EXECUTIVE ENGINEER ED BIJBEHARA
EXECUTIVE ENGINEER ED BIJBEHARA
Creation of 25KVA Sub-Station along with HTLT network for Fire and Emergency Station building Sallar.
2023_PDD_213574_1
EDB/e-tender/18 of 2023-24
Open Tender
Electrical Works
Turn-key
30 days
Aishmuqam
Please refer Tender documents.
5 documents required · 5 mandatory
₹200
EXECUTIVE ENGINEER ED BIJBEHARA
₹6,000
9 Jun 2023
26 May 2023
9 Jun 2023
26 May 2023
8 Jun 2023
26 May 2023
26 May 2023 - 3 Jun 2023
Amount
Creation 0f 25KVA sub-station along with HT/LT Network
Supply, Installation, Testing and commissioning of 25kVA,11/0.433KV, 3-phase Distribution Transformers (level-II) with Bimetallic Terminal connrction and with LV Cable box having detachable Aluminium Gland Plate. Transformer should be arranged for vertical takeoff.
Supply,erection, testing and commissioning of S.T Pole 9mtr Long SP-33 with base plate & cap for HT. Strictly as per REC standards
Supply, laying, strininging and commissiong of ACSR 30mmsq (Weasel) Conductor
Providing & fixing of GI Channel/Angle/Flat of sizes including clamps
Supplying and erection of GI V cross-arm with top Bracket including clamp(2 Nos)
Supplying and fixing of Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip as per REC standards.
Painting of poles with one coat of red oxide and two coats of Aluminium paint as per Standards. This also includes numbering of ploes with paint, submission of Pre and Post Execution photographs.
Supply,fixing, testing & commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type as per IS Standards
Supply,fixing, testing & commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A as per IS Standards
Supply,fixing, testing & commissioning of 11 kV Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type as per IS Standards
Supply,fixing, testing & commissioning of 11 KV Pin Insulators (polymer/porcelain) with Pins(5KN)
Cement bottoming 1:2:4 mix as per REC Standards 0.5cum/pole
Providing & fixing of Sundry items like aluminium lugs, Jumpers, binding Tape etc
Supply Installation Testing and commissioning of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Supply, laying of 35 mmsq Single Core XLPE, FRLS unaroumed Cable
Supplying and fixing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Providing, Fixing of nuts and bolts for fixing of x-arms and other accessories.
Providing and fixing of 3-Ø, 4-Wire Trivector Meter with CT
Providing and fixing of 63 Amps TPN Switch Disconnector Fuse Unit.
Providing and fixing of Danger Plates with clamps.
M/S ALI MOHD MISGAR
M/S NAZIR AHMAD MIR
M/S JAVAID AHMAD BEIGH
stage.html
html • 0.02 MB
finance_569870.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .