Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.9 CrAccepted-AOC BHAGWATI BHAWAN PO HASIMARA DIST JALPAIGURI PIN 735215 | ALIPURDUAR | WEST BENGAL | 735215 | ₹8.9 Cr | L1 | Accepted-AOC Lowest Bidder |
| 2 | L2₹9.2 Cr+₹28.3 L (3.17%)Rejected-Finance | ₹9.2 Cr+₹28.3 L (3.17%) | L2 | Rejected-Finance Other Than Lowest Bidder |
| 3 | L3₹9.3 Cr+₹35.4 L (3.95%)Rejected-Finance GOKUL APARTMENTS BLOCK C SHIVMANDIR ROAD PUNJABI PARA SILIGURI 734 401 WEST BENGAL | SILIGURI | WEST BENGAL | 734401 | ₹9.3 Cr+₹35.4 L (3.95%) | L3 | Rejected-Finance Other Than Lowest Bidder |
| 4 | L4₹9.3 Cr+₹38.8 L (4.34%)Rejected-Finance 3A RAM MOHAN MULICK GARDEN LANE UNIT NO 6A 3RD FLOOR KOLKATA 700010 | KOLKATA | WEST BENGAL | 700010 | ₹9.3 Cr+₹38.8 L (4.34%) | L4 | Rejected-Finance Other Than Lowest Bidder |
| 5 | L5₹9.4 Cr+₹46.1 L (5.15%)Rejected-Finance | ₹9.4 Cr+₹46.1 L (5.15%) | L5 | Rejected-Finance Other Than Lowest Bidder |
Tender Value
₹8.2 Cr
EMD Value
₹7.4 L
Closing Date
16 Apr 2024, 6:00 pmClosed
CHIEF ENGINEER AF SHILLONG ZONE
HQ CHIEF ENGINEER AF SHILLONG ZONE MILITARY ENGINEER SERVICES ELEPHANT FALLS CAMP PO NONGLYER SHILLONG 793009
PROVISION OF DEFICIENT MARRIED ACCN AND ALLIED SERVICES AT AF STN DIGARU
2024_MES_644408_1
88454/DIG/E8
Open Tender
Civil Works
Lump-sum
545 days
DIGARU
As per tender documents
8 documents required · 8 mandatory
₹3,000
AGE (I) (AF) DIGARU
₹7.4 L
Yes
31 May 2024
28 Feb 2024
18 Apr 2024
28 Feb 2024
16 Apr 2024
8 Apr 2024
Amount
SCHEDULE "A" Part - I (BUILDINGS/STRUCTURES WORK) Details of Buildings are given here-in-before:-
SCHEDULE "A" PART- II ( SITE CLEARENCE AND DEVELOPMENT ) Details of prepriced Schedule is given in tender documents
SCHEDULE "A" PART- III ( INTERNAL ELECTRIFICATION) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-IV ( INTERNAL WATER SUPPLY ) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART- V (ROADS) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART- VI (AREA DRAINAGE) Details of prepriced Schedule is given in tender documents
SCHEDULE "A" PART- VII (SEWAGE DISPOSAL) Details of prepriced Schedule is given in tender documents
SCHEDULE "A" PART- VIII (GARBAGE BIN) Details of prepriced Schedule is given in tender documents
SCHEDULE "A" PART- IX (UG SUMP) Details of prepriced Schedule is given in tender documents
SCHEDULE "A" PART- X (EXTERNAL WATER SUPPLY) Details of prepriced Schedule is given in tender documents
SCHEDULE "A" PART- XI (FIRE FIGHTING SYSTEM) Details of prepriced Schedule is given in tender documents
SCHEDULE "A" PART- XII (HOT WATER SUPPLY) Details of prepriced Schedule is given in tender documents
SCHEDULE "A" PART- XIII (LIFT) Details of prepriced Schedule is given in tender documents
SCHEDULE "A" PART- XIV (LIGHTENING PROTECTION) Details of prepriced Schedule is given in tender documents
SCHEDULE "A" PART- XV (EXTERNAL ELECTRIFICATION) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART- XVI (STANDBY POWER SUPPLY) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART -XVII (MISCELLANEOUS ITEMS) Note:- This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col.' F ' signifies this fact only.
INTERNAL ELECTRIC SUPPLY Supply & fixing TV socket outlet for Drawing room/ Hall & Master bedroom complete with all accessories, complete all as specified and as directed.
Supply & fixing PVC insulated HD satelite RG-6 co-axial copper cable (TV Cable) with connectors and other connected accessories complete all as specified and as directed.
Supply & testing of Single Phase tamper proof Smart Prepaid energy meter based on WAN Communication system with tamper proof box, AC Single Phase two wire 240V AC, 50 HZ current rating 5-60A or 10-60A having accuracy class 1.0, conforming to relevant indian Standards (IS-16444 : 2015 (Reaffirmmed 2020) and relevant IEC Standards with dual mode (Credit/Prepay) support. Smart Prepaid Energy Meter should have marked as "PROPERTY OF MES" & must have following:- (a) Capacitive touch /Push Button Keypad in meter, Calibration LED & Load controlling feature with provisions for TOD (Time of Day) tariff & RTC (Real Time Clock) in a suitable tamper proof box. (b) Additional Bluetooth features must be enabled in meter for manually & remote vending Token transfer and ABC (Authenticated Billing Code) reading collection through remotely operated Mobile app (compatible for Android / iOS / Windows phones). (c) The Mobile App should have a provision of Offline & Online Vending token process. (d) SMS Facility for providing the vending token to consumer mobile number should be there. (e) All Prepaid meters should be provided with integrated cloud system for smart prepaid energy Note:- Warranty :- 10 Years from date of Supply with no quibble.
Installation, testing and commissioning of Single Phase Smart prepayment energy meter with box by skilled technical staff such that no faults in metering system due to poor installation, alongwith training of end user on new metering system and working with consumer & Installer mobile app, Initial reading data capturing during installation and providing the same to MES personnel's for further record keeping and accounting, SLA driven installation and commissioning work of the metering system complete all as specified and directed.
Hosting and Configuration of the Web based Software, Website Setup, User Credential Creation with following modules & services along with live Demos, accessability in above system. OTP features must be required either by APP or registered mobile number for login the Web System through Admin/Supervisor Manager & BSO/Cashier. The supplied Web/Vending Software must be configured in 2 Nos or more of MES PCs which will be given at the time of commission comprising the following :- (i) Consumer and Meter Management Module The Consumer and meter management module would be responsible for creating and managing the consumer information. System should be capable to add/remove the consumers triggered through transfers/service completion of the employees. The module shall be capable of supporting following applications :- (a) Consumer attributes update triggered through authenticated channel (b) Replacement and updation of the defective meters (c) Sanctioned load/demand update on requests through authenticated channel (d) Record keeping of the meters
Serial Item No. 22.00 (Contd....) (ii) Tariff management module The Tariff management module shall be capable of keeping up the latest tariffs consumer category wise. It will also be able to manage the revisions in existing tariffs against the government orders. System should be capable to define and manage the tariffs for both mains and auxiliary supplies. The module shall also be capable to add/update the existing tariff category and respective tariffs. (iii) Occupation and Vacation Module - The system should be capable of support the occupation and vacation of the officers as well as of other private consumers in the system. (iv) Consumer App - The occupant officers / customers should be able to view energy data and billing data on mobile application android and IOS apps. (v) Communication - Email and SMS communication to users and consumers (vi) User Administration (vi) MES User Training (vii) Website Setup (vii) Capable to connect any number of metering points in the setup
M&L for charges for comprehensive vending transaction which include for issue of token in prepaid mode via SMS or App facility, 24x7 customer support in Toll free number, reconfiguration of software in replaced meters for each supplied meters on yearly basis (to be paid in advance for 4 years) complete all as specified and directed. Note :- Contractor shall submit necessary supporting documents from OEM before taking any payment from department.
Supply and fixing LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and as directed.
Supply, installation, commissioning and testing of electric distribution board (indoor type), floor/wall mounted, dust & vermin proof factory made, fabricated out of 2.0mm thick CRCA sheet suitable for 3 Phase, 440V, 50Hz, AC supply with aluminium bus bar chamber of rating 200 Amps for 3 Phase & 4 wire system duly insulated with heat shrinkable type sleeves as per colour code comprising of following:- Incoming :- (a) MCCB 4 pole, 100 Amp, 25 KA- 01 No. Outgoing :- (a) MCB TP, 63 Amp, 25 KA-06 Nos (b) Complete internal wiring with suitable size stranded wire & suitable size lugs.
Supply and fixing LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection including street light GI pipe bracket of medium grade 40mm dia., 1.5m long bend to required size and shape including two coat of aluminum paint over a coat of red oxide primer complete in all respect all as specified and directed.
S&F piano flush type switch, 5/6 Amp, 230V, single pole, 2 way complete all as specified and as directed.
INTERNAL WATER SUPPLY S&F brass angle stop cock CP high pressure with capstan head long shank screwed down 15mm dia. bore complete all as specified and directed.
SEWAGE DISPOSAL RCC Septic tank designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, RCC M-25 Design mix in walls, Base slab, Baffle wall and roof slab including beams etc with Vent shaft, manhole opening with covers connection etc. for 100 users, dimensions of septic tank shall be as per TD drawing given for 100 users complete all as specified and as directed.
Soakage well excavation, in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M-25 concrete including intercepting chamber and screen chamber made of Brick masonry in CM, RCC cover slab in M- 25/SFRC cover, inter connecting pipes of RCC/DWC complete filled with brick bats of size 3.25 mtr dia x 4.8 mtr effective depth, complete all as specified and as directed.
Material & labour for cutting of existing DI pipe of size 100mm dia. including inserting of DI Tee & connection for tapping of new PP-R pipe dia 50 mm complete all as specified and as directed.
Supply and fix 50mm dia. cast iron valve reflux, confirming to IS-5312 with by-pass arrangement complete all as specified and as directed.
Supply and fix cast iron foot valve conforming to IS 4038, 63/65mm dia. complete all as specified and as directed.
M&L for Centrifugal Pump Set of capacity 2.0 HP (0.9WHP) with bronze impeller mounted on a common base plate and coupled directly through a set of flexible coupling with induction Motor for operation AC 230 Volt, Single Phase, 50Hz, water pump discharge capacity not less than 85 LPM at minimum 25 Mtr head, suitable RPM of 1450, including suitable size of starter, single core copper wire of suitable size for making connection stater to motor including PCC foundation as per manufacturer instruction.
M&L for construction of brick masonary valve pit of size 60cmx60cmx60 cm ( internal dimentions) with one brick thick wall in cement mortat 1:4 on 100 mm thick PCC 1:4:8 D2 ( using 40 mm graded broken stone aggregate) provision of hings welded with MS cover 3.15 mm thick, with 12mm dia. MS handel welded with MS cover and suitable locking arrangement incl 65 mm dia Godrej pad lock and applying two coats synthetic enamel paints over a coat of red oxide primer incl necessary excavation and earth work in any type of soil complete all as specified and as directed.
FIRE FIGHTING SYSTEM Supply and fix of burden type, stainless steel dial type pressure gauge 100 mm dia with ball valve for measuring the line pressure upto 0-75 Kg/sqmm range complete all as specified and as directed.
Supply and fix cast iron automatic air release valve 50mm dia. suitable for domestic water with 50mm gun metal stop valve complete all as specified and as directed.
M&L for Water type Fire Extinguisher having 9 Kg capacity complete all as per IS-15683 specifications complete all as specified and as directed.
M&L for light weight squeeze grip type CO2 Fire Extinguisher having 3 Kg Capacity complete all as per IS-15683 specifications complete all as specified and as directed.
M&L for Dry Powder (ABC) type Fire Extinguisher having 9 Kg capacity complete all as per IS-15683 specifications complete all as specified and as directed.
M&L for Mechanical Foam type Fire Extinguisher having 9 Ltr capacity complete all as per IS-15683 specifications complete all as specified and as directed.
Supply, installation, testing and commissioning of automatic AC supply control panel compatible for automatic operation of 02 Nos firefighting booster pumpsets of 900LPM discharge capacity each (01 main/working pump + 01 standby pump) at 45m head including panel control wiring for 3phase AC supply, phase indicators, toggle switches, ampere meter, voltmeter, ON-OFF push buttons, DOL starter, contactors, MCB/MCCBs etc. complete all as specified and directed. Note:- The panel should be designed in such a way so as to make enable the standby booster pump to be automatically operated in case of failure of main pump.
S&F ERW MS Intake or Suction Header pipe 150mm bore as per IS:3589, 6mm wall thickness, steel grade Fe 330, in 1.5 mtr length with welded flanges, MS flanges not less than 24mm thick, on both ends closed with end plates or with MS Dummy flanges not less than 33mm thick fixed with correct size of MS nuts, bolts and washers and buffalo leather gasket and including provision of 02 Nos inltets from water storage tank side and 02 Nos outlets for pump suction side. Both the inlet connections from tank side and outlet connections for suction of electric driven and diesel driven pumps will be made out by using MS pipe of size 100mm bore of suitable length having 6mm wall thickness as per IS: 3589. The header will be provided 01 Nos pressure gauge 0-75 kg/cm2 with brass knob on distribution branch header pipe with using a long threaded GI socket duly welded and including sluice valves (150mm dia, PN 1.6 - 02 Nos & 100mm dia, PN 1.6 -02 Nos) at inlet/outlet connections, including painting with two coat of synthetic enamelled paint over one coat of red oxide primer and including PCC work complete all as specified and directed.
S&F ERW MS distribution header pipe 150mm bore as per 1S:3589, 6mm wall thickness, steel grade Fe 330, in 1.5 mtr length with welded flanges, MS flanges not less than 24mm thick, on both ends closed with end plates or with MS Dummy flanges not less than 33mm thick fixed with correct size of MS nuts, bolts and washers and buffalo leather gasket and including provision of 02 Nos inlets from pump delivery side and 01 Nos outlet for distribution side. 02 Nos inlet connection and 01 No outlet connection shall be made by using of MS Pipe of size 100mm bore of suitable length as per IS: 3589, 6mm wall thickness including 01 No pressure gauge 0-30 kg/cm2 with brass knob on distribution header pipe with using a long threaded GI socket duly welded and including sluice valves (100mm dia, PN-1.6 - 03 Nos) as directed, including painting with two coat of synthetic enamelled paint over one coat of red oxide primer and including PCC work complete all as specified and directed.
S&F 25mm dia. PVC conduit having wall thickness not less than 1.6mm, concealed type, incl of all fittings such as elbows, tees, bends, reducers etc. as required, complete all as specified and directed.
Supply, laying & testing PVC insulated, PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (Heavy duty) with stranded copper conductor of size 4.0 sqmm x 2 core, 1100 Volts grade with all accessories complete all as specified and directed.
Supply, laying & testing PVC insulated, PVC sheathed, unarmoured, electric control cables (Heavy duty) with stranded copper conductor of size 2.5 sqmm x 2 core, 1100 Volts grade with all accessories and complete in all aspects, the cable shall be having cable pointers at every 1 Meter complete all as specified and directed.
LIGHTENING PROTECTION Earthing complete with copper earth plate electrode 600mmx600mmx3.15mm thick buried directed in ground (earth plate not less than 2.25m deep below normal ground level) with) with top edge of the plate not less than 1.5m below normal ground level) connected to and including copper earth strip 20x3mm by means of bolts, nuts, check nuts and washers of galvanised iron including PCC 1:2:4 in pit, angle iron 25x25x3mm frame work with precast RCC 1:2:4 cover reinforced with 8mm dia TMT bars @ 150mm C/C both ways and 12 mm dia MS fabricated handle, medium grade GI watering pipe 20mm bore with funnel, wire mesh and light grade GI protection pipe 40mm bore upto 5m length for drawing in earth lead wire, salt, charcoal, etc. Including excavation and earth work in any type of soil, removal of surplus soil to a distance not exc. 50m complete all as shown in electrical plate No 3 of MES schedule 2009 (Pt-I) and connected to main control board all as specified or indicated including testing on completion complete all as specified and directed.
EXTERNAL ELECTRIFICATION Supply, Installation, testing and commissioning step down transformer of 100KVA, outdoor type plinth mounted, HT 11 KV 3 phase 433 volts, 4 wire, 50Hz Delta/star connected, vector group DYN-II double copper wound, ONAN, manual type OFF load tap changing facility on HT side to vary secondary voltage to have steps at +7.5%, +5%, +2.5%, 0%, (-) 2.5%, (-) 5% & (-) 7.5% (seven steps). The transformer shall confroming to IS-1180 part 1: 2014 on March 2021 as per latest amendement issued by BEE/ IS with maximum total lose 435W AT 50% load and 1500W at 100% load and BEE certified level -II complete with all standard fittings and accessories gauges, first filling of transformer oil etc. complete including suitable platform with PCC/brick work and finished with cement mortar 1:4 as per manufacture recommended length, width and height shall be1500mmx1750mm (foundation depth should be 750mm from ground level) 125mm thick RCC slab (1:2:4) all as specifeid and as desire Type B-1 (Nominal mix) using 20mm graded stone aggregate on top of the platfrom reinforcement should be 10 mm dia @ 150c/c both way 02 nos ISMB150 comprising of following:- (a) Oil conservation with filling hole and cap drain valve and oil level gauge. (b) Silica gel breather with connecting pipe, first fill of dehydratiing agent. (c) Explosion relief mounted on tank with double diaphragm and equalizer pipe connected to conservator air spoon (Pressure release valve).
Serial Item No.46.00 (Contd....) (d) Air release piug. (e) Oil temperature indicator (gauge) having range 0° C to 200°C. (f) Thermometer pocket with thermometer dial size 100 mm dia. (g) Drain valve with threaded adapter. (h) Sampling valve (j) cover lifting eyes (k) Jacking pads, handling and lifting lugs. (l) Roller type four No wheels. (m) Rating plate and terminal marking plate cable end box on LT side. Also extra bushing for neutral outside, the LV side hand hole of sufficient size to assess the interior of the tank. (n) HT bushing on 11KV (o) First fillling of transformer oil. Note:- (i) Contractor shall submit the general aggrangment drawing and details for approval before placing order. (ii)Factory Test shall be carried out by testing officer nominated by AO. (ii) Pre- commissioning test shall be carried out SEI/EI.
S&F LED aviation obstruction light comprising of aluminium housing with Polycarbonate, 302 nos. LED are provided complete all as specified and directed.
S&F of polycarbonate cable junction box of size 300x200x105mm with complete three phase terminal with connecting clamps, nuts, screws etc. complete with fixing arrangement complete all as specified and directed.
M&L 4 mtr long GI tubing, light grade of size 20mm bore dia. to be fixed on LT tubular poles with all necessary clamps, nuts, bolts including PVC fiexible cable not less than 6 mtr length having stranded copper conductor of size 4.0 Sqmm, 2 core alongwith copper thimbles/lugs passing through the GI tubing for making electric connection from junction box to security/street light all as specified and as directed by Engr-in-Charge
Supply, installation, commisioning & testing of (Primary) LT panel board outdoor type floor mounted, dust and vermin proof factory made, fabricted out of 3.15 mm thick CRCA sheet suitable for 3 Phase, 440 volts, 50 Hz, AC supply, busbar chamber with aluminium busbar of 400 Amp rating for 3 Phase and 4 wire system duly insulated with heat shrinkable type sleeves as per colour code comprising of following :- . Incoming (a) MCCB, 4 pole, 200Amp, 36 KA - 01 No. Qutgoing (a) MCCB, 3 pole, 80Amp, 25 kA - 02 Nos. (1 for Proposed Bldg Elect DB + 1 spare) (b) MCCB, 3 pole, 63 Amp, 25kA - 01 No. (to prop secondary LT Panel for standby supply) (c) Multifunction digital meter compatible to measure current, voltage, power factor & frequency with 3 lines LCD display in 96 x 96 sqmm flush mounted case, accuracy class 1.0 - 01 No. (d) Resin cast CT 200/5A cast resin base — 01 set of 03. (e) LED indication lamp AC, 415 Volts , 50Hz for RYB - 03 Nos. (f) Control wiring with suitable size copper stranded wire. Note:- (i) The panel shall be front operatded with cable entry from the bottom with cable glands. The fault with standing capacity shall be 50kA & earth bus shall be part of the LT panel. (ii) Fabrication of panel box to be done by CPRI approved manufacturer. (iii) Cost of earth work and construction of platform for panel, brick masonary in cement mortar 1:6 with foundation PCC 1:4:8 (type D-2) including plaster work, PCC coping 1:2:4 (20mm thick crushed stone aggregate) deemed to be included in this item rate.
Supply, installation, commisioning & testing of (secondary) LT Panel board outdoor type floor mounted dust and vermin proof factory made, fabricted out of 3.15 mm thick CRCA sheet suitable for 3 Phase, 440 volts, 50 Hz, AC supply, busbar chamber with copper busbar of 125 Amp rating for 3 Phase and 4 wire system duly insulated with heat shrinkable type sleeves as per colour code comprising of following :- Incoming :- (a) MCCB, 4 pole, 63 Amp 25kA - 01 No. (Incoming) Outgoing (a) MCCB, 3 pole, 32 Amp, 16 KA - 02 Nos. (01 for LIFT + 1 Spare) (b) MCCB, 3 pole, 25 Amp, 16 kA - 01 No. (For Firefighting Booster Pump) (c) MCB, SPN, 32 Amp, 10 kA- 01 No, (for C/F Monoblock Pumpset) (d) MCB, SPN. 16 Amp, 10 kA - 01 No. (for Street Lights) (e) Multifunction digital meter compatible to measure current, voltage, power factor & frequency with 3 lines LCD display in 96 x 96 sqmm flush mounted case, accuracy class 1.0 - 01 No. (f) Resin cast CT 200/54 cast resin base — 01 set of 03. (g) LED indication lamp AC, 415 Volts , 50 Hz for RYB - 03 Nos. (h) Control wiring with suitable size copper stranded wire. Note:- (i) The pannel shall be front operatded with cable entry from the bottom with cable glands. The fault with standing capacity shall be 50 kA & earth bus shall be part of the LT panel. (ii) Fabrication of panel box to be done by CPRI approved manufacturer. (iii) Cost of earth work and construction of platform for panel, brick masonary in cement mortar 1:6 with foundation PCC 1:4:8 (type D-2) including plaster work, PCC coping 1:2:4 (20mm thick crushed stone aggregate) deemed to be included in this item rate.
Earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6mm thick buried directed in ground (earth plate not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5m below normal ground level) connected te and including galvanised iron earth lead wire 4.0 mm dia by means of bots. nuts. check nuts and washers of galvanised iron including PCC 1:2:4 in pit, angle iron 25x25x3mm frame, work with precast RCC 1:2:4 cover reinforced with 8mm dia TMT bars @ 150mm C/C both ways and 12 mm dia. MS fabricated handle, medium grade Gl watering pipe 20mm bore with funnel, wire mesh and light grade Gl protection pipe 15mm bore upto 5m length for drawing in earth lead wire, salt, charcoal, etc. Including excavation and earth work in any type of soil, removal of surplus soil to a distance not exc. 50m complete all as shown in electrical plate No 3 of MES schedule 2009 (Pt-I) and connected to main control board all as specified or indicated including testing on completion.
Earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6mm thick buried directed in ground (earth plate not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5m below normal ground level) connected te and including galvanised iron strip 32x6mm as earthing lead by means of bots. nuts. check nuts and washers of galvanised iron including PCC 1:2:4 in pit, angle iron 25x25x3mm frame, work with precast RCC 1:2:4 cover reinforced with 8mm dia TMT bars @ 150mm C/C both ways and 12 mm dia. MS fabricated handle, medium grade Gl watering pipe 20mm bore with funnel, wire mesh and light grade Gl protection pipe 15mm bore upto 5m length for drawing in earth lead wire, salt, charcoal, etc. Including excavation and earth work in any type of soil, removal of surplus soil to a distance not exc. 50m complete all as shown in electrical plate No 3 of MES schedule 2009 (Pt-I) and connected to main control board all as specified or indicated including testing on completion.
M&L for boring of holes under road, pavement, hard standing by trenchless technology or by mechanical means including making good to existing disturbed surfaces matching with existing complete all as specified and directed
STANDBY POWER SUPPLY Construction of Brick masonary platform in CM 1:6 of size 3.5 x 2.5 Mtr of height 30cm from ground level finished with 50mm PCC 1:2:4 type B-1 floor over 75mm thick 1:4:8 type D-2 sub-base over 100mm thick hardcore over rammed earth including finished with external plaster in CM 1:4 applying two coats of cement base paint over a coat of primer complete all as specified. Note:- Quoted rates shall be deemed to be included of excavation, returning filling & removing of surplus soil etc.
Supply, installation, commissioning and testing of diesel engine driven generating set of capacity 30 KVA with AMF panel complete with suitable acousatic enclosures all as per central pollution control board (CPCB) latest guidelines, 50 cycle per second with 0.8 PF, engine as per IS-10001/10002 and altemator as per IS- 13364 complete. The Engine and alternator shall be capable to take 10% over load for one hour in every 12 hours operation. The altemator of rating 30KVA of generator set shall be directly coupled with Diesel Engine mounted on common base plate with alternator and all specified and comprising of the following :- (A) Diesel Engine :- Inline, 4 cylinder diesel engine of min 30 KVA rated at 1500 RPM as per ISO 3046/BS- 5514/649 or 10002 direct injection type with turbo charger and water cooled engine electric starting system, arrangement of starting and the engine shall be capable of running 12 hours continuously and with 10% of overloading for one hour in each 12 hours running, The engine shall be equipped with all standard fittings all as per manufactures recommendations. Engine shall be directly coupled with alternator mounted on common base plate with the following :-
Serial Item No.56.00 (Contd....) (a) Electric Motors 12 volts with 01 No 12 volts, 90 AH battery with battery charger and battery charger having electronic control consisting of diodes, rectifiers contacts, resistance etc. The battery charger shall be able to charge the battery at all time whenever electric supply is given to the battery charger through control panel. (b) Heavy duty industrial silencer fitted with expansion joint and silencer pipe duly lapping with asbestos rope from engine to outside power house building up to 0.50 meters and independently supported with and including frame fixed to wall/floors. (c) Fly wheel with coupling bolts. (d) Lub oil filter. (e) Instrument panel comprising of microprocessor based controller for measuring parameters like coolant temperature, running hours, lubricating oil pressure etc. (f) Engine speed govemor (Electro Mechanical) class Al, Governing as per BS 5514. (g) Air filter (Dry type). (h) Turbocharger of suitable capacity. (j) Gear pump for forced feed lubrication. (k) Fuel Injection pump. (i) Fuel filter double bow. (m) Microprocessor based controller in panel for high cooling water temperature and low lube oil pressure with alarm and shut down facility. (n) Radiators. (0) Flexible rubber coupling.
Serial Item No. 56.00 (Contd....) (p) Set of fuel pipes of suitable length. (q) Base plate. (r) Fuel tank capacity as per manufacture's design with all connecting pipe and fabricated MS stand including level gauge. (s) Anti vibrating pads and mounting for the generators set, Engine and altemator. (t) Lagging of exhaust manifold with asbestos rope to exposed pipes. (u) 40mm bore flexible exhaust pipe with end flanged. (v) Engine emissions should be confoming the CPCB latest guidelines of emission limits. (B) Alternator :- Alternator of rating capacity 24 KW (30 KVA) and capable to take 10% extra load at every 12 hours interval for one hour, 3 phase, 4 wire, 50Hz, 415 volts, 0.8 power factors, 1500 RPM self excited self regulated required to be, coupled with above engine. The alternators shall be conforming to IS-4722 & IS-4728 as per following specifications:- (a) Type : Salient poles, single bearing brushless type suitable for direct coupling to engine. (b) Rating : Guaranteed to deliver required output at the ambient temp conditions. Suitable for an over load of 10% for 1 hour in every 12 hours operations. (c) Voltage regulation : Provided with fast response thyristors type electronics automatic voltage regulators, which holds output voltage with in desired limits (+/- 1%) (d) Self excited - self regulated. (e) Alternator loading : suitable for taking rated load immediately after machines reaches rated voltage and speed.
Serial Item No. 56.00 (Contd....) (f) Vibration : Suitable for direct coupling with engine and mounted on Common MS channel base frame. (g) Enclosures : screen protected drip proof enclosure with IP23 degree of protection (h) Cooling : Air cooled type with radial fan mounted on rotors. (j) Control panel shall be provided with PC 1.1 Controller and digital display for measuring of line / phase voltages / currents, frequency etc. and having MCCB of 63 Amps with overload and short circuit protection. (C) AMF Panel :- (i) Standard control panel for DG set shall be made of fabricated sheet cubical type with front hinged cover, with internal copper wiring and of suitable size complete with microprocessor based controller with following features :- (a) State of the art compact Microprocessor based fully configurable technology. (b) Integration of all engine and alternator parameters. (c) For ease of viewing, high performance graphical LCD and prominent display. (d) Event logging history for easy of maint/service. (e) Capability of withstanding wide range of operating temp. (f) Individual touch buttons for manual, auto and test mode. (g) LED indications for genset status and alarms. (h) Battery conditions monitoring. (j)Statistical cumulative counters like, No of starts, Engine run Hrs, Kwh. (k) Setting provisions for different parameters on front panel. (l) Two Nos. Microprocessors based EDO , MCCB 63 Amps, 25 KA breaking capacity, one for main supply and other for DG set supply. (m) Two No contactors of 100 Amps capacity for main and DG. (n) Aluminium bus bars of 100 Amps capacity provide with termination.
Serial Item No. 56.00 (Contd....) (ii) Display Parameters :- (a) Electrical parameters : Phase voltage , line current, frequency, average voltage, average current, KW, KWH, KVA, KVAR, power factor. (b) Mechanical parameters : Lube oil pressure, coolant temp, engine speed, fuel status, engine run hours, battery voltage. (iii) Protections :- (a) Electrical protections : Under/Over voltage, under/over frequency, phase failure. Phase sequencer reverse, over current, Over KW. (b) Mechanical Protections : Under/over speed, low lube oil pressure, high engine coolant temp, low fuel level alarm, start/stop fail, charging alternator fail. (iv) Cable entry gland plate with out cable glands. (D) Connection of alternator control panel to LT panel with PVC insulated unarmoured single core copper cable of size 25 Sqmm, 1100 volts grade including copper tube terminal heavy duty at both ends for connections and 40m long (E) Foundations :- DG Set shall be installed on new foundation block as per manufacture recommendations. Note :- The foundation shall be measured and paid seperately.
Comprehensive maintenance and repair of fully automatic electrically operated fire elevator lift of any make installed for Stilt+4 configuration building comprising of all devices and accessories through out 12 months on all days including holidays for period of 03 years after expiry of defects liability period as shown below and all as specified and directed by AGE(I).
(a) 1st year after expiry of defects liability period
(b) 2nd year after expiry of defects liability period
(c) 3rd year after expiry of defects liability period
BHOWMICK ENTERPRISES INDIA
M/s KASHMIRA SINGH BARMI AND SONS
NARSINGH DEVELOPERS LLP
DNS CONSTRUCTION COMPANY
VERMA BROTHERS
surendra infrastructure pvt ltd
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .