Loading…
Loading…
Tender Value
₹1.0 Cr
EMD Value
₹2.0 L
Closing Date
3 Apr 2026, 5:00 pmClosed
Electrical (General) work in connection with "Reconstruction / Improvement / Renovation along with up-gradation of facilities at Booking offices at LLH, BEQ (ABO), KOG (ABO & MBO), HMZ (ABO & MBO), UPA (ABO & MBO), BBAE, MUU, HPL, AMBG, MAYP, DBP, PDA, BCGM & RSLR stations under jurisdiction of Sr.DEN/1/HWH".
EL-HWH-25-21-3571
EL-HWH-25-21-3571
Open
180 Days
West Siang, Arunachal Pradesh
₹0
₹2.0 L
13 Mar 2026
13 Mar 2026
20 Mar 2026
A-Electrical (General) work in connection with "Reconstruction /
Wiring of Light / Fan / Call Bell / Glow Sign point by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral 1 in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab )
Wiring of 6A / 3 pin Plug board consisting with one plug socket and one 6A switch by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 2 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab )
Wiring of 6/16A 3 pin Plug board consisting with one 16/6A 3 pin plug socket and one 16A switch by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 3 2.5 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab )
Wiring of Multi Plug board consisting with three nos. 6A / 3 pin plug socket, three nos. 6A switch, one no. 6/16A 3 pin plug socket, one no. 16A switch, one no. 10A fuse kit-kat / MCB and 4 one indicator ( Red ) by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 4.0 sq. mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab )
Wiring of Submain by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper 5 conductor cable of size 4.0 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 2.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab )
Wiring of Mainline by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper 6 conductor cable of size 6.0 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 4.0 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab )
Wiring of Mainline by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper 7 conductor cable of size 10 sq.mm, 1100V grade for phase and neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 4.0 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab )
Wiring of Mainline by 4 nos. single core HRFR / FRLS grade, PVC insulated, copper 8 conductor cable of size 10 sq.mm, 1100V grade for 03 phases and 01 neutral in PVC conduit / casing along with 1 no. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 4.0 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ) ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab )
Extra cost for conceal wiring in respect to PVC conduit / casing for light, fan, plug, power plug, multi-plug point etc. including make good of wall surface as its original condition
Extra cost for conceal wiring for main / submain with respect to PVC conduit / casing including make good of wall surface as its original condition
Extra cost involvement for modular switch, bell push, plug socket, fan regulator, USB point, TV socket etc. with other accessories ( Make of Modular switch, socket, box, cover plate etc. - ABB / Anchor ( Panasonic ) / Havells ( Crabtree ) / Legrand / LK (L&T) )
Dismantling of old wiring including light, fan, call bell, plug, power plug, sub-main, main etc. of different types of offices / stores / quarters including transportation of released materials from site to depot store with loading and unloading charges.
Fixing, connection, testing and commissioning of indoor LED luminaire fittings with suitable arrangement. ( LED indoor light fitting will be supplied by Railway )
Fixing, connection and commissioning of Street Light luminaire with suitable dia heavy gauge GI bend pipe with GI clamps made of GI flat of size 40mm x 6mm and GI nut-bolts on structure / wall ( LED Street / Flood light fitting will be supplied by Railway )
Fixing, connection and commissioning of out door LED Flood light / Street Light fitting on High Mast Tower / Pole / Structure with suitable arrangement. ( LED outdoor light fitting will be supplied by Railway )
Dismantling of old light fittings and fixing, connection and commissioning of new 16 street light / flood light LED fittings on High Mast Tower / Pole / Structure / surface with suitable arrangement including transportation from site to stores. ( LED Street / Flood light fitting will be supplied by Railway )
Fixing, connection and commissioning of BLDC Ceiling fan with suitable size GI clamps made of GI flat and GI nut-bolts. ( BLDC Ceiling Fan will be supplied by Railway )
Fixing, connection and commissioning of AC Exhaust Fan with suitable size and shape GI clamps / GI nut & bolts including necessary masonry work ( AC Exhaust Fan will be supplied by Railway )
Installation, connection and commissioning of above Wall Bracket fan with GI clamps made of GI flat of suitable size and GI nut-bolts on wall / structure. ( Wall Bracket Fan will be supplied by Railway )
Supply of SPN DB ( Metal Enclosure with Metal Door ), 8 way, 50Hz, complete with 4 20 nos. SP MCB of current rating from 6A to 32A, 10kA, 240V, 50Hz as per requirement of load and 1 no. DP RCBO of current rating 40A, 300mA, 10kA, 230V, 50Hz ( Make of MCB, RCBO and Metal Distribution Board - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S / Havells )
Fixing, connection and commissioning of above SPN MCB DB with suitable arrangement including all incoming and outgoing cable connection with suitable cable termination arrangement.
Supply of TPN MCB DB ( Heavy duty, Outdoor type, UV ray protected, self fire- extinguishing and resistant to abnormal heat and fire up to 650 degree C GWT, shock resistance IK08 or above and IP65 degree of protection grade transparent DB box, similar to ABB Mistral65 - 20 22 Modules or equivalent ), 3Ph, 50Hz, 415V, 4 way per phase, 415V, 50Hz, complete with total 12 nos. SP MCB of current rating from 6A to 32A, 10 kA, 240 Volt, 50Hz per phase as per requirement of load and one no. FP RCBO 63A, 300mA, 10 kA, 415V, 50Hz, Suitable for AC + Pulsating DC (Type A) + Harmonics ( Make of MCB & RCBO - LK (L&T) / Siemens / ABB / Hager Legrand / Schneider ) ( Make of TPN DB - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / Spelsberg / Hensel / Eaton )
Fixing, connection, testing and commissioning of above TPN MCB DB including all incoming and outgoing cables glanding, cable connection with cable termination and suitable wall hanging arrangement as per site condition with all associated accessories.
Supply of Polycarbonate distribution box enclosure (IP-65) complete with 1 no. DP 24 Automatic Changeover with Current Limiter of current rating 30A / 20A, RoHS compliant, conforms to IEC 60947-6 suitable for operation in 240V, 50Hz power supply system. ( Make of DP Automatic Changeover with Current Limiter - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S / Havells ) ( Make of Polycarbonate Enclosure - Grasp / OBO Bettermann / ABB / Schneider )
Fixing, connection, testing and commissioning of above Change Over Switch 25 including all incoming and outgoing cables glanding with socketing, cable connection with cable termination and suitable wall hanging arrangement as per site condition with all associated accessories.
Trenching and laying of cable underground by pucca floor / concrete cutting with 26 covering of cable through suitabe dia HDPE pipe including supply of HDPE pipe (PE-100 grade, PN-10 or higher) along with refilling the trench and make good of surface as its original condition ( Cable will be supplied by Railway )
Trenching and laying of cable under ground by soil cutting through suitable dia HDPE 27 pipe including supply of HDPE pipe (PE-100 grade, PN-10 or higher) alongwith refiling of trench by excavated soil and make good of surface as its original condition. ( Cable will be supplied by Railway )
Trenching and laying of cable underground by pucca floor / concrete cutting and commissioning of cable alongwith make good of floor surface as its original condition after laying of cable ( Cable will be supplied by Railway )
Trenching and laying of cable underground by pucca floor / concrete cutting and commissioning of cable through 80mm dia GI pipe including supply of GI pipe alongwith make good of floor surface as its original condition after laying of cable ( Cable will be supplied by Railway )
Trenching, laying under road / track through 50 mm dia GI pipe ( medium gauge ) including supply of GI pipe and commi- ssioning of cable including back filling of trench with excavated soil after laying of cable ( Cable will be supplied by Railway )
Drawing of cable on wall / structure with suitable size and shape GI clamps including supply of suitable size GI Clamp and GI nut- bolts and commissioning of cable ( Cable will be supplied by Railway )
Drawing of cable through one no. 2" dia, 3.0 Mtrs. long GI pipe ( Make - Tata / Jindal / Bansal ) for protection of cable on pole with proper GI clamps and GI nuts & bolts including supply of GI pipe ( Cable will be supplied by Railway )
Supply of Straight Through Jointing Kits ( Heat shrinkable ) suitable for XLPE / PVC 33 insulated stranded Aluminium conductor cable of size 4 / 3.5 x 50-95 sq.mm., 1100V grade complete with all accessories including jointing, testing and commissioning. ( Make - m-seal / Raychem / Mahindra / Densons / 3M / Polycab )
Drawing / Relocation of cable through cable tray / wall / shed structure by GI clamp or suitable arrangement.
Supply of PVC Cable Duct with ROHS compliant and FRLS grade of Size (W X H) - 45 mm x 60 mm including fixing and commissioning of cable duct with suitable arrangement. ( Make : LK (L&T) / Legrand / Salzer / Hensel )
Supply of Polycarbonate Junction Box of dimension 280mm x 280mm x 130mm consisting with 1 no 63A 10kA DP MCB, 1 no 100A STUD Type Terminal and 2 nos. Cable glands with 36 Ingress protection: IP66 or higher complete with hinged door with locking arrangement including fixing, connection and commissioning of above Junction Box on AT Mast with GI clamps made of GI flat of size 40mm x 6mm with GI nuts-bolts. ( Make of Junction Box - Grasp/OBO Bettermann/ABB/Schneider )
Supply of Dust and vermin proof metal Busbar Chamber made of 16 SWG ( 1.6mm ) MS sheet duly powder coated consisting of 4 nos. tinned copper busbar of each bar of capacity 100 37 Amp, 4 way, suitable for 415V, 50Hz supply system including all accessories alongwith fixing, connection, testing and commissioning of incoming and outgoing cables glanding, cable socketing and connection with all suitable arrangement. ( Make - Havells / Standard / HPL / C&S / LK (L&T) / Indoasian )
Supply of Vertical TPN DB with MCCB Incomer ( Metal Enclosure with Metal Door - IP43 ), 3Ph, 50Hz, 415V, 8 way per phase, 415V, 50Hz, complete with total 24 nos. SP MCB of current rating from 6A to 32A, 10 KA, 240 Volt, 50 Hz per phase as per requirement of load and one no. 38 MCCB, 4 Pole, ( 40 - 100 ) Amp, 415V, 50Hz, 36kA, ( Ics = 100% Icu ), Microprocessor based release with following features :- 1) Adjustable Over Load, 2) Adjustable Short Circuit, 3) Inbuilt ground fault protection, 4) Inbuilt Instantaneous protection, 5) Adjustable neutral overload protection, 6) Provision of Thermal Memory, 7) Microprocessor protection-based MCCB must have facility of individual 'LSIG' fault indication. ( Make of MCB, MCCB and Metal Distribution Board - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider C&S )
Fixing, connection and commissioning of above panel with suitable arrangement including all incoming and outgoing cable glanding, socketing and connection with suitable cable termination arrangement.
Supply of LT cubicle type indoor wall / floor mounted Distribution Panel Board made 40 of 14 SWG ( 2mm ) MS sheet duly powder coated comprising with the following : a) MCCB, 4 Pole, ( 25 - 63 )Amp, 415V, 50Hz, 36kA, ( Ics = 100% Icu ) Microprocessor based release with following features :- 1) Adjustable Over Load, 2) Adjustable Short Circuit, 3) Inbuilt Ground Fault protection, 4) Inbuilt Instantaneous protection, 5) Adjustable neutral overload protection, 6) Provision of Thermal Memorry, 7) Microprocessor protection-based MCCB must have facility of individual 'LSIG' fault indication - 1 no. b) MCB, 4 Pole, 32Amp, 415V, 50Hz, 10kA ( C-curve ) - 1 no. c) MCB, 4 Pole, 20Amp, 415V, 50Hz, 10kA ( C-curve ) - 2 nos. d) MCB, 2 Pole, 16Amp, 240V, 50Hz, 10kA ( C-curve ) - 2 nos. e) MCB, 2 Pole, 10Amp, 240V, 50Hz, 10kA ( C-curve ) - 2 nos. f) DP Change Over Switch, 25Amp, 230V, 50Hz - 2 nos. g) Tinned Copper Busbar ( 4 Bar ) each of capacity 100 Amps., 415V, 50 Hz - 1 set h) Static Multifunction panel mounting LED Energy Meter suitable for operation on 3Ph, 415V, 50Hz supply, Cl 1 with provision of RS485 communication port having display parameters - V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Runhours, On hours, Phase angle, Interrupts, THD, Events ( High-Low ), Neutral Current, K Factor - 1 no. i) CT of suitable ratio for MFM - 3 nos. j) LED indication lamp for Phases and "ON & OFF" indication for operating status of breakers - 6 nos. complete with all other accessories, internal wiring by single core FRLS grade copper conductor cable of suitable size and 1100V grade along with fabrication work, cable glanding, socketing etc. ( Make - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S ) ( Make for Energy Meter - ABB / Schneider / Secure / Legrand / LK (L&T) / Genus / Conzerv / Elmeasure / Stelmec / HPL / Socomec / Anchor / C&S )
Fixing, connection, testing and commissioning of above panel including all incoming 41 and outgoing cables glanding, cable socketing and connection and construction of concrete foundation or suitable wall hanging arrangement as per site condition with all associated accessories.
Supply of LT cubicle type indoor wall / floor mounted Distribution Panel Board made of 14 SWG ( 2mm ) MS sheet duly powder coated comprising with the following : a) MCCB with Microprocessor Release of breaking capacity 36kA at 415V, AC 50Hz ( Ics = 100% Icu ) with following features :- 1) Adjustable Over Load, 2) Adjustable Short Circuit, 3) Inbuilt ground fault protection, 4) Inbuilt Instantaneous protection, 5) Adjustable neutral overload protection, 6) Provision of Thermal Memory, 7) Microprocessor protection- based MCCB must have facility of individual 'LSIG' fault indication suitable for Release Range ( 63-160 )Amp, 4 Pole - 2 nos. b) MCCB, 4 Pole, 125 Amp, 415V, 50Hz, 36kA, without protechtion release, used as bus coupler isolation - 1 no. c) MCCB, 4 Pole, ( 16- 42 40 )Amp, 415V, 50Hz, 36kA, ( Ics = 100% Icu ) Microprocessor based release with above features mentioned in (a) - 6 nos. d) Tinned Copper Busbar ( 4 Bar ) each of capacity 200 Amps., 415V, 50 Hz - 1 set e) Static Multifunction panel mounting LED Energy Meter suitable for operation on 3Ph, 415V, 50Hz supply, Cl 1 with provision of RS485 having display parameters - V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Runhours, On hours, Phase angle, Interrupts, THD, Events ( High-Low ), Neutral Current, K Factor - 8 nos. f) CT of suitable ratio for MFM - 24 nos. i) LED indication lamp for Phases and "ON & OFF" indication for operating status of breakers - 32 nos. complete with all other accessories, internal wiring by single core FRLS grade copper conductor cable of suitable size and 1100V grade along with fabrication work, cable glanding, socketing etc. ( Make - LK (L&T) / Siemens / ABB / Hager / Legrand / Schneider / C&S ) ( Make for Energy Meter - ABB / Schneider / Secure / Legrand / LK (L&T) / Genus / Conzerv / Elmeasure / Stelmec / HPL / Socomec / Anchor / C&S )
Fixing, connection, testing and commissioning of above panel including all incoming 43 and outgoing cables glanding, cable socketing and connection and construction of concrete foundation or suitable wall hanging arrangement as per site condition with all associated accessories. Square
Supply, installation and commissioning of different size and 2 inch width self- illuminated LED display system with all necessary accessories : 1) Aluminium panel - 3mm Pvdf coated aluminium composite panel. ( Make - Alstone / Aludecor / Alstom / Timexbond ) Designed artwork by ER shall be for flat cutting alphabets to be flushed with the ACP sheet. 2) 1" x 1" 18g MS square pipe structure with red oxide and white enamel paint, ISI marked. 3) Imported translucent Acrylic sheet for making alphabets : a) Physical form - Sheets b) Thickness range - 3mm (+/-) 0.5mm c) Colour - White mild translucent d) Outdoor Stability - UV Stabilised e) Output - Excellent to cast 44 Vinyl and self display f) Make - acast / Mitsubishi / sumiplex 4) 26g Galvanised iron sheet / 3mm acp for back panel. ( Make - Tata / Jindal / Bansal ) 5) Light Emitting Diodes ( LED ) sign modules - ( Make of LED chip - NICHIA / CREE / OSRAM / SEOUL / PHILIPS / LUMILEDS / AVAGO ) a) Power consumption - 1 watt each module b) Operating Temperature - (-) 40 degree to 60 degree C c) Viewing Angle - 150 degree d) Input Voltage - 12V DC e) Protection Class inbuilt - IP 66 or higher f) Standards - UL94HB g) Certifications - UL. CE. C tick. ROHS h) Housing material of the module - PC & ROHS compliant i) Colour - White / Red / Warm white 6) Power Drivers - ( Make - Union / Meanwell or similar ) a) Protection Class - IP 65 b) Rated Supply Voltage - 108V - 305V AC c) Frequency - 50/60 Hz d) Power Factor - greater than 0.9 e) Driver Output current - .8A to 25 Ampere f) Operating Temperature - (-) 40 degree to 60 degree C g) Output Voltage Tolerance - 10%
Supply of GI ( minimum coating thickness 65 microns ) conical / octagonal ( minimum 45 sheet thickness - 3mm ) Pole of overall length 7 M with single / double arm bracket, top cover, base plate including hinged door-inbuilt Junction box complete with copper bar, insulator, Hylam sheet for cable termination and fuse kit-kat / MCB ( Make - Utkarsh / B.P. Projects / Crompton / Bajaj / Surya )
RCC foundation, erection and commissioning of above GI pole with construction of 46 cement concrete muffing ( Cement : Stone : Sand = 1 : 2 : 4 ) with foundation accessories including earthing of pole with 1 no. of 50 mm dia, 3 M long GI pipe ( Make - TATA / Jindal / Bansal ) with necessary earth connection from pipe to pole by GI Strip / GI wire
Wiring of light point by 2 nos. single core HRFR / FRLS grade, PVC insulated, copper conductor cable of size 1.5 sq.mm, 1100V grade for phase and neutral through pole from inbuilt pole 47 Junction Box's porcelain fuse kit-kat / MCB to light fitting along with 1 no. single core HRFR / FRLS grade, PVC insulated copper conductor cable of size 1.5 sq.mm, 1100V grade for Earth Continuity Conductor ( ECC ). ( Make of Copper conductor cable - Anchor / KDK / Havells / Finolex / Gloster / KEI / Polycab / RR Kabel / Mescab )
Dismantling / Cutting of existing pole and make good of surface including transportation from site to stores
Dismantling, Shifting, reinstallation, testing and commissioning of existing LT distribution panel board including all incoming and outgoing cable connection.
Earthing with 2 nos.of 50 mm diametre, 3.0 metres long heavy gauge GI pipe ( Make 50 - Tata / Jindal / Bansal ) including construction of earth pit and necessary earth connection from pit by suitable Galvanized Iron ( GI ) strip. ( For details not covered in this specifications, Indian Standard Code of Practice for earthing IS : 3043 - 1987, Reaffirmed - 1996 should be followed ) 1586174.0
Goods & Services Tax ( at present @ 18% )
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
GCC_April-2022.pdf
ATTACHMENT
Advancecorrectionslips.pdf
ATTACHMENT
Annexure-VA.pdf
ATTACHMENT
TenderBooklet.pdf
ATTACHMENT
TenderFormandAnnexuresnew_1.pdf Tender form and annexure
ATTACHMENT
HTLTstandardspecification.pdf
ATTACHMENT
3571Clause.pdf
ATTACHMENT
AnnexureVIB.pdf
ATTACHMENT
TenderFormandAnnexuresnew_1.pdf
ATTACHMENT
Download all tender documents and submit your bid