| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
Tender Value
₹2.7 L
EMD Value
₹5,463
Closing Date
20 Feb 2023, 4:00 pmClosed
EE(E),BSNL ED-II HYD
6th floor BSNL bhavan Adarsh nagar Hyderabad
Shifting and installation of 160kVA RTU DG set from TE Madhapur to TE Erragadda and other connected works.
2023_BSNL_144901_1
90/BEDH-II/22-23
Open Tender
Electrical Works
Works
60 days
HYDERABAD
Please refer tender documents
16 documents required · 16 mandatory
₹590
AO cash Main BSNL Hyderabad
₹5,463
24 Feb 2023
10 Feb 2023
21 Feb 2023
10 Feb 2023
20 Feb 2023
10 Feb 2023
Amount
(Dismantling&ITC)
Dismantling of the existing 160 kVA RTU EA set,silencer , Exhaust MS pipe and bellow flexible piping including removal of incoming and out going power cables of size not less than 31/2x185 Sqmm and control panel , earthing GI/copper strips, neural connections, and other connected accessories, for easy loading of DG set at TE Bldg Madhapur etc as required.
Loading of 1No 160 kVA RTU EA set into the transport vehicle by arranging the technical supervisor, labour with suitable capacity of crane with necessary lifting equipments like belts, Iron ropes with D hooks as per site conditions etc as required.
Providing Transportation of 1No 160 kVA RTU EA set from TE Madhapur to TE Bldg Erragadda etc. as required
Unloading the 160 KVA RTU DG set at site, arranging the labour and other lifting equipements like chain pulley / crane and other alternate methods as per site conditons, from vechicle and positioning at designated location etc. as required.
ITC of the existing 160 kVA RTU EA set along with existing exhaust MS pipe and silencer on the existing EA bed i/c extension of Earthing,power cables interconnections in the control panel etc. as required.
Providing consumables for 1No 160 kVA EA Set of Kriloskar make with the following items.
Rocker Cover Gaskets
Lub Oil (15W - 40 Grade)
Lub Oil filters (Full flow Spin-on type)
Diesel Oil filters (1.1 Ltr capacity with "O" ring)
Supply and fixing hydraulic diesel flexible pipes by removing perished / damaged ones etc. as required.
Air filter element
Servicing of fuel injection pump by removing from Engine, taking it to an authorised work shop for replacing the faulty items like delivery valves, cleaning of elements, replacement of "O" rings etc, and bringing back to site fixing the same to Engine etc. as required
Servicng of nozzles and pressure testing etc. as required
Supply and fixing of relief value etc. as required
Repairing of 24 V Self startor of EA set including removing the starter from Engine, transporting to an authorised work shop for repair, replacement of faulty items like carbon brushes, bushes, body coil winding , bringing back to site, fixing the starter to Engine, interconnecting the battery cables +VE and -Ve and testing etc., as required
Complete servicing of radiator by removing the existing coolant mixed water and cleaning the same for de-scaling of existing both bottom and top tanks with necessary cleaning agents etc, as required
Providing replacement of following spares for the existing radiator i/c removing faulty etc.,as required.
Radiator hoses
Hose Clips (SS)
Radiator coolant
Arresting water leakages from roof of the canopy with sealant material at the Joints etc. by arranging the labour etc. as required
Suppy and fixing of battery leads both + Ve and - Ve (not less than 1 Mtr. including inter link Cable (not less than 0.5 Mtr) for 24 V with suitable PVC insullated single core multi strand copper cable not less than 50 Sq.mm. with heavy duty battery terminals and lugs including necessary brazing and connections etc. as required.
Supplying and fixing of SCR Controlled battery charger for continous charging of EA set battery i/c S/F of incoming connecting wires etc., as required.(M/S SHREETECH Power systems&services or S S Make)
A) 24 volts 10 Amps Battery Charger
Complete cleaning of existing diesel tank by opening the fuel suction and return adoptors and drain plug etc. as required.
Extension of existing DG Set concrete BED by provdig Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 40 mm nominal size) as per the Engineer in charge dirction and making good damages as required including plastering.finishing etc., as required
Complete servicing of engine alternator set including cleaning of over spilled diesel/ oil, tightening of " V " belts, all nuts and bolts, testing of the same in no load condition and load testing of DG set on exchange full load for 1 hr and recording the parameters like Volatge,current ,frequency,lub oil pressure and submitting service report i/c arranging diesel etc. as required.
(Earthing &Cabling)
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 25mm x 5mm GI strip on surface of wall or in recess for connections etc. as required.
Supplying and fixing of 2Nos GI earth bus bar made of size 300mm x 25mm x 5mm thick with suitable holes made to connect the bus bar strips, the bus bars shall be mounted of suitable size porcelian insulators including making good the damages done etc., as required.
Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
A) 31/2x185 Sqmm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following cables of size above 95 sq. mm and upto 185 sq. mm in the following ways etc.,as required.
On surface of wall clamped with 25/40x3mm MS flat clamp.
In the existing masonary/open duct
In the existing RCC/ HUME/ METAL pipe as required.
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
A) 31/2x185 Sqmm
Removing the 725 KVA EA Set-1 out going cable connections (of approximate size 31/2x240 Sqmm -2nos) from the DG set control panel and also at other end in Essential Panel I incoming ACB and keeping the cable in the duct by bunching the same etc.,as required.
Supplying and fixing of 250 Amps.4 pole on load changeover switch suitable for operation on 415Volts,3 phase AC supply with MS Enclosure including interconnections etc.,as required.(make;HPL or SS make)
Providing and fixing of 12V, 180 AH capacity Lead Acid maintenance free Battery including transportation and installing the same at site including interconnections and testing etc. as required. (Make: Exide Express or SS make)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .