Loading…
New: tenders and results on WhatsApp
New: Find tenders, results and companies on WhatsApp, by text or voice note
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹3.9 CrAdmitted-Finance 2ND FLOOR 4 25 KIRTI NAGAR INDUSTRIAL AREA WEST DELHI DELHI 110015 | WEST DELHI | DELHI | 110015 | L1 | Admitted-Finance | ||
| 2 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification | ||
| 3 | Not Admitted-Fee/PreQual/Technical 688 LIG FLAT FIRST FLOOR POCKET 13 MANGLAPURI DWARKA PHASE I NEW DELHI 110075 | NEW DELHI | NEW DELHI | DELHI | 110075 | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹3.8 Cr
EMD Value
₹7.6 L
Closing Date
30 Jun 2025, 3:30 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Superintending Engineer
IWD IIT Kanpur
Construction of cooling infrastructure for Data centre Under NSM 2 in Computer Centre
2025_IITK_863883_1
10/AC/EE/2025
Open Tender
Electrical Works
Percentage
90 days
IIT Kanpur
AS per tender
6 documents required · 6 mandatory
₹0
₹7.6 L
Office of Executive Engineer
16 Jul 2025
10 Jun 2025
2 Jul 2025
10 Jun 2025
30 Jun 2025
10 Jun 2025
10 Jun 2025 - 18 Jun 2025
18 Jun 2025
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1SITC of Stainless Steel Plate Type Heat exchanger of around 300kW heat exchange capacity between chilled water incoming at 8degC and outgoing at 13degC. The process water shall be designed for inlet temperature of 37deg C and outlet temperature of 32degC. Flow rate for 32m3/Hr. Unit shall be designed for a pressure drop not exceeding 8mWC. To be supplied complete with vibration isolators and grooved couplings on all pipe connections. Heat exchanger shall have 10% extra plates and selection shall be submitted for approval. All connections shall be on one side only. 2 Year comprehensive warranty is covered under the quote. | |||||
| 1.01 | Unit Capacity - 300kW | 1 | Nos | 1,29,531 | ₹1,29,531 |
| 2SITC of Stainless Steel Plate Type Heat exchanger of around 250 kW heat exchange capacity between chilled water incoming at 8degC and outgoing at 13degC. The process water shall be designed for inlet temperature of 20 deg C and outlet temperature of 15 degC with matching Flow rate . Unit shall be designed for a pressure drop not exceeding 8mWC. To be supplied complete with vibration isolators and grooved couplings on all pipe connections. Heat exchanger shall have 10% extra plates and selection shall be submitted for approval. All connections shall be on one side only. 2 Year comprehensive warranty is covered under the quote. | |||||
| 2.01 | Unit Capacity - 250kW | 2 | Nos | 1,69,449 | ₹3,38,898 |
| 3SITC of Horizontal end suction, centifugal and top discharge Primary Pump sets for chilled water with pump integrated VFD and with Pump logic controller. The pump efficiency shall not be less than 70% and motor efficiency shall be minimum of EN2 standards. The pump should be of cast iron body, bronze impeller, SS shaft and mechanical seal with provision to change the seal and coupling without dismantling of the pump. It should be coupled with a factory mounted TEFC motor of suitable rating and IE5 efficiency. Accessories required: Pump supporting frame for taking bottom support, Pressure gauges along with fittings suitable for mounting on to pump pressure ports on suction and discharge side and counter flanges. Chilled water pumps shall be insulated with 25 mm thick nitrile rubber insulation. 2 Year comprehensive warranty is covered under the quote. | |||||
| 3.01 | Capacity: 32m3/Hr, Head: 26 m, Total 3 nos pump with PLC | 1 | Set | 10,38,667 | ₹10,38,667 |
| 3.02 | Capacity: 43m3/Hr, Head: 26 m, Total 2 nos pump with PLC | 1 | Set | 10,49,187 | ₹10,49,187 |
| 4SITC of Adiabatic Dry Cooler with a vertical/V-configuration complete with honeycomb cellulose pads with spray nozzles, SS Collection trays, SS water sump with level switches and pumps with integrated speed controller , solenoid valves, pressure sensor & level sensors, 4Row copper coil with aluminium fins and copper header with steel flanged connection, EC motor driven low noise low speed axial flow fans with mesh/ guard, GI Powder coated effective corrosion protection frame works, electrical controls and Dry cooler controller with main power switch, emergency cutout, circuit breaker, micro processor based IP 55 enclosure, (RS 485 for BMS Controlling) with graphic display of parameters i.e. details of electrical parameter , water parameter, temperature details, fan speed etc. and auto control of fan speed for maintaining the water temperature with minimum energy consumption, auto start / stop of water flow for cutting IN/ OFF of adiabatic heat exchange and maintaining the water outlet temperature at all weather conditions. Computer selection considering the selection points for required performance shall be submitted for approval. 2 Year comprehensive warranty is covered under the quote. | |||||
| 4.01 | capacity of 300kW heat exchange for ambient DBT of 43C and 29C WBT in summer and 35DBT and 29.5WBT in monsoon. Required outlet temperature 32 to 35oC at Inlet temperature 37 to 40oC | 2 | Nos | 44,27,173 | ₹88,54,346 |
| 5 | SITC of MS fabricated closed loop buffer tank with baffles, dish end complete with inlet and outlet flange connection, drain, air purge connection with purge valve, inspection door, passivated and painted. The tank shall be insulated with 25mm thick chemically cross linked polyolefin with UV protected Aluminimum cladded finish. The insulation shall be sealed with 75mm wide self adhesive OEM supplied aluminimum finished tape in a neat aesthetic manner. The tank shall be pressure tested hydraulically for at least 10bar pressure or pneumatically at 3bar pressure. The tank capacity shall be not less 10 m3 excluding the dish end zone, and it shall be able to provide constant chilled water flow without mixing with hot water for 250KW load for min. 10 min | 1 | Set | 8,44,362 | ₹8,44,362 |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 2.24 MB
Tendernotice_2.pdf
PDF • 0.82 MB
Tendernotice_3.pdf
PDF • 0.19 MB
Tendernotice_4.pdf
PDF • 23.42 MB
Tendernotice_5.pdf
PDF • 2.53 MB
BOQ_908230.xls
BOQ • 0.36 MB
BOQ.xls
BOQ • 0.37 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .