| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.8 LAccepted-AOC | L1 | Accepted-AOC MS Raj Aryan Construction is lowest and accepted | |
| 2 | L2₹20.8 L+₹1.1 L (5.55%)Rejected-Finance B 1203 VRINDA RESIDENCY BARIATU ROAD RANCHI JHARKHAND 834009 | RANCHI | RANCHI | JHARKHAND | 834009 | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹25.0 L+₹5.3 L (26.8%)Rejected-Finance | L3 | Rejected-Finance Not Lowest | |
| 4 | L4₹28.9 L+₹9.1 L (46.4%)Rejected-Finance 30 INDUSTRIAL AREA KOKAR RANCHI 834004 JHARKHAND | RANCHI | JHARKHAND | 834004 | L4 | Rejected-Finance Not Lowest | |
| 5 | L5₹29.6 L+₹9.8 L (49.9%)Rejected-Finance | L5 | Rejected-Finance Not Lowest |
Tender Value
₹23.2 L
EMD Value
₹46,460
Closing Date
27 Jun 2023, 6:00 pmClosed
Y K Gour
HQ CWE Ranchi, MES, Dipatoli Cantt
REPAIR AND MAINTENANCE OF 33KV 11KV OUTDOOR SWITCH YARD TRANSFORMER HT SWITCH GEAR HT UG CABLE OH LINE AND ALLIED WORKS UNDER GE DIPATOLI
2023_MES_599515_1
80599/1477/E8
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
GE Dipatoli
Please refer Tender documents.
5 documents required · 5 mandatory
₹500
GE Dipatoli
₹46,460
Yes
HQ CWE Ranchi
11 Aug 2023
30 May 2023
4 Jul 2023
30 May 2023
27 Jun 2023
13 Jun 2023
30 May 2023 - 6 Jun 2023
6 Jun 2023
Amount
M &L for overhauling/Servicing/preventive maintenence of 33 KV VCB, 400 Amp indoor door type of cleaning isolating contacts ,moving parts removing dust particles from bus bar chamber spout gear mechanism and moving parts,repair to motor charge spring mechanism including greasing of the moving parts,cleaning of the moving/Stationary contact with CTC,Removing of moisture by means of hot air blower,renewal of gaskets,nuts/bolts etc entire trolly components and replacement of all unserviceable spares as required at site and all as directed ,inserting in trolley,testing commissioning and putting on the supply on load complete and as per under mention scope complete all as specified and as directed at site. (i) Examination of auxiliary switches, indicating devices and interlocks to ensure that they are in good order physically. (ii) Check fixed and moving contacts. (iii) Physical checking of Epoxy Housing (iv) Check close & trip coil (v) Checking of control circuit & tighten the connection if any. (vi) Test shall be carried out closing & opening timing test for all three poles (vii) Test shall be carried out IR test with megger- using 5 Kv Meggar (viii) Test shall be carried out contact resistance Kit for all three poles (ix) Caliberation & testing of relay for closing, tripping with necessary current setting as required at site.
M&L for overhauling/Servicing/preventive maintenence of 11 KV VCB, 400/630 Amp indoor door type cleaning isolating contacts ,moving parts removing dust particles from bus bar chamber spout gear mechanism and moving parts,repair to motor charge spring mechanism including greasing of the moving parts,cleaning of the moving/Stationary contact with CTC,Removing of moisture by means of hot air blower,renewal of gaskets,nuts/bolts etc entire trolly components and replacement of all unserviceable spares as required at site and all as directed ,inserting in trolley,testing commissioning and putting on the supply on load complete and as per under mention scope complete all as specified and as directed at site. (i) Examination of auxiliary switches, indicating devices and interlocks to ensure that they are in good order physically. (ii) Check fixed and moving contacts. (iii) Physical checking of Epoxy Housing (iv) Check close & trip coil (v) Checking of control circuit & tighten the connection if any. (vi) Test shall be carried out closing & opening timing test for all three poles (vii) Test shall be carried out IR test with megger- using 5 Kv Meggar (viii) Test shall be carried out contact resistance Kit for all three poles (ix) Caliberation & testing of relay for closing, tripping with necessary current setting. Note:- (i) Spares/ parts required shall be measured and paid separately under supply only items. (ii)The job included all types tools & plants required for satisfactory completion of job. Note for ser item No 1 and 2: (i) Spares as required for replacement will be of the same company as of existing make or as recommended by the OEM. The contractor/Rep of OEM should visit the site asess the serviceability of parts and list out the unservicceable spare parts for replacement during the preventive maintenance. (ii) Cost of spares will be measured and paid separately under relevantsupply only items. (iii)The job included all types tools & plants required for satisfactory completion of job. (iv) Test Report must be submitted by contractor before placing of RAR/ Final bill.
Supply and fix only for replacement of closing coil - 24V DC suitable for 33 KV VCB 400 Amps as per existing make and model complete all as specified and directed .
Supply and fix for replacement of shunt trip coil - 24v/30v DC suitable for 33 KV VCB 400 Amps as per existing make and model complete all as specified and directed .
Supply and fix for replacement of closing coil - 24V DC suitable for 11 KV VCB 400/630/800 Amps as per existing make and model complete all as specified and directed .
Supply and fix for replacement of shunt trip coil - 24v/30v DC suitable for 11 KV VCB 400/630/800 Amps as per existing make and model complete all as specified and directed .
Supply and fix for replacement of charging Pawl set suitable for 11 KV VCB 400/630/800 Amps as per existing make and model complete all as specified and directed .
Supply and fix for replacement of Multifuntion Meter 5 Amps for 11 KV VCB 400/630/800 Amps as per existing make and model complete all as specified and directed .
Supply and fix in replacement Epoxy cast CT rating 200-100-50/5+5 Amp, 15 VA , Class 1.0, 5P10 of mould type suitable for 11 KV VCB 630/800 Amps as per existing make and model complete all as specified and directed .
Supply and fix in replacement Vaccum bottle interrupter as per exissting make and model complete all as specified and directed .
Supply and fix in replacement of charging motor suitable for 11 KV VCB 220/24 VDC as per existing make and model complete all as specified and directed .
Supply and fix in replacement spout for busbar circuit of panel suitable for 11 KV VCB 630/800 Amps as per existing make and model complete all as specified and directed .
M&L for servicing of oil type transformer 3.15 MVA 33/11 KV out door type of any make by disconnecting of HT bus bar connection,opening of doors etc complete cleaning of the inside compartment ,core and coils by vacuum cleaner incl lead supports,tap changer terminal boards,bushing and other insulated surface be wiped clean with dry cloth and all connections must be checked for tightening after cleaning up to the satisfaction of Engr-in- Charge the transformer must be meggred and connecting all connection and necessary testing complete with under mentioned scope of work. (i) Cleaning of transformer. (ii) Testing the transformer for IR values (iii) Checking/servicing/calibration of WTI for healthiness (iv) Magnetic balance test (v) IR Value check before and after the work (vi) Voltage ratio test at 440 V. (vii) DC logic test (viii) Commissioning of transformer after completion of work. Note :- (i) Test results obtained shall be recorded and produced to the Engr-in- Charge. (ii) All measuring equipments and T&P required shall be arranged by the contractor. (iii) Any item/activity not listed/covered here above and required during/completing the overhauling work will have to be arranged by contractor himself. (iv) The rate quoted shall be deemed to include for disconnection of transformer HV/LV terminations for testing work and re-connections after completion of repair work
M&L for servicing of oil type transformer capacity 25 KVA to 250 KVA 11/.433 kV Indoor/out door type of any make by disconnecting of HT bus bar connection and providing electric power to user by alternative arrangement, opening of doors etc complete cleaning of the inside compartment,core and coils by vacuum cleaner incl lead supports,tap changer terminal boards,bushing and other insulated surface be wiped clean with dry cloth and all connections must be checked for tightening after cleaning up to the satisfaction of Engr-in- Charge the transformer must be meggred and connecting all connection and necessary testing complete with under mentioned scope of work. defective part measured and paid under respective item howver fixing charges included. (i) Cleaning of transformer. (ii) Testing the transformer for IR values (iii) Checking/servicing/calibration of WTI for healthiness (iv) Magnetic balance test (v) IR Value check before and after the work (vi) Voltage ratio test at 440 V. (vii) DC logic test (viii) Commissioning of transformer after completion of work. Note :- (i) Test results obtained shall be recorded and produced to the Engr-in- Charge. (ii) All measuring equipments and T&P required shall be arranged by the contractor. (iii) Any item/activity not listed/covered here above and required during/completing the overhauling work will have to be arranged by contractor himself. (iv) The rate quoted shall be deemed to include for disconnection of transformer HV/LV terminations for testing work and re-connections after completion of repair work.
All as per above item for capacity above 250 to 630 kVA
M & L of HT bushing of transformer including metal and rubber parts and replacing with new bushes complete with new metal and rubber parts of any size and shape required for transformer from 25kVA to 250 kVA complete all as specified and as directed.
All as per above item for capacity above 250 to 630 kVA
M & L of LT bushing of transformer including metal and rubber parts and replacing with new bushes complete with new metal and rubber parts of any size and shape required for transformer from 25kVA to 250 kVA complete all as specified and as directed.
All as per above item for capacity above 250 to 630 kVA
Supply and Fix for incorporated to the repair of transformer off load tap changer switch of existing model / type of transformer of capacity 25 to 630 kVA complete all as specified and as directed..
M&L for dehydration/centrifuging of transformer oil minimum 3 cycles to achieve dielectric strength 50 kV in 2.5 mm gap electrode with centrifuging machine at site and testing of transformer oil before and after de- hydration complete all as specified and directed .
M&L for topping up/replacement of transformer chamber and conservator with new transformer oil upto a required level ( 60 KV di-electric strength in 2.5 mm gap electrode to with stand for one minute) in any type and capacity of transformer complete all as specified and directed .
M&L for high voltage coil of transformer including double paper insulated conductor of existing gauge and all insulating material,varnished etc complete all as specified and as directed
M&L for low voltage coil of transformer including double paper insulated conductor of existing gauge and all insulating material,varnished etc complete all as specified and directed .Matting with vaccum impregnation and baking of coil suitable for 250 KVA transformer complete all as specified and as directed.
Supplyand fix in replacement of silica gel complete all as specified and as directed .
S&F in replacement of top cover gasket of transformer suitable for any type/make/capacity upto 630 KVA(made up of cork sheet 5 mm thick) complete all as specified and directed .
Taking down defective transformer upto 630 KVA capacity from pole/structure/sub station after disconnecting the existing connection complete and removing to sub station then transporting the same to a reputed work shop for repairs.After repairing the same transporting back the repaired transformer (including loading and loading) to the directed location. After installing the transformer connection of LT and HT shall be done complete all as specified and as directed .
Attending any breakdown immiediately of 3.15 MVA power transformer by OEM service engineer to check and repair /replace any spares related break down and make the power transformer serviceable complete all as specified and directed at site. Note :-(i) Spares will be paid separately under relevant items. (ii) Checking of all electrical connection for its proper tightness. (iii) Proper care shall be taken to isolate the supply and it shall be ensured that repairs are carried out on No LIVE switch gears. (iv) Each switch gear/Load break switch/breaker shall be counted as a separate unit for the purpose of measurement.
Attending any breakdown immiediately of 25 kVA to 250 kVA transformer by OEM service engineer to check and repair /replace any spares related break down and make the power transformer serviceable complete all as specified and directed at site. Note : (i) Spares will be paid separately under relative items. (ii) Checking of all electrical connection for its proper tightness. (iii) Proper care shall be taken to isolate the supply and it shall be ensured that repairs are carried out on No LIVE switch gears. (iv) Each switch gear/Load break switch/breaker shall be counted as a separate unit for the purpose of measurement.
All as per above item for capacity above 250 to 630 kVA
Dismantling /taking down old unserviceable 33/11 KV Air break gang operated switches vertical/horigontal mounted including insulators and operating mechanism for insulators and operating mechanism for repair/replacement of broken/worn out components and insulators etc complete all as specified and directed at site.
S&F air break switch (GOD) vertical/horizontal, double break type triple pole mechanically operated mounted on double insulartors and steel frame with operating mechanism linked with ground level operating GI rod 25mm dia medium grade. GOD suitable for current rating upto 400 amps and suitable for HT 11 KV including connecting complete with locking arrangement complete all as specified and as directed.
S&F in replacement lightening arrestor non linear pole type MCOV 33 KV, normal discharge capacity 65 KA and impulse current with all fittings suitable for 33 KV electric working pressure including strap bolts and nuts and washers etc complete all as specified and as directed.
S&F in replacement lightening arrestor non linear, pole type MCOV 11 KV discharge capacity 65 KA, with all fittings suitable for 11 KV electric working pressure including strap, bolts, nuts and washers etc complete all as specified and as directed.
Taking down and repairing/overhauling of air break gang operated switch with DO fuse unit 11 KV/ 33 KV rating 200 Amp/400 Amp capacity triple pole mechanically operated mounted on insulators and steel frame installed vertically / horizontally , replacement of broken/worn-out components, oiling and greasing of mechanical moving parts, smoothing and polishing of electric contacts with providing conducting jelly of contacts refixed the same after repair including proper allienment complete all as specified and as directed. (Note:- Worn out component/ insulators / ASCR shall be measured and paid separately under respective items of this schedule.)
Supply only Female contact or fixed contact heavy duty and high conductive metal complete capacity 200A/400 Amp, 11 KV rated complete all as specified and as directed.
Supply only Male contact or Moving contact heavy duty and high conductive metal complete capacity 200A/400Amp 11 KV complete all as specified and as directed.
Dismantling cross-arms of MS,channel or angle sections & earth wire etc complete and setting aside for re-use with in 50 m distance complete all as specified and as directed.
Supply fixing and fabricating tray holding cross arms FI clamps support U clamps strips and back plates fabrication from structural steel section incl nut bolts washer bars etc of required size and thickness for supporting of cable tray by welding incl bending or welding cold or hot,drilling holes for bolt in any shape or size indicated and applying a coat of black paint finish over a coat of red oxide primer to support the cables complete all as specified and as directed.
M &L for GI Earthing complete with GI earth plate electrode 60cm x 60cm x6 mm buried directly in ground verticvally to size of depth not less than 0.90x 0.60 x 2.25 mtr below ground level with top edge of the plate at a depth not less than 1.5 mtr below ground level, earth plate connected to galvanised earth strip of size 25 X4 mm, 7.5 mtr long by means of brazing nuts, bolts, check nuts, & washers ,testing of completion (drawn in earth lead protection pipe light gade GI of size 32/40 mm dia) by means brazing at both edges with vertical plane of electrode all as shown in plate No 3 of SSR Part - I connected to earthing lead with Main switch/main control board,filling with charcoal dust 200 Kg, and common salt 100 KG , including necessary excavation and earth work in any type of soil ,perforated watering pipe,funnel with wire mesh,earth lead protection pipe light grade PCC chamber 1:3:6 type C1 (for even finish on both the faces) and RCC cover 1:2:4 Type B1,450 x450 x50 mm thick with 6 mm dia CTD bars 150 mm c/c with 2 Nos of handles of 10 mm dia steel rod all as specified and directed and testing on completion and connected to equipment with lugs and screw nuts etc all as specified and directed by EIC Note : (i) 7.5 RM GI earth wire deemed to be included in quoted rates beyond 7.5 RM wire shall be measured and paid separately. (ii) Earth resistance of earth pit should be not more than 02 Ohms on testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost. (iii) Rate quoted by the tenderer is deemed to included salt & Charcoal upto & above 450 mm top of GI Plate. iv) Megger required for testing will be be provided at site by the contractor. v) Contractor shall submit earth resistance testing report before submission of RAR.
S&F in replacement GI earth strip (25x4) mm strip with and including necessary clamps, nut bolts laid in ground complete all as specified and as directed.
S&F aluminium strip (25x3) mm by replacing unserviceble strip with and including necessary clamps nut bolts complete all as specified and as directed. Note for ser item No : Strip will be fixed on porcelain insulators with vertical insulators.
Traking down/dismantling HT PCC/steel tubular poles ,studs,insulator including V clamp,cross arms , earth wire support etc complete all as specified and as directed.
M&L Steel tubular swaged poles complete with cast iron base plate,finial taper plug,bolts,nuts & screws as specified type 410 SP-55 ( 11.00 Meters long) complete all as specified and directed at site rate include necessary excavation ,earth work & PCC work complete all as specified and as directed. .
M&L for painting of HT poles up to 11 mtr long including channels and applying two coats of aluminium paint including base paint strips and pole numbering with synthetic enamel paint of approved colour complete all as specified and as directed.
M&L for Spray Painting of Transformer of capacity 3.15 MVA , 33/11 kV outdoor type applying two coats of synthetic enamel paint over a coat of red oxide primer after cleaning, scraping, and filling of cavities complete all as specified and as directed.
M&L painting of 4 pole structure of any type/size/length and removing from existing pole painting by using wire brush and using with emary paper and cleaning with chemical agents after cleaning of steel tubular pole and GI brackets and cross arms and applying two coats of silver oil painting over a coat of red oxide primer upto smooth finishining and painting to satisfactorly by engr-in-charge and painting work carryout at any height and including marking of pole number as directed and safety eqpts & tools will be own arrangements by the contractor complete all as specified and directed.
M&L painting of 2 pole structure of any type/size/length and removing from existing pole painting by using wire brush and using with emary paper and cleaning with chemical agents after cleaning of steel tubular pole and GI brackets and cross arms and applying two coats of silver oil painting over a coat of red oxide primer upto smooth finishining and painting to satisfactorly by engr-in-charge and painting work carryout at any height and including marking of pole number as directed and safety eqpts & tools will be own arrangements by the contractor complete all as specified and directed.
M&L painting of transformer / 4 pole/ 2 pole structure fencing of any type/size/length and removing from existing fencing painting by using wire brush and using with emary paper and cleaning with chemical agents and applying two coats of silver oil painting over a coat of red oxide primer upto smooth finishining and painting to satisfactorly by engr-in-charge and painting work carryout at any height and including marking of pole number as directed and safety eqpts & tools will be own arrangements by the contractor complete all as specified and directed.
M&L for GI stay assembly set comprising of 20 mm dia 380 mm iron stay bow 1800 mm long stay rod 20 mm dia 300x300x6mm stay plate thimble GI stay wire 7/8 SWG of required length ,incl,loop insulator,earth work and PCC complete withh all accessories as shown in electrical plate No.1 complete all as specified and directed.
Material & Labour cable jointing kit for 11 KV (Earthed) grade cable for indoor and termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 sqmm to 95 sqmm complete complete all as specified and directed.
Material & Labour cable jointing kit for 11 KV (Earthed) grade cable for outdoor and termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 sqmm to 95 sqmm complete all as specified and directed.
Material & Labour cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 sqmm to 95 sqmm complete all as specified and directed.
S & F Cable route indicator / Marker made up of PCC Block in cement mortar 1:3:6 (20 mm graded aggregrate) of size 900 x 300x 100 mm thick with "DANGER / 11 KV CABLE /MES or DANGER/ 11 KV HT JOINT/ MES" embossing on cable route Indicator / Marker including painting as per approved colour and buried in ground 45 Cms including necessary earth work (as required/ ordered at site) complete all as specified and as directed.
Taking down or up UG HT Cable including cable cover laid in trenches/ cable duct or connection to HT panel /GOD and removing from site and transporting to store for safe custody for reuse or for issue under Sch of Credit all as specified and directed at site including patrolling the complete length and inspecting for any punctures,blow holes,damages and meggering all the cables ,removing the damaged portion complete all as specified and directed.
Relaying the HT cable obtain from item No. 55 any capacity any size complete all as specified and directed.
Material and labour XLPE insulated ,screened ,PVC bedded,galvanised steel strip or wire armoured,electric power cables (heavy duty) with aluminium conductor,11000 volts(Earthed),grade cross sectional area 95 sqmm complete all as specified and directed.
Excavation in trenches not exc. 1.5 m wide and not exec 1.5 mtr in deep for foundation etc.or for shafts,wells,cesspits,mainholes,pierholes etc.in any type of soil for foundation and getting out and levelling of bottom surface to required level all as specified and directed by Engineer-in- Charge.
Material and labour for river washed and screened ,dry sand for filling in trenches/sub stations below and around underground cables for cushioning of cables etc complete all as specified and directed.
Returning filling including leveling,watering and well ramming soil in layers not exceeding 1.5 m above the starting level complete all as specified and directed.
Removing the excavated materials not exceeding 50 m and depositing where directed at level not exceeding 1.5 m above the starting level complete all as specified and directed.
Supplying and laying unreinforced precast cement concrete cable covers, Class HV, Type- 1, Flat, size 300 mm x 180 mm x 40 mm in trenches for cable protection, embossed with "HT ELECTRIC" on the top surface complete all as specified and directed.
Relaying the HT cable cover obtain from ser item No. 57 any capacity any size complete all as specified and directed.
Equipment and Electrician for fault finding on 11 KV HT cables in trenches of any size and any length with fault detective(fault finding) machine by thumbing method and injection suitable high voltage proper fault finding equipment and all as manufactures instructions and including necessary excavation, returning filling, removing surplus soil,sand, existing bricks etc where find the cable faulty complete all as specified and directed. Note : (i) Necessary earth work etc. shall be included in the quoted rate. (ii) Spares will be paid separately under relative items.
M&L for trenchless boring under road crossing/foot paths etc complete all as specified and directed.
Supply and laying in replacement of GI pipe 80 mm bore,Light grade (for cable protection ) ISI marked complete all as specified and directed.
Supply and laying in replacement of GI pipe 100 mm bore,Light grade (for cable protection ) ISI marked complete all as specified and directed.
Supplying and laying synthetic Rubber insulated mats 2.5 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified and directed.
Supplying and laying synthetic Rubber insulated mats 3 mm thick for voltage upto 33 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified and directed.
Providing tools and labour for cutting of tree branches including cutting of trunk branches & stacking of serviceable material and disposal of unsv materials to a distance not exc 50 mtr & clearing site complete all as specified and directed. Note:- (i) Safety measures will be provided by contractor. (ii) During tree /branches/vegitation cutting any damages occured on OH lines/installation will be contractor's responsibility to make good the damages. (iii) Approximately distance covered both side for the HT lines/installatons not exc 100 mtr measured as a one Job only. (iv)up to 50 mtr length to be measured as one span
arics infrastructure
Associated Engineers
Raj Construction
M/S Akash Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .