Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.1 LAccepted-Finance | L1 | Accepted-Finance Lowest | |
| 2 | L2₹8.7 L+₹64,700 (8.04%)Accepted-Finance | L2 | Accepted-Finance Other than Lowest | |
| 3 | L3₹9.5 L+₹1.5 L (18.0%)Accepted-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L3 | Accepted-Finance Other than Lowest | |
| 4 | L4₹10.3 L+₹2.3 L (28.3%)Accepted-Finance HYDERABAD TELANGANA 500076 INDIA UDYAM TS 02 0009467 | MEDCHAL MALKAJGIRI | TELANGANA | 500076 | L4 | Accepted-Finance Other than Lowest | |
| 5 | L5₹12.4 L+₹4.4 L (54.6%)Accepted-Finance | L5 | Accepted-Finance Other than Lowest |
Tender Value
Refer Docs
EMD Value
₹30,000
Closing Date
9 Dec 2020, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (U) Chandimandir
GE (U) Chandimandir Chandimandir Cantt Panchkula (HR)
GE(U)/CHM-27/2020-21 - REPAIRS / MAINTENANCE CUM PREVENTIVE MAINTENANCE OF AIR TERMINATION NETWORK, EARTHINGS, AVIATION LIGHTS OF VARIOUS OVERHEAD WATER STORAGE TANKS / RESERVOIRS AND RELATED MISCELLANEOUS WORKS AT CHANDIMANDIR CANTT
2020_MES_394315_1
GE(U)/CHM-27/2020-21
Open Tender
Miscellaneous Works
Item Rate
120 days
Chandimandir Cantt
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE (U) Chandimandir
₹30,000
Yes
12 Dec 2020
10 Nov 2020
11 Dec 2020
10 Nov 2020
9 Dec 2020
26 Nov 2020
60 days
Amount
Earthing complete with galvanized steel plate electrode 600mm x 600mmx6mm thick burried directly in ground (earth pit not less than 2.25m deep below ground level), with top edge of the plate not less than 1.50m below ground level, connected with and including GI /Steel 32 mm x 6mm earth lead strip by means of bolts, nuts, check nuts & washers of galvanized iron / steel complete all as shown in electrical plate No 5 of MES Schedule Part-I and connected to earthing test point all as specified or indicated and testing on completion as directed by Engineer-in-Charge including excavation and earth work in any type of soil, funnel, plain cement concrete (1 :3:6) type C-1 Chamber, precast reinforced cement concrete (1:2:4) type B-1 pit cover of appropriate size with and including steel reinforcement, of thickness 50mm, charcoal, common salt including protection of earthing strip by and including 40mm bore galvanized steel tubing, medium grade and 20mm bore galvanized steel tubing, medium grade pipe for watering complete all as specified as shown on drg /plates as indicated and as directed including dismantling existing earthing and removing demolished materials outside the MoD land as directed. Notes :- (a) RCC pit cover shall be precast with cement concrete 1:2:4 type B1 reinforced with 8mm dia TMT steel bars @ 100mm c/c bothways. (b) Earth lead 32mm x 6m of galvanised iron / steel protected with 40mm bore GI pipe shall be provided upto a length of 7.50 metre.
All as per the description of serial item-1 here-in above but with earth lead of GI wire 4mm dia protected with and including 15 mm bore steel water tubing, medium grade. Notes :- (a) RCC pit cover shall be precast with cement concrete 1:2:4 type B1 reinforced with 8mm dia TMT steel bars @ 100mm c/c bothways. (b) Earth lead of 4mm dia GI wire protected with 15mm bore GI pipe shall be provided upto a length of 7.50 metre.
Steel water tubing, 40mm bore galvanised, medium grade provided as protection to earthing strip in any position, in or over ground including necessary excavation and earth work as required complete all as specified and as directed including taking down l out old GI pipe and removing from site of work outside to MoD land complete all as directed.
All as per the description of serial item-3 here-in above but of 15mm bore
32mm x 6mm galvanised iron I steel strip as earth continuity conductor or main earthing lead fixed to walls or batten or recess or chases or burried directly in ground or drawn in and including conduit I pipe or any other situation I location for loop earthing with and including arrangements for fixing to walls or battens or recess and including cutting chases as required and making good including excavation and earth work as required complete all as specified and as directed.
All as per the description of serial item No 5 here-in-above but 4mm dia galvanised iron / steel wire.
Air termination single pointed aluminium rod , 12mm dia, 300 mm long with base plate / saddles fixed to any location / situation as directed with and including requisite fixing arrangements complete all as specified and as directed including dismantling / taking down existing strip and removing from site of work outside to MoD land all as directed.
Aluminum strip 25mmx3.15mm with saddles & fixing screws and fixed to any location / situation as earth continuity / roof conductor / down conductor on overhead /water storage tanks / reservoirs complete all specified and as directed including dismantling / taking down existing strip and removing from site of work outside to MoD land all as directed.
Twin core cable 6 Sqmm fixed with saddles / conduit in any location I situation complete all as specified and as directed including taking down existing cable and removing from site of work outside the MoD land all as directed.
Cement concrete 1:3:6 type C-1 using 20mm grade crushed stone aggregates as in bed plates, bed blocks, protection to pipes under floors or any other location I situation as directed including necessary formwork as required and finishing exposed surfaces even and smooth complete all as specified and as directed including dismantling/ demolishing existing concrete all as directed and removing rubbish outside the MoD land.
Test point terminal block made of gun metal or phosphorus bronze of size 75mmx 75mmx5mm drilled and screwed with and including 03 Nos : 8mn dia 25mm long hexagaonal head screws fixed in any position and location complete all as specified and as directed including taking down old terminal block and removing from site of work outside to MoD land.
LED aviation light twin type 2x6 watts capacity with LDR IP-65 protection, red lighting fixed to any location / situation with and including requisite fixing arrangement complete all as specified and as directed including taking down old existing Iight and removing from site of work outside to MoD land.
DMC insulator of size SP-20 having approx size 50mm x 25mm x 25mm duly fixed on wall / roof / overhead tank / reservoir with two No steel screws and PVC rawl plugs grouted in wall / roof with drilling machine and 01 No strip holding GI bolt 6mm dia 25mm long with double nut and washers complete all as specified and as directed including taking down existing insulator and removing from site or work outside to MoD land.
All as per the description of serial item 13 here-in above but insulator of size SP-35 having approx size 90mmx40mmx35mm.
Line contactor 415 volts, AC, 50Hz 3 pole current rating AC-3, 250A with one pair of auxiliary contacts (01 NO + 01 NC) fixed to any location / situation complete all as specified and as directed including taking down existing contactor and removing from site of work outside to MoD land.
All as per the description of serial item-15 here-in above but contactor, 415 volt AC, 50Hz, 3 pole, current rating AC-3 145A
Dismantling existing unserviceable I deteriorated L T panel, removal from site and depositing to MES store yard, Supply, installation, testing and commissioning of outdoor type floor mounting Polycarbonate CPRI approved OEM made L T Panel suitable for outside, shall be made of modular POLY CARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance in accordance with IEC 61439-1, clause 10.2.4 : The panel should be anti-acid & anti corrosive. Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer of panel shall submit a copy of CPRI TEST REPORT IN POLYCARBONATE OF DEGREE OF INGRESS PROTECTION IP65 IN ACCORDANCE WITH IEC 60529. The gasket should be internally embedded made of polyurethane. The manufacturer of panel SHALL submit a copy of TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel in accordance with IEC 60439-1. The CPRI report shall have mention of following tests performed and passed out satisfactorily: Temperature Rise, Dielectric Properties, Short circuit withstand current - Rated peak & short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits. The board manufacturer must submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS will not be applicable. Guarantee and warrantee certificates will be accepted only from original manufacturer.
The panel should pass glow wire test 9600C in accordance with 60695-2-11 flame retardant and self extinguishing with MC 75 for base frame & angle iron 50 x 50 x 6 mm size legs , 04 Nos legs 600mm long, PCC 1 :2:4 type B-1 for grouting of base, suitable for 3 phase 415 volts 50 Hz 4 wire AC supply complete all as directed with and incl the following: (a) INCOMING : (i) 4 POLE ONLOAD CHANGEOVER SWITCH 400 amp01. (ii) MCCB 4 pole, 415 Volts , rating 400 Amps , 36 KA, Ics=100%lcs, line load reversibility, adjustable thermal & adjustable magnetic release - 01 No. (iii) Multifunctional digital meter compatible to measure current, voltage, power factor & frequency with 3 lines LCD display in 96x96 Sqmm flush mounted case, accuracy class 1.0 - 01 No (iv) Resin cast CT 600/5A cast resin base -01 No set of 03 Nos. (v) LED indication lamp C, 415 volts , 50 Hz for RYBV-03 Nos. BUS BAR : 3 Phase 4 wire copper bus bars of suitable length & section not less than 60x10mm and length not exceeding 120cm each strip covered with coloured heat shrinkable anti track insulation tape of make Dension 1M-seal or equivalent of finished thickness not more than 1 mm and length not less than 1 mm and fixed on epoxy base post insulation tape of make Denson / M-seal of equivalent of finished thickness not more than 500mm-01 Set. (b) OUTGOING: (i) MCCB 3 pole, 415 volts, rating 250 Amps, 36 KA, Ics=100%lcu, line load reversibility, adjustable thermal & magnetic release type - 3 Nos. (ii) MCCB 3 pole, 415 Volts, rating 100 Amps, 36KA, Ics=100Ics, line load reversibility, adjustable thermal & magnetic release type -01 No. Note: (i) All existing and new connections of incoming l out going cables shall be done through appropriate size of copper thumbless. (ii) Drawing, circuit diagram and all materials I instruments etc for LT panel shall be got approved by GE before fabrication. (iii) Location for panel - Sec ‘C’ Pump house.
M/S RAGBIR ENGINEERING SERVICES
R D Bansal
POWER TECH ENGINEERS
AKAALTECH
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .