Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
16 Jan 2024, 6:00 pmClosed
CWE (AF) JORHAT
HQ CWE (AF) JORHAT ROWRIAH 785004
84013/ E8 REPAIR MAINT OF HT ELECTRIC SUPPLY 33 KV VCB 11 KV VCB CT PT LIGHTNING ARRESTORS HT CABLES AND OTHER CONNECTED WORKS AT AF STN JORHAT UNDER GE AF JORHAT
2023_MES_624394_2
84013/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (AF) JORHAT
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE(AF) JORHAT
₹70,000
Yes
29 Feb 2024
3 Jan 2024
17 Jan 2024
3 Jan 2024
16 Jan 2024
11 Jan 2024
Amount
Disconnecting and Taking out existing 11 KV HT VCBs of any Make from Housing, Cleaning, Rubbing and Overhauling the Mechanical Parts, Servicing of 11 KV Indoor VCB, Checking of quality of Vacuum Interrupter, Insulation Resistances, Static Contact Resistance, Testing (IR Value, Ratio Test, Polarity Test) and Connection and Verification of 6.6 KV Current Transformer (Set of Three) by Primary Injection Kit and Testing and Calibration of Relay (Set of Two Over Current and One Earth Fault) by Secondary Injection Kit including all other Functional Tests of the VCB, C&R Panel and CTs, PTs Setting Right the Mechanism and Re-assembling, Testing and Commissioning, etc. as required, complete all as specified and as directed. (a) Taking out Trolley Unit from Metal Clad Housing and Dismantling complete, Carrying out Inspection Cleaning, Mechanical Spring, complete all as specified and directed. (b) Opening of Bus-bar Chambers, Carrying out Inspection, Cleaning of Complete Unit and Re-fixing of the Bus-bar, complete all as specified and directed. (c) Carrying out Testing of all Metering Instruments, Replacement of Worn out Spares, Meter, Wiring Cable, etc. and Testing, complete all as specified and directed. (d) Inspection and Checking of all Protection Devices, Relays, complete all as specified and directed. (e) Carrying out Inspection and Testing of Auxiliary Power System, complete all as specified and directed. (f) Assembling of Complete HT Switch Gear Unit, proper Greasing, Oiling for Easy Operation and Connection of Incoming and Outgoing Cable and making all necessary Adjustment and Testing, complete all as specified and as directed. NOTE : New Spares such as Vcauum Intrupter, HT Trolley, Mono block diode, CT, LED Indicator, HT 11 KV VCB Panel Spout Insulator, HT 11 KV VCB Panel TNC Switch and HT 11 KV Bus-bar Insulator and Copper Cable will be Measured and Paid separately under BOQ Item No. 2 to 10 here-in-after.
Supply only 11 KV Vacuum Interrupter with TC (as per existing/ as approved) suitable for 11 KV VCB Panel, complete all as specified and as directed. MAKE : SCHNEIDER, Model : VG2 or equivalent Model in Make : ABB/ SIEMENS as approved by GE.
Supply only HT Trolley Chamber (as per existing/ as approved) suitable for HT VCB Panel, complete all as specified and as directed. MAKE : ABB / SCHNEIDER / SIEMENS
Supply only Mono Block Diode (as per existing/ as approved) suitable for HT VCB Panel, complete all as specified and as directed. MAKE : ABB / SCHNEIDER / SIEMENS
Supply only CT Ratio 100-50/5-5A, 15 VA, Class 1 Accuracy (as per existing/ as approved) suitable for Metering and Protection Resin Cast Current Transformer, complete all as specified and as directed. MAKE : ECS/ GEMINI/ JSL/ L&T/ PRAGATI/ SCHNEIDER
Supply only LED Indicator with Wiring (as per existing/ as approved) suitable for HT VCB Panel, complete all as specified and as directed.
Supply only 2.5 Sqmm, 4 Core Copper multi-stand Cable 1100 Volt (as approved), complete all as specified and as directed.
Supply only HT 11 KV VCB Panel Spout Insulator (as per existing/ as approved) suitable for HT VCB Panel, complete all as specified and as directed. MAKE : ECS/GEMINI/JSL/L&T/PRAGATI/SCHNEIDER or as per existing in VCB's.
Supply only HT 11 KV VCB Panel TNC Switch BCA02 (as per existing/ as approved) suitable for HT VCB Panel, complete all as specified and as directed.
Supply only HT 11 KV Bus-bar Insulator with Bolts, Nut, Washers, etc. (as per existing/ as approved) suitable for HT VCB Panel, complete all as specified and as directed.
Shifting 11 KV HT VCB Panel after carefully Disconnecting Cables, Glands, Lugs, etc. from the existing Panel and Re-fixing/ Re-installation the same at specified Location and Providing necessary Connections, complete all as specified and as directed. NOTE : New Cable Glands, Cable Lugs will be Measured and Paid separately under BOQ Item No. 12 to 29 here-in-after.
Supply only Cable Gland of Size 22mm, complete all as specified and as directed.
Supply only Cable Gland of Size 28mm, complete all as specified and as directed.
Supply only Cable Gland of Size 32mm, complete all as specified and as directed.
Supply only Cable Gland of Size 38mm, complete all as specified and as directed.
Supply only Cable Gland of Size 45mm, complete all as specified and as directed.
Supply only Cable Gland of Size 50mm, complete all as specified and as directed.
Supply only Cable Gland of Size 57mm, complete all as specified and as directed.
Supply only Cable Gland of Size 75mm, complete all as specified and as directed.
Supply only Aluminum Lug of Size 10mm, complete all as specified and as directed.
Supply only Aluminum Lug of Size 35mm, complete all as specified and as directed.
Supply only Aluminum Lug of Size 50mm, complete all as specified and as directed.
Supply only Aluminum Lug of Size 95mm, complete all as specified and as directed.
Supply only Aluminum Lug of Size 150mm, complete all as specified and as directed.
Supply only Aluminum Lug of Size 185mm, complete all as specified and as directed.
Supply only Aluminum Lug of Size 240mm, complete all as specified and as directed.
Supply only Aluminum Lug of Size 300mm, complete all as specified and as directed.
Supply only Aluminum Lug of Size 400mm, complete all as specified and as directed.
Supply only Aluminum Lug of Size 630mm, complete all as specified and as directed.
Supply only Spring Charge Motor with Gear (as per existing/ as approved) suitable for ACB Panel as per existing Make, complete all as specified and as directed. MAKE : ABB/ L&T/ SCHNEIDER/ SIEMENS
Supply only Cam Switch with Wiring (as per existing/ as approved) suitable for existing ACB Panel, complete all as specified and as directed.
Supply only LED Indicator with Wiring (as per existing/ as approved) suitable for existing ACB Panel, complete all as specified and as directed.
S&F Pin type 33 KV Composite Polymer Insulator after Taking down carefully Old Unserviceable Insulator, complete all as specified and as directed.
S&F Disc type 33 KV Composite Polymer Insulator after Taking down carefully Old Unserviceable Insulator, complete all as specified and as directed.
S&F Pin type 11 KV Composite Polymer Insulator after Taking down carefully Old Unserviceable Insulator, complete all as specified and as directed.
S&F Disc type 11 KV Composite Polymer Insulator after Taking down carefully Old Unserviceable Insulator, complete all as specified and as directed.
M&L XLPE insulated, Heavy duty, Galvanised Steel Strip or Wire Armoured, Stranded Copper Conductor Electric LT Cable, 1100 Volts grade, Cross Sectional Area 2.5 Sqmm, 4 Core after Taking down/ out Unserviceable Cable of any description, complete all as specified and as directed.
M&L 33 KV Single Phase Out Door Oil Cooled PT of Ratio 33 KV/rt 3/110V/rt 3/110V/rt 3 Class 0.5-3, Burden 50 VA – 50 VA, Insulation Level 70KV/170 KV, Voltage Factor 1.2 Cont and 1.9 for 30 Sec, conforming to IS-3156 and Providing all Connections, etc. after Dismantling/ Taking out existing Old Unserviceable 33 KV PT, complete all as specified and as directed. MAKE : AE/ AREVA T&D/ CROMPTON GREAVES/ SCHNEIDER
M&L Disconnecting Connections and Servicing of 33 KV CT/PT Vertical/ Horizontal Mounted including Insulators and Operating Mechanism for Repairs/ Replacement of Broken/ Worn out Components, etc., complete all as specified and as directed. NOTE :- (a) New Parts will be Measured and Paid under BOQ Item No. 42 to 44 as 'Supply only' here-in-after. However Labour Component involved in Replacement is included in Unit Rate quoted against this Item. The Quoted Unit Rate shall deemed to be included for Handling of Serviceable Materials for Reuse at Site of Work, complete all as specified and as directed. (b) Any Minor Repairs involved to make the CT/PT Functional even if notified by Engineer-in-Charge shall be carried out by the Contractor without any Extra Cost to the Department.
Supply only Connector Box 12 Pole (as per existing/ as approved) suitable for existing 33 KV CT, complete all as specified and as directed.
Supply only PT Terminal Box 6 Pole (as per existing/ as approved) suitable for existing 33 KV PT, complete all as specified and as directed.
Supply only Cadium Bolts & Nuts (as per existing/ as approved) suitable for existing 33 KV CT/ PT, complete all as specified and as directed.
Dismantling Air Break Gang Operated Switches HT 11 KV 3 Phase of any capacity (200 Amp/ 400 Amp) Vertical/ Horizontal mounted including Insulators and Operating Mechanism for Repairs/ Replacement of Broken/ Worn out Components and Insulators, etc. with or without Taking down from the Pole(s), complete all as specified and as directed. NOTE :- (a) New Parts will be Measured and Paid separately as 'Supply only' under BOQ Item No. 46 to 50 here-in-after. However, Labour Component involved in Replace-ment is included in Unit Rate quoted against this Item. The Unit Rate shall deemed to be included for Handling of Serviceable Materials for Reuse at Site of Work, complete all as specified and as directed. (b) Any Minor Repairs involved to make the GOD Functional even if notified by Engineer-in-Charge shall be carried out by the Contractor without any Extra Cost to the Department.
Supply only Male Contact/ Moving Contact Blade (as per existing/ as approved) suitable for existing Air Break Gang Operated Switches HT 11 KV 3 Phase, complete all as specified and as directed.
Supply only Female Contact/ Fix Contact Jaw (as per existing/ as approved) suitable for existing Air Break Gang Operated Switches HT 11 KV 3 Phase, complete all as specified and as directed.
Supply only Tinned Copper Flexible Jumper 200/400 Amp (as per existing/ as approved) suitable for existing Air Break Gang Operated Switches HT 11 KV 3 Phase, complete all as specified and as directed.
Supply only MS Jumper Carrier (as per existing/ as approved) suitable for existing Air Break Gang Operated Switches HT 11 KV 3 Phase, complete all as specified and as directed.
Supply only Back Connector Plate (as per existing/ as approved) suitable for existing Air Break Gang Operated Switches HT 11 KV 3 Phase, complete all as specified and as directed.
M&L Disconnecting & Taking out for Servicing of existing Air Break Switch (Isolator) Off Load, Rotating type, 33 KV, 800 Amp to 1250 Amp capacity, with proper Alignment of Isolator Rotating Blades, with Fixed Contact Jaws, Arcing Horns, Applying Petroleum Jelly to Moving Mechanism, Cleaning and Lubricating to Isolator Gear Box Assembly, Tightening all Nuts, Bolts and Clamps of Jumpers, etc., Making in proper Serviceable Condition for Smooth Functioning, Testing and Commissioning On Load, complete all as specified and as directed. NOTE :- (a) New Parts will be Measured and Paid as 'Supply only' under BOQ Item No. 52 to 54 here-in-after. However, Labour Component involved in Replacement is included in Unit Rate quoted against this Item. The Unit Rate shall deemed to be included for Handling of Serviceable Materials for Reuse at Site of Work, complete all as specified and as directed. (b) Any Minor Repairs involved to make the GOD Functional even if notified by Engineer-in-Charge shall be carried out by the Contractor without any Extra Cost to the Department.
Supply only Male/ Moving Contact/ Rotating Blade of HDE Copper Silver plated of Air Brake, Off Load Isolator Switch, Rotating type, 33 KV, 800 Amp to 1250 Amp capacity with all Fixing Nuts, Bolts, etc., complete all as specified and as directed.
Supply only Fixed Contacts of HDE Copper Silver plated of Air Brake, Off Load Isolator Switch, Rotating type, 33 KV, 800 Amp to 1250 Amp capacity with all Fixing Nuts, Bolts, etc., complete all as specified and as directed.
Supply only Terminal Pad for Air Brake, Off Load Isolator Switch, Rotating type, 33 KV, 800 Amp to 1250 Amp capacity with all Fixing Nuts, Bolts, etc., complete all as specified and as directed.
S&F Pin type 33 KV Porcelain Insulator including Taking down/ out Unserviceable Insulator of any description, complete all as specified and as directed.
S&F Disc type 33 KV Porcelain Insulator including Taking down/ out Unserviceable Insulator of any description, complete all as specified and as directed.
S&F Disc Insulator 33 KV, 3 in Series, Porcelain type with Tension Clamp for Conductor including Taking down/ out Unserviceable Insulator of any description, complete all as specified and as directed.
S&F Line Post Insulator 33 KV, Porcelain type including Taking down/ out Unserviceable Insulator of any description, complete all as specified and as directed.
S&F 33 KV Single Phase Out door type Oil Cooled CT of ratio 50-25/5-5 Amp Class 1.0 - 5P10, Burden 15 VA, Insulation Level 70 KV/170 KV, Confirming to IS-2705, Providing all Connections including Dismantling and Taking out of Old Unserviceable 33 KV CT of any description, complete all as specified and as directed. MAKE : AE/ AREVA T&D/ CROMPTON GREAVES/ SCHNEIDER
M&L Callibration of Feeder Protection Micro-processor based (OC & EF) Relay 11 KV and 33 KV by Secondary Injection and Generating Report by an Authorised Testing Agency, complete all as specified and as directed.
M&L Servicing, Testing of Transformer 1000 KVA to 2000 KVA, 33/11 KV Outdoor, Disconnecting all Internal Connections of HT Side for Periodical Maintenance such as Cleaning of Core and Winding by means of Washing by Hosing Down with Clean Dry Oil to removed Dust/Sludge on Core and Coil, Cleaning of Oil Tank to removed Sludge deposited, Replacement of Rusted Gasket Set, Burnt Spindle, Broken/ Unserviceable HV/LV Ceramic Bushing, Broken Arc Horn, Surge Arrestor, Replacement of Silica Gel, etc. after Assembling, complete all as specified and as directed. NOTE : New Spares/ Parts & New Transformer Oil will be Measure and Paid as 'Supply only' under BOQ Item No. 62 to 67 & 77 here-in-after.
Supply only Breather Assembly filled with Silica Gel for Transformer 1000 KVA to 2000 KVA, 33/11 KV Outdoor as approved, complete all as specified and as directed. NOTE : New Silica Gel will be Measure and Paid as 'Supply only' under BOQ Item No. 75 here-in-after.
Supply only Brass Spindle for Terminal on HT Side Threaded complete with Nut, Washers, etc. of dia as ordered, as approved and suitable for Transformer 1000 KVA to 2000 KVA, 33/11 KV, complete all as specified and as directed.
Supply only Brass Spindle for Terminal on LT Side Threaded complete with Nut, Washers, etc. of dia as ordered/ as approved and suitable for Transformer 1000 KVA to 2000 KVA, 33/11 KV, complete all as specified and as directed.
Supply only Ceramic Bushing and Gasket on LT Side of Transformer 1000 KVA to 2000 KVA, 33/11 KV, complete all as specified and as directed.
Supply only Ceramic Bushing and Gasket on HT Side of Transformer 1000 KVA to 2000 KVA, 33/11 KV, complete all as specified and as directed.
Supply only Gasket (Cock Sheet) 6.0mm thick with Conical Rubber Bush Complete as approved and suitable for Transformer 1000 KVA to 2000 KVA, 33/11 KV, complete all as specified and as directed.
M&L Servicing, Testing of Transformer 100 KVA to 630 KVA, 11000/433 Volt Indoor / Outdoor, Disconnecting all Internal Connections of HT/LT Side for Periodical Mainten-ance such as Cleaning of Core and Winding by means of Washing by Hosing Down with Clean Dry Oil to removed Dust/Sludge on Core and Coil, Cleaning of Oil Tank to removed Sludge deposited, Replacement of Rusted Gasket Set, Burnt Spindle, Broken/ Unserviceable HV/LV Ceramic Bushing, broken Arc Horn, Surge Arrestor, Replacement of Silica Gel, etc. after Assembling, complete all as specified and as directed. NOTE : New Spares/ Parts & New Transformer Oil will be Measure and Paid as 'Supply only' under BOQ Item No. 69 to 75 & 77 here-in-after.
Supply only Breather Assembly filled with Silica Gel for Transformer 100 KVA to 630 KVA, 11000/433 Volt Indoor/Outdoor as approved, complete all as specified and as directed. NOTE : New Silica Gel will be Measure and Paid as 'Supply only' under BOQ Item No. 75 here-in-after.
Supply only Brass Spindle for Terminal on HT Side Threaded complete with Nut, Washers, etc. of dia as ordered/ as approved and suitable and suitable for Transformer 100 KVA to 630 KVA, 11000/433 Volt, complete all as specified and as directed.
Supply only Brass Spindle for Terminal on LT Side Threaded complete with Nut, Washers, etc. of dia as ordered, as Approved and suitable and suitable for Transformer 100 KVA to 630 KVA, 11000/433 Volt, complete all as specified and as directed.
Supply only Ceramic Bushing and Gasket on LT Side of Transformer 100 KVA to 630 KVA 11000/433 Volt, complete all as specified and as directed.
Supply only Ceramic Bushing and Gasket on HT Side of Transformer 100 KVA to 630 KVA 11000/433 Volt, complete all as specified and as directed.
Supply only Gasket (Cock Sheet) 6.0mm thick with Conical Rubber Bush Complete as approved and suitable for Transformer 100 KVA to 630 KVA 11000/433 Volt, complete all as specified and as directed.
Supply only Silica Gel Grains in Breather Assembly of Transformer of any Capacity, complete all as specified and as directed.
M&L Dehydration/Filtration of Transformer Oil by means of Centrifugal Filtration Plant to achieve the specified Di-electric Strength Miniumum 40 KV at 2.5mm Gap in existing Position of Transformer of any Capacity and Transformer Oil for Topping Up at various Sub-station and Testing, complete all as specified and as directed. NOTE : New Transformer Oil to be used for Topping Up will be Measured and Paid separately under BOQ Item No. 77 here-in-after.
Supply & Pouring of New Transformer Oil, conforming to IS:335-1983 to achieve a Di-electric Strength Miniumum 40 KV at 2.5mm Gap to Topping Up of the Transformer of any Capacity, complete all as specified and as dirdirected. NOTE : Dehydration/Filtration of New Transformer Oil to achieve a Di-electric Strength Miniumum 40 KV at 2.5mm Gap (as/if required) will deemed to be included in the Quoted Unit Rate.
Dismantling Cross-Arms of Mild Steel Channel or Angle Sections, etc of any Size, includ-ing Mild Steel Bolts, Nuts, Washers, etc. Segregating of Serviceable Mild Steel Works of any description and kept in Safe Custody for re-use, complete, complete all as specified and as directed.
M&L Cross-arms, Bracings, Supports, Clamps and Back Plates fabricated from Structural Steel Sections including Nuts, Bolts, Washer, Welding, Bending Cold or Hot, Drilling Holes for Bolts, in any Shape or Size as indicated/ directed and inclusive of Two Coats of Aluminium Paint over a Coat of Aluminium Primer, complete all as specified and as directed.
Re-fixing only Cross-arms, Bracings, Supports, Clamps and Back Plates (Serviceable Steel Sections obtained from BOQ Item No. 78 here-in-before) including Nuts, Bolts, Washer, Welding, Bending Cold or Hot, Drilling Holes for Bolts, in any Shape or Size as indicated/ directed including applying Two Coats of Aluminium Paint, complete all as specified and as directed.
Taking down/ out Unserviceable or Serviceable UG Cables of any Cross Sectional Area after disconnections, Cables laid in Trenches and/ or Fixing with Walls/ Poles including Segregating of Serviceable Materials viz Bricks, Cables, Cable Protection Pipes, etc. and kept in Safe Custody for re-use, complete all as specified and as directed. NOTE : Earth Work will be Measured and Paid separately under relevant Items.
Excavation in Trenches not exc. 1.50 Metre in Wide and not exc. 1.50 Metre in Depth and Getting out in Soft/ Loose Soil including maintaining Level Bottom of Trenches, complete all as specified and as directed.
Returning, Filling in including Spreading, Levelling, Watering, Well Ramming in Layers not exc. 25 Cm, Providing Heaps not exc. 100mm and upto 1.20 Metre Width Strip along the Route of the Cable Lines, etc. with Surplus Soil in Soft/Loose Soil, complete all as specified and as directed.
Horizontal Boring for Passing Cable Protection Pipe upto 80mm Bore (dia), under Road/ Footpath, not exc. 10 Metre in a Single Length, complete all as specified and as directed. NOTE : Cable Protection Pipe will be Measured and Paid separately under relevant Items.
Supply & Laying or Passing through Pipe XLPE Insulated, Screened PVC Bedded, Galvanized Steel Strip or Wire Armoured, Heavy duty, HT Electric Power Cables (Unearthed) with Stranded Aluminium Conductor, 11000 Volts, Cross Sectional Area 95 Sqmm, 3 Core and Testing, complete all as specified and as directed. NOTE : Necessary Earth Works will be Measured and Paid separately under relevant Items.
Re-Laying/Fixing or Passing through Pipe, XLPE insulated, Armoured, HT/LT Electric Power UG Cable with Aluminium Conductor, of any description and Size (Serviceable Cable obtained from BOQ Item No. 81 here-in-before) including Providing Brass Compression Cable Glands, Terminal Lugs, etc, complete all as specified and as directed. NOTE : Necessary Earth Works will be Measured and Paid separately under relevant Items.
M&L Sand Cushioning (Dry) in Trenches for Protection of UG Cables (Below, Above and Around the UG Cable laid in Trenches) of 230mm Spread thickness and Consolidated (Punned) upto 180mm thickness, complete all as specified and as directed. NOTE : For the purpose of Payment, Only Punning thickness of Sand Cushioning will be Measured and Paid for.
S&F Sub-Class 'B' Brick, Well burnt, laid Breadth-wise along the Length of Cable laid in Trenches over Sand Cushioning laid for UG Cable Protection, complete all as specified and as directed.
Re-laying Old Brick in Trenches for UG Cable Protection (Serviceable Bricks obtained from BOQ Item No. 81 here-in-before), complete all as specified and as directed.
S&F Galvanised Iron Pipe 50mm Bore (dia) ‘Light Grade’ for Protection of UG Cable, laid in Trenches or through Road Crossing, complete all as specified and as directed.
S&F Galvanised Iron Pipe 50mm Bore (dia) ‘Light Grade’ for Protection of UG Cable, laid in Floor or Fixing to Walls, Poles, etc. with suitable Size and Shaped Mild Steel Flat Iron 40x5.0mm Clamps, Nuts, Bolts, etc., complete all as specified and as directed.
S&F Galvanised Iron Pipe 80mm Bore (dia) ‘Light Grade’ for Protection of UG Cable, laid in Trenches or through Road Crossing, complete all as specified and as directed.
S&F Galvanised Iron Pipe 80mm Bore (dia) ‘Light Grade’ for Protection of UG Cable, laid in Floor or Fixing to Walls, Poles, etc. with suitable Size and Shaped Mild Steel Flat Iron 40x5.0mm Clamps, Nuts, Bolts, etc., complete all as specified and as directed.
S&F Outdoor Termination Cable Jointing Kit, Heat Shrinkable type, complete with Joint-ing Materials and Accessories suitazble for 11 KV (Earthed) XLPE armoured Aluminium Conductor Cable, Cross Sectional Area 50 Sqmm to 95 Sqmm, 3 Core and Testing including Disconnecting & Taking out Unserviceable Cable Joints of any description, complete all as specified and as directed.
S&F Straight Through Cable Jointing Kit, Heat Shrinkable type, complete with Jointing Materials and Accessories suitable for 11 KV (Earthed) XLPE armoured Aluminium Conductor Cable, Cross Sectional Area 50 Sqmm to 95 Sqmm, 3 Core and Testing including Disconnecting & Taking out Unserviceable Cable Joints of any description, complete all as specified and as directed.
S&F Outdoor Termination Cable Jointing Kit, Heat Shrinkable type, complete with Jointing Materials and Accessories suitable for 33 KV (Earthed) XLPE armoured Aluminium Conductor Cable, Cross Sectional Area 240 Sqmm, 3 Core and Testing including Disconnecting & Taking out Unserviceable Cable Joints of any description, complete all as specified and as directed.
S&F Straight Through Cable Jointing Kit, Heat Shrinkable type, complete with Jointing Materials and Accessories suitable for 33 KV (Earthed) XLPE armoured Aluminium Conductor Cable, Cross Sectional Area 240 Sqmm, 3 Core and Testing including Disconnecting & Taking out Unserviceable Cable Joints of any description, complete all as specified and as directed.
Dismantling of ACSR or AAC Conductors of any description, complete all as specified and as directed.
S&F Aluminium Conductor Steel Reinforced (ACSR) as Overhead, Conductor for Connection 33 KV equipment/ 33 KV Distribution System with necessary Connections with PG Clamp and Jumpers of suitable Size, complete all as specified and as directed.
DEDUCT TOTAL AMOUNT OF CREDIT NOTE : Bidders are required to Quote the SAME AMOUNT (catered at SCHEDULE OF CREDIT including NOTES therein of Tender documents) under Column 'UNIT RATE' (M) against Row No. 112.
R C TRADING COMPANY
THE SUPPLY AGENCY
M/S SANTOSHI TRADERS
NIHAR ENTERPRISE
satyabhama and co
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .