GE(AF) E/M CHAKERI
O/o GE(AF) E/M CHAKERI
COMPREHENSIVE MAINTENANCE OF SOLAR SUB STATION AND CONNECTED WORKS AT AFS CHAKERI.
2026_MES_799009_1
8865/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AOR of GE(AF) E/M CHAKERI
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE(AF) E/M CHAKERI
₹80,000
Yes
19 Nov 2026
19 Nov 2026
15 Dec 2026
19 Nov 2026
8 Dec 2026
2 Dec 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Servicing and cleaning of solar power central inverter 1000 kW, Model PVS-800, make ABB, including checking of DC and AC output, cleaning of air filter and removal of all dust particles, cleaning of all parts with suitable blower or cleaning material, removal of carbon deposited inside the moving contacts, greasing of all moving parts of the inverter, checking of all cable connections and proper tightening of any loose connection, checking of the power evacuation equipment such as cables, transformers, LT panels, HT panels, pooling stations, AC control cables, auxiliary transformers, fire safety kit, earthing and lightning arresters, preliminary and pre-operative checking of the complete operating mechanism for proper functioning and reporting of any defective parts; and servicing and cleaning of main monitoring and receiving string panels 8 Nos of any size or type, including checking of continuity and voltage on positive and negative sides, checking and cleaning of existing fuses, checking of incoming voltage and current of each string module-wise one by one, checking and tightening of string connectors, checking of the complete operating mechanism for proper functioning and reporting of any defective parts, complete all as specified and directed by Engineer-in-Charge. Note: 1. One job shall mean the complete servicing described above carried out once in a calendar month. 2. Replacement of defective wires, fuses, cables, connectors and other spares, including labour, shall be measured and paid separately under the relevant items 2 to 18 of this schedule. | 6 | Job per month | 1.25 | ₹7.5 |
| 2 | Supply and fixing in replacement of stored energy motor operator type MOE for ABB Tmax T4-T5 moulded case DC switch of the solar inverter, rated 220-250 V AC/DC, including taking down the defective motor operator, connecting and testing, complete all as specified and directed by Engineer-in-Charge. Make: ABB or equivalent approved by GE. | 2 | Each | - | - |
| 3 | Supply and fixing in replacement of inverter filters complete all as specified and directed by Engineer-in-Charge. | 3 | Each | 100 | ₹300 |
| 4 | Supply and fixing in replacement of sealed maintenance free VRLA battery 12 V, 7 Ah for UPS, including taking down the old battery, connecting and testing, complete all as specified and directed by Engineer-in-Charge. Make: Exide/Amaron or equivalent approved by GE. | 2 | Each | 53 | ₹106 |
| 5 | Supply and fixing in replacement of 110 V DC battery bank comprising 55 Nos sealed maintenance free VRLA cells of 2 V, 100 Ah each, conforming to IS 15549, including inter-cell connectors, taking down the old battery bank, connecting, initial charging and testing, complete all as specified and directed by Engineer-in-Charge. Make: Exide/Amaron or equivalent approved by GE. | 1 | Set | 10 | ₹10 |
| 6 | Supply and fixing in replacement of heavy duty exhaust fan 300 mm sweep in the solar inverter room for maintaining ambient temperature, including connecting and testing, complete all as specified and directed by Engineer-in-Charge. | 1 | Each | - | - |
| 7 | Supply and fixing in replacement of switch disconnector 1000 V DC, 315 A, of the same make and type as existing, including taking down the old switch disconnector, connecting and testing, complete all as specified and directed by Engineer-in-Charge. | 2 | Each | 100 | ₹200 |
| 8 | Supply and fixing in replacement of solar photovoltaic module 520 W or next high rating, compatible with the same model and make of string inverter as existing, conforming to IS 14286, including taking down the unserviceable module, fixing on the existing module mounting structure, connecting and testing, complete all as specified and directed by Engineer-in-Charge. | 76 | Each | 53 | ₹4,028 |
| 9 | Supply and fixing in replacement of under voltage release coil 24 V DC, of the same make and frame size as the existing circuit breaker, including taking down the defective coil, connecting and testing, complete all as specified and directed by Engineer-in-Charge. Note: Sample shall be got approved from Engineer-in-Charge before supply. | 6 | Each | - | - |
| 10 | Supply and fixing in replacement of cooling fan suitable for the solar power system, of the same make, size and rating as existing, including taking down the old fan, connecting and testing, complete all as specified and directed by Engineer-in-Charge. | 3 | Each | 100 | ₹300 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.35 MB
Workdetails.pdf
Additional Documents • 0.09 MB
Tender_Acceptance_Letter.pdf
Additional Documents • 0.08 MB
BOQ_896417.xls
BOQ • 0.82 MB
Schedule_of_Credit_8865.pdf
Additional Documents • 0.24 MB
Tender_Document_8865.pdf
Tender Documents • 0.60 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .