Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹63.3 LAccepted-AOC 1202 SAI PROVISO DHNISHT PLOT NO 72 73 SECTOR 20 KOPARKHAIRANE NAVI MUMBAI | THANE | MAHARASHTRA | 400601 | L1 | Accepted-AOC AOC | |
| 2 | L2₹66.2 L+₹1.2 L (1.83%)Rejected-Finance | L2 | Rejected-Finance Other Than Being Lowest | |
| 3 | L3₹75.6 L+₹10.6 L (16.4%)Rejected-Finance ROOM NO 680 GANESH MURTY NAGAR PART NO 03 CAPT PRAKASH PETHE MARG COLABA MUMBAI 400 005 | MUMBAI | MAHARASHTRA | 400005 | L3 | Rejected-Finance Other Than Being Lowest | |
| 4 | L4₹79.4 L+₹14.4 L (22.2%)Rejected-Finance A 14 USHA SADAN NEAR POST OFFICE COLABA MUMBAI 05 | MUMBAI | MUMBAI | MAHARASHTRA | 400005 | L4 | Rejected-Finance Other Than Being Lowest | |
| 5 | L5₹85.6 L+₹20.6 L (31.7%)Rejected-Finance B 134 GANESH MURTHI NAGAR PART III COLABA MUMBAI 400 005 | MUMBAI | MAHARASHTRA | 400005 | L5 | Rejected-Finance Other Than Being Lowest |
| Sl No | Description | Qty | Unit | SHRI SAI ENTERPRISES L5 | NOEL ENGINEERS L2 | S S ENTERPRISES L4 | ASHOK ENTERPRISES L1 | Vandan Enterprises L6 | B P ENTERPRISES L3 |
|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m depth in hard/dense soil for laying of cable/ GI pipe and getting out complete all as specified and directed by Engineer_in_Charge. | 270 | Cum | 400 ₹1,08,000 | 150 ₹40,500 | 200 ₹54,000 | 145 ₹39,150 Lowest | 300 ₹81,000 | 245 ₹66,150 |
| 2.00 | Returning, filling in including spreading levelling watering well ramming in layers not exceeding 25cm each complete all as specified and directed by Engr in Charge. | 240 | Cum | 50 ₹12,000 | 20 ₹4,800 Lowest | 20 ₹4,800 Lowest | 40 ₹9,600 | 220 ₹52,800 | 175 ₹42,000 |
| 3.00 | Removing surplus soil to a distance outside MD land and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed by Engr in Charge. | 30 | Cum | 600 ₹18,000 | 25 ₹750 Lowest | 100 ₹3,000 | 45 ₹1,350 | 200 ₹6,000 | 245 ₹7,350 |
| 4.00 | Supply and replace a hot-dip galvanized, anti-corrosive, weatherproof octagonal windsock pole 6.0 m long complete with a 1500 mm arm/bracket, taper plug, base plate, bolts, nuts and screws; supply, install and grouting on PCC foundation as per the manufacturer’s foundation design; include removal and lawful disposal of the existing damaged pole, alignment, final leveling and finishing paint. Contractor to submit foundation drawing and lifting plan for Engineer’s approval prior to installation complete all as specified and directed by Engr in Charge. | 15 | Each | 15,000 ₹2,25,000 | 13,200 ₹1,98,000 | 16,000 ₹2,40,000 | 9,800 ₹1,47,000 Lowest | 95,000 ₹14,25,000 | 12,500 ₹1,87,500 |
| 5.00 | Supply and lay cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 70 Sqmm 3.5 core including taking down old faulty cable complete all as directed by Engineer-In-Charge. | 150 | RM | 350 ₹52,500 Lowest | 570 ₹85,500 | 400 ₹60,000 | 390 ₹58,500 | 1,750 ₹2,62,500 | 425 ₹63,750 |
| 6.00 | Supply and lay cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 50 Sqmm 3.5 core including taking down old faulty cable complete all as directed by Engineer-In-Charge. | 250 | RM | 300 ₹75,000 | 290 ₹72,500 Lowest | 400 ₹1,00,000 | 300 ₹75,000 | 1,300 ₹3,25,000 | 345 ₹86,250 |
| 7.00 | Supply and lay cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 35 Sqmm 3.5 core including taking down old unsv faulty cable complete all as directed by Engineer-In-Charge. | 250 | RM | 250 ₹62,500 | 265 ₹66,250 | 500 ₹1,25,000 | 225 ₹56,250 Lowest | 950 ₹2,37,500 | 265 ₹66,250 |
| 8.00 | Supply and lay cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 25 Sqmm 4 core including taking down old faulty cable complete all as directed by Engineer-In-Charge. core and all as directed by Engineer-In-Charge. | 250 | RM | 220 ₹55,000 | 235 ₹58,750 | 300 ₹75,000 | 155 ₹38,750 Lowest | 720 ₹1,80,000 | 240 ₹60,000 |
| 9.00 | Supply and lay cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 16 Sqmm 4 core including taking down old faulty cable complete all as directed by Engineer-In-Charge. | 450 | RM | 180 ₹81,000 | 160 ₹72,000 | 160 ₹72,000 | 150 ₹67,500 Lowest | 550 ₹2,47,500 | 185 ₹83,250 |
| 10.00 | Material and labour for repair, overhauling and servicing of existing LT electric panel by taking shutdown from the appropriate authority and carrying out the following works complete all as specified and directed by the Engineer-in-Charge:
(i) Thorough cleaning inside the panel including all incoming and outgoing feeders, MCCBs, SFUs, changeover switches, contactors and ACBs using a vacuum cleaner.
(ii) Checking of all loose connections in incoming and outgoing feeders and rectifying the same by replacing defective nuts, bolts and washers with new GI nuts, bolts and washers.
(iii) Replacement of burnt-out colour-coated PVC sleeves of main and feeder busbars with appropriate size of new PVC heat shrinkable sleeves – one job.
(iv) Replacement of burnt-out voltmeters, ammeters and indicating lamps as required (Note: new items shall be measured and paid separately under relevant supply items) – one job.
(v) Replacement of burnt-out control wiring of ammeters, voltmeters, indicating lamps and CTs with 2.5 / 1.5 sqmm single-core copper conductor cable of 1100V grade – one job.
(vi) Replacement of burnt-out busbars of incoming and outgoing feeders with appropriate size of new copper/aluminium busbar (Note: busbar shall be measured and paid separately) – one job.
(vii) Replacement of burnt-out insulators of incoming and outgoing feeders with appropriate size of new insulators – one job.
(viii) Spray painting of the complete panel board with one coat of synthetic enamel paint after surface preparation. | 12 | Each Job | 2,000 ₹24,000 | 500 ₹6,000 Lowest | 500 ₹6,000 Lowest | 3,000 ₹36,000 | 32,000 ₹3,84,000 | 1,350 ₹16,200 |
Tender Value
₹98.5 L
EMD Value
₹1.7 L
Closing Date
22 Dec 2025, 6:00 pmClosed
CWE (NW) Mumbai
CWE (NW) Mumbai
REPAIR REPLACEMENT OF ELECTRIC SUPPLY LT CABLE,PANELS,MCCBS,EARTHING AND ALLIED WORKS AT MARRIED AND OTM ACCOMMODATIONS UNDER GE (NW) NOFRA,MUMBAI
2025_MES_741340_1
8658/CWE(NW)Mumbai/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (NW) NOFRA
Class C
Category b(i)
7 documents required · 7 mandatory
₹1,000
GE (NW) NOFRA
₹1.7 L
Yes
26 Feb 2026
24 Nov 2025
24 Dec 2025
24 Nov 2025
22 Dec 2025
17 Dec 2025
24 Nov 2025 - 13 Dec 2025
Amount
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m depth in hard/dense soil for laying of cable/ GI pipe and getting out complete all as specified and directed by Engineer_in_Charge.
Returning, filling in including spreading levelling watering well ramming in layers not exceeding 25cm each complete all as specified and directed by Engr in Charge.
Removing surplus soil to a distance outside MD land and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed by Engr in Charge.
Supply and replace a hot-dip galvanized, anti-corrosive, weatherproof octagonal windsock pole 6.0 m long complete with a 1500 mm arm/bracket, taper plug, base plate, bolts, nuts and screws; supply, install and grouting on PCC foundation as per the manufacturer’s foundation design; include removal and lawful disposal of the existing damaged pole, alignment, final leveling and finishing paint. Contractor to submit foundation drawing and lifting plan for Engineer’s approval prior to installation complete all as specified and directed by Engr in Charge.
Supply and lay cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 70 Sqmm 3.5 core including taking down old faulty cable complete all as directed by Engineer-In-Charge.
Supply and lay cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 50 Sqmm 3.5 core including taking down old faulty cable complete all as directed by Engineer-In-Charge.
Supply and lay cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 35 Sqmm 3.5 core including taking down old unsv faulty cable complete all as directed by Engineer-In-Charge.
Supply and lay cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 25 Sqmm 4 core including taking down old faulty cable complete all as directed by Engineer-In-Charge. core and all as directed by Engineer-In-Charge.
Supply and lay cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 16 Sqmm 4 core including taking down old faulty cable complete all as directed by Engineer-In-Charge.
Material and labour for repair, overhauling and servicing of existing LT electric panel by taking shutdown from the appropriate authority and carrying out the following works complete all as specified and directed by the Engineer-in-Charge: (i) Thorough cleaning inside the panel including all incoming and outgoing feeders, MCCBs, SFUs, changeover switches, contactors and ACBs using a vacuum cleaner. (ii) Checking of all loose connections in incoming and outgoing feeders and rectifying the same by replacing defective nuts, bolts and washers with new GI nuts, bolts and washers. (iii) Replacement of burnt-out colour-coated PVC sleeves of main and feeder busbars with appropriate size of new PVC heat shrinkable sleeves – one job. (iv) Replacement of burnt-out voltmeters, ammeters and indicating lamps as required (Note: new items shall be measured and paid separately under relevant supply items) – one job. (v) Replacement of burnt-out control wiring of ammeters, voltmeters, indicating lamps and CTs with 2.5 / 1.5 sqmm single-core copper conductor cable of 1100V grade – one job. (vi) Replacement of burnt-out busbars of incoming and outgoing feeders with appropriate size of new copper/aluminium busbar (Note: busbar shall be measured and paid separately) – one job. (vii) Replacement of burnt-out insulators of incoming and outgoing feeders with appropriate size of new insulators – one job. (viii) Spray painting of the complete panel board with one coat of synthetic enamel paint after surface preparation.
Notes: (a) Spare parts such as busbars, meters, CTs, indicating lamps etc. will be measured and paid separately under relevant supply items (Item Nos. 12 to 15 of this schedule). (b) Rate quoted shall include labour, consumables, minor accessories, cleaning materials, tools and tackles, scaffolding, shutdown coordination and testing after completion.
Material & Labour for repairs/ Overhauling /Servicing to Existing LT electric panels/Feeder pillar/ meter panel/ star delta motor panel by taking shut down from appropiate authority including checking loose connections and tight connection and cleaning inside/out side all connection, replacing all cable glands,thimbles and lugs as per the size of existing cable, applying petrolium jelly on the contactors, providing new insulation tape to bus bars, repair to broken /hanging doors by fixing hinges or welding the door to make it servicable, spray painting (silver colour) / powder coating and testing the entire panel board after the completion of servicing up to the satisfication of Engr-in-charge all as directd and specified. Note :- The tenders quoted rate per unit shall deemed to be inclusive of taking out burnt Voltmeter/ Ampiermeter/CT/LED lamps of any type and discription etc and refixing the same, which shall be measured and paid as supply only vide relivent items of this schedule complete all as specified and directed. (i) Cleaning inside the panel and all incoming and out going feeders i.e including MCCB/SFU/Changeover switches/Contactors/ ACB's thorouly with help of Vaccum Cleaner. (ii) Checking the loose connections of incoming and out going feeders and rectifify the same with help of new GI nut bolts and washers (iii) Replacing the burnt out color coated PVC Sleeve of main and fedders bus bar with appropriated size of New PVC heat shrinkable sleeves -01Job
(iv) Replacing Burnt out Voltmeters/Ammeters/Indicating Lamps/.(Note: New items will be measured and paid separatly)-01Job (v) Replacing burnt out control wiring of Ammeter/Voltmeter/Indicating lamps and CT'swith 2.5/1.5Sqmm copper single core,1100V grade copper conductor cable- 01Job (vi) Replacing Burnt out Bus Bar of incomming and out going feededs with approprieted size of new bus bar (Copper/Aluminum) -01Job( Note : Bus Bar will measured and paid separately). (vi) Replacing Burnt out Insulators of incomming and out going feeders with approprieted size of new Insulators -01Job (vii) Spray Painting of Panel Board with one coat of synthetic enamel paint. Note : Spare part wiil be measured and paid seprately as supply only vide relivent item No 12 to 15 of this schedule.
Supply only indicating lamp holders complete with LED bulbs of colours red, yellow, blue and green for indicating incoming supply, suitable for 24 V DC / 110 V AC / 230 V AC, complete all as specified and directed by the Engineer-in-Charge.
Dismantling Air Circuit Breaker (ACB), 3-pole or 4-pole, rating 630 A to 1250 A, 415 V, draw-out or fixed type, from its installed location and carrying out complete repair/overhauling of spring drive mechanism, operating coil, auxiliary switch including setting of overload coil, no-volt coil and tripping coil; applying multi-purpose grease for mechanical parts; cleaning and inspecting male and female contacts and applying dry graphite conductive sealant on contacts; checking of electrical wiring system; reassembling of all dismantled parts; testing and commissioning after repairs, complete all as specified and directed by the Engineer-in-Charge. Note: Spare parts such as coils, CTs, contacts, etc. shall be measured and paid separately as “Supply Only” items under relevant BOQ items 17.00 to 26.00 below.
Supply only spring charging handle suitable for up to 1250 A ACB, complete all as specified and directed by the Engineer-in-Charge. Make: L&T / C&S / Legrand / GE / ABB / Havells
Supply only current transformers suitable for air circuit breakers of rating 630 A, matching the existing system, complete all as specified and directed by the Engineer-in-Charge. Make: L&T / C&S / Legrand / GE / ABB / Havells
Supply only current transformers suitable for air circuit breakers of rating 800 A, matching the existing system, complete all as specified and directed by the Engineer-in-Charge. Make: L&T / C&S / Legrand / GE / ABB / Havells
Supply only current transformers suitable for air circuit breakers of rating 1250 A, matching the existing system, complete all as specified and directed by the Engineer-in-Charge. Make: L&T / C&S / Legrand / GE / ABB / Havells
Supply only auxiliary contact block suitable for air circuit breakers of rating 630 A to 1250 A, compatible with existing panel arrangement, complete all as specified and directed by the Engineer-in-Charge. Make: L&T / C&S / Legrand / GE / ABB / Havells
Supply only arcing contacts (fixed and moving type) suitable for air circuit breakers of rating 630 A to 1250 A, complete all as specified and directed by the Engineer-in-Charge. Make: L&T / C&S / Legrand / GE / ABB / Havells
Supply only arc chutes (for 415 V) suitable for air circuit breakers of rating 630 A to 1250 A, complete all as specified and directed by the Engineer-in-Charge. Make: L&T / C&S / Legrand / GE / ABB / Havells
Supply only shunt release unit, rated 110/220 V DC or 240/415 V AC, suitable for air circuit breakers of rating 630 A to 1250 A, complete all as specified and directed by the Engineer-in-Charge. Make: L&T / C&S / Legrand / GE / ABB / Havells
Supply only cluster contact suitable for air circuit breakers of rating 630 A to 1250 A, complete all as specified and directed by the Engineer-in-Charge. Make: L&T / C&S / Legrand / GE / ABB / Havells
Supply only trip coil suitable for air circuit breakers of rating 630 A to 1250 A, complete all as specified and directed by the Engineer-in-Charge. Make: L&T / C&S / Legrand / GE / ABB / Havells
Material and Labour for Attending Faults/Trippings and rectifieng /repairing the faults in LT Panels Boards/Capacitor Panels Boads/ MCCB's/ACB's /Change Over switches/Cable Connections/Bus Bar etc including PVC insulating Tapes/Nut bolts and all as specified and directed by Engineer-In-Charge. Note : Note : (i) Spare parts will be measured and paid separately (ii) Fault rectfication and restore the supply withing 4hrs otherwise penality liable Rs 500 per hour till supply shall be restored.
Material and labour for fault finding on LT cables of any size and any length using fault detection machine by thumping method and suitable high-voltage testing method, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix heat-shrinkable type STRAIGHT-THROUGH joint for 1100 V grade XLPE insulated, armoured aluminium conductor cable of size 16 to 35 sqmm, complete with jointing material and accessories, including testing on completion, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix heat-shrinkable type straight-through joint for 1100 V grade XLPE insulated, armoured aluminium conductor cable of size 50 to 70 sqmm, complete with jointing material and accessories, including testing on completion, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix heat-shrinkable type straight-through joint for 1100 V grade XLPE insulated, armoured aluminium conductor cable of size 70 to 95 sqmm, complete with jointing material and accessories, including testing on completion, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix heat-shrinkable type straight-through joint for 1100 V grade XLPE insulated, armoured aluminium conductor cable of size 120 to 185 sqmm, complete with jointing material and accessories, including testing on completion, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix heat-shrinkable type straight-through joint for 1100 V grade XLPE insulated, armoured aluminium conductor cable of size 240 to 300 sqmm, complete with jointing material and accessories, including testing on completion, complete all as specified and directed by the Engineer-in-Charge.
Supply and lay XLPE insulated, screened, PVC bedded, galvanized steel strip/wire armoured heavy-duty aluminium conductor power cable, 1100 V grade, size 300 sqmm, 3.5 core, including taking down old unserviceable cable, laying in trench/pipe/tray, jointing, terminating and testing, complete all as specified and directed by the Engineer-in-Charge.
Supply and lay XLPE insulated, screened, PVC bedded, galvanized steel strip/wire armoured heavy-duty aluminium conductor power cable, 1100 V grade, size 185 sqmm, 3.5 core, including taking down old unserviceable cable, laying, terminating and testing, complete all as specified and directed by the Engineer-in-Charge.
Supply and lay cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty)1100 Volts grade with stranded aluminium conductor of size 150Sqmm 3.5 core including taking down old faulty cable complete all as directed by Engineer-In-Charge.
Supply and lay XLPE insulated, screened, PVC bedded, galvanized steel strip/wire armoured heavy-duty aluminium conductor power cable, 1100 V grade, size 120 sqmm, 3.5 core, including dismantling old unserviceable cable, laying, terminating and testing, complete all as specified and directed by the Engineer-in-Charge.
Supply and lay XLPE insulated, screened, PVC bedded, galvanized steel strip/wire armoured heavy-duty aluminium conductor power cable, 1100 V grade, size 95 sqmm, 3.5 core, including dismantling old faulty cable, laying, terminating and testing, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for providing in repair a maintenance-free, environment-friendly earthing electrode set comprising 17.2 mm dia, 3.0 m long low-carbon steel rod molecularly copper-bonded to 250 microns thickness, complete with highly conductive ANSI/NSF STD-60 certified carbon backfill compound (each bag 50 lbs) setting like concrete, conforming to BS 7430 & IEEE 80, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in replacement a battery of 12 volts, 150/180 AH capacity, suitable for DG set starting, including testing and commissioning complete all as specified and directed by the Engineer-in-Charge.
Cutting of metal road/hard standing for laying of cables and reinstating the same by rematalling/making good the surface to match the existing finish, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in repair GI tubing, light grade, 100 mm dia, with all fittings, laid in trenches or fixed on wall/ceiling, including dismantling of old unserviceable pipe, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in repair GI tubing, light grade, 50 mm dia, with all fittings, laid in trenches or fixed on wall/ceiling, including dismantling of old unserviceable pipe, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for providing high-density polyethylene (HDPE) pipe, pressure rating 4 kg/cm², 90 mm dia, for road crossing of cable or for cable protection above ground surface, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for providing high-density polyethylene (HDPE) pipe, pressure rating 4 kg/cm², 63 mm dia, for road crossing of cable or for cable protection above ground surface, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for providing high-density polyethylene (HDPE) pipe, pressure rating 4 kg/cm², 40 mm dia, for road crossing of cable or for cable protection above ground surface, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix electrical insulating mat conforming to IS 15652:2006 Class B, minimum thickness 2.5 mm, maximum leakage current 10 mA, flame-retardant and low-temperature resistant, suitable for use in power houses, including pasting with adhesive resin, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for providing chequered plate as per site requirement, including cutting to required shape, preparation of surfaces and applying two coats of synthetic enamel paint over a coat of red oxide primer, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for fabrication of angle iron work of required size as per site requirement, applying two coats of synthetic enamel paint over a coat of red oxide primer, complete all as specified and directed by the Engineer-in-Charge.
Taking down old unserviceable ACB of any type and supplying, installing, testing and commissioning new LT ACB, 630 A, 4-pole, manual draw-out, microprocessor-based, 415 V, 50 Hz, suitable for existing location, including replacement of burnt aluminium bus bar with new aluminium bus bar with connected nuts, bolts and lugs, complete all as specified and directed by the Engineer-in-Charge.
Supplying, installing, testing and commissioning in repairs new LT ACB, 800 A, 4-pole, manual draw-out, microprocessor-based, 415 V, 50 Hz, suitable for existing location, including replacement of burnt aluminium bus bar with new aluminium bus bar with connected nuts, bolts and lugs, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in repair MCCB, 4-pole, 400 A, 415 V, 50 Hz, with breaking capacity not less than 36 kA, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in repair MCCB, 4-pole, 320 A, 415 V, 50 Hz, with breaking capacity not less than 36 kA, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in repair MCCB, 4-pole, 250 A, 415 V, 50 Hz, with breaking capacity not less than 36 kA, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in repair MCCB, 4-pole, 160 A, 415 V, 50 Hz, with breaking capacity not less than 36 kA, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in repair MCCB, 4-pole, 100 A, 415 V, 50 Hz, with breaking capacity not less than 25 kA, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in repair MCCB, 4-pole, 63 A, 415 V, 50 Hz, with breaking capacity not less than 25 kA, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in repair MCCB, 3-pole, 400 A, 415 V, 50 Hz, with breaking capacity not less than 36 kA, complete all as specified and directed by the Engineer-in-Charge
Supply and fix in repair MCCB, 3-pole, 320 A, 415 V, 50 Hz, with breaking capacity not less than 36 kA, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in repair MCCB, 3-pole, 250 A, 415 V, 50 Hz, with breaking capacity not less than 36 kA, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in repair MCCB, 3-pole, 160 A, 415 V, 50 Hz, with breaking capacity not less than 36 kA, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in repair MCCB, 3-pole, 100 A, 415 V, 50 Hz, with breaking capacity not less than 25 kA, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in repair MCCB, 3-pole, 63 A, 415 V, 50 Hz, with breaking capacity not less than 25 kA, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in replacement changeover switch, ON LOAD type, 415 V, 50 Hz, AC, 4-pole, in sheet steel enclosure, capacity 400 A rated current, manually operated, confirming to IS:13947 or latest edition, with high thermal and dynamic strength to withstand short circuit current level of 80 kA RMS, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in replacement changeover switch, ON LOAD type, 415 V, 50 Hz, AC, 4-pole, in sheet steel enclosure, capacity 315 A rated current, manually operated, confirming to IS:13947 or latest edition, with high thermal and dynamic strength to withstand short circuit current level of 80 kA RMS, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in repair MCCB, 3-pole, 630 A, 415 V, 50 Hz, with breaking capacity not less than 36 kA, complete all as specified and directed by the Engineer-in-Charge.
Taking down unserviceable system and supply and fix CPT Cirprotec CPT-L ESE lightning rod with stainless steel body, type advanced lightning protection system in compliance with standard NFC 17-102 and UNE 21186-96, working on the principle of Early Streamer Emission technology, providing Level-1 protection for up to 30 m radius when mounted on RCC concrete base on building at a height of 4.5 m from the place to be protected, complete all as specified and directed by the Engineer-in-Charge.
Taking down unserviceable mounting structure and supply and fix new mounting structure of 4.5 m height with base plate suitable for roof mounting on RCC concrete base, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for excavation of existing earthing, including removal of old earthing plates, strips and earthing material, and refilling with replacement coal, salt, earthing plates/strips, nut bolts, GI pipe etc., after checking serviceability, and reinstating as required, complete all as specified and directed by the Engineer-in-Charge. Note: Cost of coal, salt, earth plate and pit cover will be paid separately.
Material and labour for replacement of existing earthing plate with new plate of size 600 × 600 × 60 mm including connection with existing earth strip, funnel, nut bolts and all accessories, for improved earthing resistance, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for replacement/refilling of earthing materials such as coal and salt in sufficient quantity in existing earthing pits to improve earth resistance, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for providing PCC chamber for earthing in 1:3:6 mix, type C-1, 40 mm thick, including necessary formwork, finishing and curing, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for providing cast iron pit cover with two nos. lifting handles of suitable size for earthing pit, including finishing and fixing, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for replacement/provision of earth continuity conductor or main earthing strip of size 32 × 6 mm, fixed to wall on batten, recessed in chases, buried in ground, drawn through pipe/conduit or fixed on pole, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for replacement/provision of earth continuity conductor or main earthing strip of size 25 × 4 mm, fixed to wall on batten, recessed in chases, buried in ground, drawn through pipe/conduit or fixed on pole, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in repair test point terminal block made of gunmetal or phosphor bronze of suitable size, screwed and complete with earth test point arrangement, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in repairs new sealed maintenance-free (SMF) battery of 12/18 V, 42 AH, with battery links, capable of 30 minutes backup, including testing and commissioning, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix plug and socket enclosure with MCB, double pole, 20 A, 240 V, complete with metal clad socket, suitable for industrial duty, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix triple pole and earth plug and socket enclosure, complete with 3-pin and earth plug, socket and triple pole MCB 32 A, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix triple pole and earth plug and socket enclosure, complete with 3-pin and earth plug, socket and triple pole MCB 63 A, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in repairs new copper conductor cable of size 1 × 50 sqmm with 0.5 mm thick PVC sheath, including laying, fixing, connection and testing, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for supply and laying XLPE insulated, armoured heavy duty copper conductor power cable of size 35 sqmm, 4 core, 1100 V grade, laid in trenches/walls with suitable clamps, including testing on completion, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in replacement steel tubular swaged street light pole, 8.5 m long, type 410 SP-31, complete with 1.2 m long pole arms, cast iron base plate, finial taper plug, bolts, nuts and screws, painted with two coats of aluminium paint over one coat of primer on exposed surfaces, including dismantling of old rusted pole, complete all as specified and directed by the Engineer-in-Charge. Note: Excavation and PCC foundation shall be measured and paid separately.
Material and labour for providing cement concrete (1:3:6) type C-2 using 40 mm graded crushed stone aggregate in foundations and mass concrete, including formwork, compaction and curing, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for providing cement concrete (1:2:4) type B-1 using 20 mm graded crushed stone aggregate for coping, blocks, bed plates, kerbs, weathered finishes, slightly rounded/chamfered angles and throating, including necessary formwork, finishing and curing, complete all as specified and directed by the Engineer-in-Charge.
Cutting and removing grass, vegetation and bushes inside or outside water supply/electric supply installations and removing all rubbish to a distance not exceeding 50 m, including brooming and cleaning in water/electric supply stations, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in replacement hot-dip galvanized, anti-corrosive, weatherproof octagonal windsock pole of 7 m length with 1500 mm long arm bracket, taper plug, base plate, bolts, nuts and screws, including PCC foundation as per manufacturer’s design, erection, grouting and dismantling of old pole, complete all as specified and directed by the Engineer-in-Charge.
Supply only power contactor, 4-pole, 50 A, with 2NO + 2NC, suitable for 25 KVA DG set existing AMF panel, complete all as specified and directed by the Engineer-in-Charge.
Supply only power contactor, 4-pole, 80 A, with 2NO + 2NC, suitable for 62.5 KVA DG set in existing AMF panel, complete all as specified and directed by the Engineer-in-Charge.
Supply only power contactor, 4-pole, 100 A, with 2NO + 2NC, suitable for 82.5 KVA DG set in existing AMF panel, complete all as specified and directed by the Engineer-in-Charge.
Supply only power contactor, 4-pole, 130 A, with 2NO + 2NC, suitable for 100/110 KVA DG set in existing AMF panel, complete all as specified and directed by the Engineer-in-Charge.
Supply only power contactor, 4-pole, 160 A, with 2NO + 2NC, suitable for 125 KVA DG set in existing AMF panel, complete all as specified and directed by the Engineer-in-Charge.
Supply only ON-delay timer suitable for existing AMF panel, complete all as specified and directed by the Engineer-in-Charge.
Supply only AMF relay suitable for DG sets of capacity 25 KVA to 62.5 KVA in existing AMF panel, complete all as specified and directed by the Engineer-in-Charge.
Supply only AMF relay suitable for DG sets of capacity 82.5 KVA to 125 KVA in existing AMF panel, complete all as specified and directed by the Engineer-in-Charge.
Supply only auxiliary contactor with 4NO + 4NC contacts suitable for existing AMF panel, complete all as specified and directed by the Engineer-in-Charge. Make: L&T / Havells / C&S
Supply only PLA relay, 3 C/O, 240 V AC, complete with socket, suitable for existing AMF panel, complete all as specified and directed by the Engineer-in-Charge. Make: L&T / C&S / Schneider or equivalent
Supply only under-voltage relay suitable for existing AMF panel, complete all as specified and directed by the Engineer-in-Charge. Make: L&T / C&S / Schneider / Sycon or equivalent
Supply only LED indicating lamps in colours red, green, yellow and blue, suitable for 24 V / 230 V AC / DC, for use in existing AMF panel under under-voltage relay indication, complete all as specified and directed by the Engineer-in-Charge. Make: L&T / C&S / Schneider / Sycon / Teknic or equivalent
Material and labour for attending faults/trippings and rectifying/repairing the same in DG sets, AMF panels, MCCBs and associated systems including replacement of PVC insulating tapes, nut bolts and connections, complete all as specified and directed by the Engineer-in-Charge. Note: (i) Spare parts will be measured and paid separately. (ii) Fault rectification and restoration of supply shall be carried out within 4 hours; otherwise, penalty of ₹500 per hour will be levied till supply is restored.
Material and labour for complete servicing of DG set of 125 KVA capacity, including testing on completion for satisfactory performance at full connected load for 2 hours. The servicing shall include: (a) Draining diesel from tank into cleaned containers, removing sediments from tank bottom, filtering and refilling. (b) Draining engine oil from sump, cleaning sump thoroughly and refilling with new engine oil. (c) Replacing fuel filter strainer, fuel pipes, fuel filters, engine oil filter, air cleaner element and oil seal assembly. (d) Checking coolant level and topping up if required. (e) Checking and topping up electrolyte/distilled water in starting batteries to maintain specific gravity, cleaning battery terminals and applying petroleum jelly to poles and connectors. (f) Checking/adjusting FIP, fuel injectors, governor and turbocharger for proper DG set functioning. (g) Replacing suitable size ‘V’ belts, hoses and clamps of air cleaner. (h) Tightening all fasteners of DG set to required torque and cleaning DG set with suitable cleaning agent. Complete all as specified and directed by the Engineer-in-Charge. Make: Greaves Ltd / Kirloskar / Ashok Leyland / Cummins / Eicher Note: Spare parts, engine oil and coolant shall be measured and paid separately under “Supply Only”.
Ditto all as per Item 104.00 above, but for DG set capacity 110 KVA, complete all as specified and directed by the Engineer-in-Charge.
Ditto all as per Item 104.00 above, but for DG set capacity 100 KVA, complete all as specified and directed by the Engineer-in-Charge.
Ditto all as per Item 104.00 above, but for DG set capacity 82.5 KVA, complete all as specified and directed by the Engineer-in-Charge.
Ditto all as per Item 104.00 above, but for DG set capacity 62.5 KVA, complete all as specified and directed by the Engineer-in-Charge.
Ditto all as per Item 104.00 above, but for DG set capacity 25 KVA, complete all as specified and directed by the Engineer-in-Charge.
Supply only spare parts for DG set of 125 KVA capacity, complete all as specified and directed by the Engineer-in-Charge. Make: Greaves Ltd / Kirloskar or equivalent make as approved by GE
Fuel filters set (primary and micro filter)
Fuel pipes set (Fuel pump to filter and filter to feed pump)
Lub. oil filter
Air Filter element
V- Belts
Oil Temparature sencer
Water Temparature sencer
Supply only spare parts for DG set of capacity 110KVA and all as specified and directed by Engineer-in-Charge. Make: Greaves Ltd & Kirolskar or equivalent make as approved by GE
Fuel filters set (primary and micro filter)
Fuel pipes set (Fuel pump to filter and filter to feed pump)
Lub. oil filter
Air Filter element
V- Belts
Oil Temparature sencer
Water Temparature sencer
Supply only spare parts for DG set of capacity 100KVA and all as specified and directed by Engineer-in-Charge. Make: Greaves Ltd & Kirolskar or equivalent make as approved by GE
Fuel filters set (primary and micro filter)
Fuel pipes set (Fuel pump to filter and filter to feed pump)
Lub. oil filter
Air Filter element
V- Belts
Oil Temparature sencer
Water Temparature sencer
Supply only spare parts for DG set of capacity 82.5KVA and all as specified and directed by Engineer-in-Charge. Make: Greaves Ltd & Kirolskar or equivalent make as approved by GE
Fuel filters set (primary and micro filter)
Fuel pipes set (Fuel pump to filter and filter to feed pump)
Lub. oil filter
Air Filter element
V- Belts
Oil Temparature sencer
Water Temparature sencer
Supply only spare parts for DG set of capacity 62.5KVA and all as specified and directed by Engineer-in-Charge. Make: Greaves Ltd & Kirolskar or equivalent make as approved by GE
Fuel filters set (primary and micro filter)
Fuel pipes set (Fuel pump to filter and filter to feed pump)
Lub. oil filter
Air Filter element
V- Belts
Oil Temparature sencer
Water Temparature sencer
Supply only spare parts for DG set of capacity 25KVA and all as specified and directed by Engineer-in-Charge. Make: Greaves Ltd & Kirolskar or equivalent make as approved by GE
Fuel filters set (primary and micro filter)
Fuel pipes set (Fuel pump to filter and filter to feed pump)
Lub. oil filter
Air Filter element
V- Belts
Oil Temparature sencer
Water Temparature sencer
Supply only engine oil of grade 20W40 for DG sets of capacity 25 KVA to 125 KVA, complete all as specified and directed by the Engineer-in-Charge. Make: Servo / Castrol / Kirloskar
Supply only coolant for DG sets of capacity 25 KVA to 125 KVA, complete all as specified and directed by the Engineer-in-Charge. Make: Servo / Castrol / Kirloskar
Supply only distilled water for DG sets of capacity 25 KVA to 125 KVA, complete all as specified and directed by the Engineer-in-Charge. Make: Servo / Castrol / Kirloskar
Supply only battery acid for DG sets of capacity 25 KVA to 125 KVA, complete all as specified and directed by the Engineer-in-Charge. Make: Servo / Castrol / Kirloskar
Material and labour for repair/overhauling of dynamo including replacement of carbon brushes, brush holder, springs, commutator/spring assembly, bearings, regulator and other accessories for DG sets of capacity 25 to 62.5 KVA, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for repair/overhauling of dynamo including replacement of carbon brushes, brush holder, springs, commutator/spring assembly, bearings, regulator and other accessories for DG sets of capacity 82.5 to 125 KVA, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in replacement battery charger, 24 V, suitable for 12 V 180 AH batteries, float-cum-boost type, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for dismantling, servicing and repairing radiator assembly of DG sets of capacity 25 KVA to 62.5 KVA, including flushing, testing for water-tightness, soldering leakage points, replacing loose radiator cap, rubber hoses and reconnecting, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for dismantling, servicing and repairing radiator assembly of DG sets of capacity 82.5 KVA to 125 KVA, including flushing, testing for water-tightness, soldering leakage points, replacing loose radiator cap, rubber hoses and reconnecting, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for servicing of alternator of DG sets of capacity 25 KVA to 62.5 KVA, including cleaning of field and armature windings, varnishing, baking, polishing of slip rings, checking excitation system and making corrections, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for servicing of alternator of DG sets of capacity 82.5 KVA to 125 KVA, including cleaning of field and armature windings, varnishing, baking, polishing of slip rings, checking excitation system and making corrections, complete all as specified and directed by the Engineer-in-Charge.
Supply and replacement of Automatic Voltage Regulator (AVR) for DG sets, complete all as specified and directed by the Engineer-in-Charge of the following DG sets.
For DG set 100 KVA to 125 KVA
For DG set 62.5 KVA to 82.5 KVA
For DG set 25 KVA
Material and labour for cleaning of fuel tank of DG sets of capacity 62.5 KVA to 125 KVA, decanting diesel, removing sediments, painting with one coat of approved synthetic enamel paint, marking fuel level gauge, tank capacity and numbering, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix fuel level indicating pipe, PVC, 10 mm dia, including fixing arrangements, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for servicing of self starter 12/24 V DC for DG sets, including dismantling, replacement of solenoid, field coils, bearings, cleaning commutator strips, replacing bendix pinion, reassembling, connecting and testing, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for calibration of fuel injector of DG sets of capacity 25 KVA to 62.5 KVA, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for calibration of fuel injector of DG sets of capacity 82.5 KVA to 125 KVA, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix exhaust silencer suitable for diesel engine of capacity 25 KVA to 62.5 KVA, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix exhaust silencer suitable for diesel engine of capacity 82.5 KVA to 125 KVA, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix self starter suitable for DG sets of capacity 25 KVA to 62.5 KVA, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix self starter suitable for DG sets of capacity 82.5 KVA to 125 KVA, complete all as specified and directed by the Engineer-in-Charge.
M & L for Preparation of old painted surfaces of DG sets of capacity 25 KVA to 62.5 KVA by removing dirt, dust, grease and oil, painting complete surface including connected accessories with one coat of synthetic enamel paint of approved colour, and writing identification numbers/capacity, complete all as specified and directed by the Engineer-in-Charge.
M & L for Preparation of old painted surfaces of DG sets of capacity 82.5 KVA to 125 KVA by removing dirt, dust, grease and oil, painting complete surface including connected accessories with one coat of synthetic enamel paint of approved colour, and writing identification numbers/capacity, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for top overhauling of DG engine of capacity 25 KVA to 62.5 KVA, including the following works, complete all as specified and directed by the Engineer-in-Charge: (a)Servicing of head – 06 Nos. (b)Replacement of ‘O’ rings, springs, nuts and bolts – 01 Set. (c)Replacement of inlet and outlet valve set including lapping – 04 Sets. (d)Replacement of guides – 08 Nos. (e)Servicing and calibration of fuel pump – 01 Job. (f)Servicing and calibration of injector (04 Nos.) by authorised dealer – 01 Job. (g)Replacement of cylinder head gasket set – 04 Sets. (h)Servicing of all pistons (04 Nos.) including replacement of all types of rings – 01 Job.
Material and labour for top overhauling of DG engine of capacity 82.5 KVA to 125 KVA, including the following works, complete all as specified and directed by the Engineer-in-Charge: (a)Servicing of head – 06 Nos. (b)Replacement of ‘O’ rings, springs, nuts and bolts – 01 Set. (c)Replacement of inlet and outlet valve set including lapping – 04 Sets. (d)Replacement of guides – 08 Nos. (e)Servicing and calibration of fuel pump – 01 Job. (f)Servicing and calibration of injector (04 Nos.) by authorised dealer – 01 Job. (g)Replacement of cylinder head gasket set – 04 Sets. (h)Servicing of all pistons (04 Nos.) including replacement of all types of rings – 01 Job.
Supply and replace PVC insulated battery lead of 25 sqmm size with copper conductor cable, 1.5 m length, complete with copper/brass clamps and lugs for fixing on battery terminals and self-starter, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in replacement unserviceable pre-lubrication hydraulic lift pump VIC for DG sets of capacity 25 KVA to 62.5 KVA, taking down old unserviceable pump, complete all as specified and directed by the Engineer-in-Charge
Supply and fix in replacement unserviceable pre-lubrication hydraulic lift pump VIC for DG sets of capacity 82.5 KVA to 125 KVA, taking down old unserviceable pump, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for taking down old unserviceable water body of DG set of capacity 25 KVA to 62.5 KVA, including unscrewing fan, fan belt, hose pipes, removing existing position, replacing with new water body as per sample, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for taking down old unserviceable water body of DG set of capacity 82.5 KVA to 125 KVA, including unscrewing fan, fan belt, hose pipes, removing existing position, replacing with new water body as per sample, complete all as specified and directed by the Engineer-in-Charge.
Securing hanging or loose electrical cables of DG set, refixing XLPE insulated, PVC bedded, galvanised steel strip or wire armoured power cables up to 6 Nos., size 6 sqmm 2-core to 185 sqmm 3.5-core, fixed properly on wall, pole or roof with plastic straps, cable zip ties, galvanised ‘U’ clamps, anchor fasteners or saddles, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix in replacement industrial high-bay integral LED luminaire of 120 W capacity, min 120 lm/watt,with all accessories, installed at any height in workshop/hangar including hanging/fixing arrangement with angle, rod bar or flat iron, including taking down old fitting, complete all as specified and directed by the Engineer-in-Charge.
Supply and fix LED flood light fitting, 250 W capacity, with high-performance luminaire, pressure die-cast housing, toughened glass, secondary lens optics, IP66 ingress protection and min efficiency ≥120 lm/W, including taking down old fitting, complete all as specified and directed by the Engineer-in-Charge.
Material and labour for repairing APFC panel of capacity 100 KVAR to 400 KVAR including dismantling, servicing, repair and replacement of power contactors, auxiliary contactors, fuses, wiring, meters, timers, relay, indicating lamps, and associated components. Work includes:
Dismantling old damaged capacitor bank and supply only capacitor bank, 5 KVAR, heavy-duty type, 415 V, 50 Hz AC, for existing panel, complete all as specified and directed by the Engineer-in-Charge. Make: Prabodhan / EPCOS / Havells / Schneider
Ditto all as per item 150.00 but of rating 10 KVAR, complete all as specified and directed by the Engineer-in-Charge.
Ditto all as per item 150.00 but of rating 15 KVAR, complete all as specified and directed by the Engineer-in-Charge.
Ditto all as per item 150.00 but of rating 20 KVAR, complete all as specified and directed by the Engineer-in-Charge.
Ditto all as per item 150.00 but of rating 25 KVAR, complete all as specified and directed by the Engineer-in-Charge.
Dismantling old damaged contactor and supply only capacitor duty contactor (type MOC), 50 A, 2NO + 2NC, suitable for 415 V, 50 Hz AC supply in existing panel, complete all as specified and directed by the Engineer-in-Charge. Make: L&T / C&S / Schneider
Ditto all as per item 155.00 but of rating 40 A, complete all as specified and directed by the Engineer-in-Charge.
Ditto all as per item 155.00 but of rating 32 A, complete all as specified and directed by the Engineer-in-Charge.
Dismantling old damaged MCB and supply and fix new MCB, 63 A, TP, C-curve, 415 V, 50 Hz, with mounting rail, in existing panel, complete all as specified and directed by the Engineer-in-Charge.
Ditto all as per item 158.00 but of rating 40 A, complete all as specified and directed by the Engineer-in-Charge.
Ditto all as per item 158.00 but of rating 32 A, complete all as specified and directed by the Engineer-in-Charge.
Ditto all as per item 158.00 but of rating 20 A, complete all as specified and directed by the Engineer-in-Charge.
Dismantling old damaged contactor and supply only auxiliary contactor, 10 A, capacitor duty, with 8NO + 8NC, suitable for 415 V, 50 Hz AC supply in existing panel, complete all as specified and directed by the Engineer-in-Charge. Make: L&T / C&S / Schneider / Havells
Dismantling old damaged timer and supply only new time delay timer suitable for APFC panel, 415 V, 50 Hz AC supply, for existing panel, complete all as specified and directed by the Engineer-in-Charge. Make: L&T / C&S / Schneider / Havells
Dismantling of Old Damaged CT and Supply only Current Transformers,415V 600/5Amps,15VA burden,accuracy class 1 for metering accuracy for in existing panel and all as specified and directed. Make : AE/NSDA/MECO/C&S
Dismantling old damaged CT and supply only current transformer, 415 V, 400/5 A, 15 VA burden, accuracy class 1, suitable for metering in existing panel, complete all as specified and directed by the Engineer
Dismantling old damaged CT and supply only current transformer, 415 V, 400/5 A, 15 VA burden, accuracy class 1, suitable for metering in existing panel, complete all as specified and directed by the Engineer
NOEL ENGINEERS (BID ID -3502532)
B P ENTERPRISES (BID ID -3504378)
S S ENTERPRISES (BID ID -3504355)
SHRI SAI ENTERPRISES (BID ID -3502160)
Vandan Enterprises (BID ID -3510706)
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.41 MB
8658.rar
Tender Documents • 3.33 MB
BOQ_830116.xls
BOQ • 3.97 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .