Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.6 CrAccepted-AOC 19192 STREET NO 8 BIBI WALA ROAD OPPOSITE DAV COLLEGE BATHINDA PUNJAB PIN 151001 | BATHINDA | BATHINDA | PUNJAB | 151001 | ₹1.6 Cr | L1 | Accepted-AOC Being lowest |
| 2 | L2₹1.7 Cr+₹6.4 L (4.02%)Rejected-AOC 368 PHASE 4 SAS NAGAR MOHALI 160059 PB | S A S NAGAR | PUNJAB | 160059 | ₹1.7 Cr+₹6.4 L (4.02%) | L2 | Rejected-AOC Being other than lowest |
| 3 | L3₹1.7 Cr+₹8.1 L (5.09%)Rejected-AOC 00 00 NAPASAR ROAD NENO KA BASS BIKANER RAJASTHAN BIKANER RAJASTHAN 334022 UDYAM RJ 08 0001676 | BIKANER | RAJASTHAN | 334022 | ₹1.7 Cr+₹8.1 L (5.09%) | L3 | Rejected-AOC Being other than lowest |
Tender Value
Refer Docs
EMD Value
₹2.1 L
Closing Date
29 Mar 2024, 6:00 pmClosed
CWE (AF) Chandigarh
HQ CWE (AF) Chandigarh PIN-160003
PROVN OF GAS BASED FIRE EXTINGUISHING SYSTEM, EXTERNAL LADDER AND STEEL STAGING IN CERTAIN BUILDINGS AT AF STATION CHANDIGARH
2023_MES_631414_2
CWE/AF CHD/CHD/T-03/2023-24
Open Tender
Civil Works
Lump-sum
270 days
Chandigarh
As per NIT
8 documents required · 8 mandatory
₹1,000
GE(AF) Chandigarh
₹2.1 L
5 Sept 2024
27 Feb 2024
1 Apr 2024
27 Feb 2024
29 Mar 2024
12 Mar 2024
Amount
GENERAL SUMMARY
Lump sum price worked by contractor for 'BUILDING/STRUCTURE' Works as listed in Schedule 'A' Part I
Lump sum price worked by contractor for 'STEEL STRUCTURE FOR SERVICE TANKS' Works as listed in Schedule 'A' Part II
Lump sum price worked by contractor for 'INTERNAL ELECTRIFICATION' Works as listed in Schedule 'A' Part III
Lump sum price worked by contractor for 'ROAD, PATH AND CULVERT' Works as listed in Schedule 'A' Part IV
Lump sum price worked by contractor for 'EXTERNAL ELECTRIFICATION' Works as listed in Schedule 'A' Part V
Lump sum price worked by contractor for 'FIRE FIGHTING' Works as listed in Schedule 'A' Part VI
Lump sum price worked by contractor for 'SEPTIC TANK AND SEWAGE LINE' Works as listed in Schedule 'A' Part VII
Lump sum price worked by contractor for 'EXCAVATION AND EARTH " works as listed in Schedule 'A' Part VIII
Lump sum price worked by contractor for 'DEMOLITION AND DISMANTLING' Works as listed in Schedule 'A' Part IX
Schedule 'A' Part X "MISC ITEMS OF WORKS" Note:- This Schedule is not pre priced by MES and Pre-Priced rate as "Rs 0.00" under Column 5 signifies this fact only
FIRE FIGHTING
Supply,laying, jointing and testing MS flanged Pipes heavy grade of size 100 mm dia with all fittings laid in floors or fixed to walls upto a height of six storey building including supporting/fixing clamps made from 50x6 mm size MS flat iron duly grouted in wall and ceilings etc incl jointing materials nuts/bolts/washers/gaskets etc complete all as specified and directed. Note - Pipe and clamps shall be painted with two coats of post office red enamelled paint over a coat of red oxide primer. Unit rate quoted shall be deemed to include the cost of the same and nothing extra shall be paid on this account.
Cutting existing 80mm bore CI/GI water supply pipe line in any position for incertion of new Tee for taping new pipe line with existing complete all as specified and directed
Supply,laying, jointing and testing MS flanged Pipes heavy grade of size 50 mm dia with all fittings laid in floors or fixed to walls upto a height of six storey building including supporting/fixing clamps made from 40x5 mm size MS flat iron duly grouted in wall and ceilings etc incl jointing materials nuts/bolts/washers/gaskets etc complete all as specified and directed. Note - Pipe and clamps shall be painted with two coats of post office red enamelled paint over a coat of red oxide primer. Unit rate quoted shall be deemed to include the cost of the same and nothing extra shall be paid on this account.
S & F gun metal branch pipe 63 mm dia, male and female threaded outlet complete with hexagonal base bore zozzels as per IS 903 complete all as specified and directed.
S & F fire hose box of MS size 3' x 2' x 2' to accommodate two Nos 15 mtr long fire hoses with branch pipes, glass fronted, double door with lock , painted red outside dully fixed with supporting structure complete all as specified and directed.
Supply and fix electric motor siren conforming to IS 1941 suitable for three phase 415 V supply with motor not exceeding 3.75 KW power and able to deliver 143 DB noise level including connections with suitable size copper cables & PVC rigid/flexible conduits as required at site for satisfactory functioning complete all as specified and directed.
Supply,laying, jointing and testing of MS flanged Pipes heavy grade of size 150 mm dia with all fittings laid in floors/trenches or fixed to walls incl jointing materials nuts/bolts/washers/gaskets etc complete all as specified and directed.
Supply and fix CI non return valve flanged ends with bypass arrangement of size 150 mm dia class PN-1.6 incl all jointing materials nuts/bolts/washers/gaskets etc complete all as specified and directed.
Supply, installation, testing and commissioning of LT panel board (CPRI Approved) of suitable size factory made, compartment type, dust, water and vermin proof (IP-65 protection) duly powder coated with 7 tank process powder coating , indoor type suitable for 1100 volts grade, 3 phase, 4 wire supply, floor mounted fabricated out 2 mm thick CRCA Sheet on 50mm X 50mm X 6mm angle iron frame, 120 cm long angle iron legs 04 Nos made from 50mm X 50mm X 6mm angle iron for grouting in floor with cement concrete PCC foundation of suitable size in 1:2:4 type B-I (using 20mm graded stone aggregate) and front & rear door detachable type fixed with nuts/bolts inclusive of locking arrangements with provision of all incoming/outgoing cable entries along with suitable size of double compression type cable glands and heavy duty thimbles for incomming & out going cable all as specified and comprising the following:-
(j) Danger notice plate 440 V with conventional skull and bones in red signal colour - 01 No and earthing terminals - 02 Nos (k) Wiring from pressure switches to motor starters for automatic operation of pump sets with suitable size of FRLS copper coductor cables laid in & incl PVC rigid / flexible conduits laid under fllor/fixed to walls etc. (l) Contactors , relays, wiring of circuits , timers etc for automatic operation (ON/OFF) of pump sets as per the set pressure conditions. (m) Connections of pump set motors ( from starter upto motor terminal) with three runs of single core PVC insulted 1100 volt grade haevy duty strnaded copper conductor cable laid in & incl PVC rigid / flexible conduits laid under fllor/fixed to walls etc. Note :- Sequence of opeartion of pump sets and water pressure condions shall be as directed by Engr - in - Charge.
Supply, fixing, connecting and testing of pressure switches of suitable capacity & range for pressurised fire fighting pumping system including connections with suitable size copper cables & PVC rigid/flexible conduits as required at site for satisfactory functioning complete all as specified and directed.
Supply, installation, Commissioning and testing of silent diesel engine driven factory assembled, floor mounted, Generating set of capacity 100 KVA, 3 phase, 4 wire ,50 HZ,1500 RPM AMF (automatic on mains failure) type , complete with safety control and metering equipment, mounted on common base frame on new PCC foundation required at site and as recommended by manufacturer, all as specified and as directed comprising of the following:-
(A) Prime Mover directed coupled, diesel engine turbo charged water cooled suitably de-rated of matching BHP for driving 100 KVA capacity alternator electric start, four stroke,1500 RPM conforming to IS-10000 part- II, 1980, IS 10001/10002 for continuous running and capable for taking 10% overload for one hour complete.with the accessories :-
(i) Fly wheel to suit flexible coupling. (ii) Flexible coupling with guard (iii) Air cleaners both oil type/dry type with filters (iv) Lubricating oil filter, fuel filter, fuel pre filter. (v) Blower type fan (vi) Fuel injecting system with injection pump, nozzles, governer (electronic) of suitable capacity. (vii) Electric start equipment (viii) Lead acid storage maintenance free battery 12 volts of rating 180 AH (01 Nos) with charging alternator, ammeter, as recommended by manufacturer make-Exide along with copper battery lead and connector. (ix) Battery rack made out of MS angle iron 40 mm x 40 mm x 5mm & 150 mm height . (x) Standard safety device. (xi) Inbuilt fuel tank of suitable capacity for minimum 08 hrs run with mechanical level indicator,detachable, strainer,drain cock, fuel outlet, air vent and locking arrangement etc, including fuel pipe connections. (xii)Exhaust silencer (Residental silencer ) with exhaust piping of suitable size brought out side on top of size as per OEM's specifications and complete length of silencer and exhaust piping continuosly wrapped with 12 mm dia asbestos rope and suitable anti-vibration arrangement arournd pipe passing through wall.
(xiii) LCD display type control panel as per manufacturer's instructions indicating KWH, KVA PF,Volts, Amps ,HZ ,RPM Hour, oil pressure,oil temperature, coolant, temperature, fuel level, battery charging, ammeter, battery charging lamp and indicator lamp (RYB), panel duly pre wired and displaying protection and safeties as under- (aa) Protection :- Short circuit, overlaod, over speed, earh fault as standard and reverse power as optional . (ab)Safeties:- Auto shut down,visual & audio alarm for low lub oil pressure, high coolant temperature, low fuel lavel, canopy temperature & radiator water lavel . (B)Alternator 100 KVA brushless type at 0.8 power factor,self regulated, self excited,screen protected 3 phase with neutral 415 volts 50 Hz, 1500 RPM, as per IS :13364/IS :2613/ IS-4722 complete with automatic voltage regulator, having voltage regulation + /- 1%, SPDP encloser including making cable connections, insulation class -H and alternator control panel as supplied by manufacturer. (C) Base frame sturdy, MS febricated, channel iron base frame for mounting the engine & alternator with anti vibration pads.
(d) AMF panel (Supplied by the OEM of DG set only) suitable for 100 KVA DG set, outdoor type fabricated out of 3.15 mm thick CRCA sheet and 50x50x6 mm angle iron for base frame and legs (04 Nos legs 900 mm long), comprising of copper strip TPN bus bars 300 amps capacity mounted on epoxy insulators, 4 pole power contactors 160 amps capacity 415 volts 50 Hz for mains/DG supply/output supply, relays, timers, multifunctional digital meter for mains & DG supply, load ON DG set indicator, 4 pole MCCBs 100 amps 415 volts 50 Hz for mains input, DG input and AMF panel output supply, emergency stop button, complete wiring with copper conductor cable 1100 volts grade of appropriate size incl protection MCBs, PCC foundation 1:2:4 type B-1 for grouting of panel complete all as specified and directed - 01 No
(D) Acoustic encloser of suitable size to accommodate DG set 100 KVA, modular constuction, fabricated out of 3 mm thick, cold annealed CRCA sheet, duly epoxy painted, doors to be provided with high quality EDPN gasket, duly epoxy painted.The canopy to be equipped with heavy duty fans of reputed manufacturer for air circulation and cooling the canopy. Rock wool of requisite density per Kg M3 to be used for insulation. Enclosure to be provided with one light point controlled with one switch for internal lighting. Noise level at one metre to be 75 decibels@ one mtr in line as per CPCB norms . Note-:- (i)The engine of DG set shall be suitably conditioned to suit the climatic conditions of Chandigarh, so as to give desired outputs including and testing up to 10% over load. (ii) Foundation of the DG set (PCC/RCC) will be provided by the contractor and will be made as per the manufacturer's instructions. Cost of foundation is deemed to be included in the rate of this item. (iii) The items required for testing of DG set e.g. fuel, tripod, tools, water tank etc. and panel below, shall be provided by the contractor and the rate of which is deemed to be included in the rate of this item .Testing of DG set shall be carried out as specifed . (iv) The DG set shall only be procured after completion of work upto 75% in case earlier procurement by contractor ' No payment' shall bemade for this item.
Supply, installation, testing and commissioning of PESO approved 80 Ltrs cylinder with valve assembly and pressure gauge and cap complete all as specified and directed.
Supply, installation, testing and commissioning of PESO approved 140 Ltrs cylinder with valve assembly and pressure gauge and cap complete all as specified and directed.
Supply and filling Novec 1230 Gas FK1230/3M in 80/140 ltrs sylinders complete all as specified and directed.
Supply, installation, testing and commissioning of Master Cylinder Acesssories electric cum manual actuator & 2 inch discharge hose flexible. Make : UTC(Kidde)/Cryptzo/Synergy
Supply, installation, testing and commissioning of discharge Nozzles 360//180 degree complete all as specified and directed. Make : UTC(Kidde)/Cryptzo/Synergy
Supply, installation, testing and commissioning of Tank mounting bracket fabricated out of 50x6mm flat iron duly painted as directed for cylinder of capacity 80 ltr and 140 ltr complete all as specified and directed.
Supply and fix warning plate Exit (Signage) light fixture with 1.5 hrs battery back up for use outside room all as directed including connections with suitable size copper cables & PVC rigid conduits as required at site for satisfactory functioning.complete all as specified and directed.
Supply, installation,testing and commissioning of manifold fabricated from M.S seamless pipes as per ASTM A 106 Sch .40 complete incl fittings/supports etc to be used for piping of sizes as per OEMs specifications and site requirement for trouble free & efficient functioning of the fire extinguishing system complete all as specified and directed.
Supply, installation, testing and commiossioning of intelligent conventional multi-criteria sensor (photo- thermal) detector with mounting base complete as required including connections with suitable size copper cables & PVC rigid conduits for satisfactory functioning complete all as specified and directed.. Make : Ravel/Honeywell/Edward
Supply, installation,testing and commissionng of conventional type dual tone hooter with minimum sound level of 85dB at a distance of 1 mtr with strobe flash light with addressable control module, ceiling/ wall mounted arrangement etc as required including connections with suitable size copper cables & PVC rigid conduits for satisfactory functioning complete all as specified and directed. Make :Ravel/Honeywell/Edward
Supply,installation, testing and commissioning of manual gas release switch (MCP green) complete including connections with suitable size copper cables & PVC rigid conduits as required at site for satisfactory functioning complete all as specified and directed.Make: Ravel/Honeywell/Edward
Supply,installation, testing and commissioning of Abort switch for gas release (MCP yello) complete including connections with suitable size copper cables & PVC rigid conduits as required at site for satisfactory functioning complete all as specified and directed.. Make: Ravel/Honeywell/Edward
Supply, installation ,testing and commissioning of 2 Zone gas release panel with release module and battery backup with history of log of events including connections with suitable size copper cables & PVC rigid conduits as required at site for satisfactory functioning complete all as specified and directed. Make : Ravel/Honeywell/Edward
Supply, installation ,testing and commissioning of 2 channel wireless auto dialer(GSM Based) Voice message 40(20+20) second voice recording 09 No of Tel/ Mobile 16 Digit Each View Number & User setting any time standard Tele[hone Key Pads . Work with all types of GSM Network. Easy Menu Based Programmeing 1 Level of Password protection, Approved by various Consultants complete all as specified and directed.Make - Securico/Honeywell/Raval/Edward
Supply, laying connecting and testing of 2 core 1.5 Sqmm PVC insulated 1100 volts grade copper conductor armored cable fixed to walls/ passing through ducts or pipes etc as required complete all as specified and directed.
M & L dry powder type fire existinguisher of 9 Kg Capacity as per (IS: 15683) complete all as specified and directed.Make - Minimax/Safex/Safegaurd
M & L light weight squeeze grip type CO2 Extinguisher 4.5 Kg Cpapcity with initial gas charged as per (IS: 15683) duly ISI marked complete with one mtr long wire breaded high pressure hose pipe with horn, wheel type release valve, locking arrangment complete all as specified and directed.Make - Minimax/Safex/Safegaurd
M & L clean agent extinguisher ( Hexa- Fluoro-propane, Dicholoro -trifluoroethane or HCFC blend E- based) of 4 Kg Capacity complete all as specified and directed.Make - Minimax/Safex/Safegaurd
S & F pressure gauge 150 mm dia with range 0-10 bar along with isolation cock and pipe suitable for pressurised fire fightign pumping system etc complete all as specified and directed.
S & F MS header faricated from 200 mm dia MS C grade pipe 5mtr long with both ends flanged and closed with 25 mm thick MS plate cover incl nuts bolts washers, gaskets etc with provn of 02 Nos incoming connection 150 mm dia with flange and provn of 01 No outgoing connection 150 mm dia with flange, 01 No 100 mm dia with flange and 01 No 50 mm dia with flange complete all as specified and directed.
S & F 150 mm dia Y type strainer flanged type including all jointing materials such as nuts/bolts/washers/ gaskets etc complete all as specified and directed.
Supply and fix CI non return valve flanged ends with bypass arrangement of size 100 mm dia class PN-1.6 incl all jointing materials nuts/bolts/washers/gaskets etc complete all as specified and directed.
Supply and fix CI non return valve flanged ends of size 50 mm dia class PN-1.6 incl all jointing materials nuts/bolts/washers/gaskets etc complete all as specified and directed.
Supply and fix CI foot valve square type flanged of size 150 mm dia heavy duty incl all jointing materials nuts/bolts/washers/gaskets etc complete all as specified and directed.
Supply and fix CI sluice valve with flanged ends of size 80 mm dia heavy duty class PN-1.6 incl all jointing materials nuts/bolts/washers/gaskets etc complete all as specified and directed.
EXTERNAL ELECTRIFICATION
Refixing of earth continuity conductor any type and size with the help of saddles, screws and other fixing accessories complete all as specified and directed.
FIRE RESISTANT DOOR
Providing and fixing fire resistant door frame of section 143 x 58 mm (+/- 3 mm) having built in rebate conforming to IS 277 (primed with Zinc-Phosphate Stoving Primer and finished with Polyurethane Aliphatic grade of epoxy paint) suitable for mounting 120 minutes fire rated door frame/shutters confirming to IS: 3614 (Pt-II) & BS 476 Part 20 & 22, tested and certified as per laboratory approved by Engineer-in-charge. The frame shall be filled with rockwool/ mineral wool insulation. The frame will have a provision of G.I. anchor fastener 14 Nos (5 each on vertical style & 04 on horizontal style of size M10 x 80) suitable for fixing in the opening alongwith factory made template for SS ball bearing hinges of size 102 x 76 x 3 mm of approved make for fixing of fire rated shutter. The door frame shall be finished with Polyurethane Aliphatic grade of epoxy paint over Zinc-Phosphate Stoving Primer powder coating of not less than 60 micron in desired shade as per the direction of Engineer-in-charge
Providing and fixing 46 mm thick Double leaf fire resistant door shutters (size of one leaf 600 mm x 2000 mm each) (overall size of door is 1200 x 2000 mm excluding frame) of 120 minutes fire rating confirming to IS: 3614 (Pt-II) & BS 476 Part 20 & 22, tested and certified as per laboratory approved by Engineer-in-charge, with suitable mounting on door shutters, made out of 1.2 mm (18 SWG) thick G.I. sheet conforming to IS 277 (primed with Zinc-Phosphate Stoving Primer and finished with Polyurethane Aliphatic grade of epoxy paint) duly filled with rockwool/ mineral wool insulation. The one double leaf door shutter also provided with 1 No Mortice sash lock with lever handles, mortice ead bolt, mortice latch, Panic etc & 02 Nos concealed extended lever action flush bolts and 02 Nos Door closer provided on each leaf. The door also provided with 5 mm thick clear/wired glass of size 200 mm x 300 mm. The door shall be finished with Polyurethane Alipatic grade of epoxy paint over Zinc-Phosphate Stoving primer powder coating of not less than 60 micron in desired shade as per the direction of Engineer-in-charge”. (Make of lock/bolts/closer: Geze/Hettich/Dorma/Kich etc) Note :- The design for fire extinguishing/fighting system has been specified in respective items of tender & BOQ. The complete work of fire extinguishing/fighting system shall be got executed through a specilist agency having valid licence/certified by any Govt department for the purpose of fire prevention and fire fighting equipment manufacturing/execution. This work shall be commenced after approval of the firm by the Garrison Engineer.
Note: The Total amount shall subject to deduction of credit of Rs. 10177.00 for old Materials as per Schedule of Credit
Baba Engineers and Contractors
A.S. CONSTRUCTION CO.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .