Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.8 LAccepted-AOC CHANDURIA SIMURALI DIST NADIA PIN 741248 | NADIA | WEST BENGAL | 741248 | ₹10.8 L | L1 | Accepted-AOC AOC ISSUED |
| 2 | L2₹12.9 L+₹2.1 L (19.4%)Rejected-Finance | ₹12.9 L+₹2.1 L (19.4%) | L2 | Rejected-Finance that the bid is L1 |
| 3 | L3₹13.9 L+₹3.1 L (29.1%)Rejected-Finance | ₹13.9 L+₹3.1 L (29.1%) | L3 | Rejected-Finance that the bid is L1 |
| 4 | Rejected-Technical 33 PEMANTLE STREET KOLKATA 700016 | KOLKATA | KOLKATA | WEST BENGAL | 700016 | - | - | Rejected-Technical Due to absence of minimum credential in similar nature of work |
| Sl No | Description | Qty | Unit | ROY REFRIGERATION L1 | WEATHER CONTROLS L3 | GITANJALI ELECTRONICS AND ELECTRICALS L2 |
|---|---|---|---|---|---|---|
| 1.00Supply, Installation, Testing and Commissioning of mortuary cooler having following specifications: 1. Desired Temperature : 4ᵒ +/-1ᵒ C 2. Mortuary Room Dimesion : 6' 0" x 10' 0" x 5' 0" high - 2 Rooms 3. Plant Room : The plant will be installed in the adjustcent 15' 0" x 10' 0"room to the mortuary. 4. Thermal Insulation : a) 4" thick thermocoe insulation board will be fixed on all the three walls, ceilings & floor incl. necessary wooden framework and supply of cardicoat thick adhesive solution & finish with 0.5" thick cement plastering, providing wire net, bolts and 'U' hooks. b) Providing 4mm thick standard size glass tiles which will be layered inside of the chamber on the floor and three sides of the wals upto 5' high before themal insulation for rat protection. | ||||||
| 1.105. Front Doors : 2 X 4 = 8(eight) nos. adequately 4" thick insulated (against heat leakage) doors will be provided in the mortuary, one for each body on wooden frame & necessary work. These doors will be completed with door gasket, thickly plated brass latch & hinges, inner insulation covering with 22 swg. G.I. sheet & finished with painting & supply of door frame 4" x 4" & 4" x 5" Sal wood. 6. Inspection Door For Cold : Diffuser 2 Nos. 5" thick thermocole insulated inspection door (insulated against heat leakage) completed with 4" x 4" teak wooden frame would be provided on wall at the back of the cooling coil, door will be completed with door gasket, thickly plated brass latch & hinges, inner insulation covering with 22 swg G.I. sheet & finished with painting. | ||||||
| 1.207. Mortuary Trays : 2 x 4 = 8(eight) nos. of mortuary trays each having approx. dimension of 23"x 72" long and fabricated from 18 SWG SS304 sheet and posted on 1.5" x 1.5" x 0.25" galvanised angle iron frame completed with 4 nos. brass wheels, M.S.pins and handles incl. slideing arrangement on the frame for pulling the tray on wheels. 8. Steel Structure : Complete arrangement of 2(two) track 2(two) tire self structure of welded 3"x3"x3/8" angle iron for supplying and handling of the mortuary trays would be installed inside the morgue as per drawings. The structure will have 2 coats of red oxide and 2 coats of grey enammeled paint 2(two) sets for 2 chambers. | ||||||
| 1.309. Description of Plant & : Equipments a) 2 Nos. Main unit: Refrigeration capacity minimum about 2.6 tons to be driven by minimum 5HP Motor, 3 Phases 4 wire 415 VAC. b) 2 Nos. Standby unit: Two standby condesing unit complete with driving motor, of exact specification as of the main unit, which would be interconnected by suitable refrigeration pipe with main units on such a way than in case of any emergency this standby unit will serve the function of the main unit. c) Both the main and the standby units would be installed in the plant room adjuscent to the mortuary. d) One lot refrigeration pipe and fittings (copper tube) for interconnection between the condensing units and diffuser unit would be included. | ||||||
| 1.40e) Suitable automatic controls such as expansion valve, dial type thermometer, low & high pressure control switch, hand shut of valve, magnetic solonoid valve, drier would be incorporated in the system for maintaining desired conditions stated below. f) The would be one forged draught cooling coil complete with fan motor, deep tray and other anciliary equipments, would be installed in the mortuary in suitable location for 2(two) sets. 10. Inside & Outside Temperature : Taking average maximum temperature 45ᵒ to 50ᵒ C the plant would be capable of maintaining a temperature of 4ᵒ C. within the vicinity of about 85% humidity inside the mortuary. | ||||||
| 1.5011. Particulars of equipments : A. For Each Compressor : 1) Make 'FREEZKING' TF-450 2) Capacity in tons- 2.6 minimum 3) Refrigerant: (a) Type Mafron-22/equivalent green gas as directed by EIC (b) Quntity per charges 8(eight) kgs. Per unit. 4) Quantity of oil per charges- 10 Ltrs. For 4 Bodies x 2 Sets. B. For each condeser & cooling coil : 1) Condender - Air cooled - 4 Nos. 2) Cooling coil incl. fan motor - 2 Sets. C. For Each motor : 1) Compressor driving motor. 2) 5 H.P. - 4 Nos. (for 2 sets) 3) Make- NGEF/Crompton/Kirlosker. 4) No. of phase - 3 Phases. 5) Working Voltage - 415 Volts. 6) R.P.M. - 1400 7) Weather Maker Fan Motor make- E.P.C. or Crompton/Marathon (Single/three Phase). | ||||||
| 1.60 | 12. Panel board & Wiring :
Panel board complete with D.O.L. Starter of suitable size with suitable indication lights of plant ON, OFF, Temp inside cooler etc. make LT/Siemens/ABB 30 amps TPN MCB 15amps D.P. MCB, Multifunctional meter make AE/LT to show, V,A,F, wiring in between panel board to driving motor with suitable size FRLS copper wire including inter locking connection with suitable size FRLS copper wire for 4(four) units. Wire make Finolex/RR Kable/Havells PVC Pipe make Precision/Polycab medium type Copper pipe make Royku/Nippon, Insulation make Armasell/Ksell
DLP: 2 years | 2 | Item | 5,40,000 ₹10,80,000 Lowest | 6,97,400 ₹13,94,800 | 6,45,000 ₹12,90,000 |
| 2.00Special Terms and Conditions 1. It is stated that the above work place is existing COVID Hospital, In case of any mishap or accidental to any staff that deputed by the agency the whole responsibility is to be borne by the concern agency. 2. The Agency shall be responsible for provisioning of all COVID safety measures including regular sanitiziation of work places, vaccination of employees and compliance of stated directive and COVID appropriate norms. 3. All the issues related to the safety of the staffs should be taken care by the agency itself. (Rate should be quotated including all taxes and duties) | ||||||
Tender Value
Refer Docs
EMD Value
₹28,000
Closing Date
20 May 2022, 1:00 pmClosed
EE II KNHED PW Dte
KIT Building Annex, 4thFloor,P-16, India Exch. Place Extn., Kolkata -700073
Supply and installation of 2 into 4 bodies Mortuary Cooler at anatomy department of MCH Kolkata.
2022_PWDE_379044_1
WBPWD/EE-II/KNHED/NIQ-08/22-23
Open Tender
A/C ORG
Item Rate
45 days
Kolkata
Please refer Tender documents.
5 documents required · 5 mandatory
₹28,000
23 Sept 2026
2 May 2022
23 May 2022
4 May 2022
20 May 2022
4 May 2022
Amount
Supply, Installation, Testing and Commissioning of mortuary cooler having following specifications: 1. Desired Temperature : 4ᵒ +/-1ᵒ C 2. Mortuary Room Dimesion : 6' 0" x 10' 0" x 5' 0" high - 2 Rooms 3. Plant Room : The plant will be installed in the adjustcent 15' 0" x 10' 0"room to the mortuary. 4. Thermal Insulation : a) 4" thick thermocoe insulation board will be fixed on all the three walls, ceilings & floor incl. necessary wooden framework and supply of cardicoat thick adhesive solution & finish with 0.5" thick cement plastering, providing wire net, bolts and 'U' hooks. b) Providing 4mm thick standard size glass tiles which will be layered inside of the chamber on the floor and three sides of the wals upto 5' high before themal insulation for rat protection.
5. Front Doors : 2 X 4 = 8(eight) nos. adequately 4" thick insulated (against heat leakage) doors will be provided in the mortuary, one for each body on wooden frame & necessary work. These doors will be completed with door gasket, thickly plated brass latch & hinges, inner insulation covering with 22 swg. G.I. sheet & finished with painting & supply of door frame 4" x 4" & 4" x 5" Sal wood. 6. Inspection Door For Cold : Diffuser 2 Nos. 5" thick thermocole insulated inspection door (insulated against heat leakage) completed with 4" x 4" teak wooden frame would be provided on wall at the back of the cooling coil, door will be completed with door gasket, thickly plated brass latch & hinges, inner insulation covering with 22 swg G.I. sheet & finished with painting.
7. Mortuary Trays : 2 x 4 = 8(eight) nos. of mortuary trays each having approx. dimension of 23"x 72" long and fabricated from 18 SWG SS304 sheet and posted on 1.5" x 1.5" x 0.25" galvanised angle iron frame completed with 4 nos. brass wheels, M.S.pins and handles incl. slideing arrangement on the frame for pulling the tray on wheels. 8. Steel Structure : Complete arrangement of 2(two) track 2(two) tire self structure of welded 3"x3"x3/8" angle iron for supplying and handling of the mortuary trays would be installed inside the morgue as per drawings. The structure will have 2 coats of red oxide and 2 coats of grey enammeled paint 2(two) sets for 2 chambers.
9. Description of Plant & : Equipments a) 2 Nos. Main unit: Refrigeration capacity minimum about 2.6 tons to be driven by minimum 5HP Motor, 3 Phases 4 wire 415 VAC. b) 2 Nos. Standby unit: Two standby condesing unit complete with driving motor, of exact specification as of the main unit, which would be interconnected by suitable refrigeration pipe with main units on such a way than in case of any emergency this standby unit will serve the function of the main unit. c) Both the main and the standby units would be installed in the plant room adjuscent to the mortuary. d) One lot refrigeration pipe and fittings (copper tube) for interconnection between the condensing units and diffuser unit would be included.
e) Suitable automatic controls such as expansion valve, dial type thermometer, low & high pressure control switch, hand shut of valve, magnetic solonoid valve, drier would be incorporated in the system for maintaining desired conditions stated below. f) The would be one forged draught cooling coil complete with fan motor, deep tray and other anciliary equipments, would be installed in the mortuary in suitable location for 2(two) sets. 10. Inside & Outside Temperature : Taking average maximum temperature 45ᵒ to 50ᵒ C the plant would be capable of maintaining a temperature of 4ᵒ C. within the vicinity of about 85% humidity inside the mortuary.
11. Particulars of equipments : A. For Each Compressor : 1) Make 'FREEZKING' TF-450 2) Capacity in tons- 2.6 minimum 3) Refrigerant: (a) Type Mafron-22/equivalent green gas as directed by EIC (b) Quntity per charges 8(eight) kgs. Per unit. 4) Quantity of oil per charges- 10 Ltrs. For 4 Bodies x 2 Sets. B. For each condeser & cooling coil : 1) Condender - Air cooled - 4 Nos. 2) Cooling coil incl. fan motor - 2 Sets. C. For Each motor : 1) Compressor driving motor. 2) 5 H.P. - 4 Nos. (for 2 sets) 3) Make- NGEF/Crompton/Kirlosker. 4) No. of phase - 3 Phases. 5) Working Voltage - 415 Volts. 6) R.P.M. - 1400 7) Weather Maker Fan Motor make- E.P.C. or Crompton/Marathon (Single/three Phase).
12. Panel board & Wiring : Panel board complete with D.O.L. Starter of suitable size with suitable indication lights of plant ON, OFF, Temp inside cooler etc. make LT/Siemens/ABB 30 amps TPN MCB 15amps D.P. MCB, Multifunctional meter make AE/LT to show, V,A,F, wiring in between panel board to driving motor with suitable size FRLS copper wire including inter locking connection with suitable size FRLS copper wire for 4(four) units. Wire make Finolex/RR Kable/Havells PVC Pipe make Precision/Polycab medium type Copper pipe make Royku/Nippon, Insulation make Armasell/Ksell DLP: 2 years
Special Terms and Conditions 1. It is stated that the above work place is existing COVID Hospital, In case of any mishap or accidental to any staff that deputed by the agency the whole responsibility is to be borne by the concern agency. 2. The Agency shall be responsible for provisioning of all COVID safety measures including regular sanitiziation of work places, vaccination of employees and compliance of stated directive and COVID appropriate norms. 3. All the issues related to the safety of the staffs should be taken care by the agency itself. (Rate should be quotated including all taxes and duties)
GITANJALI ELECTRONICS AND ELECTRICALS
WEATHER CONTROLS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .