Loading…
Loading…
Tender Value
₹21.4 Cr
EMD Value
₹21.4 L
Closing Date
24 Sept 2026, 12:30 pm
Superintending Engineer
ESDC-II, UPPTCL, 13th Floor Shakti Bhawan Extn, 14-Ashok Marg, Lucknow
Construction of 2x40 MVA 132/33KV UPEIDA IMLC S/S Naseerpur, Firozabad on turnkey basis
2026_PTRCL_1176013_1
ESD-686
Open Tender
Construction Works
Turn-key
365 days
superintending Engineer ESDC-II
Please refer Tender documents.
2 documents required · 2 mandatory
₹2,950
ICICI Bank A/C No 628105038318
₹21.4 L
10 Aug 2026
10 Aug 2026
26 Sept 2026
11 Aug 2026
24 Sept 2026
11 Aug 2026
Tender Specification no. ESD-686
Name of Bidder:
SCHEDULE OF QUANTITIES & PRICES FOR SUPPLY OF EQUIPMENTS/MATERIALS AND LIGHT LUMINAIRES FOR 2X40MVA, 132/33kV SUBSTATION UPEIDA (IMLC) NASEERPUR, FIROZABAD (SAS based on Double Main and Transfer Bus Scheme)
S. N. Item/ Equipments along with all accessories as per specifications Unit Tendered Qty. Unit FOR (Ex-Works, Packaging, Forwarding, Freight & Insurance Charges) Rate without GST (Rs.) Applicable GST Amount @ 18% (Rs.) Unit FOR (Ex-Works, Packaging, Forwarding, Freight & Insurance Charges) Rate with GST (Rs.) (5+6) Total FOR Destination Price with GST (4x7) (Rs.)
1.1 POWER TRANSFORMER,40MVA,145/36KV Nos 2 To be provided by UPPTCL
1.2 STATION TRANSFORMER,250KVA,36/0.420KV No 1
2 Circuit Breaker
2.1 SF6 CB,145KV,3150A,40KA Nos 6
2.2 VCB,36KV,2000A,31.5KA Nos 10
3 Current Transformer (CT)
3.3 CONNECTOR,CT,145KV,TWIN PANTHER Nos 36
3.4 JUNCTION BOX,CT,145KV Nos 6
3.5 CT,POLY,36KV,800-400-200/1A,3C,0.2S (with Terminal Connector) Nos 6
3.6 CT,36KV,400-200/1A,2C,0.2S (with Terminal Connector) Nos 24
3.7 JUNCTION BOX,CT,36KV Nos 10
4 Potential Transformer (PT)
4.1 PT,145KV,50VA Nos 12
4.2 CONNECTOR,CVT/PT,145KV,PANTHER Nos 12
4.3 JUNCTION BOX,CVT/PT,145KV Nos 4
4.4 PT,36KV,50VA (with Terminal Connector) Nos 6
4.5 JUNCTION BOX,CVT/PT,36KV Nos 2
5.1 ISOLATOR,145KV,CBR,1250A,MOTOR,W/1ES (LINE ISOLATOR) Nos 2
5.2 ISOLATOR,145KV,CBR,1250A,MOTOR,W/O ES (BUS ISOLATOR) Nos 10
5.3 ISOLATOR,TANDEM,145KV,HCB,1250A,MOTOR (TANDEM ISOLATOR) Nos 9
5.4 ISOLATOR,36KV,1250A,W E/S (LINE ISOLATOR WITH POST INSULATOR) Nos 8
5.5 ISOLATOR,36KV,1250A,W/O E/S (BUS ISOLATOR WITH POST INSULATOR) Nos 22
5.6 FUSE,DROP OUT (WITH POST INSULATOR) No 1
6 Post Insulator
6.1 BUS POST INSULATOR,145KV Nos 162
6.2 POST INSULATOR,36KV Nos 30
7 Surge Arrester
7.1 SURGE ARRESTOR,POLYMER TYPE,120KV Nos 12
7.2 SURGE ARRESTOR,POLYMER TYPE,30KV Nos 12
8 CRP & SAS (as per Technical Specification of SAS)
8.1 RELAY PANEL,UNDER FREQUENCY,145KV No. 1
8.2 C&R PANEL,TRANSFORMER,145KV Nos 2
8.3 C&R PANEL,SIMPLEX FEEDER,145KV Nos 2
8.4 C&R PANEL,BUS COUPLER,SAS,145KV No 1
8.5 PANEL,TRANSFER BUS COUPLER,145KV No 1
8.6 C&R PANEL,TRIPLE FEEDER,36KV Nos 3
8.7 SAS (Complete Set) LS 1
8.8 OPTICAL FIBER CABLE Lot 1
9 Battery & Battery Charger
9.1 BATTERY SET,LEAD ACID,110V,200AH Set 2
9.2 BATTERY CHARGER,110V,200AH No 2
10.1 DISTRIBUTION BOARD,110V,DC No 2
10.2 DISTRIBUTION BOARD,415V,AC,SWITCH YARD No 1
10.3 DISTRIBUTION BOARD,415V,AC,LIGHTING No 2
10.4 BAY MARSHALLING KIOSK,SWITCH YARD Nos 4
11 Capacitor Bank with all Accessories
11.1 2x5 MVAR, 33kV Capacitor Bank Unit Set 2
Simplex Type Control & Relay Panel for 33kV Capacitor Bank
VCB,36KV,2000A,31.5KA
3-Phase Reactor
CT,36KV,400-200/1A,2C,0.2S (with Terminal Connector)
JUNCTION BOX,CT,36KV
ISOLATOR,36KV,1250A,W E/S (LINE ISOLATOR WITH POST INSULATOR)
ISOLATOR,36KV,1250A,W/O E/S (BUS ISOLATOR WITH POST INSULATOR)
36kV NCT Ratio 5/1A
Terminal Connector for 36kV NCT
Junction Box for 36kV NCT
PT,3 PHASE,36KV
Terminal Connector for 3-Phase PT
12.1 1.1 KV PVC FRLS Unarmoured Copper Control Cable
12.1.1 CBL,CTRL,UNARM,PVC INS,CU,2CX2.5SQMM KM 12
12.1.2 CBL,CTRL,UNARM,PVC INS,CU,4CX2.5SQMM KM 30
12.1.3 CBL,CTRL,UNARM,PVC INS,CU,6CX2.5SQMM KM 15
12.1.4 CBL,CTRL,UNARM,PVC INS,CU,10CX2.5SQMM KM 10
12.2 1.1 KV PVC FRLS Unarmoured Alluminium Power Cable
12.2.1 CBL,POWER,UNARM,3.5CX400SQMM,1.1KV,AL KM 0.0
12.2.2 CBL,POWER,UNARM,3.5CX95SQMM,1.1KV,AL KM 1
12.2.3 CBL,POWER,UNARM,3.5CX50SQMM,1.1KV,AL KM 1
13 Structure & Earthing Material
13.1 STRUCTURE,LATTICE TYPE (Galvanised Main & Auxiliary Structures with MS angles, channels, plates, nuts, bolts, step bolts, U bolts, spring washers, etc. and any other required materials) MT 160
13.2 ROUND,MS,40MM RM 6500
13.3 ELECTRODE,MS,40MM,3M Nos 300
13.4 FLAT,MS,75X10MM RM 2500
13.5 FLAT,MS,50X6MM RM 2500
13.6 FLAT,MS,25X6MM RM 2000
14 Energy Meter
14.1 ENERGY METER,3-PHASE,4-WIRE,ABT,0.2S Nos 6
14.2 METERING CUBICLE No 1
14.3 SWITCH,NETWORK,16 PORT,14CU+2FO No 1
14.4 DATA CONCENTRATOR,DCU/COMM GATEWAY No 1
14.5 CABLE,LAN KM 0.2
14.6 CONDUIT PIPE,PVC,FLXBLE,50MM KM 0.2
14.7 CABLE,FO,ARMRD,6CORE,W/HDPE PIPE,32MM KM 0.5
14.9 LIU,6 PORT,W/ACCS Nos 2
14.1 SWITCH,NETWORK,8 PORT,6CU+2FO No 1
15.1 CONDUCTOR,ACSR MOOSE KM 4
15.2 CONDUCTOR,ACSR PANTHER KM 3
16 INSULATOR,PORCELAIN,ANTIFOG,70KN Nos 2200
17 Hardware Fittings
17.1 Single Tension Fittings Suitable for
17.1.1 FITT,BLTD,SINGLE TENSION,MOOSE Nos 120
17.1.2 FITT,BLTD,SINGLE TENSION,PANTHER Nos 100
17.2 Single Suspension Fittings Suitable for
17.2.1 FITT,BLTD,SINGLE SUSPENSION,MOOSE Nos 50
17.2.2 FITT,BLTD,SINGLE SUSPENSION,PANTHER Nos 80
17.3 PG clamps suitable for -
17.3.1 PG CLAMP,MOOSE/MOOSE Nos 300
17.3.2 PG CLAMP,MOOSE/PANTHER Nos 300
17.3.3 PG CLAMP,PANTHER/PANTHER Nos 450
17.4 Bus Post Clamps suitable for-
17.4.1 CONNECTOR,BPI,PANTHER Nos 50
17.4.2 CONNECTOR,BPI,TWIN PANTHER Nos 24
17.4.3 CONNECTOR,BPI,MOOSE Nos 12
17.4.4 CONNECTOR,BPI,TWIN MOOSE Nos 12
18 Fire Fighting equipments
18.1 FIRE EXT,MECH FOAM,50LTR Nos 4
18.2 Fire Extinguisher carbon dioxide (CO2) as per latest IS
18.2.1 FIRE EXT,CO2,IS 2878/1986,22.5KGS No 4
18.2.2 FIRE EXT,CO2,IS 2878/1986,9KGS Nos 5
18.2.3 FIRE EXT,CO2,IS 2878/1986,4.5KGS Nos 6
18.3 SAND BUCKET Nos 40
18.4 STAND FOR SAND BUCKET Nos 4
18.5 ALARM,FIRE PROTECTION & DETECTION SYSTEM (SMOKE & HEAT DETECTION) LS 1
19 DG SET, 100 KVA,SILENT conforming to latest MoEFCC/CPCB guidelines Nos 1
20 GI perforated trays of various sizes for all cable trenches in switchyard, control room
20.1 CBL TRAY,PERFORATED,225MM Mtr 100
20.2 CBL TRAY,PERFORATED,75MM Mtr 250
21 Lighting and Luminaires
21.1 Supply of Complete fitting of Street Light Luminairs with LED Lamp 110 to 130 Watt, with all accessories (make Philips/CGL/Bajaj) Confirming to IP:65 Nos. 42
21.2 Supply of Complete fitting of Post Top Lantern with all accessories with LED Lamp 40 to 45 Watt (make Philips/CGL/Bajaj) Confirming to IP:65 Nos. 10
21.3 Supply of 15W LED Lamp (make Philips/CGL/Bajaj) Nos. 15
21.4 Supply of Complete fittings of 18/20 Watt LED Tube Light (make Philips/CGL/Bajaj) Nos. 50
22 TESTING EQUIPMENTS (UPPTCL approved-make)
22.1 DC on load Earth Fault Locator No. 1
22.2 Earth resistance tester (4 terminal digital type with data storage and retrieval) No. 1
22.3 Automatic testing kit for BDV measurement of T/F Oil No. 1
22.4 Digital Clamp Meter (0-300-600 A) No. 2
22.5 10kV Digital Insulation Tester No. 1
22.6 Primary Injection kit No. 1
22.7 Thermal Imager Camera (640x480 px) No. 1
22.8 Digital Multimeter (4 ½ Digit ) No. 2
22.9 Self Supported Aluminium Ladder No. 2
22.1 Cartwheel Mounted Aluminium Ladder No. 1
22.11 Earthing/Discharge Rod having, 25 sq. mm. copper cable Nos 6
23 Fiber Optic Terminal Equipment (FOTE) SDH (STM-16)
23.1 Base equipment suitable for 04 directions in subrack fully equipped with all necessary common cards, power supply cards, other hardware & accessories including 10 Nos. optical patch cords of lengths as per site requirements, DDF etc. with redundant CPU. No 1
23.2 Short Haul, STM-16, 1310nm SFP Transceiver - S16.1 Nos 2
23.3 Long Haul, STM-16, 1310nm SFP Transceiver- L-16.1 Nos 4
23.4 Long Haul, STM-16, 1550nm SFP Transceiver- L-16.2 Nos 2
23.5 E1 Interfaces (120 Ohm) ( 32 Interfaces with 2 Cards) No 1
23.6 L2 Ethernet Interfaces 10/100 Base T (16 Interfaces with minimum 2 cards) No 1
23.7 Equipment cabinet for SDH and DTPC 2200mm (h) including 100mm base, w x d should be suitable for 19" or 23" Rack (Alongwith 110V to 48V DC-DC Converter) No 1
23.8 MDF (200 Pairs), mounted in cabinet No 1
23.9 04 command standalone Digital Tele-Protection Coupler (DTPC) fully equipped with necessary common cards power Supply Cards other Hardware accessories Connectors Cables Subtrack with E I path cords set of 04 etc. No 4
0.0 SECURITY SYSTEM,CCTV LS 1
25 Air Conditioner (AC) Unit - (Hitachi/LG/O'Gen/Daikin/Voltas/Bluestar/Samsung make)
0.0 2 Ton 5 Star Inverter type Split AC unit alongwith 5 KVA Stabilizer including stand for outdoor unit and copper kit with cable Nos 12
Total (INR excluding GST)
Seal of Company
Full Signature ………………………………
Designation ………………………………
Tender Specification no. ESD-686
Name of Bidder:
HANDLING, ERECTION, TESTING & COMMISSIONING CHARGES FOR 2X40MVA, 132/33kV SUBSTATION UPEIDA (IMLC) NASEERPUR, FIROZABAD (SAS based on Double Main and Transfer Bus Scheme)
Sl. No. Item/ Equipments along with all accessories as per specifications Unit Tendered Qty Unit handling, erection, testing & commissioning charges without GST (Rs.) Applicable GST Amount @ 18% (Rs.) Unit handling, erection, testing & commissioning charges with GST (Rs.) (5+6) Total handling, erection, testing & commissioning charges with GST (4x7) (Rs.)
1.1 EREC 40 MVA,132/33KV TRF Nos 2
1.2 EREC 250KVA,33/0.4KV TRF No 1
2 Circuit Breaker
2.1 EREC OF 145KV CB Nos 6
2.2 EREC OF 36KV VCB Nos 10
3 Current Transformer (CT)
3.1 EREC OF 145KV CT Nos 18
3.2 EREC OF JB FOR 145KV CT Nos 6
3.3 EREC OF 36KV CT Nos 30
3.4 EREC OF JB FOR 36KV CT Nos 10
4 Potential Transformer (PT)
4.1 EREC OF 145KV PT Nos 12
4.2 EREC OF JB FOR 145KV PT Nos 4
4.3 EREC OF 36KV PT Nos 6
4.5 EREC OF JB FOR 36KV PT Nos 2
5.1 EREC OF 145KV LINE ISO W/1ES Nos 2
5.2 EREC OF 145KV BUS ISO Nos 10
5.3 EREC OF 145KV TANDEM ISO W/1ES Nos 9
5.4 EREC OF 36KV LINE ISO Nos 8
5.5 EREC OF 36KV BUS ISO Nos 22
5.6 EREC OF 36KV DROP OUT FUSE SET No 1
6 Post Insulator
6.1 EREC OF 145KV POST INSULATOR Nos 162
6.2 EREC OF 36KV POST INSULATOR Nos 30
7 Surge Arrester
7.1 EREC OF 120KV LIGHTNING ARRESTER / SURGE ARRESTOR Nos 12
7.2 EREC OF 30KV LIGHTNING ARRESTER / SURGE ARRESTOR Nos 12
8 CRP & SAS (as per Technical Specification of SAS)
8.1 RELAY PANEL,UNDER FREQUENCY,145KV No. 1
8.2 C&R PANEL,TRANSFORMER,145KV Nos 2
8.3 C&R PANEL,SIMPLEX FEEDER,145KV Nos 2
8.4 C&R PANEL,BUS COUPLER,SAS,145KV No 1
8.5 PANEL,TRANSFER BUS COUPLER,145KV No 1
8.6 C&R PANEL,TRIPLE FEEDER,36KV Nos 3
8.7 SAS (Complete Set) LS 1
8.8 OPTICAL FIBER CABLE Lot 1
9 Battery & Battery Charger
9.1 EREC OF 110V BATTERY SET Set 2
9.2 EREC OF 110V BATTERY CHARGER No 2
10.1 EREC OF 110V DCDB No 2
10.2 EREC OF 440/415V ACDB No 1
10.3 EREC OF LIGHTING DIST BOARD No 2
10.4 EREC OF BAY MARSHALLING KIOSK Nos 4
11 Capacitor Bank & its Accessories
11.1 Erection of 2x5 MVAR, 33kV Capacitor Bank alongwith Vacuum Circuit Breaker, 3-phase reactor, CT, NCT, PT, Isolators, Control & Relay panel and all other required items (COMPLETE IN ALL RESPECT) Set 2
12.1 1.1 KV PVC FRLS Unarmoured Copper Control Cable
12.1.1 LAYING 2CX2.5SQMM UNARM CTRL CABLE including Terminations of cables (COMPLETE IN ALL RESPECT) KM 12
12.1.2 LAYING 4CX2.5SQMM UNARM CTRL CABLE including Terminations of cables (COMPLETE IN ALL RESPECT) KM 30
12.1.3 LAYING 6CX2.5SQMM UNARM CTRL CABLE including Terminations of cables (COMPLETE IN ALL RESPECT) KM 15
12.1.4 LAYING 10CX2.5SQMM UNARM CTRL CABLE including Terminations of cables (COMPLETE IN ALL RESPECT) KM 10
12.2 1.1 KV PVC FRLS Unarmoured Alluminium Power Cable
12.2.1 LAYING 3.5 core * 400 sq. mm including Terminations of cables (COMPLETE IN ALL RESPECT) KM 0.0
12.2.2 LAYING 3.5 core * 95 sq. mm including Terminations of cables (COMPLETE IN ALL RESPECT) KM 1
12.2.3 LAYING 3.5 core * 50 sq. mm including Terminations of cables (COMPLETE IN ALL RESPECT) KM 1
13 Structure & Earthing Material
13.1 EREC,STRUCTURES, MAIN/AUX, INCL ACCS: with MS angles, channels, plates, nuts, bolts, step bolts, U bolts, spring washers, etc. and any other required material MT 160
13.2 LAYG MS BAR 700MM-40MM DIA 40mm for Main Earthmat RM 6500
13.3 LAY,ELECTRODE,MS ROUND,40MMX3M,BLW GND 40mm Dia MS Electrode (3 M Long) Nos 300
13.4 FRESH EARTHG,W/FLAT,75X10MM RM 2500
13.5 FRESH EARTHG,W/FLAT,50X6MM RM 2500
13.6 FRESH EARTHG,W/FLAT,25X6MM RM 2000
14 Energy Meter
14.1 EREC OF ABT ENERGY METER Nos 6
14.2 EREC OF ABT ENERGY METERING PANEL with one main & one check rack No 1
14.3 INSTALLATION,DCU/GATEWAY/ETC including installation of Network Switch-16 Port, (14Cu+2 FO with FO Communication module (industrial frade), LIU (Light Interfacing Unit) with patchcord & accessories, Network Switch-08 Port, Data Concentrator (DCU)/ Communication Gateway (IG), laying of Lan Cable, PVC Conduit Pipe-3/4, OFC Cable Armoured (6P), HDPE Conduit Pipe 32mm Lot 1
15 Stringing of Conductors
15.1 Stringing of Bus bars comprising of Conductors Tension & Suspension stings complete with anti fog type disc insulators, tension & suspension clamps, PG clamps, Bus post clamps, connectors, earth wires and all other required material for KM 2.5
15.2 132 KV Main Bus I & II Lot 1
15.3 132 KV Transfer Bus Lot 1
15.4 132 KV Jack Bus for-
15.5 Feeder Lot 1
15.6 Power Transformer Lot 1
15.7 Bus Coupler Lot 1
15.8 33 KV Main Bus Lot 1
15.9 33 KV Auxilliary Bus Lot 1
15.1 JUMPERING TRF & ASSOC. EQUIP. Baywise interconnection of equipments with specified conductors ( jumpering ) for complete substation including but not limited to: 1. 40/63 MVA Transformer bay including 132 KV &33KV side bays 2. 132 KV Feeder Bay 3. 132 KV Bus Coupler Bay 4. 132 KV Transfer Bus Coupler Bay 5. 33 KV Feeder Bay 6. 33 KV Bus Coupler Bay 7. 33 KV Bay for station Transformer (COMPLETE IN ALL RESPECT) LS 1
16 Fire Fighting equipments
16.1 EREC OF FIRE FIGHTING SYSTEM (COMPLETE IN ALL RESPECT) JOB 1
17.1 EREC OF DG SET conforming to latest MoEFCC/CPCB guidelines No 1
18.1 INSTALL,TRAY,CABLE,INCL FABRICATION/ETC LS 1
19 FOTE Equipments
19.1 ERECTION/LAYING/T&C,STM-16,FOTE Erection of Fiber Optic Terminal Equipment (FOTE) SDH (STM-16) including but not limited to installation /erection of : 1. Base equipment suitable for 04 directions in subrack fully equipped with all necessary common cards, power supply cards, other hardware & accessories including 10 Nos. optical patch cords of lengths as per site requirements, DDF etc. with redundant CPU. 2. Optical Base Card for 04 directions (STM-16) 3. Short Haul & Long Haul 4. E1 Interfaces & L2 Etherner Interfaces 5. VOIP Phone 6. Equipment cabinet for SDH and DTPC 2200mm (Alongwith 110V to 48V DC-DC Converter) 7. MDF (200 Pairs), mounted in cabinet 8. 04 command standalone Digital Tele-Protection Coupler (DTPC) fully equipped with necessary common cards power Supply Cards other Hardware accessories Connectors Cables Subtrack with E I path cords set of 04 etc. (COMPLETE IN ALL RESPECT) LS 1
20 EREC OF WINDOW/SPLIT AIR CONDITIONER along with 5 KVA Stabilizer Nos 12
20.1 EREC OF CCTV CameraSystem for 132 kV Substation (COMPLETE IN ALL RESPECT) JOB 1
21 LIGHT LUMINAIRES
21.1 OUTDOOR LIGHTING
21.1.1 PERIFERY AND ROAD LIGHTING
a Supply and fixing of steel round pole 9.0 mt long in 1:4:8 cement concrete with 40mm brick ballast in size of 450x450x1900 and plastering of 300mm length of concrete above ground level No. 10
b Supply of junction box of size 280x225x150mm made of 16 SWG sheet with grey painting suitable for 2x4x6 C sq mm incoming cable & 2x4x6 C sq mm out going cable fitted with 3 Nos. HRC Fuse link of 5A, Cable glands, neutral link, terminal block etc. and Fixing of junction box on M.S. round pole with the help of M.S. Clamp No. 10
c Fixing of complete fitting of light luminaries with LED Lamp 110 to 130 Watt at designated height on light pole including taking out cable from junction box to light fixtures from inside pole. cable terminations and it’s testing and commissioning and earthing with 12 No. SW GI Wire No. 10
d Supply & fixing of GI pipe bend of 35mm dia 'B' class 2.5 meter long and bended at one end by quarter circle in 0.5 meter for cable entry to junction box fitted on steel round pole No. 10
e Painting of M.S. Round pole with first quality Asian /Nerolec/Burger paint, one coat of Red Oxide primer and two coats of Aluminium paint. No. 10
f Making 3 Nos. of strips of 450mm height from plinth with Post Office red colour in bottom & top and white colour in middle on each light pole of 150mm dia on M.S. Round pole and writing No. of pole. No. 10
21.1.2 SWITCHYARD LIGHTING
a Supply of junction box of size 280x225x150mm made of 16 SWG sheet with grey painting suitable for 2x4x6 C Sqmm incoming cable & 2x4x6 C sqmm out going cable fitted with 3 Nos. HRC Fuse link of 5A, Cable glands, neutral link, terminal block and Fixing of junction box on Columns with the help of 50x6mm G.I. Clamp No. 30
b Supply and fixing of GI pipe bend of 35mm dia 'B' class 2.0 meter long and bended at one end by quarter circle in 0.5 meter for cable entry to junction box fitted on column No. 30
c Supply and fixing of Light bend of 50mm dia GI 'B' class pipe 1.5 meter long bended at 1 meter at an angle of 300 for 250W HPSV light in Switchyard. No. 30
d Fixing of complete fitting of LED 110 to 130 Watt light luminaries at designated height on Column with the help of GI clamps & Light Bend cable terminations and it’s testing and commissioning and earthing with 12 No. SW GI Wire. No. 30
21.1.3 LAWN LIGHTING
a Supply & fixing of 'B'type light pole 2.5M long and fixing of cable bend pipe & its concreting in the ratio of 1:2:4 with 20mm stone granite and cement concrete in the size of 500x300x300mm including excavation, back filling, curing etc. to complete the job No. 5
b Supply of Junction Box of size 180x150x100mm made of 16 SWG steel with grey painted suitable for 2x2x6 C Sqmm cable fitted 2 Nos. HRC Fuse link of 5A & 1 No. Neutral link terminal block, cable glands etc and fixing of junction box on light pole with the help of M.S. clamps and then making plinth of size 225x300x300 in the ratio of 1:2:4 cement & coarse sand with 20mm granite with JB embedded in the plinth and the top surface of plinth being tapered from all four sides of plinth with 30mm height in the centre including all associated works of finishing, plastering etc. No. 5
c Supply & fixing of 50mm dia GI pipe light pole of 'B' class quality No. 5
d Supply & fixing of 'J' bend of 25mm dia GI pipe of 'B' class for cable entry No. 5
e Assembling and fixing of complete fitting of post top lantern with LED Lamp 40 to 45 Watt over the light poles, cable terminations, testing & commissioning etc. No. 5
f Making 3 Nos. of strips of 150mm height from plinth with Post Office red colour in bottom & top and white colour in middle on each light pole of 50mm dia No. 5
21.1.4 GATE LIGHTING
a Supply & fixing of junction box of size 180x150x 100mm as specified above at si.no. C_2 No. 4
b Assembling and fixing of Complete fitting of post top lantern with LED Lamp 40 to 45 Watt with cable terminations, testing and ,commissioning No. 4
21.1.5 CABLE LAYING AND TERMINATIONS
a Laying of 4cx2.5 sq mm copper control cable from control room to various point and for lawn lighting in excavated trench M 100
b Laying of 2cx2.5 sq mm Copper control cable for lighting in switchyard periphery, road etc. in excavated trench M 500
c Taking out above cable from junction box to light fittings fixed over the column by fixing GI clamps of 40x5mm flat with each crossed bracing on structures proper dressing etc M 500
d Excavation of trench of size 300 x 600 mm for laying of cable, putting ganga sand & Ist class bricks over the cable and then earth filling etc. 500
f Supply & fixing of Cable marker made of cast iron No. 60
21.2 INDOOR LIGHTING FOR CONTROL ROOM AND STORE
a Wiring for light point/fan point/ Exhaust Fan point/Call bell point with 3/22, 1.5mm2 PVC insulated copper conductor in PVC conduit concealed in wall with 2.24mm dia bare copper earth continuity wire & piano type switches etc. complete in all respect. Nos. 70
b Wiring for 3 Pin 5A light plug point socked outlet on existing switch board with 3/22, 1.5mm2 PVC insulated copper conductor in PVC conduit concealed in wall with 2.24mm dia bare copper earth wire continuity along with piano type switch complete in all respect. Nos. 12
c Supply and fixing of metal box of size 180x100x80mm deep in recess with suitable size of white laminated sheet cover in front including providing & fixing 3 pin 15 A socket & switch connection piano type with 7/22, 4.0mm2 PVC insulated copper conductor concealed in wall with 2.24mm dia bare copper earth wire continuity complete in all respect. Nos. 8
d Supply & wiring of sub main with PVC insulated copper wire of size & no. as detailed below along with 2.24mm dia bare copper earth wire continuity in PVC conduit concealed in wall complete in all respect.
e 2x4mm2 with 1 No. earth wire M 40
f 4x4mm2 with 2 No. earth wire M 30
g 2x1.5mm2 with 1 No. earth wire M 40
h 4x1.5mm2 with 2 No. earth wire M 50
i Supply & fixing of angle/button holder suitable for LED Lamps complete in all respect Nos. 8
j Supply & fixing of Factory Wired in-door decorative luminairs with LED Lamp for ceiling mounting with mirror optic suitable for 2x20/2x18W LED complete in all respect of category 'A' (make Philips/CGL/Bajaj) Nos. 8
k Supply & fixing of factory wired in-door decorative luminairs for surface mounting with oval polystyrene diffuser suitable for 1x20/1x18 W LED Lamp complete in all respect of category 'A' make.(make Philips/CGL/Bajaj) Nos. 10
l Supply & Fixing of complete set of street light luminair with LED Lamp 110 to 130 Watt complete in all respect with integral control gear of category 'A' make.(make Philips/CGL/Bajaj) Nos. 3
m Supply & fixing of factory wired LED light fitting suitable for 1x20W LED complete in all respect of category 'A' make.(make Philips/CGL/Bajaj) Nos. 10
n Supply & Fixing of Fancy wall bracket 1x15W LED fittings Nos. 12
o Supply & Fixing of decorative ceiling luminairs for 1x10W LED Lamp complete with round twin PVC insulated flexible cord, approved holder complete in all respect with bulb for DC lighting Nos. 7
p Supply & Fixing of 1200mm ceiling Fan complete with electronic regulator with double ball bearing and approved colour of category 'A' make as approved by Engineer. Nos. 10
q Supply & fixing of 18" Exhaust fan of category 'A' make as approved by the Engineer. Nos. 4
r Supply & Fixing of 12" Fresh Air Fan of category 'A' make as approved by the Engineer Nos. 4
s Supply & fixing of 6000 capacity Desert cooler of size made of 20 SWG galvanized sheet duly wired fitted with 18" Exhaust fan of cat 'A' make and vertical pump along with stand & other thing required to complete the jobs satisfactorily. Nos. 2
t Supply and fixing of Four Pole Isolator of 60/63 A. No. 1
u Supply and fixing of surface/flush mounting 8 ways SPN Distribution board with MCB complete in all respect. No. 1
v Supply & fixing of Call bell of approved make on white laminated sheet board including making connection etc. complete in all respect. Nos. 1
w Supply & Fixing of 600x800x8mm GI plate vertically for earthing with its top at least 3M below the ground level complete with 20mm dia GI pipe & funnel for watering and one earthing lead of one No. 8 to 10 SWG GI wire within 15mm dia GI pipe up to switch board 30cm square CI frame with hinged cover masonry housing alternate layer of charcoal/coke and salt at least 150mm thick alround etc as per direction of Engineer complete in all respect Nos. 1
x Supply & Fixing of Distribution box 6 bay TPNDB with 100 Amp. Isolator and 18 No. SP MCB of different capacity Havells make. Nos. 2
Total (INR excluding GST)
Full Signature ………………………………
Seal of Company
Designation ………………………………
Tender Specification no. ESD-686
Name of Bidder:
Bill Of Quantity Name of Work: Construction of Main Gantry,Aux. Foundation, Cable Trenches, Transformer Foundation, Fire wall, Capacitor Bank, Control Room Building, Store shed, Sump House, Chain link fencing, Drain, Culvert, C.C. Road, Earth filling, Turfing, Park & Plantation, Water supply works, O.H. Tank, Tube Well Boring and Mis. Development Works etc. at 132/33KV UPEIDA (IMLC) Sub-station Naseerpur, Firozabad .
Sl. No. Item Description Unit Tendered Qty. Unit Rate without GST (Rs) Applicable GST Amount @ 18% (Rs.) Unit Rate with GST (Rs) (5+6) Amount with GST (Rs) (4X7)
1 Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, for all lift, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50m in All kinds of soil (DSR 2.8.1) Cum 6500
2 Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials. All kinds of soil (DSR 2.26.1) Cum 3000
3 Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared.( DSR No 2.31) Sqm 20000
4 Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete.(DSR 2.27) Cum 230
5 Excavating, supplying, stacking and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in foundation trenches, plinth, sides of foundation etc. complete for all lift.(DSR 2.25(a)) Cum 23000
6 Extra for levelling & neatly dressing of disposed soil completely as directed by Engineer-in-charge.(DSR 2.36) Cum 5000
7 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources)(DSR 4.1.8) Cum 450
8 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:1½:3 (1 Cement: 1½ coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources)(DSR 4.1.2) Cum 400
9 Providing and laying cement concrete in kerbs, steps and the like at or near ground level excluding the cost of centering, shuttering and finishing.1:1½:3 (1 Cement: 1½ coarse sand(zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources)(DSR 4.4.1) Cum 40
10 Centering and shuttering including strutting, propping etc. and removal of form work for :Foundations, footings, bases for columns DSR 4.3.1 Sqm 8000
11 Centering and shuttering including strutting, propping etc. and removal of form work for :Retaining walls, return walls, walls (any thickness) including attached pilasters, buttresses, plinth and string courses fillets, kerbs and steps etc. DSR 4.3.2 Sqm 1000
12 Centering and shuttering including strutting, propping etc. and removal of form for(Suspended floors, roofs, landings, balconies and access platform) (DSR 5.9.3) Sqm 500
13 Centering and shuttering including strutting, propping etc. and removal of form work for :Columns, piers, abutments, pillars, posts and struts DSR 4.3.3 Sqm 300
14 Providing and fixing up to floor five level precast cement concrete string or lacing courses, copings, bed plates, anchor blocks, plain window sills, shelves, louvers, steps, stair cases, etc., including hoisting and setting in position with cement mortar 1:3 (1 Cement : 3 coarse sand), cost of required Centering complete.1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) derived from natural sources : 3 graded stone aggregate 20mm nominal size derived from natural sources)(DSR 4.5.1) Cum 10
15 Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) DSR 5.1.2 Cum 690
16 Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources).(DSR 5.3) Cum 120
17 Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement :1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) (DSR 5.2.2) Cum 50
18 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in:Cement mortar 1:6 (1 cement : 6 coarse sand)(DSR 6.1.2) Cum 38.6
19 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in:Cement mortar 1:4 (1 cement : 4 coarse sand)(DSR 6.1.1) Cum 830
20 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in :Cement mortar 1:6 (1 cement : 6 coarse sand) DSR 6.4.2 Cum 250
21 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in :Cement mortar 1:4 (1 cement : 4 coarse sand) DSR 6.4.1 Cum 15
22 Making soak pit 2.5 m diameter 3.0 metre deep with 45 x 45 cm dry brick honey comb shaft with bricks and S.W. drain pipe 100 mm diameter, 1.8 m long complete as per standard design. With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 DSR 19.32.1 Each 3
23 Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level.Cement mortar 1:3 (1 cement :3 coarse sand) DSR 6.13.1 Sqm 25
24 Providing and laying damp-proof course 40mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 12.5mm nominal size derived from natural sources)( DSR 4.10) Sqm 80
25 Providing and fixing panelled or panelled and glazed shutters for doors, windows and clerestory windows, fixing with butt hinges of required size with necessary screws, excluding panelling which will be paid for separately, all complete as per direction of Engineer-in-charge. (Note:- Butt hinges and necessary screws shall be paid separately) Kiln seasoned selected planks of sheesham wood 35 mm thick shutters (DSR 9.5.3.1) Sqm 10
26 Providing and fixing panelling or panelling and glazing in panelled or panelled and glazed shutters for doors, windows and clerestory windows (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured). Panelling for panelled or panelled and glazed shutters 25 mm to 40 mm thick : Float glass panes 5.0 mm thick glass panes (weight not less than 12.50 kg/sqm).(DSR 9.7.7.2) Sqm 10
27 Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge. With stainless steel cover plate minimum 1.25 mm thickness DSR 21.4.1 Each 10
28 Providing and fixing false ceiling at all heights with integral densified calcium silicate reinforced with fibre and natural filler false ceiling tiles of Size 595x595mm of approved texture, design and patterns as per CPWD Specification 2019, to be laid in true horizontal level suspended on inter-locking metal T-Grid of hot dipped galvanised iron section of 0.33mmthick (galvanized @ 120 grams per sqm including both sides)comprising of main-T runners of size 24x38 mm of length 3000 mm,cross - T of size 24x32 mm of length 1200 mm and secondaryintermediate cross-T of size 24x32 mm of length 600mm to formgrid module of size 600 x 600 mm, suspended from ceiling usinggalvanised mild steel items (galvanizing @ 80 grams per sqm) i.e. 12x50 mm long dash fasteners, 6 mm dia fully threaded hanger rod upto 1000 mm length and L-shape level adjuster of size 76x25x25x1.6 mm fixed with grid and Z cleat of size 25x37x25x1.6mm thick with precut hole on both 25mm flange to pierce into 12x50mm or even bigger size dash fastener if require, fixed with Glavanised iron perimeter wall angle or size 24x24x0.40 mm of length 3000 mm to be fixed on periphey wall / partition with the help of plastic rawl plugs at 450mm center to center and 40 mm long dry wall S.S screws. The workshall be carried out as per specifications, drawing and as per directionsof the Engineer-in-Charge .With 16 mm thick beveled tegular mineral fibre Anti-microbial false ceiling tile confirming to ISO 5 (class 100 ) specifications DSR 26.27.3 Sqm 250
29 Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters. 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws DSR 9.20.1 Sqm 20
30 Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc.as requred In stringers, treads, landings etc. of stair cases, including use of chequered plate wherever required, all complete DSR 10.25.1 Kg 28500
31 Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.DSR 10.2 Kg 19500
32 Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more.DSR 5.22.6 Kg 59900
33 Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters.80x1.25 mm M.S. laths with 1.25 mm thick top cover DSR 10.6.1 Sqm 20
34 Providing and fixing ball bearing for rolling shutters. DSR 10.7 Each 6
35 Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. Made of G.I. wire of dia 4 mm (DSR 16.70.1) Sqm 240
36 Supplying at site :Welded steel wire fabric of required width having rectangular mesh painted with two or more coats of enamel paint of approved shade over a coat of primer (Priming & Painting to be paid for separately).DSR 16.15.2 Kg 490
37 Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 stone aggregate 10 mm and down gauge), including finishing with cement mortar 1:3 (1 cement : 3 fine sand) as per standard design :DSR 12.21.1 In 75x75 mm deep chase Meter 100
38 12 mm cement plaster of mix : 1:4 (1 cement: 4 coarse sand) DSR 13.4.1 Sqm 5500
39 15 mm cement plaster on the rough side of single or half brick wall of mix :1:4 (1 cement: 4 fine sand)DSR 13.2.1 Sqm 2500
40 12 mm cement plaster finished with a floating coat of neat cement of mix :1:4 (1 cement: 4 fine sand) DSR 13.7.2 Sqm 250
41 Cement plaster skirting up to 30 cm height, with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement. 18 mm thick DSR 11.6.1 Sqm 50
42 Extra for providing and mixing water proofing material in cement concrete work in doses by weight of cement as per manufacturer's specification.DSR 4.12 Per bag of cement 499
43 Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections.(DSR 5.30) Meter 450
44 Neat cement punning. DSR 13.18 Sqm 2000
45 Providing and laying rectified Glazed Ceramic floor tiles of size 300x300 mm or more (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in all colours, shades, except White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick Cement Mortar 1:4 (1 Cement : 4 Coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including pointing the joints with white cement and matching pigments etc., complete.DSR 11.39 Sqm 40
46 Providing and fixing glass strips in joints of terrazo/ cement concrete floors.40 mm wide and 4 mm thick DSR 11.13.1 Meter 220
47 Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only . Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily.Glazed vitrified floor tiles polished finish of size (DSR 11.41A.2.1) Size of Tile 600 x 600 mm Sqm 280
48 Providing and fixing 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali resisting mortar bedding, and joints filled with acid and/or alkali resisting cement as per IS : 4457, complete as per the direction of Engineer-in- Charge.In dado/skirting on 12 mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand) Acid and alkali resistant tile DSR 11.21.2.1 Sqm 45
49 Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. Polished Granite stone slab colour of Black, Cherry/Ruby Red or equivalent DSR 11.56.1 Sqm 120
50 Providing and fixing 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali resisting mortar bedding, and joints filled with acid and/or alkali resisting cement as per IS : 4457, complete as per the direction of Engineer-in- Charge. In flooring on a bed of 10 mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand) Acid and alkali resistant tile DSR 11.21.1.1 Sqm 30
51 Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture DSR 13.62.1 Sqm 1400
52 Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.(DSR 13.80) Sqm 2300
53 Finishing walls with Acrylic Smooth exterior paint of required shade :New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm) DSR 13.46.1 Sqm 1200
54 Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gram/litre, of approved manufacturer and of required shade and colour all complete to achieve even shade and colour :New work (two or more coats) over and including water thinnable priming coat with cement primer having VOC content less than 50 gram/litre DSR 13.41.1 Sqm 1100
55 Providing 10 mm thick plaster of Paris (gypsum anhydrous) ceiling up to a height of 5 m above floor level, over first class kail wood strips 25x6 mm with 10 mm gap in between and reinforced with rabbit wire mesh fixed to wooden frame (frame work to be paid separately): Flat surfaces DSR 12.31.1 Sqm 150
56 Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road roller including making good the undulations etc. and re-rolling the sub grade and disposal of surplus earthwith lead upto 50 metres.DSR 16.1 Sqm 2100
57 Construction of granular sub-base by providing close graded Material conforming to specifications, mixing in a mechanical mix plant at OMC, carriage of mixed material by tippers to work site, for all leads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per specifications and directions of Engineer-in-Charge. With material conforming to Grade-III (size range 26.5 mm to 0.075 mm ) having CBR Value-20(DSR No. 16.78.3) Cum 346
58 Brick on edge flooring with bricks of class designation 7.5 on a bed of 12 mm cement mortar, including filling the joints with same mortar, with common burnt clay non modular bricks:DSR 11.1.1 1:4 (1 cement : 4 coarse sand) Sqm 350
59 Providing and laying C.C. pavement of mix M-25 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator , vacuum dewatering process and finally finished by floating, brooming with wire brush etc. complete as per specifications and directions of Engineer-in-charge. (The panel shuttering work shall be paid for separately). (DSR 16.75)- (DSR 16.76) Cum 242
60 Extra for providing and mixing hardening compound of approved quality as per manufacturer's specification in cement concrete.DSR 16.44 Litr 258
61 Providing and filling in position rubberized bitumen hot sealing compound for sealing of expansion joints in roads / pavements all complete as per direction of the Engineer-in-Charge.Providing and filling in position rubberized bitumen hot sealing compound for sealing of expansion joints in roads / pavements all complete as per direction of the Engineer-in-Charge. DSR 16.46.1 Activity unit 350
62 Providing and laying 60mm thick faciory made cement concrete interlocking paver block of M -30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50mm thick compacted bed of coarse sand, filling the joints with line sand etc. all complete as per the direction of Engineer-in-charge.DSR 16.68 Sqm 220
63 Providing and laying Non Pressure NP-3 class (Medium duty) R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete 450 mm dia RCC pipes.DSR 19.35.1 Meter 18
64 Providing and laying Non Pressure NP-3 class (Medium duty) R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete 600 mm dia RCC pipes.DSR 19.35.2 Meter 12
65 Providing and laying Non Pressure NP-3 class (Medium duty) R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete 900 mm dia RCC pipes. DSR 19.35.3 Meter 12
66 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : For fixed portion Powder coated aluminium (minimum thickness of powder coating 50 micron) DSR 21.1.1.2 Kg 400
67 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately) Powder coated aluminium (minimum thickness of powder coating 50 micron) DSR 21.1.2.2 Kg 1200
68 Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): With float glass panes of 5 mm thickness (weight not less than 12.50 kg/sqm) DSR 21.3.2 Sqm 220
69 Providing and fixing ISI marked aluminium butt hinges anodised (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour or shade with necessary screws etc. complete: 125x75x4 mm DSR 9.95.1 each 100
70 Providing and fixing ISI marked aluminium butt hinges anodised (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour or shade with necessary screws etc. complete: 100x75x4 mm.DSR 9.95.3 each 100
71 Providing and fixing aluminium sliding door bolts, ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, with nuts and screws etc. complete : 300x16 mm.DSR 9.96.1 each 30
72 Providing and fixing aluminium sliding door bolts, ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, with nuts and screws etc. complete : 250x16 mm.DSR 9.96.2 each 40
73 Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : 200x10 mm. DSR 9.97.3 each 50
74 Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : 150x10 mm. DSR 9.97.4 each 80
75 Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : 100x10 mm 9.97.5 each 80
76 Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete : 125 mm 9.100.1 each 60
77 Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete : 100 mm 9.100.2 each 60
78 Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete. Single rubber stopper 9.101.1 each 30
79 Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer-in-charge, upto 90 metre depth below ground level. All types of soil 350 mm dia DSR 23.1.1.2 Meter 180
80 Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer-in-charge, beyond 90 metre & upto 150 metre depth below ground level. All types of soil 350 mm dia DSR 23.2.1.2 Meter 60
81 Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge. 200 mm nominal size dia DSR 23.4.3 Meter 160
82 Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge. 150 mm nominal size dia DSR 23.4.2 Meter 60
83 Providing and fixing Bail plug/ Bottom plug of required dia to the bottom of pipe assembly of tubewell as per IS:2800 (part I). 200 mm dia DSR 23.15.3 Each 4
84 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. External work 25 mm nominal dia Pipes DSR 18.9.3 Meter 100
85 Development of tube well in accordance with IS : 2800 (part I) and IS: 11189, to establish maximum rate of usable water yield without sand content (beyond permissible limit), with required capacity air compressor, running the compressor for required time till well is fully developed, measuring yield of well by "V" notch method or any other approved method, measuring static level & draw down etc. by step draw down method, collecting water samples & getting tested in approved laboratory, i/c disinfection of tubewell, all complete, including hire & labour charges of air compressor, tools & accessories etc., all as per requirement and direction of Engineer-in-charge. DSR 23.12 Hour 32
86 Providing and fixing gun metal non- return valve of approved quality (screwed end) : 80 mm nominal bore Horizontal DSR 18.19.6.1 Each 4
87 Gravel packing in tubewell construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer-in-charge. DSR 23.8 Cum 24
88 Supplying and stacking at site dump manure from approved source, including carriage upto 5 km lead complete (manure measured in stacks will be reduced by 8% for payment) : Screened through sieve of I.S. designation 20 mm DSR 2.4.1 Cum 30
89 Trenching in ordinary soil up to a depth of 60 cm including removal and stacking of serviceable materials and then disposing of surplus soil, by spreading and neatly levelling within a lead of 50 m and making up the trenched area to proper levels by filling with earth or earth mixed with sludge or/and manure before and after flooding trench with water (excluding cost of imported earth, sludge or manure). DSR 2.1 Cum 50
90 Supplying and stacking of good earth at site including royalty and carriage upto 5 km lead complete (earth measured in stacks will be reduced by 20% for payment). DSR 2.2 Cum 50
91 Providing and laying Neelgiri/Mexican grass turf with earth 50mm to 60mm thickness of existing ground prepared with proper level and ramming with tools wooden (Dhurmos) and than rolling the surface with light roller make the surface smoothen and light waterning with sprinkler and maintenance for 30 days or more till the grass establish properly, as per direction of officer-in-charge. DSR 2.33 Sqm 180
92 Preparation of beds for hedging and shrubbery by excavating 60 cm deep and trenching the excavated base to a further depth of 30 cm, refilling the excavated earth after breaking clods and mixing with sludge or manure in the ratio of 8:1 (8 parts of stacked volume of earth after reduction by 20%: one part of stacked volume of sludge or manure after reduction by 8%), flooding with water, filling with earth if necessary, watering and finally fine dressing, leveling etc. including stacking and disposal of materials declared unserviceable and surplus earth by spreading and leveling as directed, within a lead of 50 m, lift up to 1.5 m complete (cost of sludge, manure or extra earth to be paid for separately) DSR 2.13 Cum 40
93 Digging holes in ordinary soil and refilling the same with the excavated earth mixed with manure or sludge in the ratio of 2:1 by volume (2 parts of stacked volume of earth after reduction by 20% : 1 part of stacked volume of manure after reduction by 8%) flooding with water, dressing including removal of rubbish and surplus earth, if any, with all leads and lifts (cost of manure, sludge or extra good earth if needed to be paid for separately) Holes 60 cm dia, and 60 cm deep DSR 2.14.3 Each 100
94 Providing and stacking of Polyalthia pendula (Ashok Pendula) of height 150-165 cm. in earthen pots of size 25 cm as per direction of the officer-in-charge. DSR 7.76 Each 50
95 Providing and stacking of Azadirachta indica ( Neem ) of height 120-130cm in big polybag of size 25 cm as per direction of the officer-in-charge.DSR 7.5 Each 180
96 Providing and stacking of Bottle palm of ht. 150-180 cm bottom girth 20-25cm well developed in big poly bags of size 25 cm as per direction of the officer-in-charge.DSR 7.10 Each 20
97 Plantation of Trees, Shrubs, and Hedge at site i/c watering and removal of unserveiceable material's as per direction of officer in charge (excluding cast of plant & water) Trees Plant DSR 2.57.1 Each 200
98 Providing and displaying of Areca Palm having ht. 90 cm to 1.20 m with 4 to 5 suckers, well developed, fresh and healthy with lush green foliage in 25 cm size of Earthen pot/Plastic pot & as per direction of the officer-in-charge.DSR 3.18 Each 10
99 Providing and Displaying Standard Rose (H.T. variety) 3 to 4 healthy branch 90 cm and above ht. well developed with one and above flowers in 25 cm Earthen Pot, as per direction of the officer-in-charge.DSR 4.93 Each 10
100 Providing and stacking of Ficus nuda of height 150-165 cm., bushy with healthy branches and lush green foliage in big size HDPE bags as per direction of the officer-in-charge. DSR 7.35 Each 50
101 Providing and Stacking of Ficus panda plant of height 90 -105 cm. multibranches, well developed in poly bags of size 25 cm as per direction of the Officer-in- charge. DSR 11.33 Each 50
102 Providing and displaying of Brassia Variegated having ht. 30 cm to 45 cm, well developed with fresh and healthy foliage in 25 cm size of Earthen pot /Plastic pot. & as per direction of the officer-in-charge.DSR 3.24 Each 50
103 Providing Circular Cement Concrete pots of specified size, cast with cement concrete of nominal mix 1:2:4 (1 cement: 2 coarse sand: 4 graded stone aggregate 6 mm nominal size), reinforced with 7 Nos ( 3 nos horizontal & 4 nos vertical “ U “ shape) M.S. wires of 3.5 mm dia as per design, including required form work, finishing with cement punning on exposed surface, curing for specified period and stacking in required rows & height, all complete as per direction of Officer-in-charge. Top inside dia 30 cm, outer bottom dia 20 cm, total height 30 cm & with wall thickness of 25.4 mm DSR 2.30.1 Each 15
104 Supplying and stacking of good earth at site including royalty and carriage upto 5 km lead complete (earth measured in stacks will be reduced by 20% for payment).DSR 2.2 Cum 30
105 Supplying and stacking sludge at site including royalty and carriage upto 5 km lead complete (sludge measured in stacks will be reduced by 8% for payment).DSR 2.3 Cum 20
106 Mixing earth and sludge or manure in the required proportion specified or directed by the Officer-in-charge DSR 2.9 Cum 20
107 Spreading of sludge, dump manure and/or good earth in required thickness as per direction of officer-in-charge (cost of sludge, dump manure and/ or good earth to be paid separately).DSR 2.8 Cum 30
108 Providing and stacking of Jasmine humile (Yellow) of height 30 cm to 45 cm. in 20 cm size of Earthen pots / Plastic pots & as per direction of the officer-in-charge. DSR 9.9 Each 100
109 Providing and stacking of Delonix regia (Gulmohar) of height 150-165 cm. in big poly bags of size 25 cm as per direction of the officer-in-charge DSR 7.24 Each 50
110 Boring with hydraulic piling rigs with power units, providing and installing cast in situ single under reamed piles of specified diameter and length below pile cap in M-25 cement concrete, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and the length of the pile to be embedded in pile cap etc. all complete. (Length of pile for payment shall be measured upto to the bottom of pile cap) : 300 mm dia piles DSR 20.3.1 Meter 720
111 Boring with hydraulic piling rigs with power units, providing and installing cast in situ single under reamed piles of specified diameter and length below pile cap in M-25 cement concrete, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and the length of the pile to be embedded in pile cap etc. all complete. (Length of pile for payment shall be measured upto to the bottom of pile cap) : 400 mm dia piles DSR 20.3.2 Meter 600
112 Extra over single under ream for providing additional bulbs in under reamed piles, under specified diameter(only the nos. of extra bulbs are to be paid) 300 mm dia piles DSR 20.4.1 Each 160
113 Extra over single under ream for providing additional bulbs in under reamed piles, under specified diameter(only the nos. of extra bulbs are to be paid) 400 mm dia piles DSR 20.4.2 Each 120
114 Vertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of Engineer in-charge. Single pile upto 50 tonne Safe capacity Routine test (Test Load 1.5 times the Safe capacity) DSR 20.6.1.2 Per Test 4
115 Lateral load testing of single pile in accordance with IS Code of practice IS : 2911 (Part IV) for determining safe allowable lateral load on pile : Upto 50 tonne capacity pile DSR 20.8.1 Per Test 4
116 Integrity testing of Pile using Low Strain/ Sonic Integrity Test/ Sonic Echo Test method in accordance with IS 14893 including surface preparation of pile top by removing soil, mud, dust & chipping lean concrete lumps etc. and use of computerised equipment and high skill trained personal for conducting the test & submission of results, all complete as per direction of Engineer-in-charge.DSR 20.9 No. 30
117 Supplying and drawing following 3 x 2.5 sq. mm sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.DSR 1.17.12 Meter 1200
118 Supplying and drawing following 3 x 4 sq. mm sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.DSR 1.17.21 Meter 1400
119 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required..Group CDSR 1.10.3 Points 98
120 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 3 pin 5/6 amp socket outlet DSR 1.24.4 each 30
121 Supplying and fixing of 20 mm of medium class PVC conduit along with accessories in surface/recess including junction box, cutting the wall and making good the same in case of recessed conduit as required. DSR 1.21.1 Meter 300
122 Supplying and fixing of 25 mm of medium class PVC conduit along with accessories in surface/recess including junction box,cutting the wall and making good the same in case of recessed conduit as required. 25 mm DSR 1.21.2 Meter 400
123 Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire DSR 1.14.2 Meter 250
124 Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required 2 X 4 sq. mm + 1 X 4 sq. mm earth wire DSR 1.14.3 Meter 400
125 Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required 2 X 6 sq. mm + 1 X 6 sq. mm earth wire DSR 1.14.4 Meter 100
126 Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.DSR 5.6 Set 2
127 Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required.DSR 5.12 Meter 45
128 Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole.DSR 2.10.1 each 50
129 Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps.DSR 2.12.2 each 20
130 Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps.DSR 2.12.1 each 20
131 Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 4 way (4 + 12), Double door.DSR 2.4.1 each 25
132 Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4 way (4 + 12), Double door.DSR 2.5.1 each 10
133 Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.DSR 1.12 Meter 50
134 Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc as required. 1 or 2 Module (75mmX75mm).DSR 10.18 each 10
135 Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc as required. 3 Module (100mmX75mm).DSR 1.27.1 each 30
136 Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc as required. 4 Module (125mmX75mm).DSR 1.27.2 each 20
137 Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc as required. 6 Module (200mmX75mm).DSR 1.27.3 each 40
138 Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc as required. 8 Module (125mmX125mm)DSR 1.27.4 each 20
139 Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc as required. 12 Module (200mmX150mm)DSR 1.27.6 Each 10
140 Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing. DSR 10.18 Each 25
141 Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c cutting and making good the walls etc. Internal work - Exposed on wall 15 mm dia nominal bore DSR 18.10.1 Meter 49
142 Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c cutting and making good the walls etc. Internal work - Exposed on wall 20 mm dia nominal bore DSR 18.10.2 Meter 50
143 Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c cutting and making good the walls etc. Internal work - Exposed on wall 25 mm dia nominal bore DSR 18.10.3 Meter 50
144 Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. External work 20 mm dia nominal bore DSR 18.12.2 Meter 120
145 Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. External work 25 mm dia nominal bore DSR 18.12.3 Meter 150
146 Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. External work 32 mm dia nominal bore DSR 18.12.4 Meter 100
147 Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. External work 40 mm dia nominal bore DSR 18.12.5 Meter 50
148 Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. External work 50 mm dia nominal bore DSR 18.12.6 Meter 180
149 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 15 mm nominal dia Pipes DSR 18.8.1 Meter 25
150 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 20 mm nominal dia Pipes DSR 18.8.2 Meter 180
151 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 25 mm nominal dia Pipes DSR 18.8.3 Meter 140
152 Providing and fixing C.P. brass long nose bib cock of approved quality conforming to IS standards and weighing not less than 810 gms. 15 mm nominal bore DSR 18.50.1 Each 20
153 Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) : 25 mm nominal bore DSR18.17.1 Each 6
154 Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) : 20 mm nominal bore DSR 18.17.1 A Each 4
155 Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) : 32 mm nominal bore. DSR 18.17.2 Each 5
156 Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) : 40 mm nominal bore DSR 18.17.3 Each 5
157 Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) : 50 mm nominal bore DSR 18.17.4 Each 2
158 Providing and fixing C.P. brass shower rose with 15 or 20 mm inlet : 150 mm diameter DSR 18.22.2 Each 4
159 Providing and fixing rectangular high density polyethylene water storage loft tank with cover, conforming to ISI : 12701, colour of opaque white or as approved by Engineer-in-charge. The rate includes making necessary holes for inlet, outlet & over flow pipes. The base support i/c fittings & fixtures for tank shall be paid separately.DSR 18.48A Ltr. 10000
160 Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required : W.C. pan with ISI marked white solid plastic seat and lid DSR 17.2.1 Each 2
161 Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required: White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests DSR 17.1.1 Each 3
162 Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require: White Vitreous China Wash basin size 550x400 mm with a pair of 15 mm C.P. brass pillar taps DSR 17.7.3 Each 5
163 Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS:13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required : Kitchen sink without drain board 610x510 mm bowl depth 200 mm DSR 17.10.2.1 Each 2
164 Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard flush pipe and C.P. brass spreaders with brass unions and G.I clamps complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required : One urinal basin with 5 litre white P.V.C. automatic flushing cistern DSR 17.4.1 Each 4
165 Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. 600 mm long towel rail with total length of 645 mm, width 78 mm and effective height of 88 mm, weighing not less than 190 gms.DSR 17.73.2 Each 4
166 Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.DSR 17.31 Each 5
167 Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. DSR 23.5 Cum 5
168 Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). DSR 10.28 Kg 250
169 Providing and fixing brass curtain rods of wall thickness 1.25 mm with two brass brackets fixed with brass screws and wooden plugs etc. wherever necessary complete.25 mm diaMeter. DSR 14.28.2 Meter 100
170 Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge.DSR 23.6 Cum 10
171 Arranging and spreding 75 mm thick broken grit 20 mm (Granite stone) uniform for turfing over 100mm thick base course of C.C. In 1:4:8 (1cement:4coarse sand: 8, 40mm stone ballast) top finish by brooming of cement mortar 1:4(1cement: 4 Coarse sand) including supply of all materials, labour and tools and plants etc. required for proper completion. NSI-2 Sqm 9000
172 Supply of 28 mm. dia M.S. Anchor bolts (conforming to IS 266) 900 mm. long with base plate (75x75x6mm) welded with anchor bolts including its threading upto a length of 10cm. and also supply of a pair of galvanized standard nuts with threading including supply of 5 mm thick washer and cost of labour, material & T&P for proper completion of work (NSI-13) No 1400
173 Fixing and grouting 28 mm and above dia bolts in proper alignment level and setout with help of a template complete including supply of all labour & T&P etc. required for proper completion of the work.(labour rates only) . (NSI-14) No 1400
174 Supply of 25 mm dia.M.S. Anchor bolts (conforming to IS-226) 500 mm long with base plate(50x50x6 mm)welded with anchor bolts,including its threading upto a length of 10cm. and galvanizing upto 15cm from top, also supply of a pair of galvanized standard nuts with threading including supply of 5mm thick washer and cost of labour material and T&P etc. required for proper completion of the work. NSI-15 No 1850
175 Fixing and grouting 25 mm and below dia M.S. Anchor bolt in proper alignment level and setout with the help of a template including supply of all labour T&P etc. reqd. for proper completion of the work. (labour rates only) . (NSI 16) No 1850
176 Grouting of 90/105 lbs M.S. rail including cost of all materials, labour & T&P for fixing of rail in proper alignment, level and position in transformer plinth foundation etc. as per direction of Eng I/C. (Rail to be supplied by the dept.)(labour rates only) .NSI-18 RM 20
177 S/F in position 90 lbs M.S. Rail for transformer plinth including cost of all labour, material and T&P etc. required for proper completion of the work. NSI-19 RM 20
178 Fixing and grouting of trench edging in proper level and alignment including cost of all labour, and T&P etc. required for proper completion of the work but excluding cost of C.C. (labour rates only) . NSI-22 RM 2500
179 Fixing of cable trench racks in proper position and alignment including cost of all labour, material and T&Petc. required for proper completion of the work (Labour rate only).(SOR NSI No. 9.33) NSI-25 No. 7600
180 Fixing of template in position level and alignment for grouting of Anchor bolt in main gantry (labour rate only). NSI 23 No. 75
181 Same in NSI item-23 above but for auxiliary structure. (labour rate only). NSI 24 No. 350
182 Providing (12x15) mm section groove in plaster including all material, labour and T&P etc. required for proper completion of the work. DSR NSI-33 RM 1500
183 Champering the edge of concrete in auxiliary structure, of size 25 mm wide in triangular section including all materials, labour & T&P etc complete.NSI-34 RM 4800
184 2.5 cm thick 1:1.5:3 plain cement concrete floor with cement, approved coarse sand & 2cm graded approved stone ballast laid in panels finished with 3mm floating coat of neat cement or cement and marble dust in ratio of 5:1 as specified and removing any overlapping mortar at the joints of the panels if any and giving them a uniform finish including supply of all materials, labour and T&P etc, required for proper completion of the work. without base CC NSI-35 Sqm 750
185 As in NSI item No.-35 above but 4.0 cm thick floor in 1:1.5:3 concrete with out base concrete. NSI-36 Sqm 180
186 Painting letters & number over cable trench cover or other places with the help of stencils including painting of base of 150 mm. dia of one coat of primer and two coats of superior quality synthetic enamel paint size of letter to be 60 mm. x 10 mm. including cost of all materials labour and T&P etc. required for proper completion of the work including placing of Trench covers in required position NSI-37 No 2500
187 Pre-Construction anti-termite treatment, by creating a barrier under and around the columns pits, foundation trenches, under floors, junctions of Walls & floors, around the external perimetre of building, expansion joints, surrounding of pipes and conduits etc. (Plinth area of the building at ground floor only shall be measured as per I.S. 6313 (Part II 1981))with Eldrine emulsifiable 0.2% concentration or any other approved material such as Heptachlore or chlordance will be used. The consumption of emulsion shall be (i) Foundation and masonary @ 5 Ltrs/Sqm, (ii) Back fills in immediate contact of foundation@ 7.5 Ltrs. / Sqm, (iii) Top surface of Plinth filling @ 5 Ltrs / Sqm, ( iv) Junction of walls & floors @ 7.5 Ltrs / Sqm, (v) Soil along external perimetre of building @ 7.5 Ltrs / Sqm (vi) under apron of the building @ 5 Ltrs. /Sqm. The rates includes cost of all materials, labour, equipments, T&P complete. NSI-41 Sqm 400
188 Supply and fixing support clamps for column pipes made out of MS flats, pairs of bolt-nuts etc complete with all material, labour, T&P. 65 mm dia. DSR NSI-48b No 2
189 Transportation and installation of tube well drilling Rig m/c, compressure for development and other required equipments and accessories at site of work and dismentlling & taking them back after successful completion of the work including cleaning, levelling - dressing the site properly, also disposing off the surplus earth, silt, sand etc. NSI-51 Job 1
190 Supply and installation of 5H.P. Kirloskar or equivalent make single stage, horizontal, self priming,three phase dewatering pumpset of specification Head 14/16 M, Discharge 13.6/10 LPS, solid handle size 15.5 mm, suction 80 mm, delivery 80 mm, RPM 1500 including cost of 80 mm dia G.I. pipe for suction (3M) and delivery (4.5 M). NSI-52 No 1
191 Supply & installation of electrical control panel of L&T / Havells or equivalent make for submersible pump / pumpset containing contractor relay condenser. c) for 3 H.P pump set single phase NSI-54c NO 2
192 Supply & Installation of submersible pump of K.S.B/ CALAMA. or eqt. make including cost of labour, T&P and material required for completion of work. d) 3 HP outlet 50 mm dia. or more, Head 60/24, Discharge 6000/14000 LPH NSI-55d No 1
193 Supply & fixing of steel wire rope for submersible pump including cost of labour, T&P and material required for completion of work. NSI 56 Meter 140
194 Placing of trench cover of all size in proper position including transportation from different places within the S/S area including all labour, T&P etc. required for proper completion of the work as per direction of Engineer - in - charge. (NSI 58) No 1800
195 S/laying chicken mesh of (20 mm.)hexagonal heavy quality over roofs of joints of roof as per direction of the Engineer - in - charge.NSI-65 sqm 150
196 Supply and fixing of Single Concealed stop cock with basin spout (Composite one piece body) Jaquar make model no-FLR-5441NK . The work includes cost of all labour, material T&P for proper completion of work. NSI-92 No. 10
197 Providing and fixing soap dish chromium plated with brackets fixed to wooden cleats with brass screws including supply of all materials,labour and T&P etc.required for proper completion of the work. NSI 108 No. 5
198 Providing and laying SWR, PVC ( Finolex or equivalent ) pipe including cost of excavation, C.C etc including its jointing and connection, all materials, labour and T&P etc. required for proper completion of the work. b) 90 mm Dia.NSI-109b RM 80
199 Providing and laying SWR, PVC ( Finolex or equivalent ) pipe including cost of excavation, C.C etc including its jointing and connection, all materials, labour and T&P etc. required for proper completion of the work. c) 110 mm Dia. NSI-109c RM 100
200 Supply and Fixing of 3 blade wall fan of Havells platina 400 mm or equivalent including all material, T&P etc required for proper completion of work as approved by engineer in charge. NSI 132 Each 20
201 Providing and fixing of Godrej office table Model Enterprise 1650 With CPU Hanger 1650W*900D*728H or equivalent make including cost of all material, labour and T&P etc. cartiage at site complete as per direction of E/I.(Code 56101519SD01158) Each 5
202 Providing and fixing of Godrej office table Model T-104 1665 W* 1650W*900D*750H or equivalent make including cost of all material, labour and T&P etc. cartiage at site complete as per direction of E/I.(Code 56101519SD01112) Each 5
203 Providing and Fixing of Godrej Executive chair model regency high back godrej or equivalent make including cost of all material, labour and T&P etc. cartiage at site complete as per direction of E/I( Code 56101522SD03346) Each 5
204 Providing and Fixing of Godrej Glass door storewell for storage of drawings 1981H*916W*486D mm or Equivalent make including cost of all material, labour and T&P etc. cartiage at site complete as per direction of E/I(Code 30161806SD00120) Each 5
205 Supply & Providing of Double Bed(King bed) of size 91x187.5x204.6 cm HWL with decorated head of godrej or equivalent make adria pro imperial oak color,with 2 no side table (size 51x46x46.1cm HWD,3 Door wardrobe (size 191x120x54.8 cm HWD &Dresser (dressing table) size 171x46x46.1 cm HWD As per godrej specification including cost of all material, labour and T&P etc. complete as per direction of E/I. (a)Adria King bed imperiol oak= L.N code 56101515SD00062 (B)Adria bedside Tbl imp oak, LN code-56101719SD00028 (c)Adria 3Dr WRDRB Imp Oak,LN code-56101515SD00062 Each 1
206 Supply & Providing Soft Thermal BLANKET standerd size with 100% cotton fabric, flannel, fleece or acrylic yarn RAYMOND or equivalent make as approved by the E/I. including supply of all material , labour and T&P etc. required for proper completion of work at the required site. (NSI) Each 2
207 Supply & Providing of Centre table of size120x60x37.8 cm WDH of approved godrej make splenda in dark brown colour including cost of all materials, labour and T&P etc.complete as per direction of E/I. (CODE-56121403SD00289) Each 2
208 Supply & Providing of Sofa set cushioned chair with covered back with seat size of 92x87x78 cm WDH make of Godrej PARTO single seater matching with Godrej or equivalent make Specification including cost of all materials, labour and T&P etc.complete as per direction of E/I. (CODE-56101502SD01843) Each 4
209 Supply & Providing of Sofa set cushioned chair with covered back with seat size of 134x87x78 cm WDH make of Godrej PARTO 2 seater matching with Godrej or equivalent make Specification including cost of all materials, labour and T&P etc.complete as per direction of E/I.(CODE-56101502SD01843) Each 2
210 Supply & Providing of Sofa set cushioned chair with covered back with seat size of 175x87x78 cm WDH make of Godrej PARTO 3 seater matching with Godrej or equivalent make Specification including cost of all materials, labour and T&P etc.complete as per direction of E/I.(LN CODE-56101502SD01844) Each 2
211 Supply & Providing of Sofa set cushioned chair with covered back with seat size of 80x82x85 cm WDH make of Godrej Monarch single seater matching with Godrej or equivalent make Specification including cost of all materials, labour and T&P etc.complete as per direction of E/I.(L.N CODE-56101502SD00697) Each 4
212 Supply & Providing of Godrej or equivalent make poise work chair of size 72x72x89 to 101 CM WDH as per godrej specification, including cost of all material labour and T&P complete. (L.N CODE-56101522SD01908) Each 20
Seal of Company Full Signature ………………………………
Designation ………………………………
Tender Specification no. ESD-686
Name of Bidder:
Sl. No. DESCRIPTION Schedule Amount including GST (in Rs.)
1 Total Price for Supply of Equipments/Materials and Light Luminaires S-1
2 Total Price for Handling, Erection, Testing & Commissioning S-2
3 Net Price for Electrical works (1+2)
4 Net Price for Civil Works S-3
5 Total Bid Price (3+4)
Seal of Company Full Signature …………………………
Designation ……………
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.47 MB
TenderDocESD686.pdf
Tender Documents • 4.96 MB
BOQESD686.xls
Additional Documents • 0.46 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].