Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.8 LAccepted-AOC | L1 | Accepted-AOC Reasonable | |
| 2 | L2₹18.6 L+₹1.9 L (11.2%)Rejected-Finance | L2 | Rejected-Finance High rate |
Tender Value
₹19.3 L
EMD Value
₹38,600
Closing Date
1 Jul 2021, 5:00 pmClosed
GE NDA KHADAKWASLA
GE NDA KHADAKWASLA
PROVN OF 02 X BOILERS (CAPACITY 200 LITRES EACH) WITH ADDN/ALTN TO EXISTING ROOM AT ETT AND PROVN/UPGRADATION OF E AND M INSTALLATION AT CADETS MESS AT NDA KHADAKWASLA
2021_MES_446551_3
GE (K) 15 OF 2021-2022
Open Tender
Civil Works
Works
180 days
GE NDA KHADAKWASLA
As per Tender documents
9 documents required · 9 mandatory
₹500
Yes
GE NDA KHADAKWASLA
₹38,600
Yes
17 Aug 2021
17 Jun 2021
3 Jul 2021
17 Jun 2021
1 Jul 2021
19 Jun 2021
17 Jun 2021 - 18 Jun 2021
Amount
Dismantling of Stone slabs and tiles of any description or thickness in floors, aprons etc including cleaning off premises where directed.
Demolition of unreinforced cement concrete in ground floors and pavings n exc 15 cm thickness (below or above ground level) including cleaning off premises where directed.
Demolition of brick/ stone masonry built in Cement mortar
M&L precast cement concrete 1:3:6 type C-1 ( using 20mm graded aggregate ) block masonry with solid blocks exc10 cm thick in width and setting in cement mortar 1:6 complete in wall all as specified.
M&L for Rendering 15mm thick on fair faces of brick work or concrete surfaces in CM 1:6 finished even and smooth without using extra cement
M & L for Hand Cut superior quality Kota stone slab flooring 20-25 mm thick over cement screed , laid and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and mirror polishing complete and incl 20 mm thick screed bed or bedding layer in CM (1:6) complete all as specified and directed.
M & L for Hand Cut superior quality Kota stone slab 20-25mm thick in riser of steps, skirting, dado, pillar and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and mirror polishing complete match including bulnosed and incl 10 mm thick plaster in CM (1:3), incl taking down plaster all as specified and directed.
M&L for 20mm thick Granite (of any type) work (table rubbed and polished) in steps, jambs, pillars, window cills, cooking platforms and like including pointing in white cement (1:2) using marble dust with admixture of pigment to match with shade of granite and incl 15 mm thick screed bed or bedding layer in CM (1:4) complete all as directed.
M&L 75 mm thick PCC (1:4:8) type D2 using 40 mm graded aggregates as in sub base all as specified and directed
M&L for plastering 15 mm thick in CM 1:6 on wall in patches not exc 3 sqm each including taking down plaster,racking out joint as specified and directed .
M&L for plastering 10 mm thick in CM 1:3 on ceilling in patches no exc 3 sqm including taking down plaster, racking out joint as specified and directed
M&L for Preparing new plastered surfaces of walls applying two coats of distemper oil bound over a coat of primer all as specified and directed.
M&L Preparing new plastered surfaces of ceilling applying three coats of white wash as specified and directed.
Dismantling of Plain or corrugated steel sheeting, any gauge, thickness, including Nainital or similar pattern roof coverings
S&F pre painted galvalume aluminium zinc coating GI based corrugated steel sheet 0.50mm thick of any colour having tensile strength of 550Mpa as in roof covering /cladding to wall fixed with L hooks or J types or cranked bolts complete all as specified and as directed.
S&F MS rolled /box sections as in main and cross beams ,columns ,purlins, brackets where connected to common rafters ,fixed with angle cleats or other connecting plates , Fe 410 W ,GRADE E- 250/ box sections complete all as directed.
S&F in repairs Rotational moulded polye- thylene water storage tanks 1000 Ltr capacity (cylindrical vertical with closed top three layered ISI marked) hoisted and fixed in position all as specified in SSR Part I
S&F 20mm dia tank Nipple suitable for HDPE water tank. (Minimum weight 15 mm-38gms/20mm-45gms /25mm- 65gms) including taking down old one as specified & directed.
S&F Ball valves 20mm dia high pressure of PTMT with epoxy coated Aluminium rod & highdensity plastic ball screwed for iron pipe and fixed. (Minimum weight 15mm-142gms/ 20mm-210gms./ 25mm-455gms/ 40mm - 690 gms) including taking down old one complete all as specified and directed.
S&F Gun-metal, globe or gate valves 20mm dia, with iron wheel head, screwed both ends for iron pipe and fixed complete all as specified and direceted.
S&F galvanised mild steel medium grade tubes 15mm dia bore with all fittings and fixed to wall , floor etc. complete all as specified and directed.
-Do- all as per item No 21 above but 20mm dia pipes.
Taking down chowkhats or frame not exc 1.5 sqm each with shutters (without taking off shutters from the frames)
Taking down chowkhats or frame exc 1.5 sq. m but n exc 4 sq m each with shutters (without taking off shutters from the frames)
S&F 2nd class hard wood Plain, solid, straight, chowkats and frames, wrought, framed rebated on the solid, rounded or chamfered, put together with glue pinned at joints, supplied and fixed
S&F 35mm thick Factory made 2nd class hard wood Glazed and skeleton shutters, open rebated and prepared to receive glass, gauze, etc. (without sash bars), edges of framing plain, chamfered or rounded. fitted with cut and mitred beads for securing glass, etc.; sizes of members of shutters as specified in SSR Part I, Section 8, clause 8.24 (a); supplied and fitted to chowkats
M & L 35 mm thick Factory made Plain framed, panelled shutter (two panel) with lock rail and panel of 9 mm B.W.P commercial ply or 12 mm veneered particle board with commercial veneering on both faces. The size of rail and stile as per IS: 1003 (Part I), kiln seasoned and chemically pressure treated
M&L for Cutting holes in brick / stone walls and in floor tiles where directed in cement mortar for inserting holdfasts or frame and making good dismantled portion in cement mortar 1:3 or cement concrete 1:2:4 Type B-1 as required complete all as specified and directed.
M&L 100mm butt hinges cold rolled mild steel medium weight and fixed
S&F 150mm Aluminium handles, cast type, anodised
S&F for Aluminium anodised, barrel tower bolts 150mm long of ex- truded section and fixed
S&F 300 mm long aluminium alloy, anodised sliding door bolt with hasp staple (bolt type) and fixing clips of sheet cast or extruded section and fixing bolts and sliding bolts of extruded sections all as specified and directed
M&L for preparation of new wooden surfaces and painting two coats of Synthetic Enamel paint over a coat of pink primer.
S&F in repair Aluminium alloy wire cloth, 0.45mm nominal dia of wire and average width of aperture 1.40mm and fixed with aluminium wire staples to shutters including taking out wooden beads and re-fixed in the same position complete all as specified and directed
S&F in repair Aluminium powder coated three track sliding window with 3 to 4 mm thick tinted glass shutters and aluminium mosquito proofing 0.36mm nominal dia of wire and average aperature 1.40mm with good quality bearing ,handle,lock rubber beading and glazing clips etc using following aluminium powder coated sections conforming to catalogue of JINDAL or of equivalent make complete all as specified and as directed . (a) Bottom frame:20620 (b) Top frame and Vertical:20621 (c) Handle(side)20606 (d) Sutter interlock:20724 (e) Shuuer top and bottom:20844 (f) Glazing clip:19352 Note : rate inclusive glass pane and masquoto proofing nets and aluminium grill.
S&F Framed work such as grills, gratings ,doors etc., with ends of bars shouldered and/or riveted, or forget into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework of water tanks and similar work conforming to Fe 410-0 or Fe 310-0
M&L preparation of new or previously untreated steel surface & applying two coat synthetic enamel Painting over a coat of preiming red red oxide zinc chrome
M&L for preparation of old painted surfaces of wall , cleaning , washing with water etc , and applying one coat of exterior emulsion paint (Appex paint) , including filing the surface with crack filler wherever required all as specified and directed . Note . (i) The coulour scheme of the painting will be as decided by the accepting officer (ii) Work to be execute in any respective ht of building
M & L for providing reinforced cement concrete pipes 150mm dia class NP 2 with collars laid and jointed with cement jointed all as directed.
M & L for providing bed to drain pipes 150mm dia in cement concrete (1:3:6) type C2 using 40mm graded stone aggregate including packing under & haunching against the sides of pipes after they are laid & tested.
Supply, Laying, testing & commissioning XLPE insulated screened PVC bedded, galvanized steel strip armored, electric power cables (Heavy duty) 1100 volts grade with stranded aluminium conductor of cross sectional area 50 Sqmm 3.5 Core inclduing clamped on wall and Floors in any position by means of suitable size of nut, bolts & clamps and termination with AL Lugs at both side of Panels etc complete.
Supply, Laying, testing & commissioning XLPE insulated screened PVC bedded, galvanized steel strip armored, electric power cables (Heavy duty) 1100 volts grade with stranded aluminium conductor of cross sectional area 35 Sqmm 3.5 Core including clamped on wall and Floors in any position by means of suitable size of nut, bolts & clamps and termination with AL Lugs at both side of Panels etc complete.
Excavation in trenches, n.exc 1.5m wide and n. exc 1.5 m depth and getting out in Hard/Dense soil for foundation of pole, stay, laying of cable and pipe etc.
Ditto item No 43 but Soft and Disintegrated rock
Returning and filling in, including spreading and well ramming in layers n exc 25 cm all as specified and directed.
M&L for crushed stone dust dry sand cushioning to under ground cable in trenches including spreading, leveling and hand pinning complete all as specified and directed. Note : For measurement purpose punned thickness shall be considered.
Supply and laying in Trenches un-reinforced precast concrete cable cover, class LV, type 1, flat, size 250 mm x 150 mm x 40 mm complete all as specified and directed.
M&L for crushed stone dust dry sand cushioning to under ground cable in trenches incl spreading, leveling and hand punning complete all as specified and directed. Note : For measurement purpose punned thickness shall be considered.
Supply and lay G.I pipe light grade 80 mm dia with all fittings required for protection of under ground cable for road crossing etc
M & L for Road/PCC Cutting (45x50)cm (WxD) as required for laying pipe/cable etc including earthwork and necessary excavation including making good with required material to match with the existing one or with PCC 1:2:4 type B1 complete all as specified and as directed.
Supply, installation, testing and commissioning LT MCCB Control Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer only. The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, front side double door type with locking arrangement for front side and back side also, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with aluminium bus bars, electrolytic grade of adequate rating or specified below. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc. The panel shall be provided with digital multifunction meter, Accuracy Class 1 with RS 485 Parameters with cast Resign CTs and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be showing the arrangements of circuit shall be pasted inside the panel door and covered with transparent laminated plastic sheet . The panel shall be provided with manufacturer's name plate, skull & bones danger notice board etc. The panel shall be provided 4 Nos 50x50x6mm thick angle iron supports of not less than each 1 mt height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both sided and suitable extended rotary handles for all MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1500mmX350mmX1000mm (LxBxH). The panel shall be provided for Cable entry from bottom side for required No of Cable with suitable size of SS Cable Glands including 2 Nos of Earting Terminals one on each side of the Panel with earth strip and including following accessories:- Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved. (a) MCCB 4 Pole, 415 Volts, 100 Amp, 25 KA with adjustable Thermal and adjustable Magnetic overload protection, Conforms to IS/IEC 60947-2 & IEC-60947-2, Ics = 100% Icu suitable for Isolation with both side of spreader links and phase separator etc. (Outgoing) - 01 No (b) MCCB 4 Pole, 415 Volts, 63 Amp, 16 KA with adjustable Thermal and adjustable Magnetic overload protection, Conforms to IS/IEC 60947-2 & IEC-60947-2, Ics = 100% Icu suitable for Isolation with both side of spreader links and phase separator etc. (Outgoing) - 02 No (c) MCCB 4 Pole, 415 Volts, 40 Amp, 16 KA with adjustable Thermal and adjustable Magnetic overload protection, Conforms to IS/IEC 60947-2 & IEC-60947-2, Ics = 100% Icu suitable for Isolation with both side of spreader links and phase separator etc. (Outgoing) - 02 No (d) LED type phase indicator lamp RYB, ON, OFF & TRIP. (e) 4 Nos bus bars of high conductivity aluminium alloy for phase (R,Y,B,N) suitable for 500 Amp rating.
S & F Sheet Metal Enclosures factory made Tripple Pole and Earth enclosure with a three pin and earth plug with 63 Amp Industrial socket complete with one Four Pole MCB of 63 Amp, 415 Volts, 10 KA including wall mounting accessories and connection to Boiler complete all as directed.
S & F Sheet Metal Enclosures factory made Tripple Pole and Earth enclosure with a three pin and earth plug with 40 Amp Industrial socket complete with one Four Pole MCB of 40 Amp, 415 Volts, 10 KA including wall mounting accessories and connection to Boiler complete all as directed.
M & L for Core cutting in any type of wall from 100 to 150 mm dia complete all as speciified and directed.
M & L for Earthing complete with galvanized steel earth plate electrode 600 X 600 X 6.3 mm thick buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.50 m deep below normal ground level in any type of soil strata, connected to galvanized iron strip 32 x 6mm by means of bolts, nuts and washers of galvanised iron or steel all as shown in earth plate No 3 of MES schedule 1991 Part – I connected to outdoor LT Panel including necessary excavation and earth work in any type of soil strata, concrete pit & chamber in PCC 1:2:4 type B1 & pit cover 75mm thick in PCC 1:2:4 type B1 with lifting handle and Earth lead and 20mm Dia GI watering pipe medium grade, Funnel, wiremesh, etc. complete all as specified and directed including testing on completion.
M & L for Earthing complete with galvanized steel earth plate electrode 600 X 600 X 6.3 mm thick buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.50 m deep below normal ground level in any type of soil strata, connected to galvanized earth lead wire 4 mm dia by means of bolts, nuts and washers of galvanised iron or steel all as shown in earth plate No 3 of MES schedule 1991 Part – I connected to outdoor LT Panel including necessary excavation and earth work in any type of soil strata, concrete pit & chamber in PCC 1:2:4 type B1 & pit cover 75mm thick in PCC 1:2:4 type B1 with lifting handle and Earth lead and 20mm Dia GI watering pipe medium grade, Funnel, wiremesh, etc. complete all as specified and directed including testing on completion.
M & L for GI strip 32 x 6 mm fixed with Earth lead continuity conductor with suitable size of SMC insulators, nut bolts and washers and fixed on any type of wall and any position etc complete
M & L for 4 mm dia GI wire fixed with Earth lead continuity conductor with suitable size of SMC insulators, nut bolts and washers and fixed on any type of wall and any position etc complete
(Design & Manufacture), Supply and Installation including testing and commissioning of bulk cooker, 200 Ltrs Capacity, electric operated triple walled insulated.Inner tank 14swg ss 304 and outer 20swg ss 202, 75mm thick mineral woll insulation and spring loaded ss lid with rear flue riser, electric controls, tilting gear, SS fram etc. Note : Before manufacture design and drawing of the same should be approved
Taking down/Disconnecting carefully Incoming and Outgoing LT UG Cables of size upto 300 Sqmm 3.5 Core from Existing LT Panel and connecting new LT UG cables to newly installed LT Control panel according to site requirement after taking proper power shut down and exercising alll safety precautions for human safely including cleaning and removing foreigbn material/mud from Panel room including reconnecting all LT UG Cable connection with existing LT Panel according to existing system complete all as directed.
Supply, installation, testing and commissioning of main LT Panel weather proof indoor type double door, fabricated out of 2.0mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer only. The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-43, double door type with locking arrangement for front side and nut bolts for backside, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with aluminium bus bars, electrolytic grade of 600 Amps of current rating. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers including Lugs etc. The panel shall be provided with digital multifunction meter, Accuracy Class 1 with RS 485 Parameters with cast Resign CTs and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be showing the arrangements of circuit shall be pasted inside the panel door and covered with transparent laminated plastic sheet . The panel shall be provided with manufacturer's name plate, skull & bones danger notice board etc. The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1 mt height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both sided and suitable extended rotary handles for all MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1000mmX400mmX900mm (LxBxH). The panel shall be provided for Cable entry from bottom side for required No of Cable with suitable size of SS Cable Glands including 2 Nos of Earting Terminals one on each side of the Panel with earth strip and including following accessories:- Note : Before manufacturing drawing and design of panel including size & length of busbar shall be approved. (a) MCCB 4 Pole, 415 Volts, 400 Amp with Thermal Magnetic release, 36 KA, Conforms to IS/IEC 60947-2 , Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In & adjustable short circuit Manual type with both side of spreader links and phase separator etc – 01 No (Incomer). (b) MCCB 4 Pole, 415 Volts, 250 Amp with Thermal Magnetic release 25 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In & adjustable short circuit with both side of spreader links and phase separator etc - 02 No (Outgoing)
S&F wire mesh Cable Tray Hot Dipped Galvanized size 54x100mm, Trays should comply Standard EN ISO 1461: at least 550h of SST. The deflection of cable tray must be no more than 1/200th of the distance between two supports and tested in accordance with the standard IEC 61537, Wire cable trays must be designed with an optimum span of 1.5m, taking into account the maximum carrying capacity authorised by the manufacturer, Assemblies with specific fire resistant properties must have an E30-E90 certificate. The loading capacities of the brackets and the hanger torques must be tested in accordance with teh standard IEC 61537 including all standard wall mounting accessories e.g. SS Mounting Bracket, bends, Fastners, kitastar, nut , bolts and washers etc completer all as specified and directed. It shall be manufactured with a longitudinal ''T-welded' safety edge.
S&F on any type of wall with suitable size of shaddle, nut, bolts, screws etc including testing of LT UG power cables, XLPE Insulated, screened, PVC bedded, galvanized steel strip armoured, electric power cables (heavy duty) 1100 Volts grade with multi-stranded aluminium conductor including termination on both side of LT Panel with suitable sixe of AL lugs, Cadmium plated high tensile nuts, bolts and washers etc of size 3.5 Core150 sqmm
S & F on any type of wall with suitable size of shaddle, nut, bolts, screws etc including testing of LT UG power cables, XLpE Insulated, screened, PVC bedded, galvanized steel strip armoured, electric power cables (heavy duty) 1100 Volts grade with multi-stranded copper conductor including termination on both side of LT Panel with suitable size of Copper Lugs, Nuts, bolts and washers etc of size 3.5 Core 50 Sqmm
S/F of SS Enclosure Factory made including suitable for housing 250 Amps, 4P, 415 Volts, 25 KA, MCCB, IK08 and IP 30 Protection with wall mounting accessories in any type of wall complete all as specified and directed. Note : Cost of 4P, MCCB, 250 Amps, 25 KA , 415 Bolts shall be included in this job.
S &F of 150W Flood light Warm white/white incolour, LM6 Aluminium or higher grade powder coated and water proof pressure die cast aluminium enclosure with inbuilt electronic driver and IP66 protection complete 1-phase, 230 V etc including fixing on wall with suitable size of MS channel mounting structure as per site requirement by drilling in any type of wall, fastners, nut, bolts, washers etc complete all as directed.
Supply and fixing insulated multi-stranded copper conductor 3 Core 4 Sqmm for connection of floodlight including fixing on any type of wall, roof etc with suitable size of clamp, nut, bolts, Lugs and washers etc complete all as directed.
S&F ceiling rose surface shall comply with IS :371-1979 Bakelite 60x 25 mm two to three terminals plates and of outside diameter not less than 63.5mm.
Supply & Fix including commisioning digital automatic timer switch distribution panel board, factory assembled in powder coated sheet steel enclosure, comprising of 3 P, 32 Amps MCCB, 32 Amps 3 pole power contactor and 230V digitaltime switch for controlling Flood lights including suitable for fixing on any type of wall, floor etc with suitable size of Fatners, nut, bolts, washers etc complete all as directed.
M&L for GI earthing complete with glavanised steel earth plate elecrode 600x600x6.3 mm thick buried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.50m deep below normal ground level in any type of soil strata, connected to galvanised iron strip 25x4mm by means of bolts, nuts and washers of galvanised iron or steel all as shown in earth plate No 3 of MES schedule 1991 Part-I connected to machinery/equipment as required including necessary excavation and earth work, concrete pit & chamber in PCC 1:2:4 type B1 & MS pit cover heavy duty with ligting handle and 20mm dia GI watering pipe medium grade, Funnel, wiremesh, etc complete all as specified and directed including testing on completion.
M&L for 50 mm dia, GI tubes, light Grade, glavanised with all fittings, laid in trenches or under floor for cable protection by mechanical means and grouted in Floors or fixing on wall/surface size of GI shaddle, screws etc omplete all as specified and directed.
M&L for gI earth strip 25x4 mm size including connect with equipments / machinery beyond 7.5 mtr by means of nut, bolts, washers inlcuing SMC/FRP insulators fixed at suitable gaps/intervals etc complete all as directed.
M&L for rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top three layered, ISI marked) of capacity 5000 ltrs, hoisted and fixed in position and connecting to water incoming pipe line including all fittings such as top cover, nipple, float valve PTMT type 20mm etc complete all as specified in SSR Part I.
S&F GI medium grade tubing of bore 40mm with all fitting and fixed complete to walls/ceiling/ground complete all as specified and directed.
Removing excavated material (soils) not excedding 50m and dposting where directed at a level not exceeding 1.5m above the starting point.
Excavating in post holes (or similar) holes each n.exceeding 0.5 cum getting out returning filling in and ramming earth or broken rubble mixed with earth around, in layers not exc 25 cm, watering and removing surplus soil to a distance n.exc 50m and making food surface.
M&L cement concrete 1:3:6 type C2 using 40mm stone aggregate foundation/resting platform in foundation filling and mass concrete.
M&L for mild steel rolled section connected with each other with welding (angle, tee, channel, beam, hollow sections etc) as in main and cross beams, hip verticle hollow sections and jack rafters, purlines where connected to common rafters and running rils where vericle suctions and fixed in welded in walls in wall surface with plates and other verticle sections are fixed in ground level embedded in concrete fixed and horizontal sections fixed in wall with bolt completely, fixed with angle, cleats or other connecting plates conforming to Gde Fe-410-W (Gde E-250) quality-B complete all as specified and directed.
All as per item No 78 above but plates (plain or chequered channels, square cut or notched (ordinary and counter sunk) forming boles, without any attachment.
S&F pressure booster CM pump of 1 HP capacity with hydro pneumatic pressure tank of capacity not less than 24 ltr including necessary pressure dia and relay for constant water pressure not less than 4 bar silent operation and highly relaiable liquid temperature from 20 degree celcius to 120 degree celcius, 80 start /stop per hours including provn of panel for auto shifting of pump in form of 1W+1S and every pump not running maximum 04 hours at a time.
Supply and installation for automatic operation, single phase copper wounded voltage stabilizer & designed for input variation between 220 V to 240 V with output voltage stabilized at 230 V with accuracy + 1% and of capacity 1.5 KVA complete all specified and directed.
Supply and laying in trenches GI tubing ' Medium grade' of size 25mm bore with all fittings complete.
Supply and fixing of ISI marked GM gate valves with iron wheel head, screwed both ends for iron pipes of 25mm bore.
M/S SHREE CONSTRUCTIONS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .