Karnataka Power Transmission Corporation Limited
Srinivas T
Augmentation of 2 x 12.5 MVA, 66/11kV Transformer by 2 x 20 MVA, 66/11 kV Transformer at 66/11 KV Megalapura sub-station in Mysuru Taluk, Mysuru district.-Reserved for CAT-I Category-CALL-2
KPTCL/2025-26/SS/WORK_INDENT3277
KPTCL/2025-26/SS/WORK_INDENT3277
Reserved
Sub-Station
Two Tender Document System(Two Cover)
KPTCL CEE Transmission Zone Office Mysuru
15 documents required · 15 mandatory
The Bidder shall be registered firm as Sole Proprietorship/Partnership/Pvt Ltd Company etc
For other than proprietorship, the Bidder shall furnish the registered partnership deed and Power of Attorney
Valid Caste Certificate in support of reserved tender participation
Valid Karnataka Residential Certificate
valid Super grade Electrical Contractor License issued by the Government of Karnataka as on the date of opening of techno-commercial bid (refer 2.3 of ITT)
Minimum Average Annual Turnover (MAAT) of the bidder for best one(01) year out of last preceding five financial years, shall not be less than Amount Put to Tender as per 3.2(a) of std tender documents(ITT).
3.6: Tenderers who meet the above specified minimum qualifying criteria, will only be qualified, if their available tender capacity is more than the total tender value. The available tender capacity will be calculated as under:Assessed Available Tender Capacity: (AxNx5-B)Where A-Maximum value of works executed (KPTCL & Non-KPTCL) in any one year during the last five years (updated to FY 2024-2025) taking into account the completed as well as works in progress. N-Number of years prescribed for completion of the works for which tenders are invited.B-Value, at FY 2024-2025 price level of existing commitments (KPTCL & Non-KPTCL)and on-going works (KPTCL & Non-KPTCL) to be completed during the next 1(One)year.Note:(i)The statements showing the value of existing commitments and on-going works as well as the stipulated period of completion remaining for each of the works listed should be countersigned by the Employer in charge, not below the rank of an Executive Engineer or equivalent.(ii)A self-declaration is to be uploaded by the Tenderer stating that the information with regard to assessed available tender capacity (Works on Hand) furnished are correct.
Even though the Tenderers meet the above criteria, they are subject to be disqualified if they have:- Made misleading or false representations in the forms, statements and attachments submitted in proof of the qualification requirements and/or- Record of poor performance such as abandoning the works, not properly completing the contract, inordinate delays in completion, litigation history, or financial failures etc. and/or- Participated in the previous Tender for the same work and had quoted unreasonably high Tender prices and could not furnish rational justification.
Bidder shall ensure that soft copies of Power of Attorney, Letter of Undertaking, No Deviation CERTIFICATE as revised in Annexure , Any other undertaking / agreement (if applicable) are to be uploaded besides submitting the Originals to the office of the Chief Engineer, Electy., Operation, KPTCL, Mysuru, after the last submission date as per 3.10(xviii) of ITT
Bidder shall ensure that soft copies of i. Letter of undertaking for Non performance ii. Letter of undertaking for Risk and Cost iii. Letter of undertaking for Litigation iv. Letter of undertaking to source the supply of equipment material from KPTCL approved Vendors only (if applicable) are uploaded besides submitting the Originals to the office of the Chief Engineer, Electy., Operation, KPTCL, Mysuru, after the last submission date as per 3.10(xviii) of ITT
i. Letter of undertaking to source the equipment/material for the work from the approved Vendors who meet the eligibility clauses regarding restrictions on procurement from a country which shares a land border with India (Annexure-XVI) ii. Letter of undertaking as per clause No.1.5 of Annexure-XVII iii. Letter of undertaking as per clause No.1.6 of Annexure-XVII (if applicable) are uploaded besides submitting the Originals to the office of the Chief Engineer, Electy., Operation, KPTCL, Mysuru, after the last submission date and on or before the date and time of opening of techno commercial bids.
ESI certificate
EPF Certificate
Shall upload valid GST Certificate and PAN copy
The Bidder should have carried out erection of atleast One(01) No. of 66kV voltage class or above voltage class Sub-Station/ Additional Transformer work OR atleast One(01) No. of 66kV voltage class or above voltage class Transformer Replacement/ Augmentation work on Total or Partial Turnkey Basis in the last 10 years preceding the date of bid submission and shall be completed and commissioned prior to the date of submission of the Bid OR The Bidder should have carried out erection of atleast Two (02) Nos of Agumentation/Replacement of 66kV or above voltage class Transformer works on Labour Contract Basis in the last 10 years preceding the date of bid submission and shall be completed and commissioned prior to the date of submission of the Bid OR Bidder who has executed Additional Transformer works or Replacement of Transformer works of private firms under the direct supervision of ESCOM/KPTCL officers are eligible to participate. Such Bidder should have carried out erection of not less than Two (02) Nos. of 66kV or above voltage class Additional Transformer Work on Total or Partial Turnkey Basis in the last 10 years preceding the date of bid submission and shall be completed and commissioned prior to the date of submission of the Bid
₹910
₹36,300
26 Feb 2026
12 Feb 2026
2 Mar 2026
23 Feb 2026
Supply Estimate
Sup01 Capacitor Bank:
Design, Engineering, supply, erection, testing & commissioning of 2.9 MVAR, 12.1 kV Capacitor Bank, star connected, Double Bank with internal fuses, terminal connectors with suitable ... 2.00 Set
Sup02 11 kV class, NCT of ratio 1200-800 /1-1A for REFR protection.(of similar rating and ratio as that of 11 kV Incomer) with Terminal connectors suitable for 2 nos of 50x8 copper flats 2.00 Nos
(for Incomer/Bus Coupler of 25 kA SWG)
OUTDOOR, for Bank 3.00 Nos
Sup04 11kV isolators, Double Break 400A, with rigid b-metallic terminal connectors suitable for coyote ACSR for Outgoing feeders & Capacitor Bank 2.00 Nos
Sup05 11KV GOS/Cable Terminating Structure for 11KV Capacitor Bank(0.158 t per structure) 2.00 Nos
Sup06 Drake ACSR 360.00 Mtr
Sup07 Post insulator clamp suitable for Twin Drake ACSR Conductor 127/76 mm 66 kV 12.00 Nos
Sup08 Terminal connector clamps for Twin Drake ACSR Conductor 127/76 mm 66 kV suitable to 11kV Bank CT's 1 & 2 and Breaker Limbs 24.00 Nos
Sup09 Terminal connector clamps for Twin Drake ACSR Conductor suitable to 11kV Bushings of Power Transformer's. 12.00 Nos
Sup10 C - Type Wedge Connector Double Drake to Single Drake for PT's 1 & 2 12.00 Nos
Sup11 1.1 KV class. Size of cable.
19 Core 2.5 Sq.mm. 50.00 Mtr
Sup12 4 Core 6.0 Sq.mm. 100.00 Mtr
Sup13 4 Core 2.5 Sq.mm. 100.00 Mtr
Sup14 2 Core 2.5 Sq.mm. 100.00 Mtr
Sup15 11 KV, XLPE Insulatd UG Cable 3C X 240 Sq. mm Aluminium cable (To be run from 11kV switchgear to take off DP structure) 150.00 Mtr
Sup16 Cable Terminationkits suitable for 240Sq. mm 3 Core Indoor 2.00 Nos
Sup17 Cable Terminationkits suitable for 240 Sq. mm 3 Core Outdoor 2.00 Nos
Erection estimate
Ere01 Erection of 20MVA, 66/11kV TRANSFORMER. (39.1 MT) Power Transformers: 2.00 Nos
Ere02 Testing and commissioning of Power Transformer 2.00 Nos
Ere03 Erection of 11kV, 25 kA PCVCB (1600A for Incomer and 1250 A for feeders), outdoor type, each comprising of 1 IC with CTs & PTs etc., complete as per technical specification. 1.00 Nos
Ere04 Testing and commissioning of Switchgear 1.00 Nos
Ere05 Erection of 11 kV class, NCT of ratio 1200-800 /1-1A for REFR protection.(of similar rating and ratio as that of 11 kV Incomer) with Terminal connectors suitable for 2 nos of 50x8 copper flats 2.00 Nos
Ere06 Testing and commissioning of NCT 2.00 Nos
Ere07 Erection of 11 kV CT : 1200-800/1-1-1 A
(for Incomer/Bus Coupler of 25 kA SWG)
OUTDOOR, for Bank 3.00 Nos
Ere08 Testing and commissioning of CT 3.00 Nos
Ere09 Releasing & Re erection of existing HPI mounting structure (0.150MT/Structure) 0.90 MT
Ere10 11kV isolators, Double Break 400A, with rigid b-metallic terminal connectors suitable for coyote ACSR for Outgoing feeders & Capacitor Bank 2.00 Nos
Ere11 11KV GOS/Cable Terminating Structure for 11KV Capacitor Bank(0.158 t per structure) 0.32 Nos
Ere12 Releasing and Re-erection of existing 11kV Drake Bus 2.00 Nos
Ere13 1.1 KV class. Size of cable.
19 Core 2.5 Sq.mm. 50.00 Mtr
Ere14 4 Core 6.0 Sq.mm. 100.00 Mtr
Ere15 4 Core 2.5 Sq.mm. 100.00 Mtr
Ere16 2 Core 2.5 Sq.mm. 100.00 Mtr
Ere17 11 KV, XLPE Insulatd UG Cable 3C X 240 Sq. mm Aluminium cable (To be run from 11kV switchgear to take off DP structure) 150.00 Mtr
Ere18 Cable Terminationkits suitable for 240Sq. mm 3 Core Indoor 2.00 Nos
Ere19 Cable Terminationkits suitable for 240 Sq. mm 3 Core Outdoor 2.00 Nos
Ere20 Supplying and Grounding of Equipment with G.I.Flat 50x6mm and connecting Equipment to the earth mat/ground pit. Each point of earthing with all formation works like bending, twisting, drilling of ho... 300.00 Rmtr
Ere21 Providing C.I. Pipe of 100mm ID 13mm thick 2.75 mtr. long with 2 part GI Flat 50x6mm clamp welded allround the pipe etc., including cost of excavation (all materials supplied by contractor) 3.00 Set
Ere22 Supplying and fixing 450mm dia x 450mm height 1.5" to 2" Hume pipe collars for earth pits. 3.00 Nos
Ere23 Dismantling of 2*12.5 MVA, 66/11 KV, Transformer and parts like Radiator, Bushings, Draining of oil from transformer etc., as per the direction of site Engineer (33.5+31.9 MT) 65.40 MT
Ere24 Moving of Transformer from the plinth to the loading point as per direction of site Engineer.
65.4Mtx50mtrs x 1no.=3270 3270.00 Mtr
Ere25 Releasing of 400-800/1-1A NCT And CTS 5.00 Nos
Civ01 Earth work excavation by manual means for drains, canals, waste weir, draft, approach channels, key trenches, foundation of Buildings & bridges and such simillar works in all kinds of soils, as per dr... 37.22 Cum
Civ02 Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes... 3.10 Cum
Civ03 Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with supe... 36.27 Cum
Civ04 Steel Fabrication: Supplying, fitting and placing TMT FE 550 / 550D Steel Reinforcement including cost of all materials, machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/w... 300.00 Kg
Civ05 Structural Steel Fabrication:Providing and fixing Structural Steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and app... 400.00 Kg
Civ06 Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by r... 6.92 Cum
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
Work on Hand details format.doc
Others - others • 0.06 MB
Volume II A B.zip
Others - others • 20.14 MB
Tender document Bettadpura.pdf
Tender Document • 2.00 MB
NIT-Mys Tz-Bettadpura 2x20MVA.pdf
Instructions to Tenderers • 0.52 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .