EE JSV Division Barsar
Providing and installation of pumping machinery in Barsar Constituency
2026_HPIPH_137550_1
NIT No. 3546-645 dated 25.06.2026
Open Tender
Civil Works
Item Rate
30 days
Sub Division Bhota
Please refer Tender documents.
8 documents required · 8 mandatory
₹350
EE Barsar
₹9,000
25 Aug 2026
25 Jun 2026
6 Jul 2026
25 Jun 2026
6 Jul 2026
25 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Providing/Installation horizontal spindle horizontal split casing/end suctions (backpull out arrangement) single/double multistages centrifugal pump or combination of energy saver pump in series/parrallel of recommanded make such as KSB/Kirloskar/ any approved make as per BIS 1520-1980 with upto date ammendments, read with 1S: 9137-1978 or latest edition suitable for lifting Raw water for under mentioned characterstics with bronze impellersupriming funnels, casing ring and shaft sleaves of bronze, shaft of steel grade EN-8 with cast iron casing coupled directly through a flexible coupling on a MS/Cast steel base plate (base plate to be from the manufacturers of the pumping unit only) to Squarrel cage/ slippering drip proof induction motor of standard make such as Kirloskar/Crompton/ABB/NGEF//make and suitable for operation on 400 (+/-) 10% volts. 50 cycles/second, 3 phase AC electric supply. The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of (+) 10% and (-) 25% of the duty point head. The motor should be as per IS: 325-1978 with upto date ammendments read with IS: 900-1972. It should include cost of bearing nuts, bolts and pointing etc. and should meet the following requirements:- | 2 | Per Set | 100 | ₹200 |
| 2 | Discharge (Q)10.38 LPS
Total Dynamic Head= 102.26 Meters
LWL. in sump well (h)= 368.50
Pump Shaft level= 368.50
Level at discharge point. = 464.10
Suction lift= (+ve) Meters
Residual heat =0.00 Meters
Static Head = 95.60Meters
Rising main Length = 290 Meters Dia = 125 mm
Pumping Hours= 8 Hours
Altitude of Installation above MSL= 500 Meters
Characteristics of water. (a) Temperature= 20°C
(b) Abient Temp= 42°C (c) Turbidity Clear water < 50.00 NTU (d) Alkalanity Mg/Ca Co3 (e) Size of the solids = mm
(f) Other | - | - | - | - |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.44 MB
form6.pdf
Tender Documents • 0.45 MB
form8.pdf
Tender Documents • 1.20 MB
BOQ_203597.xls
BOQ • 0.24 MB
termscondition.pdf
Additional Documents • 0.40 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .