Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹1.4 Cr
EMD Value
₹2.1 L
Closing Date
9 Dec 2025, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Col Pawan Kumar, CWE
Headquarters, Commander Works Engineer, Bhopal, Military Engineer Services, SI Line, Bhopal, Pin Code - 462001 (Madhya Pradesh)
SPL REPAIR OF E/M (REPAIR AND ENHANCEMENT OF ILLUMINATION) OF 3 EME CENTER AOR UNDER GE BHOPAL
2025_MES_734961_1
84100/E8
Open Tender
Civil Works
Item Rate
180 days
Bhopal
AS PER NIT CONDITION
7 documents required · 7 mandatory
₹1,000
Yes
GE Bhopal
₹2.1 L
Yes
13 Oct 2025
13 Oct 2025
11 Dec 2025
13 Oct 2025
9 Dec 2025
27 Nov 2025
13 Oct 2025 - 27 Nov 2025
Supply & erection of new Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-37 (09 metres long) including painting to pole with aluminium paint and black bituminous paint as specified in SSR 2009 Part-I including writing pole numbers and making black & yellow strips upto 1.5 mtr height above the coping including taking out old poles complete all as specified and directed.
Supply and fixing energy saving LED street light fitting 90 Watt 230 V AC outdoor type with high pressure die cast aluminum housing toughened glass thermal shock and impact resistance and heat resistant complete with powered by integrad electronice driver with out put short circuit protection, surge protection, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete toughened glass, lens IP 66, IK-08 and with system efficacy of 125 lm/W CRI>70 , PF>0.95 complete all as specified and directed.
Dismantling of U/S high mast pole including light of any type and size complete all as specified and directed.
M & L for errect, test and commissioning of High Mast pole system consisting of two section suitable for 55m/s wind speed alongwith head frame, made out of hot dip galvanised steel structure 16 Mtrs long, steel wire rope 6mm dia 97/19 guage, double drum winch, luminiaries carriage suitable for 06 luminiaries in symmetrical arrangement and 10 watt RED LED aviation lightof make- Bjaj, havells/Philips and other accesories manufactured in factory with raising lowering system comprising double drum winch, trailing cable, connector, integral power tool motor, manual handle, junction box, lightining finial, (Wiring material from Junction Box to individual luminiare & MCB in base compartment are not included and are a part of installation), with supply of foundation bolts manufactured from special steel along with nuts, washers, anchor plate and common template and outdoor stand mounted feeder pillar with 32A TPN MCB incomer, single dial time switch, 25A TP contactor for the automatic switching of luminiaries and timer switch with all connected accessories for automatic switching of light, power tool control with 2 No 9A contactors and raise lower push button, Incoming 25 sq. mm and out going 2.5sq. mm terminals. 16 M High mast complete all as specified and directed. Note : Foundation bolts manufactured from special steel along with nuts, washeres, anchor plates and templates complete as recommeded by manufacturer or complete all as specified and directed.. (i) The cost of Aviation light, feeder piller box, copper cable 6 core, 2.5 Sqmm from feeder piller box to 170 Watt LED light deemed to be included in the quoted rate. (ii) The cost for RCC foundation shall be born by the contractor and design should be as per manufacturer recommendations & no extra amount will be paid to the contractor on this account. (iii) Design/drawing for foundation is as per manufactrer approval. (iv) The excavation of soil for RCC work for the foundation deemed to be included in the quoted rate
Item 4.00 contd/……. HIGH MAST SYSTEM MAKE : Bajaj /Havells/Halonix/Surya or equivalent shall be approved by GE. Height of mast : 16 Meter No. of Section : Two Material Construction : E350 Grade as per IS 2062/BS-EN10025 Base dia and top diameter (A/F) : Top : 150mm Botton : 360 mm Cross section of Mast : 20 side polygon plate thickness - Top 3 mm and Bottom 3 mm Standard for Galvanisation : A per BS EN ISO 1461 Size of Opening and door at base : 1050 x 250 mm Diameter of base plate : 520 mm Thickness of base plate : 25 mm Lighting protection finial : GI single spike of length 1200mm Max. wind speed : 55m/s as per IS 875 (Part III) Number of foundation bolts : 6 Nos PCD of foundation bolts : 445 mm Type / diameter / length of foundation bolts : TS 600/24mm dia/ 850 mm long LUMINAIRES CARRIAGE Material of construction : 50 NB ERW Class B-M.S Pipe Diameter of carriage ring (mm) : 450 mm (ID) Construction : 06 Arm, Welded, 2 Sections Load carrying capacity : 12 Luminaire TRAILING CABLE Conductor : Copper, 6 core, 2.5 Sqmm Insulation : PVC Flexible No.of circuits per mast : One No cable per mast
Item 4.00 contd/……. WINCH / POWDER TOOL Type /SWL of winch : Double drum, SWL 350 Kg Method of Operation : Integral Motor Motor Capacity : 1.0 HP ( Including suitable starter) No of Speeds : 6 Pole, Single speed Torque Limitor : With Mechanical Tripping Facility STAINLESS STEEL WIRE ROPE Grade / construction : AISI 316, 7/19 Construction Number of Ropes : Two Continuous Diameter (mm) : 6 mm, 97/19 guage, Breaking load Capacity : 1350Kg x 2
Supply, laying, connecting and testing LT XLPE insulated, screened, PVC bedded, galvanised steel strip armoured, heavy duty cable, 1100 volts grade ISI Marked, laid in trenches, passing through pipes/ducts, on walls with shadel, with stranded aluminium conductor of size 16 Sqmm nominal cross section x 4 core complete all as specified and directed.
Supply, laying, connecting and testing LT XLPE insulated, screened, PVC bedded, galvanised steel strip armoured, heavy duty cable, 1100 volts grade ISI Marked, laid in trenches, passing through pipes/ducts, on walls with shadel, with stranded aluminium conductor of size 10 Sqmm nominal cross section x 2 core complete all as specified and directed.
Supply, laying, connecting and testing LT XLPE insulated, screened, PVC bedded, galvanised steel strip armoured, heavy duty cable, 1100 volts grade ISI Marked, laid in trenches, passing through pipes/ducts, on walls with shadel, with stranded aluminium conductor of size 10 Sqmm nominal cross section x 4 core complete all as specified and directed.
M&LEarthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and directed as shown in electrical plate No 3 of SSR Part-I 2020. Notes : CONTRACTOR SHALL BE PRODUCE TEST RESULT DATA SHEET ,IF RESULT NOT CAME AS REQUIRED ,HE HAS TO REDONE WITHOUT ANY EXTRA COST. (i) The unit rate includes for 40mm dia medium grade protection pipe and earth lead upto 7.50 meter. (ii) Any variation in length of earth lead and protection pipe beyond 7.5 m shall be measured & paid seperately separately. (iii) PCC pit shall be provided at least 500mm away from the pit and not on the earth pit itself and the extra cost of additional height of watering pipe, bends, elbow etc shall be deemed to be included in the unit rate.
Dismantling of ACSR conductor of any type and size complete all as specified and directed.
Supply and fixing energy saving flood light power by an entegral electronic driver with out put short circuit protection, sugre protection LED flood light made of poly die casting, epoxy powater coated with smooth finishing aluminium housing suitable lens & toughened glass, IP66 with system efficacy of 100lm/W 170 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp. and with all fixing arangement , nuts, bolts and washer connecting to electric system with 2.5 sqmm PVC Aluminium stranded conductor 2 core upto require length,on pole , testing and completion CRI>70, power factor>0.95, complete all as specified and directed at site.
Excavating in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth for pole foundation, cable trench, etc and getting out in soft/hard soil OR rock complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm each complete all as specified and directed.
Removing excavated materials (soil) to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
M&L for sand filling with clean dry fine sand unwashed including gently punning around cables in trenches for cable protection (8 cm below cable & 15 cm above cable) complete all as specified and directed. Note:- Compacted/punned thickness shall be measured & paid.
Supplying and laying Class LV, Type I, flat, size 250mm x 150mm x 40mm for cable protection cover laid flat and dry in trenches over the cable perpendicular to the direction of cable complete all as specified and directed.
S&F 40mm GI tubing light grade with all fittings as required for passing through cables under floors, along the wall or along the pole, etc with suitable size M.S.flat iron clamps incl nut,bolt and washer including taking down old rusted pipe complete all as specified and directed.
S&F 50mm GI tubing light grade with all fittings as required for passing through cables under floors, along the wall or along the pole, etc with suitable size M.S.flat iron clamps incl nut,bolt and washer including taking down old rusted pipe complete all as specified and directed.
S & F in replacement for GFS Polycarbonate Thermoplastic oval shape weather proof junction boxes IP65,with internal embedded polyurethane material gasket .IK-09 as per IEC 60695-2-11 for street lights size not less than 155 mm x 210 mm x 92 mm with metric knockouts for cable entry, weather proof for outdoor installation and including glands and with 4 terminals for terminating of rating 32 Amps for three phase and neutral mounted with locking arrangement and fixed to the PCC/Steel Poles by means of suitable size of clamps with nut and bolts and incl provn for fixing 01 nos of single pole MCBs 6-32 amps,10KA all as specified and directed by Engr-in-Charge.
M&L PCC (1:3:6) type C-2 using (40mm) graded stone aggregates as in foundation filling and mass concrete (for foundation bed concrete in stays /poles or any other directed site)
M&L making coping to the new/existing PCC/Steel Poles above the GL with PCC 1:2:4 type B-1 using 20 mm graded broken stone aggregate as in mass concrete complete all as specified and directed. ( Note :- Quoted rates deemed to be including for dismantling of broken copings)
M&L PCC (1:4:8) type D-2 using (40mm) graded stone aggregates as in foundation filling and mass concrete (for foundation bed concrete in stays /poles or any other directed site)
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.34 MB
BOQ_822982.xls
BOQ • 0.25 MB
84100TenderDocuments.pdf
Tender Documents • 1.12 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .