| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.7 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹13.1 L+₹1.3 L (11.5%)Rejected-Finance | L2 | Rejected-Finance L2 | |
| 3 | L3₹13.9 L+₹2.2 L (18.6%)Rejected-Finance | L3 | Rejected-Finance L3 | |
| 4 | Not Admitted-Finance | - | Not Admitted-Finance Others-Non submission of Documents as per NIT and manual of conracts |
Tender Value
₹14.4 L
EMD Value
₹28,800
Closing Date
30 Apr 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GARRISON ENGINEER NAVY LKD
GE (Navy) Lakshadweep C/o NOIC (LAM) Navy Office Coast Guard Road Kavaratti Islands UT of Lakshadweep-682555
PROVISION OF FITMENT OF 415V AC 3PH 100A LT PANEL UNDER AGE E M MINICOY OF GE NAVY LAKSHADWEEP
2022_MES_516378_1
8328/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GARRISON ENGINEER NAVY LAKSHADWEEP
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
Yes
GARRISON ENGINEER NAVY LAKSHADWEEP
₹28,800
Yes
14 Jun 2022
4 Apr 2022
2 May 2022
4 Apr 2022
30 Apr 2022
13 Apr 2022
4 Apr 2022 - 12 Apr 2022
60 days
Amount
Supply and Install, test and commission factory made outdoor type/Floor mounted thermoplastic polycarbonate cubical type feeder pillar box IP 65 protection suitable for 3 phase 4 wire 415 V, 50 Hz of size (1700x2050x700mm) with 400 Amps rated copper busbar, internal pre wired with suitable size copper cables and MS angle iron based frame painted with two coats of synthetic enamel paint over a coat of red oxide primer including PCC foundation to accmoomodate and comprising of following:- (i) On Load change over switch TPN 415V 250A 36kA-01 (incoming) (ii) MCCB TPN 415V 100A 36kA-04 & 63 Amps 25 KA -04 (outgoing ) (iii) Digital voltmeter 0-500 V 01 No (iv) Digital ammeter with Cts 250 amps- 01 No (v) Temper proof digital KWH energy meter 1 number with CTs- 3 Nos (vi) Indi cator lamp LED type 240V AC (RYB) - 01 set (vi) street light Timer with MCB , power contactor& relays for Auto on/off of street lights Note :- (a) The rate quoted by the tenderer is inclusive of taking down the existing steel. (b) LT feeder pillar box shall be manufactured by CRPI approved manufacturer and test certificate shall be produced by the contractor from the manufacturer. complete all as specified and as directed by Engineer-in-Charge.
Material and labour for Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised iron strip 25×4mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point or indicated including testing on completion complete all as specified and as directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sq mm 3½ core including all connection complete all as specified and as directed by Engineer-in-Charge.
Material and labour for sand cushioning with Sand in two layer,first layer of 80mm thick before laying of cable and second layer of 150mm thick after laying of cable in trenches/ducts for cable including consolidation of each layer complete all as specified.Note:Thickness of sand cusioning shall be measured after punning complete all as specified and as directed by Engineer-in-Charge.
Supply and laying unreinforced pre cast concrete cable cover class LV, Type I, flat, size 250 mm x 150mm x 40mm complete all as specified and as directed by Engineer-in-Charge.
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 depth and getting out soft/loose soil for laying cables/pipes/erection of poles etc. complete all as specified and as directed by Engineer-in-Charge.
Returning filling in, with excavated soils incl. spreading, levelling, watering and well ramming in layers n.exc. 25 Cms .complete all as specified and as directed by Engineer-in-Charge.
Removing excavated material/ surplus soil exceeding 250 M and n.exc. 500M and depositing where directed at a level n.exc. 1.50M above the starting point, complete all as specified and as directed by Engineer-in-Charge.
M & L for PCC 1:3:6 type C-2 (40 mm graded aggregate) for foundation for poles and for keeping AC outdoor units complete all as directed
Material and labour for PCC 1:2:4 type B-1 (20 mm graded aggregate) for pole coping complete all as specified and as directed by Engineer-in-Charge.
Material and labour for Cutting the hard standing not less than 25 cm in deep and 45 cm in wide for laying of underground cable through GI pipe and making good the disturbed surfaces complete all as specified and as directed by Engineer-in-Charge.
PHEJAYS AGENCIES
R.K. Builders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .