| Sl No | Description | Qty | Unit | CORONET ENGINEERS P LTD L1 | Kevin Electricals Pvt Ltd L3 | Mahalakshmi Electricals L2 |
|---|---|---|---|---|---|---|
| 1.00 | Design, fabrication, assembling, Factory testing, supply, installation, site acceptance testing, and commissioning of 415 V, 630 A, 50 KA/ 1sec EMCC-001 panel as per the technical specification and drawing. | 1 | No | 17,52,893 ₹17,52,893 Lowest | 33,00,000 ₹33,00,000 | 31,00,000 ₹31,00,000 |
| 2.00 | Design, fabrication, assembling, factory testing, supply, installation, site acceptance testing, and commissioning of 415 V, 630 A, 50 KA/ 1sec EMCC-002 panel as per the tender specification and drawing. | 1 | No | 17,52,893 ₹17,52,893 Lowest | 32,90,000 ₹32,90,000 | 30,90,000 ₹30,90,000 |
| 3.00 | Design, fabrication, assembling, factory testing, supply, installation, site acceptance testing, and commissioning of 415 V, 800 A, 50 KA/ 1sec EMCC-003 panel as per the tender specification and drawing. | 1 | No | 23,85,131 ₹23,85,131 Lowest | 44,00,000 ₹44,00,000 | 40,00,000 ₹40,00,000 |
| 4.00 | Design, fabrication, assembling, factory testing, supply, installation, site acceptance testing, and commissioning of 415 V, 800 A, 50 KA/ 1sec EMCC-004 panel as per the tender specification and drawing. | 1 | No | 23,92,992 ₹23,92,992 Lowest | 41,00,000 ₹41,00,000 | 39,45,031 ₹39,45,031 |
| 5.00 | Design, fabrication, assembling, factory testing, supply, installation, site acceptance testing, and commissioning of 415 V,250A, 50kA/ 1 Sec, NMLDB panel as per the tender specification and drawing. | 1 | No | 17,68,394 ₹17,68,394 | 14,50,000 ₹14,50,000 | 10,00,000 ₹10,00,000 Lowest |
| 6.00 | Design, fabrication, assembling, factory testing, supply, installation, site acceptance testing, and commissioning of 415 V,250A, 50kA/ 1 Sec, EMLDB panel as per the tender specification and drawing. | 1 | No | 10,37,200 ₹10,37,200 | 10,00,000 ₹10,00,000 | 7,99,999 ₹7,99,999 Lowest |
| 7.00 | Design, fabrication, assembling, factory testing, supply, installation, site acceptance testing, and commissioning of 20 kW Heavy duty VFD Panel with Star-Delta by-pass starter as per the technical specification and drawing. | 2 | Nos. | 3,40,179 ₹6,80,358 Lowest | 4,50,000 ₹9,00,000 | 3,80,000 ₹7,60,000 |
| 8.00 | Design, fabrication, assembling, factory testing, supply, installation, site acceptance testing, and commissioning of 90 kW Heavy duty VFD Panel with Star-Delta by-pass starter as per the technical specification and drawing. | 2 | Nos. | 6,78,555 ₹13,57,110 Lowest | 9,80,000 ₹19,60,000 | 8,00,000 ₹16,00,000 |
| 9.00 | Design, fabrication, assembling, factory testing, supply, installation, site acceptance testing, and commissioning of 110 kW Heavy duty VFD Panel with Star-Delta by-pass starter as per the technical specification and drawing. | 4 | Nos. | 7,27,769 ₹29,11,076 Lowest | 10,50,000 ₹42,00,000 | 9,00,000 ₹36,00,000 |
| 10.00 | Design, fabrication, assembling, factory testing, supply, installation, site acceptance testing, and commissioning of 132 kW Heavy duty VFD Panel with Star-Delta by-pass starter as per the technical specification and drawing. | 6 | Nos | 8,04,224 ₹48,25,344 Lowest | 13,00,000 ₹78,00,000 | 11,00,000 ₹66,00,000 |
Tender Value
₹3.4 Cr
EMD Value
₹6.8 L
Closing Date
16 Jan 2025, 3:00 pmClosed
Project Director, FRFCF
Office of the Project Director, FRFCF-NRB, Kalpakkam.
Design, Fabrication, Installation, Testing and Commissioning of EMCC Panels, VFD Panels, Cable Carrier Systems and its associated works at 309 Building in FRFCF, Kalpakkam
2024_BARC_837665_1
BARC/NRB/FRFCF/ELE/ETR046/2024
Open Tender
Electrical Works
Item Rate
365 days
FRFCF, KALPAKKAM
please refer tender document
8 documents required · 8 mandatory
₹0
₹6.8 L
18 Mar 2025
4 Dec 2024
17 Jan 2025
4 Dec 2024
16 Jan 2025
4 Dec 2024
4 Dec 2024 - 18 Dec 2024
Amount
Design, fabrication, assembling, Factory testing, supply, installation, site acceptance testing, and commissioning of 415 V, 630 A, 50 KA/ 1sec EMCC-001 panel as per the technical specification and drawing.
Design, fabrication, assembling, factory testing, supply, installation, site acceptance testing, and commissioning of 415 V, 630 A, 50 KA/ 1sec EMCC-002 panel as per the tender specification and drawing.
Design, fabrication, assembling, factory testing, supply, installation, site acceptance testing, and commissioning of 415 V, 800 A, 50 KA/ 1sec EMCC-003 panel as per the tender specification and drawing.
Design, fabrication, assembling, factory testing, supply, installation, site acceptance testing, and commissioning of 415 V, 800 A, 50 KA/ 1sec EMCC-004 panel as per the tender specification and drawing.
Design, fabrication, assembling, factory testing, supply, installation, site acceptance testing, and commissioning of 415 V,250A, 50kA/ 1 Sec, NMLDB panel as per the tender specification and drawing.
Design, fabrication, assembling, factory testing, supply, installation, site acceptance testing, and commissioning of 415 V,250A, 50kA/ 1 Sec, EMLDB panel as per the tender specification and drawing.
Design, fabrication, assembling, factory testing, supply, installation, site acceptance testing, and commissioning of 20 kW Heavy duty VFD Panel with Star-Delta by-pass starter as per the technical specification and drawing.
Design, fabrication, assembling, factory testing, supply, installation, site acceptance testing, and commissioning of 90 kW Heavy duty VFD Panel with Star-Delta by-pass starter as per the technical specification and drawing.
Design, fabrication, assembling, factory testing, supply, installation, site acceptance testing, and commissioning of 110 kW Heavy duty VFD Panel with Star-Delta by-pass starter as per the technical specification and drawing.
Design, fabrication, assembling, factory testing, supply, installation, site acceptance testing, and commissioning of 132 kW Heavy duty VFD Panel with Star-Delta by-pass starter as per the technical specification and drawing.
Supply, installation, testing, and commissioning of energy-efficient 20W, 2*2 feet Recess Mounted LED Luminaires With CCT of 6500K, having a minimum CRI of 80, lumen ouput of minimum 2500, minimum lumen efficiency of 110 lm/w, ingress protection minimum of IP20 and impact resistance of min IK-05 having THD of less than 10% in pressure die-cast aluminium housing, etc., with a suitable current control driver circuit and complete with all accessories including mounting arrangements with provision and connection for 2.5 sq.mm flexible copper conductor of PVC insulation wire etc., as per the detailed specification and instruction of Engineer-in-Charge.
Fabrication, assemling and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Ladder type cable trays" with GI coupler plates, GI, L clips, GI bolts, nuts & washers with thickness of 2.0 mm as per drawings, specifications and scope of work. Dimension:150mm width x 100 mm depth x 2.0 mm thickness
Fabrication, assemling, supply and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Soild type cable trays" with GI coupler plates, GI, L clips, GI bolts, nuts & washers with thickness of 2.0 mm as per drawings, specifications and scope of work. Dimension:450mm width x 100 mm depth x 2.0 mm thickness
Fabrication, assemling, supply and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Soild type cable trays" with GI coupler plates, GI, L clips, GI bolts, nuts & washers with thickness of 2.0 mm as per drawings, specifications and scope of work. Dimension:300mm width x 100 mm depth x 2.0 mm thickness
Fabrication, assemling, supply and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Soild type cable trays" with GI coupler plates, GI, L clips, GI bolts, nuts & washers with thickness of 2.0 mm as per drawings, specifications and scope of work. Dimension: 150mm width x 100 mm depth x 2.0 mm thickness
Fabrication, assemling, supply and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Perforated type cable trays" with GI coupler plates, GI, L clips, GI bolts, nuts & washers with thickness of 2.0 mm as per drawings, specifications and scope of work. Dimension: 450mm width x 100 mm depth x 2.0 mm thickness
Fabrication, assemling, supply and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Perforated type cable trays" with GI coupler plates, GI L-clips, GI bolts, nuts & washers with thickness of 2.0 mm as per drawings, specifications and scope of work. Dimension:300mm width x 100 mm depth x 2.0 mm thickness
Fabrication, assemling, supply and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Perforated type cable trays" with GI coupler plates, GI L-clips, GI bolts, nuts & washers with thickness of 2.0 mm as per drawings, specifications and scope of work. Dimension: 150mm width x 100 mm depth x 2.0 mm thickness
Fabrication, assemling, supply and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Perforated type cable trays" with GI coupler plates, GI L-clips, GI bolts, nuts & washers with thickness of 2.0 mm as per drawings, specifications and scope of work. Dimension: 100mm width x 100 mm depth x 2.0 mm thickness
Fabrication, assemling, supply and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Solid type cable tray Cover" with thickness of 2.0 mm as per drawings, specifications and scope of work. Dimension: 450mm cable tray Cover with 2.0 mm thickness
Fabrication, assemling, supply and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Solid type cable tray Cover" with thickness of 2.0 mm as per drawings, specifications and scope of work. Dimension: 300mm cable tray Cover with 2.0 mm thickness
Fabrication, assemling, supply and installation of hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Solid type cable tray Cover" with thickness of 2.0 mm as per drawings, specifications and scope of work. Dimension: 150mm type cable tray Cover with 2.0 mm thickness
Loading, Transportation, Unloading at site, installation, Testing and Commissioning of 1100 Volts Grade PVC/HRPVC/XLPE insulated, Stranded Aluminium/copper conductor cables upto 3/3.5/4Core X 25 sq.mm sizes in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the tender specification (Note: Cable will be issued free of cost by the department).
Loading, Transportation, Unloading at site, installation, Testing and Commissioning of 1100 Volts Grade PVC/HRPVC/XLPE insulated, Stranded Aluminium/copper conductor cables above 3/3.5/4Core X above 25 sq.mm & upto 120 sq.mm sizes in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the tender specification (Note: Cable will be issued free of cost by the department).
Loading, Transportation, Unloading at site, installation, Testing and Commissioning of 1100 Volts Grade PVC/HRPVC/XLPE insulated, Stranded Aluminium/copper conductor cables above 3/3.5/4Core X above 120 sq.mm & upto 240 sq.mm sizes in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the tender specification (Note: Cable will be issued free of cost by the department).
Loading, Transportation, Unloading at site, installation, Testing and Commissioning of 1100 Volts Grade PVC/HRPVC/XLPE insulated, Stranded Aluminium/copper conductor cables above 3/3.5/4Core X above 240 sq.mm & upto 400 sq.mm sizes in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the tender specification (Note: Cable will be issued free of cost by the department).
Loading, Transportation, Unloading at site, Laying, Testing and Commissioning of PVC insulated & Sheathed, armoured control cables of Upto 14 Core 2.5 sq.mm sizes in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the detailed specification.(Note: Cable will be issued free of cost by the department).
End Termination of the 4 Core X 2.5 sq.mm (including cable gland earthing) size of Copper Conductor PVC/XLPE Insulated and FRLS sheathed armoured UG Cable using Single Compression, Heavy Duty, Siemens type Brass Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Copper crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland.
End Termination of the 4 Core X 16 sq.mm (including cable gland earthing) size of Copper Conductor PVC/XLPE Insulated and FRLS sheathed armoured UG Cable using Single Compression, Heavy Duty, Siemens type Brass Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Copper crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland.
End Termination of the 3.5/ 4 Core X 35 sq.mm size of Aluminium Conductor PVC Insulated and sheathed armoured UG Cable using Single Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Comet or equivalent make Aluminium crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland.
End Termination of the 3.5/ 4 Core X 70 sq.mm size of Aluminium Conductor PVC Insulated and sheathed armoured UG Cable using Single Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Comet or equivalent make Aluminium crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland.
End Termination of the 3.5/ 4 Core X 120 sq.mm size of Aluminium Conductor PVC Insulated and sheathed armoured UG Cable using Single Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Comet or equivalent make Aluminium crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland.
End Termination of the 3.5/ 4 Core X 185 sq.mm size of Aluminium Conductor PVC Insulated and sheathed armoured UG Cable using Single Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Comet or equivalent make Aluminium crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland.
End Termination of the 3.5/ 4 Core X 240 sq.mm size of Aluminium Conductor PVC Insulated and sheathed armoured UG Cable using Single Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Comet or equivalent make Aluminium crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland.
End Termination of the 3.5/ 4 Core X 300 sq.mm size of Aluminium Conductor PVC Insulated and sheathed armoured UG Cable using Single Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Comet or equivalent make Aluminium crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland.
End Termination of the 3.5/ 4 Core X 400 sq.mm size of Aluminium Conductor PVC Insulated and sheathed armoured UG Cable using Single Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Comet or equivalent make Aluminium crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland.
End termination of 1100 Volts Grade XLPE/PVC insulated, control cables of 10 Core X 2.5 sq.mm sizes using Single Compression, Heavy Duty, Siemens type Gland connecting the cable to the equipment such as Switches / PanelBoards / Motors etc. using Dowell's or equivalent make Copper crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for the completion of the work.
Supply, fabrication and installation of 25 X 6 mm GI flat size of Hot dip Galvanised GI Flats in Built in trenches on walls, poles, RCC Concrete and through embedded pipes as per the detailed specification. No cutting or drilling permitted after galvanisation.
Supply and installation of 95 Sq.mm multi Stranded tinned copper conductor in Walls, Floors, Built in Trenches including supply of GI spacer and clamps, fixing fasteners etc as per detailed specification.
End Termination of the 95 Sq.mm multi Stranded tinned copper conductor including supply of copper crimping lugs etc.
Supply and installation of 185 Sq.mm multi Stranded tinned copper earthing Conductor in Walls, Floors, Built in Trenches including supply of GI spacer and clamps, fixing fasteners etc as per tender specification.
End Termination of the 185 Sq.mm multi Stranded tinned copper conductor including supply of copper crimping lugs etc.
Fabrication, supply and Installation of GI: MS fabrication With hot dipped galvanising Brackets, Supports, Frame work, Clamps, Base Channels, etc. fabricated out of angle / Channel / Rods etc. The rate quoted shall include the cost of fabrication / welding, cleaning and painting/ galvanising as follows including supply of required, fasteners, nuts, washers, etc.
Mahalakshmi Electricals (BID ID -3147888)
Kevin Electricals Pvt Ltd (BID ID -3154258)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tenderdocument.pdf
Tender Documents • 5.24 MB
BOQ.xls
BOQ • 0.31 MB
Tenderdocument.rar
Tender Documents • 5.48 MB
Tenderdocument_2.rar
Tender Documents • 19.96 MB
Tenderdocument_2.pdf
Tender Documents • 4.88 MB
Tenderdocument_3.pdf
Tender Documents • 32.40 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .