Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹17.4 CrAccepted-AOC | ₹17.4 Cr | 1 | Accepted-AOC Accepted |
| 2 | 2₹18.7 CrRejected-Finance | ₹18.7 Cr | 2 | Rejected-Finance Rejected |
| 3 | Not Admitted-Fee/PreQual/Technical | - | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹16.0 Cr
EMD Value
₹31.9 L
Closing Date
8 Jan 2025, 5:00 pmClosed
Amina Chawla
Division - Electrical
Design Supply Erection Testing and Commissioning of 66 6.6 kV Substation at WTP Chandu Bhudhera Gurugram by constructing 4 nos. of Bays with a provision of 2 nos. of 10 MVA 66 6.6 kV Transformers and 2 nos. 3000 kVA 6.6 .415kV Transformers VCB Panels
2024_HRY_404097_1
2024037C6834 7FBE 4D13 9A0F FD45F69AE42E1838001
Open Tender
Electrical Works
365 days
Gurugram
2 documents required · 2 mandatory
₹1,180
₹31.9 L
Yes
1 Jul 2025
15 Oct 2024
9 Jan 2025
15 Oct 2024
8 Jan 2025
15 Oct 2024
Amount
Road :- Designing and construction of 6m wide C.C road and the main road leading to 66KV switch yard shall have a embankment as gradient with 150mm thick (1:3:6) with concrete base and 200mm thick M-25 design mix concrete with kerb and channels in accordance with approved design and drawings , Supply and installation of 8.00 Mtr high LED solar street light at 30m c/c , main gates walkways , levelling etc. complete in all respect and any other work contingent thereto as per sizes and specification given in DNIT.
Foundation:- Steel structure for the following foundations:-Foundation of 66 KV CT Transformers , Foundation of 66 KV CT Metering , Foundation of 66 KV PT Metering , Foundation of 66 KV SF-6 BREAKER , Foundation of 66 KV CT LandE Switch , Foundation of 66 KV LA Line , Foundation of 66 KV CT Protection , Foundation of 66 KV PT PROTECTION ,Foundation of 66 KV PT bus bar , Foundation of 66 KV LA transformer , Foundation of 66 KV Isolator and Foundation of 66 KV CT-4 as needed and in accordance with approved design and drawings including excavation and refilling of soil complete in all respect and any other work contingent thereto as per sizes and specification given in DNIT(Steel reinforcement for R.C.C. work, where not included in the complete rate of RCC, including straightening, cutting, bending, placing in position, binding, wastage, overlaps, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire etc. complete in all respect below plinth level Note:- Reinforcement shall be measured in length including hooks, if any, separately for different diameters as actually used in work , excluding overlaps. Wastage, overlaps, couplings, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire or other methods of binding and placing shall not be measured and cost of these items shall be deemed to be included in the rates for reinforcement.Thermo-Mechanically Treated bars of grade Fe-500D kg or more( for M-30) .
Foundation :- Design and construction of RCC Grade M30 Using Concrete Mixer C.C of M30 concrete platforms for Foundation of 66 KV CT Transformers , Foundation of 66 KV CT Metering , Foundation of 66 KV PT Metering , Foundation of 66 KV SF-6 BREAKER , Foundation of 66 KV CT LandE Switch , Foundation of 66 KV LA Line , Foundation of 66 KV CT Protection , Foundation of 66 KV PT PROTECTION ,Foundation of 66 KV PT bus bar , Foundation of 66 KV LA transformer , Foundation of 66 KV Isolator and Foundation of 66 KV CT-4 including excavation and back filling as required to the complete satisfaction of Engineer-in-charge as needed and in accordance with approved design and drawings including excavation and refilling of soil complete in all respect and any other work contingent thereto as per sizes and specification given in DNIT.
Yard :- Designing and construction of yard with 100mm thick C.C of M30 concrete after preparation of plinth( i.e compaction and filling of soil followed by 75mm M-10 concrete and so as to achieve the final plinth level which should be 0.75 meter above the existing road level of WTP Basai.) including cable trenches , all electrical , mechanical works in accordance with approved design and drawings and all other works contingent thereto as per sizes and specification given in DNIT(for M-10).
Yard : Steel reinforcement for R.C.C. work, where not included in the complete rate of RCC, including straightening, cutting, bending, placing in position, binding, wastage, overlaps, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire etc. complete in all respect below plinth level Note:- Reinforcement shall be measured in length including hooks, if any, separately for different diameters as actually used in work , excluding overlaps. Wastage, overlaps, couplings, welded joints, spacer bars, chairs, stays, hangers and annealed steel wire or other methods of binding and placing shall not be measured and cost of these items shall be deemed to be included in the rates for reinforcement.Thermo-Mechanically Treated bars of grade Fe-500D kg or more( for M-30) .
Yard :- Designing and construction of yard with 100mm thick C.C of M30 concrete after preparation of plinth( i.e compaction and filling of soil followed by 75mm M-10 concrete and so as to achieve the final plinth level which should be 0.75 meter above the existing road level of WTP Basai.) including cable trenches , all electrical , mechanical works in accordance with approved design and drawings and all other works contingent thereto as per sizes and specification given in DNIT(ITEM For M-30)
Control room building :- Designing and construction of RCC M-25 Framed structure building confirming to national building code for building in accordance with approved design and drawings with single story building height 5.00mtr or more as required, including cable trenches , all electrical , mechanical and Sanitary works and all other works contingent thereto as per sizes and specification given in DNIT.
Supply and Erection of 11kV XLPE Power Cable 3C*185 sq.mm as per Technical specification of HVPNL.
SITC of 6.6KV Lightning Arrestor(LA) (9KV, 5kA LIGHTNING ARRESTER ).
Supply and Erection of ACSR Zebra Conductor as technical specification.
Supply and Erection of GSS Earth Wire 7/3.15 mm.
Supply and Installation of Trolley mounted CO2 Fire Extinguisher of Capacity 22.5 KG.
Supply and Installation of Trolley mounted CO2 Fire Extinguisher of Capacity 25 KG, FE DCP type.
Supply and Installation of Fire Buckets with stand (12 no`s buckets).
Supply and Installation of Wall mounted Fire Fighting equipment`s foam type 9 liter capacity.
Supply and Installation of Wall mounted Fire Fighting equipment`s CO2 6.5 Kg Capacity.
Supply and Installation of Wall mounted Fire Fighting equipment`s water type CO2 9 litre Capacity.
Bay marshalling kiosk made of 2.5 mm. Thick sheet steel , IP 55 enclosure protection as per specification.
SITC of 66 kV NCT
SITC of 6.6 kV NCT
Supply and Erection of 66 kV lightning arrestor. (10KA, Zinc oxide type, heavy duty, station class) .
SITC of Control Relay Panel Transformer Protection and Circuit Breaker Panel ( Without Auto Reclose)
Supply and Erection of 11kv XLPE Power Cable 3c*300 sqmm As per Technical specification of HVPNL.
SITC of 66kv Protection Current Transformers ( Ratio 600-300-150/1-1-1-1A).
SITC of 66kv Isolator 1250A, 31.5 KA (Without earth switch).
Supply and Erection of 1.1KV Control and Power Cable LT Copper Armoured FRLS Cable (FRLS, PVC type) 3CX2.5 mm2.
SITC of 1.1KV Control and Power Cable LT Copper Armoured FRLS Cable (FRLS, PVC type) 5C X 2.5 sqmm ,
Supply and Erection of 1.1KV Control and Power Cable LT Copper Armoured FRLS Cable (FRLS, PVC type) 7C X 2.5 sqmm.
Supply and Erection of 1.1KV Control and Power Cable LT Copper Armoured FRLS Cable (FRLS, PVC type) 10C X 2.5 sqmm.
Supply and Erection of 1.1KV Control and Power Cable LT Copper Armoured FRLS Cable (FRLS, PVC type) 19C X2.5 sqmm.
Supply and Erection of 1.1KV Control and Power Cable LT Copper Armoured FRLS Cable (FRLS, PVC type) 4C X 4 sqmm.
Supply and Erection of 1.1KV Control and Power Cable LT Copper Armoured FRLS Cable (FRLS, PVC type) 2C X 6 sqmm.
Supply and Erection of 4 core x 10 sqmm Al. Conductor cable , 1.1 KV PVC insulated and sheathed, steel armoured cable.
Supply and Erection of 4 core x 16 sqmm Al. Conductor cable Power Cable 1.1 KV PVC insulated and sheathed, steel armoured cable.
Supply and Erection of Termination , Double compression gland , Lugs, Thimbles etc. for 1.1kV Copper Control Cable unarmoured for 66KV bays of size 7Cx4mm2 , 4Cx4mm2, 2Cx4mm2, 2Cx6mm2, 3Cx2.5mm2, 16Cx2.5mm2, 10Cx2.5mm2, 7Cx2.5mm2 as per Technical Specification of HVPNL/ GMDA .
Supply and Erection of Grounding/ Earthing System (40mm MS Rod Etc.).
Supply and Erection of Grounding/ Earthing System (75*12mm, 75*6mm , 50*6mm GI Flat Etc.)
Supply and Erection of 66kv line ACSR Zebra Conductor including all assessories as technical specification of HVPN
Supply and Erection of 11KV XLPE Power Cable 1C*1000 Sqmm for T/F to 11 KV incomer with termination kit for both ends (2 runs per phase for each 6.6 KV I/C).
SITC of Wall mounted Fire Fighting equipment`s DCP 10 Kg Capacity,
SITC of Wall mounted Fire Fighting equipment`s DCP 5 Kg Capacity.
SITC of High wall type split AC unit of 2-ton capacity for SCADA room and CandR panel room as per specification.
FOUNDATIONS Design, engineering, supply of labour, TandP, material and construction of RCC footings and pedestals etc. for steel gantry and equipment structures complete in all respects as per technical specifications including cost of excavation, concreting, cement, reinforcement steel, form work, grouting, holding down bolts, backfilling etc. and other items not mentioned herein but required for the completion of work. Surplus earth, if any shall be disposed of to a suitable undisputed place outside the substation without any extra cost. A. Gantry Towers iii) CT-4
FOUNDATIONS Design, engineering, supply of labour, TandP, material and construction of RCC footings and pedestals etc. for steel gantry and equipment structures complete in all respects as per technical specifications including cost of excavation, concreting, cement, reinforcement steel, form work, grouting, holding down bolts, backfilling etc. and other items not mentioned herein but required for the completion of work. Surplus earth, if any shall be disposed of to a suitable undisputed place outside the substation without any extra cost. A. Gantry Towers iv) CT-5
Supply and installation of 2 fittings of 240W LED Lamps with all accessories for complete lighting of outdoor switch yard area as per specification.
Supply and installation of 35W LED tube on l tubular steel pole along with the boundary wall at distance 30 mtr as technical n specification of HVPNL.
Complete lighting of road and street by providing 90W LED lamps on tubular steel poles at a distance of 15mtr along the roads and streets as per technical specification of HVPNL.
Supply and installation of post top lalten 40W LED lamps with all complete accessories at the entrance gate of substation.
Supply and installation of 40W LED lamps with all complete accessories on comers of control room building.
SITC of 66 kV Bus PT as per Technical Specification
SITC of 66 kV LINE PT as per Technical Specification
SITC of Control Relay Panel Line Protection and Circuit Breaker Panel (Without Auto Reclose).
Cable Trench :- Supply of labour, material such as cement, reinforcement steel, Gl angles, flats, PCC and brick pills below cable trenches for construction of Out-Door Cable Trenches (ODCT) of required depth/ type with pre-cast RCC covers Including associated works like Cable Trench Culverts crossings for roads and sump- pft-cum- pump chamber with 2HP motor of reputed make, starter, volt meter, amp-meter etc. as per foundation and trench layout plan attached, HVPNL drgs. and tech. specs. complete in all respect. I) D-type trench
Cable Trench :- Supply of labour, material such as cement, reinforcement steel, Gl angles, flats, PCC and brick pills below cable trenches for construction of Out-Door Cable Trenches (ODCT) of required depth/ type with pre-cast RCC covers Including associated works like Cable Trench Culverts crossings for roads and sump- pft-cum- pump chamber with 2HP motor of reputed make, starter, volt meter, amp-meter etc. as per foundation and trench layout plan attached, HVPNL drgs. and tech. specs. complete in all respect. II) E- type trench
Cable Trench :- Supply of labor, material such as cement, reinforcement steel, Gl angles, flats, PCC and brick pills below cable trenches for construction of Out-Door Cable Trenches (ODCT) of required depth/ type with pre-cast RCC covers Including associated works like Cable Trench Culverts crossings for roads and sump- pft-cum- pump chamber with 2HP motor of reputed make, starter, volt meter, amp-meter etc. as per foundation and trench layout plan attached, HVPNL drgs. and tech. specs. complete in all respect. iii) F-type trench
Cable Trench :- Supply of labor, material such as cement, reinforcement steel, Gl angles, flats, PCC and brick pillws below cable trenches for construction of Out-Door Cable Trenches (ODCT) of required depth/ type with pre-cast RCC covers Including associated works like Cable Trench Culverts crossings forr oads and sump- pft-cum- pump chamber with 2HP motor of reputed make, starter, volt meter, amp-meter etc. as per foundation and trench layout plan attached, HVPNL drgs. and tech. specs. complete in all respect. iv) H-type trench
Cable Trench :- Supply of labour, material such as cement, reinforcement steel, Gl angles, flats, PCC and brick pillws below cable trenches for construction of Out-Door Cable Trenches (ODCT) of required depth/ type with pre-cast RCC covers Including associated workslike Cable Trench Culverts crossingsforroads and sump- pft-cum- pump chamber with 2HP motor of reputed make, starter, volt meter, amp-meter etc. as per foundation and trench layout plan attached, HVPNL drgs. and tech. specs. complete In all respect. v) Sump Pit Cum Pump Chamber
Supply and Erection of Bolted type 66 kV Single tension string assembly for overhead conductor.
Supply and Erection of Bolted type 66kV single suspension string assembly for overhead conductor.
Supply and Erection of 90 KN Disc Insulators.
Supply and Installation of 220V, 100 AH, Tubular type lead acid DC Battery Bank with SAN container.
Supply and Installation of 220V DC Battery Charger suitable for float and Float cum boost charger capable of supplying a DC continuous load of 100 Amps as per specification and with a common DCDB comprising of Battery Charger.
Supply and Erection of 3.5 core x 50 sq mm LT PVC armored cable.
SITC of 66 kV Isolator 1250A, 31.5 KA (With earth switch).
Supply, installation, testing, commissioning of 3.6MVR 11KV Capacitor Bank. With APFC Panel and allied Accessories.
Substation Automation System (SAS) for 3 no`s 66 and 11KV Panel Board 4 no`s spare bay as per technical Specification and System Architecture to be designed and approved by HVPNL/GMDA including all licensed software`s (License shall be in the name of purchaser), signal cables inclusive of telecommunication system. It includes supply of 2 no`s workstation.
Supply installation testing and commissioning of 66kv SF6 Circuit Breaker (1250 A, 31.5 KA for 1 sec,) with 20% extra SF-6 gas as per technical specification.
SITC of LT Panel board of 3000KVA Transformer with two no`s Incomer and 1 no`s Bus coupler and 10 no`s Outgoing feeders.
SITC of ABT Meter (Main and check) and TOD (Main and Check) with cubical, CMRI,Base computer software with laptop.
AC Distribution Board, supply and installation of AC 415V ,50 KA for 1 Sec cubicle type Indoor, floor mounted, auxiliary service board as per specification comprising of: 2 No. - Incoming feeders TP ACB with O/C, S/C, E/F release. Suitable to operate from remote and all status to be taken to SCADA, 1 Nos. - Bus coupler feeder TPN ACB with O/C, S/F, E/F release. Suitable to operate from remote and all status to be taken to SCADA, 30Nos. - Outgoing feeders.
Supply and Erection of Equipment Clamp Connectors etc. (CT, PT, Iso, CB, Trf, LA, C-wedge Connector Etc.).
Supply and Erection of Fible Clits, aluminum Clamp, bolts, nuts, Washers, etc. for fixing of control cable in trenches.
Supply and Erection of Lattice type steel structure for 66kv substation, supply of material, preparation of fabrication drawing etc. (Tower, Beam, CT, PT, Iso, LA, NCT, U-bolt 20mm etc.)
Supply and installation of Dewatering pump (portable type) 415 V, 1 HP as per requirement .
SITC of DCDB System : 1 No. incomer with 250A, DP DCMCCB and to terminate 2 core 50 sqmm Al. cable , 20 Nos. outgoing feeders each with 40/32 A DP rotary switch with HRC fuses as per the requirement and as per the approved drawings.
Supply of Meggar 10 KV (Motorized):- 1 no`s , Digital Multi meter :- 1No`s , Leakage tester micro Amp (Tong type) :-1 No`s , Micro-ohm meter 200A :-1No`s , D-Spanner set (Insulated) :-2 No`s , Ring-Spanner set (Insulated):- 2 No`s , Torque wrench set:-2No`s , Insulating gloves:- 5No`s , Helmets:- 5No`s , Spliced ladders:-5No`s , Oil BDV Kit 0-100 KV :-1No`s , Providing and installation of First Aid box and accident prevention chart.:-2 No`s
FOUNDATIONS Design, engineering, supply of labour, TandP, material and construction of RCC footings and pedestals etc. for steel gantry and equipment structures complete in all respects as per technical specifications including cost of excavation, concreting, cement, reinforcement steel, form work, grouting, holding down bolts, backfilling etc. and other items not mentioned herein but required for the completion of work. Surplus earth, if any shall be disposed of to a suitable undisputed place outside the substation without any extra cost. A. Gantry Towers i) BT-1
FOUNDATIONS Design, engineering, supply of labour, TandP, material and construction of RCC footings and pedestals etc. for steel gantry and equipment structures complete in all respects as per technical specifications including cost of excavation, concreting, cement, reinforcement steel, form work, grouting, holding down bolts, backfilling etc. and other items not mentioned herein but required for the completion of work. Surplus earth, if any shall be disposed of to a suitable undisputed place outside the substation without any extra cost. A. Gantry Towers ii) BT-3
Soil Testing
PANEL SET , 11 KV Switchgear Panel 17 Nos Panel board with 4 no`s Incoming and 1 no`s bus coupler , 2 no`s outgoing for transformer ,1 no`s for capacitor bank , 9 no`s Outgoing , 12kV, 500 MVA for 1 Secs., 2000 A, Indoor VCB switchgear panel with required PT`s, CT`s, protective relays, metering equipment, auxiliary equipment, extensible (both sides) copper bus bars, complete cable termination kits as per cable sizes specified in SLD, 12kV switchgear outgoing feeder panel with VCB, CTS, Metering, Copper bus bar, cable sealing kit, auxiliary relays etc., as per specification. Note: *The 11 KV Switchgear board shall be complete with Numerical relays and compatible with SCADA system as defined in the technical specifications. All outgoing feeders shall have separate Electronic Tri vector meter of accuracy class 0.2S for energy recording and have earth switch. All meters shall have recorded facility as well as data download facility and MR provisions with software and laptops as per the requirements. All the panel, relays and meters etc. shall of same make, i.e. 11KV switchgear offered should come as complete unit from the manufacture and relays, meters, panel etc. shall be of that manufacture only. All panels shall have TTBs in front for meter sealing.
Boundary wall:- Designing and construction of boundary wall of 66 KV substation in WTP Chandu Budhera with height shall be 1.50Mtr with RCC pillar @3Mtr C/C as per design / drawing foundation of boundary wall shall be minimum 0.90m below natural ground level.
Supply, installation, testing and commissioning of 10 MVA, 66/6.6 kV, 3 Ph, `YnYn0 ONAN/ONAF Transformer with OLTC and RTCC panel. with bushing NCT
3000 KVA, Copper Wound 6.6/0.433kV 3ph, Dyn-11, outdoor type `with OFF load tap changer LT Transformer with cable box on HV and LV sides.
SITC of Time synchoronization Equipments.
Supply and Erection of 2 core x 50 sqmm copper conductor cable 1.1 KV PVC insulated and sheathed, steel wire armoured .
Operation and Maintenace including Repairing/Replacement of all system faults/ faulty equipment as required at site as per the complete satisfaction of Engineer-in-Charge
Bidder Name
Amount
ETHOS POWER PRIVATE LIMITED (GSTN-06AACCE9507D1ZW) BID ID -1157173
Naresh Agarwal Constructions Pvt. Ltd. (GSTN-NA) BID ID -1183336
ETHOS POWER PRIVATE LIMITED (BID ID -1157173)
ETHOS POWER PRIVATE LIMITED (BID ID -1157173)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid