltrs complete all as specified and as direted . Note :-(i) Unserviceable condensing coil if reqd shall be measured and paid for separately .(ii) Cost of dismantling of unserviceable compressor if reqd deemed to be included in unit rate . (iii) compressor shall be measured and paid separately under respective items of sch 'A".(iv) Refilling & topping up refrigent (type & quantity as required on site is measured & paid separetely)
S&F compressor reciprocating type (hermitecally) sealed for capacity 40/80 Ltrs water cooler complete all as specified and as directed.
S&F in repair of thermostat switch suitble for existing water cooler anymake and capacity complete all as specified and as directed.
M&L in replacement of Starting relay and overload relay suitable for existing size & make water cooler complete all as specified and as directed.
M&L in replacement of Starting capacitor suitable for 40/80 ltrs water cooler of any make complete all as specified and as directed.
M&L in replacement of running capacitor suitable for 40/80 ltrs water cooler of any make complete all as specified and as directed.
M&L for dismantling of old defective condenser , fan motor of 40/80 ltrs water cooler of any make and refixing and testing the same after rewinding with super enamelled copper wire complete all as specified and as directed.
M&L servcing of Deep freezer Capacity upto 320 ltrs by cleaning greasing including painting with one coat of super synthetic enameled paint including prepartion of surfaces complete all as specified and as directed.
M&L of replacement of Cooling coil of deep freezer 320 Ltrs Capacity any make including Gas Charging and testing of leakage complete all as specified and as directed.
Cleaning /removal of blockage/De-silting of sewer line 300 mm dia with mechanical device like super sucker machine, high pressure jetting machine/gantry machine or any other mechanical device. incl taking out debris installation of adequate number of over pumping system leak proof stanching arrangement of U/S & D/S side of work length, temporary rising main etc for smooth flow of sewage system to avoid flood in the area complete all specified and as directed.
Cleaning /removal of blockage/De-silting of sewer line upto 200 mm dia with mechanical device like super sucker machine, high pressure jetting machine/gantry machine or any other mechanical device. incl taking out debris installation of adequate number of over pumping system leak proof stanching arrangement of U/S & D/S side of work length, temporary rising main etc for smooth flow of sewage system to avoid flood in the area complete all specified and as directed.
Dewatering/desilting of existing manholes of internal size n exc 0.60mx0.60m depth n exc 1.50m and removing of all solid/semi-solid matter of silt residue both organic or inorganic in nature (manual or mechanical system at contractor's discretion)and incl removing RCC manhole Covers and refixing the same after cleaning the same position, complete all specified and as directed.
Dewatering/desilting of existing manholes of internal size n exc 1.00mx1.00m depth exc 1.50m but n exc 3.00m and removing of all solid/semi-solid matter of silt residue both organic or inorganic in nature (manual or mechanical system at contractor's discretion)and incl removing RCC manhole Covers and refixing the same after cleaning the same position, complete all specified and as directed.
Taking out thick/solid sludge (sedimented sand sludge/grit ,ash rages , fibres and springe material etc) by mechanical process from septic tanks including inlet and outlet chambers and soakage well, removing and depositing the sludge outside MOD land in a pit and covering the sludge in the pit with earth and finally spraying unslaked lime, dry, around the septic tank and covering the pit with earth complete all specified and as directed. Notes;- (i)Cost of earth work in the pit is deemed to be included in the unit rate quoted by the tenderer).
De-watering of septic tanks and soakage wells, with mechanical pumping set and draining out the same disposal of sludge outside MOD land in pit to be dug out side and covering top with a layer of 25 mm thick earth filling compacting and levelling all as specified and directed by Engineer-in-Charge. , complete, all as directed and to the entire satisfaction of Engineer-in-Charge. (i) Digging of pit shall be deemed to be included in unit rate.
Demolition and breaking up of drain pipes (salt glazed ware or AC or reinforced cement concrete) set in cement mortar of 150mm dia complete all specified and as directed.
Demolition and breaking up of drain pipes (salt glazed ware or AC or reinforced cement concrete) set in cement mortar of 200mm dia complete all specified and as directed.
Material and Labour for providing concrete bed in PCC 1:3:6 type C-2 using 40mm graded crushed stone aggregate as in bed to drain pipes of 200mm bore including packing under and haunching against the sides of the pipes completely after they are laid and tested complete all specified and as directed. (Note: Width of concrete bed shall be outer diameter of drain pipe plus 30cm)
Material and Labour providing concrete bed in PCC 1:3:6 type C-2 using 40mm graded crushed stone aggregate as in bed to drain pipes of 150mm bore including packing under and haunching against the sides of the pipes completely after they are laid and tested complete all as specified and as directed. (Note: Width of concrete bed shall be outer diameter of drain pipe plus 30cm)
M&L for reinforced concrete pipes , class NP-2 drain pipes laid in trenches and jointed as specified Internal diameter of pipe in 150mm complete all specified and as directed.
M&L for reinforced concrete pipes , class NP-2 drain pipes laid in trenches and jointed as specified Internal diameter of pipe in 200 mm complete all specified and as directed.
Material and Labour for cutting into existing manholes for connecting new drains, making good to pipe and plastering the disturbed portions in CM 1:3 to match with surround surfaces, cutting out existing benching and forming branch channel (1/2 round or ¾ round section) in cement concrete 1:2:4 type B-1 finished smooth and reforming benching as required for 150mm bore pipe complete all as specified and as directed.
S&F SFRC manhole cover 75 mm thick factory made with plain surface as per requirement including 75mm x 1.55 mm flat iron frame all around the cover all around the cover complete all specified and as directed.
Dewatering the PVC water tank of capacity upto 500ltrs cleaning and removing all scales and dirt silt etc from water tank, removing lid without disturbing pipe line system and float valve/refixing of float valve and making functional after cleaning and writing letter “date of clearance, Date, month and year“ with black base and yellow letter or white base or black letter painting including cleaning of existing letter complete all specified and as directed.
Dewatering the PVC water tank of capacity of 1000 ltrs cleaning and removing all scales and dirt silt etc from water tank, removing lid without disturbing pipe line system and float valve/refixing of float valve and making functional after cleaning and writing letter “date of clearance, Date, month and year“ with black base and yellow letter or white base or black letter painting including cleaning of existing letter complete all specified and as directed.
Demolition of brick work built in cement mortar including all quoins, arches, pillar etc, but excluding ashlar facings complete all specified and as directed.
Material and labour for brick work with sub class ‘B’ bricks straight or curved on plan exceeding 6m mean radius with old size bricks built in cement mortar 1:4 complete all specified and as directed.
M & L for Brick work with sub class ‘B’ bricks, straight or curved on plan to any radius as in half brick thick wall in CM (1:4) and pointed flush with the same mortar as the work proceeds complete all specified and as directed.
Taking down cement plaster on brick or stone walls etc including raking out joints hacking for key scrubbing down with water etc. complete all specified and as directed.
M&L for 15mm thick plastering on fair faces of bricks or concrete surfaces finished even and fair w/o using extra cement in cm1:4 complete all specified and as directed.
Supply only ISI Marked integral water proofing compound complete all specified and as directed.
M&L for Preparing of new plastered surface walls and applying two coats of cement based paint over a coat of primer complete all specified and as directed.
Material and labour for cement concrete 1:2:4 Type B-1 using 20 mm graded stone aggregate as in copings, weathering, slightly rounded or chamfered angles and throating, complete all specified and as directed.
M&L for plain cement concrete 1:4:8 type D-2 (using 40mm graded stone aggregate) as in foundation, filling & mass concrete, sub base complete all specified and as directed.
S&F PVC Covers for 500/1000 ltr overhead PVC cylindrical water tanks complete including locking device etc complete all specified and as directed.
Dismantling RCC or PVC water tanks of capacity exc 250 & n exc 500 litres complete all specified and as directed.
S & F 500 litres capacity Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR Part I complete all specified and as directed.
Dismantling RCC or PVC water tanks of capacity exc 500 & n exc 1000 litres complete all specified and as directed.
S & F 1000 litres capacity Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR Part I complete all specified and as directed.
S & F for Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed, Bore dia of pipe in 20 mm, etc complete all specified and as directed.
S & F in repair 20 mm dia Ball brass valves in repairs, high pressure, with polythene float and flynut complete, screwed for iron pipe or brass ferrule and fixed to tank complete all specified and as directed.
S & F in repair 15 mm dia Ball brass valves in repairs, high pressure, with polythene float and flynut complete, screwed for iron pipe or brass ferrule and fixed to tank complete all specified and as directed.
Taking up or down steel tubing & connections incl cleaning for refixing or removal from site 15mm bore pipe complete all specified and as directed.
Taking down 20 mm dia GI steel tubing and connection, including cleaning for refixing or removal, complete all specified and as directed.
Refixing of old steel tubing and connection in new or old position of 15mm bore complete all specified and as directed.
S&F GI tubes medium grade with all fitting and fixed complete to walls, ceilings or laid in floors 15mm bore complete all specified and as directed.
Refixing old GI tubing and connections, 20 mm dia, in old or new position. (Walls, ceiling, floors, etc.) complete all specified and as directed.
M & L tubes 20 mm bore dia, medium grade, galvanised, with all fitting and fixed complete to walls and ceilings or laid in floos, complete all specified and as directed.
Demolition of cement concrete (un-reinforced) of any description as in path, paving, bed of drains etc. n.exc. 15cm thick (Belowor above ground level) and removing the same complete, complete all specified and as directed.
M & L Cement concrete type C-2, 1: 3:6 (40 mm graded aggregate) in surface channels and drains complete all specified and as directed.
Dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing), removing serviceable tiles to store and rubbish off the premises, etc complete all specified and as directed.
M & L for Coloured Non - skid Ceramic tiles 7 to 8 mm thick (square/ rectangular) area of each tile exceeding 0.06 sqm but not exceeding 0.11 sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match over and including screed bed 15 mm thick in cement mortar 1:6 complete all specified and as directed.
Demolition of Stone slabs and tiles of any description or thickness in floors, aprons etc., laid dry or laid and pointed etc complete all specified and as directed.
M & L for Granite (of any type) tiles 20mm thick machine cut, over screed bed or bedding layer 15 mm thick in CM 1:6 ,bedded and jointed with grey cement slurry and pointed with white cement with admixture of pigment to match the shade of granite stone including grinding and polish etc complete all specified and as directed.
S&F in repairs WC squatting pan “Orissa Pattern” of size 580 x 440mm white with integral foot rest (excluding flushing cistern & flush pipe) including connection to trap and to flush pipes etc and cement concrete bedding complete all as specified in SSR and including S&F trap set complete all specified and as directed.
S&F in repair One piece Vitreous China wash down water closet pan with integrated cistern, seat cover soft closing and twin flush system of size 680 x 370 x 750 mm white colour including necessary fixing acessories , IN REPAIR, complete all specified and as directed.
S&F in repair Vitreous china wash down water closet pan, pedestal pattern (EWC) white, including seat cover , fixing bolts connection to trap & to flush pipe fixed in repairs complete all specified and as directed.
S&F in repairs PVC flushing cistern 10 ltr capacity valve less syphonic action type low level with and incl ball valve float & handle, waste pipe & brackets complete set complete all specified and as directed.
S&F in repair vitreous china pedestal pattern wash hand basin (flat back) white of size 550x400mm including one number chromium plated waste fittings, 32 mm dia, brass with long screwed shanks and fly nuts, flange end bedded in red lead cement and other end fixed, with & including 32 mm dia PVC waste pipe with connector, including cutting for and pinning in ends of brackets complete all specified and as directed.
Dismantling Asbestos cement sheets (corrugated ,semi corrugated etc) in roof coverings incl ridges etc complete all specified and as directed.
M&L for Pre-painted galvatume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws complete all specified and as directed.
Excavation in post holes (or similar holes) in soft/disintegrated rock each n. exc 0.5cum, getting out, returning filling in and ramming earth or brocken rubble mixed with earth arround in layers not exc 25cm watering and removing surplus soil to a distance n. exc 50m and making good surfaces etc complete all specified and as directed.
M&L for cement concrete type B-2, 1:2:4 (40mm graded stone aggregate) as in foundations, filling and mass concrete etc complete all specified and as directed.
Dismantling wrought iron or mild steel work of any description not otherwise provided for, etc complete all specified and as directed.
Dismantling posts or struts (wood, steel or RCC) any section including taking out embedded portion (posts embedded in concrete, brick work etc.) and making good the disturbed ground complete all specified and as directed.
M & L for Mild steel work as in fencing posts, sturts & vertical colmns using ERW or induction butt welded tubes coforming to IS 1161-1979 grade st-240 etc complete with gusset plates,base plates etc including a shop coat of red oxide primer complete all specified and as directed.
M & L for Mild steel work as in roof trusses including special shaped washers etc complete using ERW or induction butt welded tubes coforming to IS 1161-1979 grade st-240 etc including a shop coat of red oxide primer complete all specified and as directed.
M&L for Mild Steel round bar 10 dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips for Gd.I, Fe-432 (Part I) etc complete all specified and as directed.
S&F 11 to 15 mm dia of shank mild steel screw bolts (machine made) with hexagonal or square heads at one end and screwed the other end,or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut but length exc 5 cm and n exc 10 cm long etc complete all specified and as directed.
Dismantling of old chain link fencing of any description of weight n exc 4.0 kg/sqm from existing fencing fixed with steel or concrete posts complete all specified and as directed.
Fixing only chain link fencing including line wires, any mesh, size and type to any type of standards, rails, straining bolts, etc. including provission of binding wire etc complete all specified and as directed.
Supplying only Chain link MS galvanisd fencing, any size or type (weight not exc 4 kg/sqm) etc complete all specified and as directed.
M&L for preparation of steel and iron surfaces (new) of any description not otherwise described over 10cm width or girth and applying two coats of synthetic enamel paint over a coat of red oxide zinc chromate primer complete all specified and as directed.
M & L for 75 mm thick, Cement concrete type D-2, 1:4:8 (40mm graded aggregate), etc complete all specified and as directed.
M&L for Cement concrete (1:2:4) type B-0 using 12.5mm graded stone aggregate as in coping including necessary formwork complete all specified and as directed.
M&L for Chequered cement concrete tiles 30cm x 30cm x 25mm thick in floors / path set, jointed & pointed in neat cement slurry using grey cement and no pigment laid over and including 15mm thick screed bed in cement mortar (1:6) including necessary cutting as per site requirement complete all specified and as directed.
Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line , level and curvature,jointed withcement mortar 1:3 ( 1 cement : 3 coarse sand ) , including making joints with or without grooves ( thickness of joints except at sharp curve shall not to more than 5 mm) , including making drainage opening whereever required . complete all specified and as directed.
Providing and laying 60 mm thick factory made chamfered edge cement concrete paver block of M-35 grade with approved , design & pattern as in footpath , parks , lawns,drive ways or light traffic parking etc. of required strength , thickness & size/shape, made by table vibratory method using PU mould , laid in required colour & pattern over and including 50 mm thick compacted bed of fine sand , compacting and proper embedding/laying of interlocking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator,filling joints with sand andcutting of paver block as per required size and pattern,finishing and sweeping extra sand complete all specified and as directed.
Providing and laying 80 mm thick factory made chamfered edge cement concrete paver block of M-30 grade with approved , design & pattern as in footpath , parks , lawns,drive ways or light traffic parking etc. of required strength , thickness & size/shape, made by table vibratory method using PU mould , laid in required colour & pattern over and including 50 mm thick compacted bed of fine sand , compacting and proper embedding/laying of interlocking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator,filling joints with sand andcutting of paver block as per required size and pattern,finishing and sweeping extra sand complete all specified and as directed.
Galvanised 2 strand, steel barbed wire 2.24mm dia barbed with 2mm dia barbs at 75mm spacings and straining and fixing to any type of standard rails straining bolts, including securing or tying at crossings withand provision of galvanised mild steel wire, staples or steel pins etc IN REPLACEMENT complete all specified and as directed.
Ish Engineers and Contractors (BID ID -3138736)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .