Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.2 LAccepted-Finance FLAT NO 101 2ND FLOOR RAGHAVENDRA RESIDENCY PLOT NO 1 2 3 SURVEY NO 27 PICKET SECUNDERABAD 500026 | HYDERABAD | TELANGANA | 500026 | ₹19.2 L | L1 | Accepted-Finance Valid documents received and accepted |
| 2 | L2₹21.1 L+₹1.9 L (10.0%)Accepted-Finance | ₹21.1 L+₹1.9 L (10.0%) | L2 | Accepted-Finance Valid documents received and accepted |
| 3 | L3₹22.8 L+₹3.7 L (19.1%)Accepted-Finance | ₹22.8 L+₹3.7 L (19.1%) | L3 | Accepted-Finance Valid documents received and accepted |
| 4 | L4₹27.5 L+₹8.3 L (43.4%)Accepted-Finance | ₹27.5 L+₹8.3 L (43.4%) | L4 | Accepted-Finance Valid documents received and accepted |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
2 Nov 2023, 6:00 pmClosed
Shri Sagar Maheshwari, IDSE
GE (AFA) Hyderabad PIN-500043
REPAIR/RENEWAL TO EXTERNAL ELECTRIFICATION WORKS IN TECHNICAL AREA AT AFA HYDERABAD
2023_MES_621793_1
8387/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (AFA) Hyderabad
As per tender pages
4 documents required · 4 mandatory
₹500
GE (AFA) Hyderabad
₹50,000
Yes
10 Nov 2023
5 Oct 2023
4 Nov 2023
5 Oct 2023
2 Nov 2023
19 Oct 2023
5 Oct 2023 - 18 Oct 2023
Amount
Excavation in trenches in any kind of soil n.exc 1.5 m wide and n. exc 1.5 m depth and getting out, including trimming the sides and forming bottom surface to required levels for laying cables complete all as specified and as directed. In soft/lose soil
M&L River dry sand cushioning to UG cables (8 cm deep before laying of cable and 15 cm deep over the cable) in trenches including punned thickness up to 18 cm and consolidation, complete all as directed. Note :- Punned thickness only will be considered for payment.
Returning, filling in trenches in any kind soil in layers n.exc. 25 cm after laying of cables including spreading, levelling, and well ramming complete all as specified and directed.
Re laying of old retreived bricks vide excavation in trenches of exisitng laid cables
Supply & lay common burnt, clay building bricks, sub class 'B' designation over the sand cushioning in cable trenched for protection of cables (LT) complete all as specified and as directed
Removing surplus excavated material (soil) to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and as directed
Taking down of old unserceable LT UG cables any type any size
Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 240 sqmm 3.5 core including dismantling and taking out the unserviceable cable all as directed.Make :- Havells/ Polycab / Finolex
Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 185 sqmm 3.5 core including dismantling and taking out the unserviceable cable all as directed.Make :- Havells/ Polycab / Finolex
Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 120 sqmm 3.5 core including dismantling and taking out the unserviceable cable all as directed.Make :- Havells/ Polycab / Finolex
Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 95 sqmm 3.5 core including dismantling and taking out the unserviceable cable all as directed.Make :- Havells/ Polycab / Finolex
Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 70 sqmm 3.5 core including dismantling and taking out the unserviceable cable all as directed.Make :- Havells/ Polycab / Finolex
Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 50 sqmm 3.5 core including dismantling and taking out the unserviceable cable all as directed.Make :- Havells/ Polycab / Finolex
Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 35 sqmm 3.5 core including dismantling and taking out the unserviceable cable all as directed.Make :- Havells/ Polycab / Finolex
Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 25 sqmm 3.5 core including dismantling and taking out the unserviceable cable all as directed.Make :- Havells/ Polycab / Finolex
Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 16 sqmm 4 coreincluding dismantling and taking out the unserviceable cable all as directed.Make :- Havells/ Polycab / Finolex
Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 10 sqmm 4 coreincluding dismantling and taking out the unserviceable cable all as directed.Make :- Havells/ Polycab / Finolex
Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 10 sqmm 2 core including dismantling and taking out the unserviceable cable all as directed.Make :- Havells/ Polycab / Finolex
Dismantaling /Removing of unserviceable joints kits any type any size
M&L straight through joints (heat shrinkable type) cable joint kit including jointing materials for making joints of UG electric cable 1100 volt grade heavy duty with PVC/XLPE insulated aluminium conductor nominal cross sectional area 16 to 35 sqmm 3.5/4.0 core and testing complete all as specefied and as directed.
M&L straight through joints (heat shrinkable type) cable joint kit including jointing materials for making joints of UG electric cable 1100 volt grade heavy duty with PVC/XLPE insulated aluminium conductor nominal cross sectional area 50 to70 sqmm 3.5/4.0 core and testing complete all as specefied and as directed.
M&L straight through joints (heat shrinkable type) cable joint kit including jointing materials for making joints of UG electric cable 1100 volt grade heavy duty with PVC/XLPE insulated aluminium conductor nominal cross sectional area 95 to 120 sq mm. 3.5 core and testing complete all as specefied and as directed.
M&L straight through joints (heat shrinkable type) cable joint kit including jointing materials for making joints of UG electric cable 1100 volt grade heavy duty with PVC/XLPE insulated aluminium conductor nominal cross sectional area 150 to 300 sq mm. 3.5 core and testing complete all as specefied and as directed.
M&L fault locating at LT UG Cable of size 3.5 core 50/95/120/150/185 Sqmm by removing the both ends of the cable and locating the fault with HIPOT (HIGH POTENTIAL) elect cable fault locater of TSSPDCL and arrange neccesary manpower for execavating the fault area and rectifying the fault with serviceable cable etc including earth work as per site requirement complete all as specified and directed by Engineer-in-Charge. Note:- Additional length of cable, if required (Maximum 5.0 RM) shall deemed to be included in the unit rate quoted but the cost of joints and labour for jointing will be measured and paid separately under respective items.
S & Laying Low Density Poly Ethylene (LDPE) flexible pipe of following dia and of pressure rating 6 Kg/cm² laid inside the P.C.C. coping of poles for easy bending and passing of cables all as specified and directed.
40 mm Dia
25 mm Dia
Supply and fix in repairs MCCB adjustable thermal & fixed magnetic release 4 pole 50 kA 630 A including dismantling and taking out the existing unserviceable MCCB , connecting up complete all as directed at site.
Supply and fix in repairs MCCB adjustable thermal & fixed magnetic release 4 pole 36 50 kA 400 A including dismantling and taking out the existing unserviceable MCCB , connecting up complete all as directed at site.
Supply and fix in repairs MCCB adjustable thermal & fixed magnetic release 4 pole 36 kA 250 A including dismantling and taking out the existing unserviceable MCCB , connecting up complete all as directed at site.
Supply and fix in repairs MCCB adjustable thermal & fixed magnetic release 4 pole 35 kA 200 A including dismantling and taking out the existing unserviceable MCCB , connecting up complete all as directed at site.
Supply and fix in repairs MCCB adjustable thermal & fixed magnetic release 4 pole 16 kA 160 A including dismantling and taking out the existing unserviceable MCCB , connecting up complete all as directed at site.
Supply and fix in repairs MCCB adjustable thermal & fixed magnetic release 4 pole 16 kA 100 A including dismantling and taking out the existing unserviceable MCCB , connecting up complete all as directed at site.
Supply and fix in repairs MCCB adjustable thermal & fixed magnetic release TP 16 Ka 25 Amp to 100 A including dismantling and taking out the existing unserviceable MCCB , connecting up complete all as directed at site.
Supply and fix in repairs MCCB adjustable thermal & fixed magnetic release TP 16 kA 125 A including dismantling and taking out the existing unserviceable MCCB , connecting up complete all as directed at site.
M&L for cutting of road / hard standing upto 0.3m in depth and 0.45m wide for laying of cable protection pipe including refilling, watering, well ramming and finishing with PCC 1:2:4 and matching with surroundings, removing the broken P.C.C / road materials and clearing the site complete all as directed by Engineer-in-Charge.
S&F bus bar boxes made out of 3 mm thick CRCA sheet , front opening aluminium bus bar strips of 100 Amp and 200 mm long each , insulator, nut/bolts incl one no of 100 Amps MCCB FP 25 kA as incoming, MCB TPN 63 A 16 kA-01 No, MCB TP 25 KA-02 Nos as outgoing, terminating the existing incoming and outgoing cables and necessary glands, lugs, after Remove the unsv extg bus bar box, disconnecting the cable, uncoiling the loop etc alongwith earth work, painting with 2 coats of synthetic enamel paint over a coat of red oxide primer complete with 40x 6 mm angle iron support of length not less than 0.5 m grouted on PCC plateform for proper fixing arrangements complete all as specified and directed
Supply and fix in repairs PVC conduit of size 25 mm dia inlcluding necessary fixing arrangemet to wall/pole/surface such as pvc clamps/hooks as required on site complete all as specified and directed .
Supply and fix in repairs PVC flexible pipe of size 40 mm dia inlcluding necessary fixing arrangemet to wall/pole/surface such as pvc clamps/hooks as required on site complete all as specified and directed .
Dismantling ACSR or AAC conductors from the disturbed span including removing the binding with insulator, removing line spacer, of any size for LT/HT OH Line, etc complete all specefied and as directed
Re Stringing and Fixing only in position of sagged ACSR conductor of required size in over head line including biniding with aluminium binding wire complete after removing and refixing of UG cables/services wires to the ACSR conductor complete all as specified and as directed by the Engr-in-charge
M&L for Stringing and Fixing in position of new ACSR conductor in over Head lines conductor (squirrel/wessel/rabbit) including binding with aluminium binding wire complete all as specified and as directed
S&F in repairs pin type polymer insulators including one galvanized steel spindle two galvanized iron washers and one galvanized iron nut 100 mm height, 65mm dia for 1100 volts grade complete including dismantling of old unserviceable insulator complete all as specified and as directed
S&F in repairs Shackle Type Porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers, insulator bolts, washers and nuts 75 x 90mm for 1100 volts grade complete including dismantling of old unserviceable insulator complete all as specified and as directed
Supply & Fix PVC LT line separators 4 way with nut, bolt arrangement, in the existing O/H line on pole on height 7.0-7.50 mtrs above ground level complete all as directed.
Supply and fix in repairs Change Over Switch 400 Amps, front operated, open execution type Make :L&T/Standard /Schneider/Legrand
Supply and fix in repairs Change Over Switch 250 Amps, front operated, open execution type Make :L&T/Standard /Schneider/Legrand
Supply and fix in repairs Change Over Switch 160 Amps, front operated, open execution type Make :L&T/Standard /Schneider/Legrand
M&L for stay assembly complete with accessories as shown in elect plate no- 1 of SSR pt -I 2009 for dia of stay rod 20 mm incl GI stay strand of size 7/3.15 mm (maximum length 11.00 mtr) to keep the pole in vertical position incl loop insulator stay all as specified and directed including dismantling and taking out old unsv stay assembly set complete (PCC will be measured and paid separately) including dismantling and taking out the exisiting unserviceable stay assembly.
S & F in repairs cable junction box 200 x 160 x 98 mm in size, made out of thermoplastic, having IP 65 protection for outdoor installation fixed with 4 way bakelite cable terminals including 03 Nos polymide gland with check nut (M-32-02 N0 N0 & M- 25 -01 N0 ) fixed on poles with aluminium clamps of size 25 x 3, unts, bolts, washers etc., including taking out of old unserviceable cable junction box complete all as specified and as directed Make Cat No . K-9250 of HENSEL or equivalent in SPELSBERG/RITTAL.
Taking out of old unserviceable GI pipe any type any size
M&L for light grade galvanized pipe ISI marked with all fitting ISI marked, laid in trenches, under road or fixing on wall/pole/ crossing nallah etc of bore 100 mm complete all as specified and as directed .
M&L for light grade galvanized pipe ISI marked with all fitting ISI marked, laid in trenches, under road or fixing on wall/pole/ crossing nallah etc of bore 80 mm complete all as specified and as directed .
Boring of holes under road, pavement hard standing by using trenchless technology using ultrasound technique and necessary machine to insert pipe of 50 to 100mm light grade GI pipes as per site requirement with all fittings such as bends, elbows, Tees, etc, for protection of cable complete including all plant & machinaries, alongwih Butt fusion welding machine with all accessories, T&P etc required all as specified and as directed. Note :- Protection pipe will be measured and paid separately
Demolition & dismantling Cement concrete plateform on floor of any description and in any position not otherwise specifically complete all as specified and directed by Engr- in- charge.
M&L PCC 1:2:4 type B2 using 40mm graded stone aggregate as in platform, filling and mass concrete, coping to pole for embedding stay road all as specified, including necessary form work and applying two coats of white wash to exposed surface of coping/platform all as specified.
M&L PCC 1:4:8 type D2 using 40mm graded stone aggregate for pole foundation filling and mass concrete all as specified.
Material and labour for providing PCC 1:3:6 type C-2 mix using 40mm graded stone aggregate for stay wire all as directed.
Taking out/dismantling of existing old cable tray any type any size and making the surface good
Suply & fixing perforated cable tray, made of 2.0mm Galvanized Steel sheet, duly bended to required shape by sheet bending machine, including cover, made of 1.2mm thick Plain Galvanized Steel sheet duly screwed with the cable tray and duly fixed on the wall / ceilings including suitable Galvanized Steel brackets or hanging from the ceiling with suitable suspender as required at site all as specified and as directed by the Engineer -in Charge for the following sizes
a) 100mm (4 inch) width
b) 150mm (6 inch) width
c) 200mm (8 inch) width
d) 250mm (10 inch) width
Supply & fixing including taking out unserviceable electronic driver for LED street light 45/50 watt complete all as directed. Note :- Suitable for street light of Crompton/Havells/Phillips/ Bajaj/Luker/Kripa/Wipro. Driver will be procured as per sample, as required on site compatable for existing light fittings.
Disconnecting and taking out existing ACBs from housing and cleaning, rubbing and overhauling the mechanical parts and making serviceable of Local/Remote electrical operation of the panel incl Greasing Oiling , replacement of UNSV Trip coil, Breaker System ,Gear Pinion, roller Switch and re-assembling the same, Servicing of 440V in door ACB 630A to1600A capacity, fixed type/ MDO/ EDO checking of quality of Air interrupter, insulation resistances, static contact resistance, Testing (IR value, ratio test, polarity test) , connection testing and calibration of relay including all other functional tests of the ACB, panel complete all as specified and as directed.
M&L Repairing of panel boards / busbar of any size by removing of incomer/out going cables and connecting the same with same size of new lugs , nut bolts & welded the damgaged / broken portion making all doors to freely operatable by using grease and painting of two coats of synthetic enamel paint over one coat of red oxide primer for metal surface of panels/ busbar surface area etc.
M&L for one coats Aluminium paint over the exisiting steel tubular poles 7.5/9.20 mtrs above ground including cross arms/ bracings/ clamps etc complete all as specified after cleaning the existing poles and making good surface and surrounding and writing the pole numbers with white letters on black background all/ stickers as specifeid and directed by the Engr-in-charge.
M&L for painting the PSC poles of height 7.0-9.20 mtr above ground with two coats of cement based paint above ground and two coats of aluminium paint on cross arms/ bracings/ clamps etc complete all as specified after cleaning the existing poles and making good surface and surrounding and writing the pole numbers with white/Black letters on black background all as specifeid and directed by the Engr-in-charge. all as directed at site.
M&L for cross arms, bracings, clamps and back plates fabricated from structural steel section with painting of one primer coat and under coat and one finishing coat including nuts, bolts, washers, drilling holes for bolts in any shapes or size all as directed and including taking out unserviceable material complete all as specified and as directed.
Dismantling/taking down old unserviceable cross arms, bracings, support, clamp including nuts, bolts and washers complete.
S&F of steel tubular swaged poles complete with CI base plate and finial taper , plugs bolts, nuts and screw as specifed type410 SP-31 (9.0 meter long) including applying two coats of Aluminium paint over a coat of red oxide primer including dismantling PCC and removing of old steel pole complete all as specified and directed .
Supply and fix 3 Pole power contactor of AC 3 duty rating of 63 amps having 240 volts rated no volt coil and having 2 NO (Normally open) + 2 NC (Normally closed) configuration- 01 No
Supply and fix Auxilary contact ,2 No 0.5 module having 240 volts rated ,Complete all as specified and directed
Dismanling PCC and removing of old pre-stressd concrete pole and Material and labour for pre-stressed concrete pole, 9.0 metres long, 102mm x 172mm at top and 12mm x 279mm at bottom, class 10 complete as directed by Engr-in-Charge including taking out PSC pole of any description.Note:Excavation, Earthwork, PCC foundation, copping etc will be measured and paid separately.
OM SAI POWER SYSTEMS
AKSHITA ELECTRICAL
S J REDDY
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .