SM EE
SM EE RHQ SR
Augmentation of AirConditioning System at ATS Complex and NAVAIDS by Replacing AHUs Phase II and Split ACs at Southern Region Chennai Airport
2024_AAI_192006_1
AAI/RHQ/SR/ED-II/AHU/2024
Open Tender
Electrical Works
Item Rate
150 days
RHQ SR
Please refer Tender documents.
18 documents required · 18 mandatory
₹1,180
₹2.6 L
9 Oct 2024
21 Mar 2024
16 Apr 2024
22 Mar 2024
15 Apr 2024
22 Mar 2024
22 Mar 2024 - 4 Apr 2024
Amount
SH-I: AHU RELATED WORKS:
Supply, Installation, Testing and Commissioning of factory built floor mounted chilled water double skin type Air Handling Units (AHUs) made out of 25mm thick panels consisting pre coated G.I casing of thickness 0.8mm outside layer and 0.8mm inside layer with polyurethene foam (PUF) insulation having 38 kg/cu.M density, factory injected between them by injection moulding machine, complete with blower section with Backward curve blower, blower suitable for static pressure as detailed below, UVGI lamps between cooling coil and drift eliminators with necessary door limit switch ON/OFF control, PVC drift eliminators, Four row deep cooling coil with 0.15mm thick hydrophilic coated aluminium fins, copper tubes having min 0.5mm wall thickness & 12.5mm dia, filter sections with 50mm thick metal viscous /washable synthetic type MERV8 air pre-filters having 90% efficiency down to 10 Microns, drain connections, 18G thick stainless steel 304 grade drain pan with PUF / Nitrile rubber insulation, LED lights in each section of AHU with door switch control, belt drive package with TEFC drive motor of efficiency class IE4 suitable for 3 phase, 415 ± 10% volts, 50Hz, AC Supply, suitably designed for variable frequency drive applications, PCC cubicals to position the base frame of AHUs, necessary vibration isolation arrangement etc., including Installation, Testing and Commissioning of AHUs as detailed below: a) Necessary modification in the existing GI ducting to made suit the mouth connection with the new AHU including supply & fixing of necessary thermal & acoustic insulation as required. b) Necessary modification in the existing MS Chilled water pipeline including supply, fabrication of NEW MS 'C' class pipes of required size and length between cooling coil of AHU Inlet / AHU Outlet and butterfly valves of the AHU, supply & fixing of 2 Nos. drain valves (25mm ball valve) in chilled water pipes, supports, insulation with PUF sections, vapour barrier, GI wire mesh, sand cement plastering, approved coloring, etc as required. c) Necessary modification in the existing drain water piping for trouble free draining of condensate water including fabricating, supplying, fixing a removable 'U' trap having both side flanges with bolt nut arrangement (easy removal for cleaning), thermal insulation, sand cement plastering, coloring at the drain outlet of AHU. d) Termination of existing power cable, earth wires, control cables, Fire panel cable, Remote control cables for remote ON & OFF of AHU from remote location, etc. (with new starter panel) complete as per specifications and of following capacities:
a) 10 TR Capacity, 5,600 CFM, 9,515 CMH b) K.Calorie per hour-30,000 c) Static pressure -75mmWC d) Quantity of Blower - 1 No. e) Location: Ground floor, 1st floor & 2nd floor
a) 15 TR Capacity, 8,240 CFM, 14,000 CMH b) K.Calorie per hour-45,000 c) Static pressure -75mmWC d) Quantity of Blower - 1 No. e) Location: 1st floor, 2nd floor & 3rd floor
a) 20 TR Capacity, 10,900 CFM, 18,500 CMH b) K.Calorie per hour-60,000 c) Static pressure -75mmWC d) Quantity of Blower - 1 No. e) Location: Ground floor & 1st floor
a) 30 TR Capacity, 16,800 CFM, 28,544 CMH b) K.Calorie per hour-90,000 c) Static pressure -55mmWC d) Quantity of Blower - 1 No. e) Location: Ground floor
10 TR Capacity AHU at Ground floor, 1st floor & 2nd floor
15 TR Capacity AHU at 1st floor, 2nd floor & 3rd floor
20 TR Capacity AHU at Ground floor & 1st floor.
30 TR Capacity AHU at Ground floor.
Supply & fixing of MERV-13 air filter, washable type suitable to fix in flanges having size of 550mm x 550mm within existing supply air plenum of AHU rooms with necessary fixing arrangements like clamps, bolt, nut, washer etc complete as required.
Supply and Fixing of following size butterfly valves wafer type with matching flanges, bolt, nuts, insulation, etc after cutting in the existing chilled water header pipes of AHU rooms including removal of existing insulation, providing one set of individual Tools, Men & Matrials for every two numbers butterfly valves at a time (i.e Five set of tools, men & materials for Ten butterfly valves at a time to minimise the down time of Air conditioning), etc complete as required.
100 mm dia
80 mm dia
Supply and Fixing of following size butterfly valve wafer type with matching flanges, bolt, nuts, insulation, etc after cutting in the existing supply & return chilled water pipes of AHUs including welding and removal of existing insulation etc complete as required.
80 mm dia
65 mm dia
50 mm dia
Supply and Fixing of following size balancing valve with matching flanges, bolt, nuts, insulation, etc after cutting in the existing supply & return chilled water pipes of AHUs including welding and removal of existing insulation etc complete as required.
80 mm dia
65 mm dia
50 mm dia
Supply and Fixing of following size MS " Y" Strainer with matching flanges, bolt, nuts, insulation, etc after cutting in the existing supply & return chilled water pipes of AHUs including welding and removal of existing insulation etc complete as required.
80 mm dia
65 mm dia
50 mm dia
Supply, Installation, Testing and Commissioning of following size 3-way Modulating valve with actuator, matching flanges, bolts, nuts, insulation, Thermostat with temperature adjustment, necessary wiring for normal working, etc complete as required.
80 mm dia
65 mm dia
50 mm dia
Supply and Fixing of 25 mm ball valve with MS pipe nipple for AHU Chilled water Header lines including welding etc complete as required.
Suply and Fixing of digital type Thermometer with adopter for AHU chilled water line including welding etc complete as required.
Supply and Fixing of dial type Pressure gauges of 150mm dia for AHUs including forged ball valves and pipe stem, welding etc. complete as required.
Supply and Fixing of Canvass Connection between AHU & Duct made of fire retardant type cloth of required size with suitable fixing arrangement etc complete as required.
Supply & fixing of extruded aluminium powder coated fresh air grills without collar dampers with necessary fixing arrangements like clamps, screws, washer etc.
Supply, Installation, Testing and Commissioning of Opposed blade G.I Construction box type factory fabricated duct Volume Control Damper made of 18 SWG thick GI Sheet complete with nuts, bolts, screw, linkage, flanges, duct lever and quadrants etc complete as required.
Dismantling the existing Air Handling Units (AHUs) of following capacity from different floors of Air Traffic Service (ATS) Complex i/c motor, blower, cooling coil, electrical panel, complete UVGI system, Chilled water pipelines at Inlet & Outlet of AHUs upto 3-way mixing valve, etc with all associated accessories and handing over of all dismantled items to AAI stores, including transportation, loading & unloading etc. complete as required.
4.95 TR capacity
6.75 TR capacity
9.27 TR capacity
13.81 TR capacity
18 TR capacity
25.80 TR capacity
SH:II FRESH AIR VENTILATION SYSTEM
Supply, installation, balancing and commissioning of GSS sheet metal rectangular/round ducting (fabricated at site) as per IS 655-2006 complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.
0.63 mm thick
0.80 mm thick
Supply, Installation, Testing and Commissioning of following capacity ceiling suspended type axial flow fan complete with suitable capacity AC 3 Phase induction motor, DOL Starter Panel having protections for single phasing, phase reversal, overload, short circuit etc with auto restart facility during power failure, Electrical terminal box at outside of fan, dry pre-filter, volume control damper, suspension arrangement made of GI threaded rod / angle iron, vibration arresters, electrical termination, earth connections, etc as reqd.
3000 CFM, 25mmWC Static pressure
1500 CFM, 25mmWC Static pressure
Supply, Installation, Testing and Commissioning of 24G thick GI cowl and bugmesh shall be fixed to the discharge side of the fans at variuos levels of building with necessary supporting arrangenents, fasteners, etc complete as reqd.
GI Cowl
GI Bug mesh
Supply, Installation, Testing and Commissioning of GI back draft damper with suitable links shall be fixed to the discharge side of the fans with necessary supporting arrangenents, fasteners, etc complete as reqd.
Dismantling the existing fresh air ventilation system from following locations i/c tube axial fans, Ducts, supports, VCDs, End cowl, etc. complete with all associated accessories and handing over of all dismantled items to AAI stores, including transportation, loading & unloading etc complete as required. i. Ground floor air side AHU room - 1 set ii. First floor air side AHU room - 1 set iii. Second floor air side AHU room - 1 set iv. Third floor air side AHU room - 1 set v. Third floor city side AHU room - 1 set
SH-III: SITC OF UNITARY AIR CONDITIONERS:
Supply, Installation, Testing and Commissioning of 4 TR capacity Floor standing tower type Split AC unit, fitted with hermetically sealed compressor operating on 415 V +10% 50 Hz 3 phase AC supply with evaporator and condensing unit made of copper tubes with aluminium fins i/c cordless remote control, Angle iron floor stand for indoor unit, angle iron wall / floor stand for condensing unit, etc complete as required.
Supply, Installation, Testing and Commissioning of 2 TR capacity wall mounted type Split AC unit, 5 star rated, invertor type, fitted with hermetically sealed compressor operating on 220 V +10% 50 Hz Single phase AC supply with evaporator and condensing unit made of copper tubes with aluminium fins i/c cordless remote control, copper piping for both suction and discharge of 3 metres standard length alongwith power & control cables and thermal insulation, angle iron wall / floor stand for condensing unit, etc complete as per specifications complete as required
Supply, Installation, Testing and Commissioning of 1.5 TR capacity wall mounted type Split AC unit, 5 star rated, invertor type, fitted with hermetically sealed compressor operating on 220 V +10% 50 Hz Single phase AC supply with evaporator and condensing unit made of copper tubes with aluminium fins i/c cordless remote control, copper piping for both suction and discharge of 3 metres standard length alongwith power & control cables and thermal insulation, angle iron wall / floor stand for condensing unit, etc complete as per specifications complete as required
Supply and Installation of Copper pipe for the following capacity Air conditioners including suction and delivery copper pipes with all accessories such as insulation, power & control cabling, etc. as per specifications complete as required
For 4 TR floor standing tower type Air conditioner
For 2 TR Split Air conditioner (beyond 3 meters per Split AC unit)
For 1.5 TR Split Air conditioner (beyond 3 meters per Split AC unit)
SITC of following capacity voltage stabilisers with copper wound coil having range of 170 to 270 voltage single phase, 50 Hz AC supply i/c necessary fixing arrangements, clamps, screws, metal clad top, connecting 3 core cable of 1 metre length, complete, etc as per specifications complete as required.
5 KVA stabilizer for 2 TR Spilt AC
4 KVA stabilizer for 1.5 TR Spilt AC
Supplying & laying of condensate water drain pipe made of PVC having size of 40mm dia, 6kg/cm capacity, for additional requirement for AC units i/c necessary clamps, screws, supports, etc as per specifications complete as required
Supply and fixing of following rated Cyclic timer for Split / Tower type air conditioners, suitable for cycle the air conditioners between duty and standby units at predetermined intervals that are suitable between 1 to 12 hours, with necessary buttons, display, inbuilt power and control contactors, control circuits, terminals, etc., as per specifications complete as required.
Cyclic timer for split AC having 2 TR capacity, AC single phase power supply. Similar to Model no. A-MCT-02, make of Presevi Industries Pvt Ltd.
Cyclic timer for split AC (Floor standing, Tower typer) having 4 TR capacity, AC, 3 Phase power supply. Similar to Model No. A -MCT-02-AM, make of Presevi Industries Pvt ltd.
Dismantling and shifting of following capacity Indoor and outdoor units to AAI store /any location specified by AAI, including gas pumping down, pipes, cables, etc.,complete as required.
1.5 TR capacity split AC
2.0 TR capacity split AC
3.0 TR capacity split AC
SH-IV: ELECTRICAL WORKS:
Supply of following size XLPE insulated PVC sheathed aluminium conductor armoured power cable of 1.1KV grade confirming to IS 7098 (PART-l) with upto date amendments etc as required.
4C x 10 sq.mm
4C x 16 sq.mm
Laying and fixing of one number XLPE insulated PVC sheathed aluminium conductor armoured power cable of 1.1KV grade of size upto 35 sq.mm on wall surface including suitable size clamping as per CPWD specification etc as required.
Laying and fixing of one number XLPE insulated PVC sheathed aluminium conductor armoured power cable of 1.1 KV grade of size upto 35 Sqmm size on cable tray including suitable size clamping as per CPWD specification etc as required.
Supplying and making end termination with brass compression gland and aluminium lugs for following size of XLPE insulated PVC sheathed aluminium conductor armoured power cable of 1.1 KV grade etc as required.
4 X 10 Sq.mm (25 mm)
4 X 16 Sq.mm (28 mm)
4 X 25 Sq.mm (28 mm)
Providing and fixing 6 SWG dia G.I wire on surface or in recess for loop earthing etc as reqired.
Supply, Installation, Testing and Commissioning of 16/20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A "C" curve, SP, MCB in sheet steel enclosure, with chained metal cover for the socket outlet and complete with connections, etc. as required.
Supply, Installation, Testing and Commissioning of 25/32 A "C" curve, 4 pole, MCB in sheet steel enclosure, complete with connections, etc. as required.
SH-V Buyback of AHUs, Split Acs & Ventilation System
Buyback of following capacity dismanled Air Handling Units, Split AC units and ventilation system of following capacity from different floors of Air Traffic Service (ATS) Complex on "As Is Where Is" Basis. (a) AHU consist of Motor, blower, cooling coil, all sheet steel panels, Air filters, electrical starter panel, Chiller water pipilines at Intel & Outlet of AHUs upto and including IN & OUT valves, 3-way mixing valve, Balancing valve, Volume control damper, etc (b) Split AC consist of Indoor & outdoor units and associated copper tubes etc (c) Fresh Air Ventilation System consist of axial flow fans, starter, duct, VCD etc
Air Handling units and associated installations
4.95 TR, 3000 CFM capacity - 2 Set
6.75 TR, 5000 CFM capacity - 1 Set
9.27 TR, 5600 CFM capacity - 1 Set
13.81 TR, 8300 CFM capacity - 4 Set
18 TR, 10800 CFM capacity - 4 Set
25.80 TR, 15500 CFM capacity - 1 Set
Split/Tower type Air-conditioners
1.5 TR capacity split AC - 31 Set
2.0 TR capacity split AC - 15 Set
3.0 TR capacity split AC - 11 Set
Ventilation system
Ground floor air side AHU room - 1 Set
First Floor air side AHU room - 1 Set
Second floor air side AHU room - 1 set
Third floor air side AHU room - 1 set
Third floor city side AHU room - 1 Set
All the above from 40.00 to 40.17
GEMINI COOLING SYSTEMS PROJECTS PRIVATE LIMITED
VOLTAS LIMITED
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .