Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.6 CrAccepted-AOC 1ST FLOOR KRISHNA TOWERS OPP TO THRIKKAKARA TEMPLE THRIKKAKARA P O COCHIN 682 021 | ERNAKULAM | KERALA | 682021 | ₹7.6 Cr | L1 | Accepted-AOC AS PER FINANCIAL EVALUATION |
| 2 | L2₹8.1 Cr+₹43.8 L (5.72%)Rejected-AOC 12 041 BHASKAR COMPLEX ASHOK NAGAR GAUTAM BUDDHA MARG LUCKNOW 226018 | LUCKNOW | LUCKNOW | UTTAR PRADESH | 226018 | ₹8.1 Cr+₹43.8 L (5.72%) | L2 | Rejected-AOC AS PER FINANCIAL EVALUATION |
| 3 | Rejected-Technical | - | - | Rejected-Technical AS PER TECHNICAL EVALUATION |
| 4 | Rejected-Technical | - | - | Rejected-Technical AS PER TECHNICAL EVALUATION |
| 5 | Rejected-Technical 1ST FLOOR B 116 VIBHUTI KHAND GOMTI NAGAR LUCKNOW U P | LUCKNOW | LUCKNOW | UTTAR PRADESH | - | - | Rejected-Technical AS PER TECHNICAL EVALUATION |
Tender Value
₹8.8 Cr
EMD Value
₹17.6 L
Closing Date
21 May 2020, 3:00 pmClosed
ADDL PROJECT MANAGER ( E )
ELECTRICAL UNIT-3, PLOT NO-4, GOMTI NAGAR EXTENSION-7, SHAHEED PATH, LUCKNOW
CONSTRUCTION OF EMERGENCY MEDICINE CLINICAL AND WARD AREA AND UPLIFTING OF KIDNEY TRANSPLANT CENTRE IN THE PREMISES OF SGPGI RAIBARAILY ROAD LUCKNOW SUB HEAD STATION EQIPMENT AND ALLIED WORKS
2020_UPRNN_449698_1
200/APM ( E )/EU-3/RNN/TENDER/2020 DT. 16-03-2020
Open Tender
Electrical Works
Item Rate
120 days
LUCKNOW
AS PER TENDER DOCUMENT
2 documents required · 2 mandatory
₹11,800
UPRNN LTD
₹17.6 L
18 Dec 2020
17 Mar 2020
21 May 2020
17 Mar 2020
21 May 2020
17 Mar 2020
17 Mar 2020 - 31 Mar 2020
Amount
BOQ PART (A ) SUBHEAD- I: L.V. PANEL BOARD
MAIN LT Panel
Supply, erection, testing & commissioning of IP -42 cubicle type Panel fabricated (folded joints construction) out of 14 SWG CRCA sheet steel floor mounted totally enclosed extendable on both sides switchboard of uniform width with top cable entry and suitable for use on 415 V, 3 phase 4 wire 50 c/s having 65 KA fault capacity complete and housed with incomming and outgoing aluminium bus-bars,interconnection between feeders etc. and their accessories including supply and fixing of base channels of 100x50x6mm as required with provision for following incoming and outgoing switchgear with protection, metering etc. and terminals for scheduled cables and also compataible to PC/PLC/BMS with communiction port RS-485, complete as required and as per specification and schematic diagram complete as required. confirming IS 61439
Note-1) DESIGN, TESTING & CERTIFICATION OF LT MAIN PANEL's MUST COMPLY IEC-61439, ALONG WITH IEC-61641 FOR INTERNAL ARC FLASH
2) PROVISION OF BUSDUCT/CABLE MUST BE AS PER SLD.
The incoming of Transformer feeders & DG feeders as shown on drawing shall be connected through bus duct. The suitable adopter box shall be provided on top only and Solar Incommer through cable from bottom.
All Intelligent ACB shall have Micro processor based O/C, S/C & E/F release RS485 on board communication port. The release setting of all ACB's shall be possible from communication & also user can see the energy parameter of release from BMS/SCADA/Webpage and display module/HMI shall be provided on panel for each ACB to see the release data of ACB. All ACB's shall have Ics=Icu=Icw=65KA for 1Sec & should be supplied with Adopter Terminal Connections whose orientation can be changed on site.
All Intelligent MCCB shall have Micro processor based release with RS485 on board communication port, the release setting of all MCCB shall be possible from communication & user can see the release from BMS/SCADA/Webpage and a indication shall be provided on panel for each MCCB . All CTs and PTs shall be cast resin type. All MCCB shall have Ics = 100% Icu & should have Isolation Feature & Class II Front Face as standard.
All Intelligent ACB'S shall have spare wired contacts for ON,OFF,Trip,rackin,rackout spring charge status for BMS/SCADA communication along with LCD display.
All Intelligent MCCB shall be motorised with Microprocessor based release having spare wired contacts for monitoring ON/OFF and Trip shall be provided for SCADA communication. Control: ON & OFF.
TVM Shall have RS 485 Modbus RTU on board Communication protocol for SCADA communication.
All outgoing feeders shall have touch display module/HMI with RS-485 ports
Night mode and day mode for APFC CT in the transformer incomer.
The LT Panel manufacturer shall provide necessary,CT's Aux. contacts; multiply those contacts in the respective panels etc. to hook up in to PLC system
INCOMING
TRANSFORMER INCOMER [4 Nos.] shall be equipped as: (3000 KVA)
1 No. 5000 A, 65KA FP, draw out type electrically operated air circuit breaker with 230 V A.C. spring charged motor and micro processor based O/C, S/C & E/F releases, with communication port through RS-485 compatible with PLC/PC/BMS etc
1 No. 24 volt D.C.Shunt release
1 No. 230 volt A.C.closing coil
1 No. 415 volt A.C. under voltage release.
1 No. 5000 Amp. Ammeter (digital type) with inbuilt ASS
1 Set of CTs 5000 A/ 5A class-1 for metering
1 No.Volt Meter (digital type) with inbuilt VSS & control fuses.
1 No.P.F. meter (digital type)
1 No.KWH meter (digital type)
1 No. C.T.5000/3200/2500/1600/5 / 5A Class-1 for Capacitor panel.
Under Voltage relay 415 V A.C.
Over Voltage relay 415 V A.C.
O/C, S/C, and E/F relay
Breaker control switch
1 Set of phase indication lights R,Y,B.
1set of ON-OFF-TRIP ckt. Healthy. indication lights
Spring charged indication.
D.G. PANEL INCOMERS FROM DG BACKUP PANEL[2 Nos.]
1 No. 5000 A, 65KA FP, draw out type electrically operated air circuit breaker with 230 V A.C. spring charged motor and micro processor based O/C, S/C & E/F releases, with communication port through RS-485 compatible with PLC/PC/BMS etc
1 No. 24 volt D.C.Shunt release
1 No. 230 volt A.C.closing coil
1 No. 415 volt A.C. under voltage release.
1 Set of CTs 5000 A/ 5A class-1 for metering
Digital Tri-Vector meter with KVAR, KW, KWH, PF, Ampere, Volts, Frequency metering
Battery charger 230 V/ 24 V DC, 20 A with DC ammeter and DC voltmeter. Charger should have all basic protections like over load, over Voltage reverse polarity etc.
Under Voltage relay 415 V A.C.
Over Voltage relay 415 V A.C.
O/C, S/C, and E/F relay
Restricted Earth Fault relay
Three phase differential relay
Trip circuit supervision relay
Auxillary relay
Master trip relay
Breaker control switch
Automatic load supervision relay
1 Set of phase indication lights R,Y,B.
1set of ON-OFF-TRIP ckt. Healthy. indication lights
Spring charged indication.
SOLAR POWER PLANT INCOMERS [1 Nos.] shall be equipped as: (550 KWp)
1 No. 1250 A, 65KA FP, draw out type electrically operated air circuit breaker with 230 V A.C. spring charged motor and micro processor based O/C, S/C & E/F releases, with communication port through RS-485 compatible with PLC/PC/BMS etc
1 No. 24 volt D.C.Shunt release
1 No. 230 volt A.C.closing coil
1 No. 415 volt A.C. under voltage release.
1 Set of CTs 1250 A/ 5A class-1 for metering
Digital Tri-Vector meter with KVAR, KW, KWH, PF, Ampere, Volts, Frequency metering
Battery charger 230 V/ 24 V DC, 20 A with DC ammeter and DC voltmeter. Charger should have all basic protections like over load, over Voltage reverse polarity etc.
Under Voltage relay 415 V A.C.
Over Voltage relay 415 V A.C.
O/C, S/C, and E/F relay
Restricted Earth Fault relay
Three phase differential relay
Trip circuit supervision relay
Auxillary relay
Master trip relay
Breaker control switch
Automatic load supervision relay
1 Set of phase indication lights R,Y,B.
1set of ON-OFF-TRIP ckt. Healthy. indication lights
Spring charged indication.
BUS BARS:-
6300 Amps. 4P aluminium bus bars (65 KA)
BUS COUPLER:-
4 No. 6300A ,4POLE ,EDO ACB with 230 V A.C. spring charged motor.
4 sets Breaker Control switch
4 Sets of phase indication lights R,Y,B.
4 sets of ON-OFF-TRIP ckt. Healthy. indication lights
Interlocking: Transformer incomers ,DG Panel Incommers,Emengency & Normal HVAC Outgoing Feeders and bus couplers shall be electrically and mechanically interlocked so that no different source can be paralled at any point of time.
OUTGOINGS:-
5 Nos. 400 A FP MCCB , 65KA, with M.R.,O/C, S/C & E/F releases & indicating lamps (R.Y.B. Phase indication with ON/OFF & Trip Indication) & Multifunction meter with all functions with set of CTs etc. with communication port through RS-485 compatible with PLC/PC/BMS.
8 Nos.250 A FP MCCB , 65KA, with M.R.,O/C, S/C & E/F releases & indicating lamps (R.Y.B. Phase indication with ON/OFF & Trip Indication) & Multifunction meter with all functions with set of CTs etc. with communication port through RS-485 compatible with PLC/PC/BMS.
5 Nos.200 A FP MCCB , 65KA, with M.R.,O/C, S/C & E/F releases & indicating lamps (R.Y.B. Phase indication with ON/OFF & Trip Indication) & Multifunction meter with all functions with set of CTs etc. with communication port through RS-485 compatible with PLC/PC/BMS.
9 Nos.100 A FP MCCB , 65KA, with M.R.,O/C, S/C & E/F releases & indicating lamps (R.Y.B. Phase indication with ON/OFF & Trip Indication) & Multifunction meter with all functions with set of CTs etc. with communication port through RS-485 compatible with PLC/PC/BMS.
Supplying, installing, testing and commissioning of following capacity outdoor type IP-65, Sandwich Type Bus Trunking for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with metal clad enclosure made of 1.6mm thick steel sheet duly powder coated in convenient sections complete with outdoor 1.2 mm GI sheet canopy, 4 Nos aluminium bus bars, necessary joints, elbow & expansion joints and bends, fire barrier adopter box and copper flexible for joints,silver/tinned plated at connecting joints upon copper, earthing with 2 Nos aluminium strip of suitable size including, G.I. clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required (confirming IEC 61439 Part-6)
Design, supply, installation & testing of GI support structure suitable for 5000/2500/2000 Amp Sandwich type busduct, consisting GI steel pole with of 4 / 6 meter as per site requirement having 80 to 100 micron plating.With ladder type construction suitable for 6 run of busduct.(Including crossing of road and height of structure for span must be 6 Mtr)
Design, supply, installation & testing of rain & weather proof 1.6 mm powder coated GI Canopy including G.I. Frame suitable for each run of Sandwich type busduct.
SUB HEAD -II
SUB-HEAD -II : L.V. CABLES
Supply, laying and testing of undernoted sizes of aluminium conductor XLPE insulated PVC sheathed & sleeved armoured and overall PVC sleeved 1.1 KV grade power distribution cables conforming to relevant IS code and as per specification in ground (in existing trenches) through pipe or on wall / racks cable trays including dressing and clamping the cable with MS zinc passivated clamps etc. as required.
3.5 x 400 sq.mm
3.5 x 300 sq.mm
3.5 x 240 sq.mm
3.5 x 185 sq.mm
3.5 x 150 sq.mm
3.5 x 120 sq.mm
3.5 x 95 sq.mm
3.5 x 70 sq.mm
3.5 x 50 sq.mm
3.5 x 35 sq.mm
3.5 x 25 sq.mm
4 x 16 sq.mm
4 x 10 sq.mm
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required.
100mm dia
250mm dia
Supply and making end termination with brass double compression gland including providing and crimping of aluminium solderless lugs / ferrules for XLPE armoured power aluminium conductor cable 1.1 KV grade of following sizes:-
3.5 x 400 sq.mm
3.5 x 300 sq.mm
3.5 x 240 sq.mm
3.5 x 185 sq.mm
3.5 x 150 sq.mm
3.5 x 120 sq.mm
3.5 x 95 sq.mm
3.5 x 70 sq.mm
3.5 x 50 sq.mm
3.5 x 35 sq.mm
3.5 x 25 sq.mm
4 x 16 sq.mm
4 x 10 sq.mm
4 x 6 sq.mm
Supply, laying and testing of under noted sizes of copper conductor XLPE insulated PVC sheathed & sleeved armoured and overall PVC sleeved 1.1 KV grade power distribution cables conforming to relevant IS code and as per specification in ground (in existing trenches) through pipe or on wall / racks cable trays including dressing and clamping the cable with MS zinc passivated clamps etc. as required.
4 x 6 sq.mm
4 x 4 sq.mm
4 x 2.5 sq.mm
Supply and making end termination with brass double compression gland including providing and crimping of copper solderless lugs / ferrules for XLPE armoured power copper conductor cable 1.1 KV grade of following sizes:-
4 x 6 sq.mm
4 x 4 sq.mm
4 x 2.5 sq.mm
Supplying, laying, connecting,terminating, testing & commissioning of under noted sizes of PVC insulated, PVC sheathed unarmoured and overall PVC sleeved 1.1 KV grade control cables in pipe, wall, racks, cable trays, including, dressing, clamping with M.S Zinc passivated clamps etc as required conforming to relevant IS code and technical specifications.
8C x 1.5 sq.mm
10C x 1.5 sq.mm
14C x 1.5 sq.mm
Supply and fixing of cable tray/steel work in position including clamps, frame work of flats, angle iron, channel with fabrication work including cutting, bending, welding, drilling bolting etc. as per design as required. One coat of primer and 2 coats of enamel paint of approved shade shall be provided.
Supply and fixing of perforated 2mm thick CRCA sheet steel power coated cable tray of following sizes complete with bend/tee joints, coupling plate & nuts bolts etc. including providing and fixing of M.S. painted hanger etc. as required.
300mm wide 62.5mm depth
450mm wide 62.5mm depth
600mm wide 75mm depth
900mm wide 75mm depth
Supplying and fixing ladder type prefabricated CRCA sheet steel Stove enameled cable tray complete with bend/tee joints, coupling plate and nut bolts washers etc. with side runner 20 x 100 x 2.5mm and centre rungs of size 15 x 30 x 2.5mm c/c 250mm. including providing and fixing of hangers etc. as required.
Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
SUB HEAD- III
SUB-HEAD -III: EARTHING
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
SUB HEAD -IV
SUB HEAD-IV: D.G. SETS
Design, supply at site, installation, testing & commissioning of 3-phase, 415 volt, 1500 RPM, 50 HZ, Diesel generator set with prime rating capacity of 1250 KVA at 0.8 pf lagging diesel engine alternator set mounted on common base frame in outdoor type acoustic enclosure , day tank, with PCC Panel,Adopter box with AL extended bus bar, battery, batter charger, return fuel cooler, anti vibration mounting pads including residential silencer, engine alternator, pcc based auto start & synchronization set, safeties with accessories as per specification complete as required. Diesel engine shall conform to IS:10000 and alternator shall be self excited complete with AVR to IS:4722.Genset should be capable to take an average loading of minimum 85%. net output shall be designed @ 50 degree ambient .Synchronisation should be based on No Master Logic for system reliability . Any genset reaching rated RPM should automatically become master .AVR should be digital type AVR to provide fast response with respect to change in load , it should provide digital governing with digital isochronous synchronisation. To improve the reliability of the System , the synchronizing module should be part of Engine Controller . No external controller should be used for synchronising and shall not be accepted.Genset controller should have Weak Battery Monitoring system . The control system should test the battery each time the genset is signalled to start and indicate a warning if the battery is weak
EXHAUST SYSTEM
Supply amd installation of exhaust piping of following sizes MS B Class exhaust pipes conforming to IS:3589 with welding joint including bends, clamps, dash fastener, flanges ,nuts, boltsetc. complete as required and as per specifications detailed below. (Make - Jindal/Surya/Tata)
Control Cables
Supplying, Laying, terminating, testing, commissioning of following sizes of Copper Conductor PVC insulated, PVC sheathed armoured cable 1100 V grade. On surface the cable run shall be fixed on G.I. clamps etc of suitable size or as directed by the E-I-C complete in all respects. Supply and providing cable identification markers. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. as per specifications complete with end termination as required.
24 C x 2.5 Sqmm
4 C X 2.5 Sqmm
2 C X 2.5 Sqmm
2 C X 4.0 Sqmm
Supplying, Laying, terminating, testing, commissioning of following sizes of Copper Conductor PVC insulated shielded , PVC sheathed armoured cable 1100 V grade. On surface the cable run shall be fixed on G.I. clamps etc of suitable size or as directed by the E-I-C complete in all respects. Supply and providing cable identification markers. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. as per specifications complete as required.
8 C X 0.75 Sqmm
SUB HEAD -V
SUB HEAD-V: SUB-STATION EQUIPMENTS
TRANSFORMER
Supply , Installation, testing & commissioning of 3000/3150 KVA copper wound 11/0.433 KV, 50 C/S, Delta star connected oil immersed outdoor type transformer with ON load circuit tap changer unit range with RTCC, minus 15% to plus 5% on HT side in steps of 2.5% complete with first filling of oil along with complete accessories as per specifications including supply & fixing of MS channel of size 100x50x6 mm, drying/ filtration of oil etc as required. (Confirming IS 2026 )
11 KV 1250 AMP,350MVA HT RMU
HT PANEL BOARD
Supply Installation testing and commissioning of extendable type HT panel board suitable for indoor installation for use on 11 KV 50 C/S earthed system having a symmetrical breaking capacity of 350MVA for 1 Sec. at 11 KV comprising triple pole VCB. Panel shall be equipped with following accessories as per specifications and schematic drawing.
Panel shall be comprising of:
A. Incomming Panel 2 Nos. each shall be comprising of:
1- Metal Clad housing with track having 1250A TP integral VCB with Electric operated draw out type mechanism (spring charged motor - 230 VAC).
1- Set of air insulated copper bus bar & chamber.
1- Set of isolating plug and receptacle.
1- Set of Automatic safety shutter.
1- Set of breaker control switch (TNC)
2- Sets of CT's
CT- I -800/400/5A class 5P-10(15 VA)
CT- II –800/400//5A class -1(15 VA)
3 - Nos. PT's 11KV /Rt.3 /110V/Rt 3 of (100 VA) cast resin type.
1 - H.T. Cable box for 3C x 300 sq.mm aluminium conductor XLPE cable (11 KV earthed system).
1 - No. Tripping coil & closing Coil 24V DC/110V A.C.
1 - Set of ON/OFF/Trip & circuit healthy and phase indicating lights.
1- 3 element O/C, EF & SC relay (IDMTL & Hi - set) with required setting.
1- set Auxiliary relay.
1- Master trip relay
1-set Trip circuit supervision
1-Restricted Earth fault relay
B. Buscoupler Panel 1 No. shall be comprising of:
1- Metal Clad housing with track having 1250A TP integral VCB with Electric operated draw out type mechanism (spring charged motor - 230 VAC).
1- Set of breaker control switch (TNC)
1 - Set of ON/OFF/Trip & circuit healthy and phase indicating lights.
C. Outgoing Panel 4 Nos. each shall be comprising of:
1- Metal Clad housing with track having 630A TP integral VCB with Electric operated draw out type mechanism (spring charged motor - 230 VAC).
1- Set of air insulated copper bus bar & chamber.
1- Set of isolating plug and receptacle.
1- Set of Automatic safety shutter.
1- Set of breaker control switch (TNC)
2- Sets of CT's
CT- I -200/100/5A class 5P-10(15 VA)
CT- II - 200/100/5A class -1(15 VA)
1 - H.T. Cable box for 3C x 300 sq.mm aluminium conductor XLPE cable (11 KV earthed system).
1 - No. Tripping coil & closing Coil 24V DC/110V A.C.
1 - Set of ON/OFF/Trip & circuit healthy and phase indicating lights.
1- 3 element O/C, EF & SC relay (IDMTL & Hi - set) with required setting.
1- set Auxiliary relay.
1- Master trip relay
1-set Trip circuit supervision
1-Restricted Earth fault relay
Supply, erection, testing & commissioning of 230 V, single phase, 2 wire, A.C. to 24V D.C. 180 AH sealed maintenance free batteries with semiconductor/ IGBT (half wave rectifier) with auto-manual trickle boost facility battery charging units complete including 1 No. Distribution board having 63 Amps DP MCB incomer and 12 No. 16/ 20 Amps DP MCBs (D.C. duty) as outgoing complete as required as per technical specifications.
Supplying and fixing of non-skid rubber mat 25mm thick and 900mm width as required including cutting to required lengths of approved make with Test Certificates for H.T. 11 KV panels.
Supplying and fixing of non-skid rubber mat 16mm thick and 900mm width as required including cutting to required lengths of approved make with Test Certificates for L.T. panels.
Supplying and fixing of fire bucket painted red and duly filled with sand conforming to IS: 2546-1974.
Supplying and fixing of MS stand suitable for supporting two buckets (Pedestal type)
Supplying and fixing of MS stand suitable for supporting four buckets (Pedestal type)
Supplying and fixing of shock restoration chart written in English and Hindi duly framed in as required.
Supplying and fixing of carbon dioxide fire extinguisher type 4 kgs. Capacity of approved make with wall mounting bracket as required conforming to IS: 2878/1976 (Push type).
Supplying and fixing of first aid box as approved complete with standard kit as prescribed by Indian Red Cross.
Supply and fixing of H.T. Danger notice plate of 250x200mm made of mild steel at least 2mm thick and vitreous enameled white on both side with inscription in signal red colour on front side as required.
SUB HEAD -VI
SUB HEAD-VI : MV CABLES and Allied Works
Supplying, laying, of following sizes XLPE, 11 KV earthed cable in existing open structure/ Hume pipe/in trench including in vertical formation as per technical specification and complete as required. (The payments of cable length shall only be made upto gland in panel on both sides not for loop and connection cables of approximate length upto 2 metres either sides.)
3Cx300 Sq.mm.
Supply and Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 kV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required.
3Cx300 Sq.mm.
supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 kV grade as required.
3Cx300 Sq.mm.
Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 kV grade as required.
3Cx300 Sq.mm.
Supplying and making straight through cable jointing with heat shrinkable jointing kit complete with all accessories including ferrules suitable for following size of 3 core, XLPE aluminium conductor cable of 11 kV grade as required.
3Cx300 Sq.mm.
Providing and fixing UPVC pipes as per IS:13592 suitable for 6 Kg/ sq cm pressure, including all fittings with accessories i.e bends, junctions, cowls, offsets, PVC pipe clips/holders etc. and jointing with rubber rings and cement solvent complete as per manufacturer's specifications with excavation, refilling and disposal of surplus earth, including cutting holes in walls and floors ,wherever required and making good the same, complete as directed by the Engineer-in-Charge.
110 sq.mm outer dia
200 sq.mm outer dia
BOQ PART ( A ) STREET LIGHT
EXTERNAL LIGHTING
Supplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor mounted totally enclosed , extensible on both sides, switch board suitable for use on 415 Volts 3-phase, 4 wire, 50 Hz system having required fault capacity, housed with incoming and outgoing, Aluminium bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required. (Street lighting Panel)
INCOMER:-
1 Nos.100 Amps. TPN MCCB(25 KA) with electronic releases.
1 Set phase indication lights (R, Y, B)
1 No. Volt Meter (digital type) with inbuilt VSS & control fuses.
1 No. 0-200 Amp. Ammeter (digital type) with inbuilt ASS
BUS BARS:-
200 Amps. TP&N Aluminium bus bars (25 KA)
OUT GOINGS:-
10 Nos. 63A TPN, MCB (10KA).
6 Nos. 24 Hr Timer Switch
6 Nos. 63A TPN contactor
Supply and fixing of decorative 40 to 45 Watt LED Post top indirect light luminaire having Pressure die cast aluminium body and Clear glass with driver set confirming to IP 65 and above protection complete in all respect including connecting copper wiring.CAT-AAA
Supply and fixing of decorative 8 to 16 Watt LED bollard luminaire with driver set confirming to IP 65 protection complete in all respect including foundation and connecting copper wiring. CAT-AAA
Supply and fixing of LED Street light Fitting having die cast aluminium body and diffuser with driver set suitable for 140 to 150 Watt. Confirming to IP 66 Protection complete in all respects including connecting copper wiring (CAT- AAA)
Supply & fixing of 8mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 135 mm and base plate 12mm thik) having 3mm thikness with single arm bracket (1 Mtr length) on RCC foundation including the cost of foundation, foundation bolts, excavation & back filling and with inbuilt junction box with MCB,and wiring till fixture, sleeve in foundation,Required T&P completee in all respect.
Supply and fixing of factory wired integral LED flood light luminaires with die cast aluminium housing built with dirver set suitable for 70 to 90 Watt. Confirming to IP 65 protection complete in all respect including connecting copper wiring.CAT-AAA
Supply and burying of 40mm dia x 4.5 metres long G.I. Pipe vertically for earthing having 12mm dia. Holes spaced 75mm apart drilled up to 2 metre from the bottom complete with earthing lead of No. 6 to 8SWG GI wire in G.I. Pipe up to appron (and from appron to switch board the cost of G.I. wire and pipe will be extra) upto switch board, 30cm square C.I. box with hinged cover masonary enclosure, funnel at top, alternate layers of charcoal/coke and salt at least 150mm thick alround etc. as per directions of Engineer-in-charge complete in all respects as per drawing.
M/s Acme Pumps and Power Projects Limited
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .