Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.0 LAccepted-AOC RZ 212F D BLOCK RAJ NAGAR PART II PALAM COLONY NEW DELHI 110077 | SOUTH WEST | DELHI | 110077 | L1 | Accepted-AOC AOC | |
| 2 | L2₹44.9 L+₹2.9 L (6.93%)Rejected-Finance HOUSE NO 142 GALI NO 07 PREM VIHAR NANGLI SAKRAWATI NAJAFGARH NEW DELHI 110043 | NEW DELHI | NAJAFGARH | DELHI | 110043 | L2 | Rejected-Finance Not being lowest tender | |
| 3 | L3₹46.1 L+₹4.1 L (9.87%)Rejected-Finance | L3 | Rejected-Finance Not being lowest tender | |
| 4 | L4₹46.9 L+₹4.9 L (11.7%)Rejected-Finance | L4 | Rejected-Finance Not being lowest tender | |
| 5 | L5₹49.9 L+₹7.9 L (18.8%)Rejected-Finance | L5 | Rejected-Finance Not being lowest tender |
Tender Value
₹43.7 L
EMD Value
₹87,500
Closing Date
4 Mar 2025, 6:00 pmClosed
HQ CWE (U) Delhi Cantt-110010
HQ CWE (U) Delhi Cantt-110010
AUGUMENTATION 33/11 KV HT CABLES, LT CABLES, LT PANEL AND STREET LIGHT POLES NEAR APS COLONY FOR CONSTRUCTION OF DIRECT ROUTE FROM 23 ACRES TO 12 ACRES IN THE AREA OF AGE(U) E/S NO III UNDER GE(U) ELECT SUPPLY DELHI CANTT-10
2025_MES_697255_1
CWE (U)/ D-46/2024-25
Limited
Electrical and Maintenance Works
Item Rate
120 days
HQ CWE (U) Delhi Cantt
Please refer Tender Documents
9 documents required · 9 mandatory
₹500
GE(U) Elect Supply, Delhi Cantt -110010
₹87,500
Yes
5 Apr 2025
19 Feb 2025
6 Mar 2025
19 Feb 2025
4 Mar 2025
27 Feb 2025
Amount
Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in Soft soil for laying of cables or GI pipe and getting out and levelling of bottom surface to required level complete all as specified and directed.
Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc, complete all as specified and directed.
Supplying & laying for un-reinforced precast concrete cable cover Class HVP, type 1, for 11 KV flat size 300 mm x 180 mm x 40mm. complete all as specified and directed.
Returning filling in. Including spreading, levelling, watering and well ramming in layers, not exceeding 25 cm thick complete all as specified and directed.
Removing excavated material from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point complete all as specified and directed.
Supplying & laying for un-reinforced precast concrete cable cover, Class LV, type 1, for 1.1 KV flat size 250mm x 150 mm x 40mm.all as specified and directed
Taking out HT 33 KV UG cable of size 300/400 sqmm 3 core at site from trench including excavation ,returning & filling in properly for reuse complete all as specified and directed.
Taking out HT 11 KV UG cable of size 300 sqmm 3 core at site from trench including excavation ,returning & filling in properly for reuse complete all as specified and directed.
Taking out HT11 KV UG cable of size 185 sqmm 3 core at site from trench including excavation ,returning & filling inproperly for reuse complete all as specified and directed.
Labour and T&P only for relaying the HT cables of size 400/300 sqmm 3 core 33 KV in any position complete all as specified and directed. Note: ( Excavation, earth work, cable protection, sand fillings, shall be measured and paid separately.)
Labour and T&P only for relaying the HT cables of size 300 sqmm 3 core 11 KV in any position complete all as specified and directed. ( Excavation, earth work, cable protection, sand fillings, shall be measured and paid separately.)
Labour and T&P only for relaying the HT cables of size 185 sqmm 3 core 11 KV in any position complete all as specified and directed. ( Excavation, earth work, cable protection, sand fillings, shall be measured and paid separately.)
Supplying, laying, jointing testing and connecting of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) (E) of size 400 sqmm x 3 core with multistranded aluminum conductors, 33 KV grade, IS 7098 marked, laid in trenches including jointing & testing complete all as specified and directed. Note: ( Excavation, earth work, cable protection, sand fillings, cable joint shall be measured and paid separately.)
Supplying, laying, jointing testing and connecting of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) (E) of size 300 sqmm x 3 core with multistranded aluminum conductors, 33 KV grade, IS 7098 marked, laid in trenches including jointing & testing complete all as specified and directed. (Excavation, earth work, cable protection, sand fillings, cable joint shall be measured and paid separately.)
Supplying, laying, jointing testing and connecting of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) (E) of size 300 sqmm x 3 core with multistranded aluminum conductors, 11 KV grade, IS 7098 marked, laid in trenches including jointing & testing complete all as specified and directed. ( Excavation, earth work, cable protection, sand fillings, cable joint shall be measured and paid separately.)
Supplying, laying, jointing testing and connecting of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) (E) of size 185 sqmm x 3 core with multistranded aluminum conductors, 11 KV grade, IS 7098 marked, laid in trenches including jointing & testing complete all as specified and directed. ( Excavation, earth work, cable protection, sand fillings, cable joint shall be measured and paid separately.)
Supply and fixing of cable jointing kit for 33 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 400 Sqmm. complete all as specified and directed.
Supply and fixing of cable jointing kit for 33 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 300 Sqmm. complete all as specified and directed.
Supply and fixing of cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size185 Sqmm. complete all as specified and directed.
Supply and fixing of cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 300 Sqmm complete all as specified and directed.
Labour and T&P for taking out the GI Octagonal Street light poles in any position for shifting at another location complete all as specified and directed.
Labour and T&P for refixing GI Octagonal street light pole complete all as specified and directed including the following:- (foundation work) Casting in position M-30 grade reinforced cement concrete pole foundation of size 550mm x 550mmx1500mm including cutting, bending and placing in position reinforcement of 8 Nos cold twisted verticle bars of 12mm dia and reinforcement of cold twisted bars of 8mm dia with 190 mm spacing and fixing of J bolts ,terminal blocks MCB etc including providing and placing 63 mm internal dia . DWC pipe double wall corrugated with corrugation on outer face and plain surface on minor side,HDPE pipe of suitable bore of suitable length for cable inlet and exit as specified and directed.
Supply, Laying, connecting, testing and commissioning of LT XLPE cable insulated, screened,PVC beded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 V graded with stranded aluminium conductor of Following sizes .
240 sqmm 3.5 core.
120 sqmm 3.5 core.
95 sqmm 3.5 core.
35 sqmm 3.5 core.
16 sqmm 4 core.
Labour and T&P only for Disconnection of LT connections and earthing strip from LT panel and re-fixing LT Panel at new location including all the fabrication and foundation work complete all as specified and directed.
M&L for earthing with galvanized steel earth plate electrode of size 60cm x 60cm x 6 mm thick, buried directly in ground (earth pit not less than 2.10 m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level, connected to galvanized iron strip 32 x 6mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel as shown in electrical plate No 3 of SSR Part I, connected to earth test point and the equipment on the other nuts and washers of galvanised ironside complete all as specified, including testing and commissioning complete all as specified and directed.
M&L for boggy of hole under road, pavement, hard standing by manually for laying cable HT/LT through HDPE pipe of suitable size complete all as specified and directed. ( Note: The cost quoted is deemed to be inculded for repiars / rectification for damages done to the existing elecrtical / comminication and water supply system / Sewage System during execution of work )
M&L for laying HDPE pipe suitable for 0.4 mpa working pressure under road, pavement, hard standing of following sizes complete all as specified and directed.
100 mm dia
80 mm dia
S K ENGINEERS AND CONTRACTOR (BID ID -3252882)
Microsys Controls India (BID ID -3253644)
DS CONSTRUCTION (BID ID -3253634)
GILL ENGINEERS (BID ID -3254463)
Bidder Name
GILL ENGINEERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
PDF • 0.18 MB
tech_eval.pdf
PDF • 0.21 MB
fin_bid_open.pdf
PDF • 0.17 MB
boq_comp_chart.xlsx
xlsx • 0.01 MB
fin_eval.pdf
PDF • 0.18 MB
aoc.pdf
PDF • 0.20 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .