CWE AF NAGPUR
HQ CWE AF NAGPUR VAYUSENA NAGAR, NAGPUR 440007 MILITARY ENGINEER SERVICES
PROVISION OF POWER SUPPLY TO NFS BUILDING (SITE- II) AT VAYUSENA NAGAR, NAGPUR
2021_MES_423743_2
80442
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
GE AF NAGPUR
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE AF NAGPUR
₹22,000
7 Jun 2021
7 Apr 2021
22 Apr 2021
7 Apr 2021
21 Apr 2021
7 Apr 2021
60 days
Amount
Supply, install, test & commissioning of transformer confirming to IS 1180 : 2014,Level 2, 160 KVA Outdoor type step up/down 11 KV/433 Volt copper wound 3 Phase, 4 Wire, 50 Hz, oil immersed naturally cooled and other standard fittings / accessories and 7 position off circuit tap changer (tapping range +/-7.5% in steps of 2.5 % each) with vector group dyn-11 with first fill of transformer oil up to maximum level confirming to IS 335 and all standard fittings including cable box at both HT/LT side , oil temperature indicator from 0 to 120 degree C, accessories as per latest IS and as per manufacturers design making necessary incoming & outgoing connections and earthing connection arrangement at site complete all as specified and as directed. following :- (a) Three Nos porcelain bushing suitable for 11 KV on HV side, complete with Brass rods, nuts and washers and arching horns. (b) Four Nos porcelain bushing suitable for 0.433 KV on LV side, complete with Brass rods, nuts and washers with cable end box. (c) Monogram plate.
(d) Oil conservator with filter and drain plug. (e) Prismatic / transparent oil gauge. (f) Pressure relief valve. (g) Air release plug. (h) Lifting lugs for complete transformer. (j) Top filter valve. (k) OTI (Oil temperature indicator) (l) First filling of new and unused transformer oil, IS-335 marked, filtered and tested upto 60 KV dielectric strength of 2.5 mm air gap between testing eletrodes. Make: Savita / Apar / Power Oil Note : - (i) Installation of the transformer shall be carried out as per IS - 10028. (ii) The contractor should make necessary arrangment for Pre-Commissionery testing by senior Electrical Inspector)
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 3 core 95 sq mm Complete.
Supply & fixing Cable joining kit for 11 KV (Earthed) grade cable for indoor end termination heat shrink type joint complete with joining material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3½ core Complete all as specified and directed .
Supply and installation of Automatic Power Factor Correction (APFC) Capacitor bank of 50 KVAR capacity , 415 V , AC 50 Hz supply completeMake Havells SecuRite Cat Part No : QHKTCB5050X0 or equivalent in L&T, ABB etc all as specified below :- Range • Output Rating: 50 kVAr , Delta connected Heavy Duty Cylindrical capacitors having Switching Contactor / Thyristorised (Ultra Fast) contactors Features • Manufactured with highly precise modern Amada CNC machine • 11 tank process for corrosion proof powder coating • Ergonomic, compact and robust design • Designed with Fully copper conductor • Heavy Duty power capacitor for long life • Advance C-MOS technology based micro processor relay for intelligent power factor control • Air core reactor for extra safety from inrush current (High currents) • Provision of top and bottom cable entry • Automatic temp. control through fans and louvers in panel• Double side earthing connection • Ref. Standard: IEC 61921/ IS 8623 / IS 16636 / Principle Operation • Continuously sense and monitor the load conditions by the use of the external CT (whose output is fed to the control relay). • Automatically switch ON and switch OFF relevant capacitor steps to ensure consistent power factor. • Ensure easy user interface for enabling reliable understanding of system operation, such as display of real time power factor, number of switching operations carried out etc. • Protect against any electrical faults in a manner that will ensure safe isolation of the power factor correction equipment
Supply and installation of Voltage stabilizer for automatic operation, three phase naturally oil cooled indoor type & designed for input variation between 340 V to 460 V with output voltage stabilized at 415 with accuracy ± 2.5% and speed of correction 8 Volts per second and of capacity 100 KVA Complete suitable for unbalance load .
OUT GOING I. MCCB, 4pole, 160 Amps , rupturing capacity 25 KA magnetic thermal release - 01 Nos. (Legrand Cat No 4200 17/ Siemens/ Schneider) II.MCCB, 4pole, 100 Amps , rupturing capacity 16 KA magnetic thermal release - 01 Nos. (Legrand Cat No 4200 15/ Siemens/ Schneider)
Material and labour for earthing complete with galavanized steel earth electrode, 600x600x6.00 mm thick, buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level, connected to galvanozed earth strip of size 25 x 4mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No-3 connected to earthing test point all as specified or indicated inclding testing on completion including PCC pit type C-1 (1:3:6) in cement concrete & 50 mm thick precast RCC cover in (1:2:4) type B-1 reinforced with 8 mm dia MS round bar @ 75 c/c both ways with 02 Nos lifting handles of 12 mm dia MS plain bar, GI pipe 20 mm dia light grade with funnels & wire mesh for watering and 40 mm dia light grade GI pipe for earth lead protection etc including necessary earth work and excavation complete all as specified and directed. Note: The quoted rate shall deemed to be included for GI earth strip, GI pipe & protection and beyond 7.5mtrs length will be measured separtely.
Material and labour for earth continuty conductor or main earthing lead as 25x4 mm GI strip fixed to wall on batten or recess or chasses or burried in ground or drawn in conduit /pipe or fixed to pole or any other situation for loop earthing etc. complete all as specified and directed.
Excavation in trenches not exceeding 1.50 mtr wide and not exceeding 1.50 meter in depth for foundation and getting out in soft/loose soil all as specified and directed.
Excavation in trenches not exceeding 1.5 meter wide and not exceeding 1.5 m in depth for laying of cables and getting out in soft/ loose soil of excavated material complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the pipes have been laid and tested complete all as specified and directed.
Removing excavated soil to a distance not exceeding 50 meter and depositing where directed at a level not exceeding 1.50 meter above the starting point complete all as specified and directed.
Material and labour for High density polyethylene pipes (HDPE) of pressure rating 6 kgf/cm2 of size 50 mm dialaid in trenches for passing of HT/LT cable complete all as specified and directed.
Material and labour for PCC (1:4:8) type C2 using 40mm graded stone aggregate as in foundation filling and mass concrete all as specified and directed.
Material and labour for PCC cable route indicator in mix of 1:2:4 type B1 of size 450x200x75mm with oval shape and writing the letter HT/LT cable with synthetic enamel paint and embedded with PCC foundation type D2 1:4:8 of size minimum 250 mm depth including necessary earth work complete all as specefied and directed.
Material and labour brick work with flyash bricks straight or curved on plan exceeding 6m mean radius built in cement mortar 1:6 all as specified and directed.
Material and labour for Moorum filling and forming embankment including raising (or lowering) Moorum brought from out side MD land, spreading in layers not exceeding 30 cm thick, watering, ramming/ rolling and finishing to required size, shape, etc.not exceeding 1.5 m high from base all as specified and directed.
Material & labour for hard core (broken stone or boulders) of gauge n. exc. 63 mm, deposited, spread and leveled in layers n. exc. 15 cm thick, watered and rammed to a true surface all as specified and directed.
Material and labour for PCC (1:3:6) type C2 using 40mm graded stone aggregate as in foundation filling and mass concrete all as specified and directed.
Material and labour for reinforced cement concrete M-25 (design mix) for foundations, including rafts, footings, foundation beams, plinth beams, bases for coloumns, etc, basement slabs, under-reamed piles and similar articles complete as specified and directed.
Supply and fix mild steel TMT bars 10mm dia and over cut to length bent to shape required including cranking, bending spirally for hooping for columns, hooking ends, binding with mild steel annealed wire not less than 0.9mm dia or securing clips, complete all as specified and directed.
Material and labour for rendering 10 mm thick in cement mortar 1:4 on vertical fair faces of brick/ concrete surfaces complete all as specified.
Material and labour for preparation of surfaces of walls and applying two coats of cement based paint over a coat of cement primer all as specified and directed.
Excavation in post holes each not exc 0.5 Cum and getting out in any type of soil, and removing excavated soil to a distance not exceeding 50 m distance complete all as specified and as directed.
Supply and fix mild steel bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips chain link fencing confirming to Fe-410-W(Gde.E-250)quality-A or Fe290(Gde-E-165) complete all as specified and as directed.
Supply and fix mild steel screw bolts (machine made) 5 to 10 mm dia of shank with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, exc 10cm but n exc 15cm long
Supply and fix mild steel angles , bars , flats, etc as in supports for stiffening of fencing , wall ties, hold fasts, clamps plain angle cleats for securing purlins and similar small articles confirming to Fe 410-O or Fe 310-O complete all as specified and as directed.
Supply only Chain link MS Galvanized fencing, 10 guage and 50 mm mesh size.
Fixing only chain link fencing, 10 guage and 50 mm mesh size including line wires, rails, straining bolts, etc., including provision of binding wire.
N. H. Saluji & Associates
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .