Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.4 LAccepted-AOC | L1 | Accepted-AOC Lowest and reasonable | |
| 2 | L2₹14.9 L+₹37,153 (2.56%)Rejected-Finance 179 URBAN ESTATE RAM TIRATH ROAD NR GURUDAWARA DARSHAN SINGH AMRITSAR PUNJAB 143001 | AMRITSAR | PUNJAB | 143001 | L2 | Rejected-Finance Other than Lowest | |
| 3 | L3₹20.6 L+₹6.1 L (41.9%)Rejected-Finance | L3 | Rejected-Finance Other than Lowest | |
| 4 | L4₹23.8 L+₹9.3 L (64.4%)Rejected-Finance B 56 LANE NO 4A SECTOR 7 VASHNAVI ENCLAVE CHANNI HIMAT JAMMU 180015 | JAMMU | JAMMU AND KASHMIR | 180015 | L4 | Rejected-Finance Other than Lowest | |
| 5 | Rejected-Technical | - | Rejected-Technical Rejected due to EPF copy not uploaded. |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
23 Mar 2024, 6:00 pmClosed
HQ CWE (AF) Jammu
Headquarters, CWE (AF) Jammu, Near Gurdwara Sahib and Mandir, Airforce Station Satwari, Jammu. Pin - 180 003
REPAIR/REPLACEMENT AND DAY TO DAY MAINTENANCE OF PERIMETRE SECURITY LIGHTS,STREET LIGHTS,BULDING SECURITY LIGHTS,POST TOP LANTERN,GARDEN LIGHTS,HIGH MAST LIGHTS IN TECHNICAL AREA AND DOMESTIC AREA AT AF STN JAMMU AND KALUCHAK
2024_MES_642215_1
CWEAFJ-33/2023-24
Open Tender
Civil Works
Item Rate
180 days
GE (AF) Jammu
As Per Tender Document
9 documents required · 9 mandatory
₹500
GE (AF) Jammu
₹40,000
Yes
24 May 2024
14 Feb 2024
25 Mar 2024
14 Feb 2024
23 Mar 2024
9 Mar 2024
Amount
Dismantling and taking down the existing defective street light/security light fitting of any type and any capacity fixed at any height by replacing UNSV part including cover checking loose connection etc, restroration of electric supply, detecting and repair of UG cable fault whenever required round the clock all as directed at site on daily complaint basis. One complaint shall be considered as one Job. Necessary T&P required at site will be provided by contractor without any extra payment and rate shall be included in the job iteslf.Complaint shall be attended in less than 24 hrs or else double the quoted rate shall be recovered from the firm for not attending complaints within 24 hrs.
S&F Security lights 45 watt of Powder coated pressure die cast alluminium compact high power LED street light fittings/flood lights with heat resistant toughned glass with lense and top opening having including making electric connections using two run of 1.5 sqmm single core unarmoured wire from junction box, fixed in repair.
S&F by taking out old U/S security lights any type,any make and any size and Fixing of Powder coated pressure die cast alluminium compact high power LED street light fittings/flood lights with heat resistant toughned glass with lense and top opening having 60 watt including making electric connections using two run of 1.5 sqmm single core unarmoured wire from junction box, fixed in repair.
S&F by taking out old U/S security lights any type,any make and any size and Fixing of Powder coated pressure die cast alluminium compact high power LED street light fittings/flood lights with heat resistant toughned glass with lense and top opening having 90 watt including making electric connections using two run of 1.5 sqmm single core unarmoured wire from junction box, fixed in repair.
S&F by taking out old U/S security lights any type,any make and any size and Fixing of Powder coated pressure die cast alluminium compact high power LED Flood light fittings/flood lights with heat resistant toughned glass with lense and top opening having 100 watt including making electric connections using two run of 1.5 sqmm single core unarmoured wire from junction box, fixed in repair.
S&F by taking out old U/S security lights any type,any make and any size and Fixing of Powder coated pressure die cast alluminium compact high power LED Flood light fittings/flood lights with heat resistant toughned glass with lense and top opening having 120 watt including making electric connections using two run of 1.5 sqmm single core unarmoured wire from junction box, fixed in repair.complete all as specified and directed by Engr-in-Charge.
S&F in repairs Aviation light , S&F LED aviation light 10 watt, rating voltage 215-240 V including necessary connection with two run of 1.50 sqmm single core unarmoured copper cable from junction box, complete all as specified and directed by Engr-in-Charge.
S&F in replacement outdoor garden lights,Bollard lights,Garden lights and path LED lights warm white,size 24 to 30" (inch), including taking down complete all as specified and as directed by Engr-in-Charg
S&F in trafic light and fixing new trafic light, green and red , including taking down complete all as specified and as directed by Engr-in-Charg
S&F in repair in Decorative 50W Lighting pole alongwith light for outdorr, IP 65, body matrial aluminium, round shape LED warm light , all as specified and as directed by Engr-in-Charg
Note for Items No. 02 to 10:- (i)A certificate from the manufacturer for warranty minimum upto 05 years shall be obtained and submitted to GE/AGE. (iI) Any touch up of the existing surface due to changing of fittings shall be done by contractor with similar surface finish without extra cost to the department. (iii) CA No shall be written on each fitting before installation. (iv) Necessary T&P required for rectifing complaints shall be provided by the contractor and ite expense shall be included in the quoted rates.No extra payment will be done to the firm for T&P required. 1. Driver shall be potted antivibration type. 2. LM-79 and LM-80 test report with 1 Lakh burning hours LED life from NABL lab shall be povided. 3. CRI (Colou Rendring Index) of fixture shall be > 70. 4. CCT (Colout Correlated Temprature of fixture shal be 5700K ± 300 K. 5. System Lumen Efficacy shall be > 100Lm/W 6. 5KV separate Surge Protector shall be provided as a part of fitting. 7. 5 years Warrantee shall be provided by contractor suppoted by OEM covering all parts of luminaire.
Material and labour for repair to existing LED street light fitting 45 Watt to 60 Watt of any make including supply and replacement of driver, LED Strips and other minor allied items required at site to make the light fitting serviceable complete all as specified and directed by Engineer-in-Charge.
Material and labour for repair to existing LED street light fitting 90 Watt to 100 Watt of any make including supply and replacement of driver, LED Strips and other minor allied items required at site to make the light fitting serviceable complete all as specified and directed by Engineer-in-Charge.
Material and labour for repair to existing LED Flood light fitting 100 Watt to 150 Watt of any make including supply and replacement of driver, LED Strips and other minor allied items required at site to make the light fitting serviceable complete all as specified and directed by Engineer-in-Charge.
Labour only for taking down and lifting up high mast light fitting including replacing the unserviceable items to make the fitting serviceable ,serving, greasing of steel ropeand adjust/repair the timer, S&F in replacement the contacts lifting mechanism with all accessories as required, complete all as directed by the Engineer-in-Charge. Note :- Spares like chokes, ignitor lamp & LED Drivers will be measured and paid separately)
Supply and laying of DWC (Double Wall Corrugated) HDPE Pipe, ISI Marked IS 16205 Part-II, of outer dia of 77 mm and inner dia 63 mm with smooth internal and profiled external surface for non pressure under ground cable including all connected accessories like coupler, 'O' Ring etc, for protection of cable complete all as specified and as directed
S&F fixed in repairs cable Junction Boxes with terminals` IP 66 "halogen free and weather proof” for outdoor installation (with metric knockouts for cable entry - Black Colour) Cable Size 16/25 Sqmm, Box Dimensions-200 x160 x 98, Catalog No-KF 9255(hensel) complete taking out of loop of cable from ground by neccessary earth work, complete all as spcefied and directed by Engr-in- charge.
Supply & Fixing PVC insulated sheathed service wire twin core 2.5 Sqmm aluminium multi stranded conductor 1100 volts grade incl taking down complete all as spcefied and directed
Supply & Fixing PVC insulated sheathed service wire twin core 04 Sqmm aluminium multi stranded conductor 1100 volts grade incl taking down complete all as spcefied and directed
Supply & Fixing PVC insulated sheathed service wire twin core 06 Sqmm aluminium multistranded conductor 1100 volts grade incl taking complete all as spcefied and directed
Supply & Fixing PVC insulated sheathed service wire twin core 10 Sqmm aluminium multistranded conductor 1100 volts grade incl taking complete all as spcefied and directed
Supply & fixing Sub main wiring with two single core PVC insulated unshesthed cable copper conductor(FRLS-H) of size 2.5 sqmm multistranded and one run of 2.5 sqmm PVC insulated unsheathed copper conductor(FRLSH) as earth continuty conductor drawing in and including non-metalic PVC rigid conduit 25 mm dia ISI marked with all conduit accessories concealed in wall, cutting of chases in walls, floors, ceilings, beams etc and making good the disturbed surfaces as directed including taking down old unservicable wiring complete all as specified and directed. Note: (Two run of single core cable and one run of earthing cable and one run of PVC conduit shall be measured as one length.)
S&F Rigid non-metallic PVC conduit 25mm dia (Heavy duty) in concealed exclusive of boxes (junction/terminal) but inclusive of all tees, bends,elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. including taking out old conduit complete all as specified and directed.
S&F MCB SPN 40 Amps 'C' Curve 25 KA with Sheet metal encloser, complete all as specified and directed.
S&F MCB Single Pole Neutral 25 Amps 'C' Curve 25 KA with Sheet metal encloser, complete all as specified and directed.
S&F Sheet metal encloser,DB Two Way complete all as specified and directed.
S&F Timelite distribution board 63 Amps single Pole/230 Volt with Astronomical time switch consisting of MCB SP 63 Amps -1 No, Timer, Power Contactor 65 Amps TP -01 No complete all as specified and directed.
Preparation of old painted surface of 9 Mtr. steel tubular poles above the top of PCC coping. Painting of pole from top of coping to a height of 1.5mtr (bottom portion of pole) with two coats of synthetic enamel paint in black and yellow alternate strip and painting the rest portion of pole of (approx length 7 mtr)including painting of cross arms/clamps etc complete with two coats of synthetic enamel aluminium paint and to the entire satisfaction of Engineer-in-Charge complete all as specified and directed
M&L for Preparation of old cement based painted surfaces of RCC pole 9 mtr by cleaning of deposited materials, and painting with one coat of exterior emulsion weather coat paint of approved make and colour complete all as specified & directed by Engineer-in-Charge
S & fix LT Cable End termination joining kit heat shrinkabale complete with jointing materials suitable for LT Armoured cable of size 10 to 35 Sqmm , complete all as specified & directed
S & fix LT Cable End Termination joining kit heat shrinkabale complete with jointing materials suitable for LT Armoured cable 3.5 core of size 50 to 95 Sqmm, complete all as specified & directed
S & fix LT Cable joining kit heat shrinkabale complete with jointing materials suitable for LT Armoured cable 3.5 core of size 120 to 185 Sqmm complete all as specified & directed
Supply , installation , Commissiong & Testing of LT feeder pillar compartmentalised design of size not less than 70 x 70 x 25 cm suitable for 440 volt 3 phase 4 wire system made out of 2.5 mm CRCA sheet powder coated having gasketed front two hinged doors with locking arrangement including bottom and top detachable gland plate complete with suitable size of rust proof nuts, bolts, and washers etc.. complete with mounting accessories including the following components :-(a) Four 30cms long Aluminium bus bar 100 Amp 6mm thickness mounted on epoxy insulators provided with rust proof nuts bolts and washers (b) LED indicating lamps - 3 nos. (Red ,Yellow, Blue) (c ) MCCB 100 Amp 4 Pole 16 KA with Sheet metal encloser with adjustable thermal and fixed magnetic setting, complete all as specified & directed
Material and labour for earth continuity conductor or main earthing lead using 4 mm dia galvanised iron or steel wire fixed to wall on batten or recess or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required including taking down old wire complete all as specified and directed by Engineer-in-Charge.
Material and labour for earth continuity conductor or main earthing lead using 25 x 4mm galvanised steel strip fixed to wall on batten or recess or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation, etc. as required including porcelain insulator saddle at the spacing nort exceeding 400mm including taking down old strip complete all as specified and directed by Engineer-in-Charge.
M&L for PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) mechanically crushed stone for mass filling in pole pit and foundation etc including provision of necessary form work to achieve fair finished surfaces complete all as specified and as directed.
M&L for PCC 1:3:6 type C-2 (using 20mm graded crushed stone aggregate) as in pole, foundation, coping, stay pits etc including provision of necessary form work i.e road cutting to aachieve fair finishes surfaces, complete all as specified and as directed.
Supply, Laying, connecting testing XLPE cable 10 Sqmm 2 core PVC insulated unarmoured and over all sheathed with aluminium conductor heavy duty 1100 volts grade laid/fixing in wall, trenches, floors, ducts passing through pipe for road crossing etc complete all as directed by Engr-in-Charge.
Supply, Laying, connecting testing XLPE cable 16 Sqmm 4 core PVC insulated unarmoured and over all sheathed with aluminium conductor heavy duty 1100 volts grade laid/fixing in wall, trenches, floors, ducts passing through pipe for road crossing etc complete all as directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, wire unarmoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm, 3.5 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm, 4 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm, 4 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm, 3.5 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sq mm, 3.5 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge. Note For srl No.38 to 43 :-Clamp, nut bolt, excavation, earth work, brick protection sand cushioning and GI pipe etc shall be measured & paid for separately
Taking out of old serviceable / unserviceable PVC under ground LT or HT Cable of any size and type fixed on pole, wall or laid in floors, trenches, across road crossing etc ,including taking out of cable covers of precast PCC / RCC slab or brick cover etc Excavation to be paid separetely.
Re-Laying only of serviceable LT or HT UG cable of any size and type in trenches, floors, across road crossing, or fixed on poles, walls, or passing through pipe, cable here-in-before complete all as specified and as directed. Note:- Handling of UG cable to working site as ordered shall be carried out by the firm and rate for the same shall deem to be included in the unit rate.
Re-Laying only of serviceable brick / PCC slab cover obtained from item 40here-in-before for cable protection cover laid width wise along length of cable complete all as specified and as directed.
Supply, install and erect in true vertical position (or to be fixed in an inclined position as strut pole) steel tubular swaged poles complete with MS base plate of 6 mm thick of size 300 mm x 300 mm, finial taper plug, pole cap, bolts, nuts and washers and screwed pole made out of FRW MS tubing conforming to IS-2713 (Part-II) 1980 type 410-SP-31 (9 meters long ) pole including drilling of holes of required size and Nos for fixing of cross arms, painting with one coat of red oxide primer and two coats of aluminium paint for exposed surfaces and two coats of black bituminous paint for portion embeded in concrete, etc complete all as specified and directed
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in any type of soil for laying of LT UG cables complete. Note:- The Rate quoted deemed to including cutting and removal of PSP Sheets wherever occured during excavation and the same shall be staged at desired location as directed at site
Returning, filling in, including spreading levelling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified and directed
Removing excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed
S&F GI tubing Medium grade 50mm dia along the wall/in trenches/in duct/in culvert/road crossing and including provisioning of suitable mild steel flat iron clamps and bolts, nuts and double washers etc for holding of GI pipe alongwith poles including taking out old broken GI pipes, complete all as specified and as directed by Engr-in-Charge.
S&F GI tubing Medium grade 80mm dia along the wall/in trenches/in duct/in culvert/road crossing and including provisioning of suitable mild steel flat iron clamps and bolts, nuts and double washers etc for holding of GI pipe alongwith poles including taking out old broken GI pipes, complete all as specified and as directed by Engr-in-Charge.
S&F GI tubing Medium grade 100 mm dia along the wall/in trenches/in duct/in culvert/road crossing and including provisioning of suitable mild steel flat iron clamps and bolts, nuts and double washers etc for holding of GI pipe alongwith poles including taking out old broken GI pipes, complete all as specified and as directed by Engr-in-Charge.
S&F in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 16 sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position ,extending the cable from cable loop including neccesory earth work and reconnecting the same complete all as specified and as directed by Engr-in-Charg
S&F in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 25 sqmmincluding cutting of exsting burn/dammaged cable after disconnecting from exsting position ,extending the cable from cable loop including neccesory earth work and reconnecting the same complete all as specified and as directed by Engr-in-Charg
S&F in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 95 sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position ,extending the cable from cable loop including neccesory earth work and reconnecting the same complete all as specified and as directed by Engr-in-Charg
S&F in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 120 sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position ,extending the cable from cable loop including neccesory earth work and reconnecting the same complete all as specified and as directed by Engr-in-Charg
S&F in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 185 sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position ,extending the cable from cable loop including neccesory earth work and reconnecting the same complete all as specified and as directed by Engr-in-Charg
S&F cable route indicator made out of 45 x 45 x 5 mm angle iron, 80 mm long embedded in PCC block of suitable size with moulded lettter HT CABLE or LT CABLE suitably incribed on CI circular plate 8 mm thick 100 dia complete including neccessary PCC 1:3:6, type C-2 (using 40 mm graded aggrregate) block of suitable size and neccessary earth work and excavation all as specified and directed.
S&F Copper wire 1.5 sqmm FRLS Green/Red/Black colour single core all as specified and directed by Engineer-in-charge.
S & fix LT Cable End termination joining kit Straight through joining kit complete with jointing materials suitable for LT Armoured cable of size 10 to 35 Sqmm all as directed .
S&F LT Cable End Termination joining kit Straight through joining kit complete with jointing materials suitable for LT Armoured cable 3.5 core of size 50 to 95 Sqmm all as directed
Supply and laying & testing sheathed Copper cable PVC Insulated, screened, PVC bedded, copper wire unarmoured, electric power cables ) 1100 Volts grade with stranded Copper conductor of size 10 sq mm, 2 core, complete including disconnecting and taking out old existing unserviceable aluminium cable all as specified and directed by Engr-in-Charge.
M&L sand cushioning with river washed and screened dry fine sand to under ground cable 23 cm thick, 8 cm below the cable and 15 cm after laying the cable, duly punned complete all as specified and as directed
Supply and Laying reinforced precast concrete cable cover class EHV type 3 flat size 450mm x 230mm x 50mm complete all as specified and as directed by Engr-in-Charg
S&F by taking and fixing only of IP 65 LED Post top with moonlight effect and efficient light distribution .
S&F MCCB 100 Amps 4 pole 25 KA with Sheet metal encloser with adjustable thermal and fixed magnetic setting, fixed in repairs complete all as specified and directed.
Cutting of tree branches of any girth along HT/ LT OH lines & street light pole at a distance not less than 2 meter on either side of the pole cleaning of bushes and shrubes of any type along entire RM of pole. Cleaning /prunning should be carried out as and when required during entire running period of contract or as when directed by Engr in charge.A fine of one time quated rate per running meter will be deducted if the over groth is found along the pole all as directed by Engr-in- Charge.
Mahajan Construction Co
VIDHATA ELECTRICALS
ANIKET TRADERS
Bidder Name
Mahajan Construction Co
ANIKET TRADERS
VIDHATA ELECTRICALS
M/S GRD ENGINEERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .