Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.4 CrAdmitted-Finance | ₹4.4 Cr | L1 | Admitted-Finance |
| 2 | L2₹4.9 CrAdmitted-Finance VILL CHOMON NEAR MAIN GUARD ROOM AIR FORCE STATION ADAMPUR DISTT JALANDHAR PB 144103 | JALANDHAR | PUNJAB | 144103 | ₹4.9 Cr | L2 | Admitted-Finance |
| 3 | L3₹5.8 CrAdmitted-Finance | ₹5.8 Cr | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | M/s Sahib and Company L2 | NEW GURBINDER INDUSTRIES L3 | GAGANDEEP SINGH & ASSOCIATES L1 |
|---|---|---|---|---|---|---|
| 1.00SCHEDULE `A' PART - I (Building Works) is not prepriced by MES and prepriced rates indicates 0.0 under column 6 signified this fact only. | ||||||
| 1.01 | Construction of Married Accn building for 14 SGT and below including ground parking in four storey (G+3) with permanent specifications complete all as specified and shown on drawings. | 1 | Each Block | 2,43,00,000 ₹2.4 Cr | 3,10,00,000 ₹3.1 Cr | 2,10,00,000 ₹2.1 Cr |
| 1.02 | Construction of Married Accn building for 5 SGT and below including ground parking in three storey (G+2) with permanent specifications complete all as specified and shown on drawings. | 1 | Each Block | 99,00,000 ₹99 L | 1,35,00,000 ₹1.4 Cr | 80,00,000 ₹80 L |
| 2.00NOTE: Schedule ‘A’ Part II to XIII under Ser No. 2.01 to 2.12 are Prepriced by MES. | ||||||
| 2.01 | Lump sum price worked out by the Contractor for “SITE CLEARANCE, EXCAVATION AND EARTH WORK” as listed in Schedule ‘A’ Part II | 1 | Lump sum | 3,00,000 ₹3 L | 2,35,000 ₹2.4 L | 4,25,000 ₹4.3 L |
| 2.02 | Lump sum price worked out by the Contractor for “INTERNAL WATER SUPPLY" as listed in Schedule ‘A’ Part III | 1 | Lump sum | 8,50,000 ₹8.5 L | 7,00,000 ₹7 L | 5,25,000 ₹5.3 L |
| 2.03 | Lump sum price worked out by the Contractor for “INTERNAL ELECTRIC SUPPLY" as listed in Schedule ‘A’ Part IV | 1 | Lump sum | 18,00,000 ₹18 L | 16,30,000 ₹16.3 L | 17,25,000 ₹17.3 L |
| 2.04 | Lump sum price worked out by the Contractor for “ROAD SHOULDERS AND HARDSTANDING" as listed in Schedule ‘A’ Part V | 1 | Lump sum | 14,50,000 ₹14.5 L | 14,15,000 ₹14.2 L | 13,75,000 ₹13.8 L |
| 2.05 | Lump sum price worked out by the Contractor for “SEWAGE DISPOSAL” as listed in Schedule ‘A’ Part VI | 1 | Lump sum | 6,50,000 ₹6.5 L | 5,60,000 ₹5.6 L | 5,50,000 ₹5.5 L |
| 2.06 | Lump sum price worked out by the Contractor for “AREA DRAINAGE ” as listed in Schedule ‘A’ Part VII | 1 | Lump sum | 2,75,000 ₹2.8 L | 2,77,726.82 ₹2.8 L | 2,75,000 ₹2.8 L |
Tender Value
₹4.5 Cr
EMD Value
₹5.2 L
Closing Date
23 Mar 2026, 6:00 pmClosed
HQ CE (AF) WAC PALAM
HQ CE (AF) WAC PALAM
PROVN OF DEFICIENT MD ACCN AT AF STN AMRITSAR CANTT
2025_MES_737375_3
CEWAC/ASR/T-02/2025-26
Open Tender
Civil Works
1530 days
AGE (I) AF AMRITSAR
Please refer Tender documents.
8 documents required · 8 mandatory
₹2,000
AGE (I) (AF) AMRITSAR
₹5.2 L
Yes
10 Apr 2026
3 Mar 2026
25 Mar 2026
3 Mar 2026
23 Mar 2026
16 Mar 2026
SCHEDULE `A' PART - I (Building Works) is not prepriced by MES and prepriced rates indicates 0.0 under column 6 signified this fact only.
Construction of Married Accn building for 14 SGT and below including ground parking in four storey (G+3) with permanent specifications complete all as specified and shown on drawings.
Construction of Married Accn building for 5 SGT and below including ground parking in three storey (G+2) with permanent specifications complete all as specified and shown on drawings.
NOTE: Schedule ‘A’ Part II to XIII under Ser No. 2.01 to 2.12 are Prepriced by MES.
Lump sum price worked out by the Contractor for “SITE CLEARANCE, EXCAVATION AND EARTH WORK” as listed in Schedule ‘A’ Part II
Lump sum price worked out by the Contractor for “INTERNAL WATER SUPPLY" as listed in Schedule ‘A’ Part III
Lump sum price worked out by the Contractor for “INTERNAL ELECTRIC SUPPLY" as listed in Schedule ‘A’ Part IV
Lump sum price worked out by the Contractor for “ROAD SHOULDERS AND HARDSTANDING" as listed in Schedule ‘A’ Part V
Lump sum price worked out by the Contractor for “SEWAGE DISPOSAL” as listed in Schedule ‘A’ Part VI
Lump sum price worked out by the Contractor for “AREA DRAINAGE ” as listed in Schedule ‘A’ Part VII
Lump sum price worked out by the Contractor for “CHAIN LINK FENCING” as listed in Schedule ‘A’ Part VIII
Lump sum price worked out by the Contractor for “EXTERNAL WATER SUPPLY” as listed in Schedule ‘A’ Part IX
Lump sum price worked out by the Contractor for “DG SET” as listed in Schedule ‘A’ Part- X
Lump sum price worked out by the Contractor for “DG SET SHED” as listed in Schedule ‘A’ Part XI
Lump sum price worked out by the Contractor for “EXTERNAL ELECTRIC SUPPLY WORKS” as listed in Schedule ‘A’ Part XII
Lump sum price worked out by the Contractor for “LIFT” as listed in Schedule ‘A’ Part XIII
SCHEDULE `A' PART - XIV MISC ITEMS is not prepriced by MES and prepriced rates indicates 0.0 under column 6 signified this fact only.
Internal Electric Supply
M & L for vertical type sheet steel enclouser distribution boards, double door factory made 3 phase 415 volts 4 way with 200 amps rating copper bus bar of suitable size and PVC insulated copper jumpers from the MCCB to the out going circuits (one incoming MCCB and 12 outgoing MCBs circuits) comprising of 3 phase 4 wire of suitable rating including MCCB 100 amps, 25 KA, 415 volts, 50 Hz = 01 No. and 12 Nos MCBs 6-32 Amps, complete all as specified and directed.
Supply and fixing ceiling fans complete with blades, down rods, modular fan step regulator,120 Watt - 2 module and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor Effciencia Prime (BLDC) complete all as specified and directed.
Supply and fixing TV Coaxial Connector Type F-1 Module designed for cable installations of white colour combines functionality with a sleek design complete all as specified and directed by Engr-in-Charge.
Supply and fixing of brass chormium plated angle valve, fancy type of size 15mm dia screwed down for high pressure CPVC pipes, complete all as specified and directed.
External Electric Supply
M&L for for construction of transformer plinth of size 2.5 mtr x 2.5 mtr x 1.5 mtr with brick masonary with sub class 'B' bricks straight or curved on plan exc 6 mean radius built in CM (1:6), PCC (1:4:8) type D-2 using 40mm graded crushed stone aggregate in foundations, filling, mass concrete etc., 100mm thick PCC (1:2:4) type B-2 using 40mm graded crushed stone aggregate as in sub base of floor, including rendering 15mm thick on fair/unfair faces of brick work or cement concrete surfaces in CM (1:4) with finished even & smooth (without using extra cement) including finishing walls with two coat of Acrylic exterior emulsion paint @ 1.67 ltr/10m² over and incl a coat of exterior primer @ 2.20 Kg/10m² including preparation of new surfaces complete including necessary excavation and earth work in any type of soil complete all as specified and directed by Engr-in-Charge. (Near Proposed two pole structure)
S&F DWC pipe of PN 4 ratings having pressure rating 6 Kgf/cm² with complete fittings such as bends rings etc for protection of electric cables as per IS 16098 size 80 mm inner diacomplete all as specified and directed.
Supply, installation, testing and commissioning of transformer of capacity 100 KVA, step down, outdoor type, level-2, copper wounded, 11/0.433KV (at no load ) Ac 3 phase 50 HZ on secondary side double wounded, oil immersed, naturally air cooled, with external cooling tubes/radiator (delta connected as on primary and star connected with neutral on secondary) side having tapping at (±) 2.5%, (±) 5%, (±) 7.5% to be changed by hand operated OFF LOAD tap changing gear, the maximium temperature rise should not exceed 45 degree centigrade in oil and 50 degree centigrade in HV/LV winding when measured by the resistance method after continuous full load run on ambient temperature the transformer shall conform to IS:2026-1997 (latest edition) and comprising of following accessories:-
a) 3 Nos porcelains HV bushing with Arching Horns on HV side suitable for 11 KV complete with bushing rods, nuts, etc. b) 01 no cable end box on LV secondary side consisting of 04 nos porcelain bushing with bushing rods and nuts, washers and cable gland suitable for reception of 3.5 core 70 sq mm cable LT 1100 Volts grade XLPE insulated heavy duty including gland joint complete. c) Oil conservator with filter type drain valve and oil level gauge. d) Dehydrating Breather with first filling of dehydrating agent. e) Explosive Vent. f) Thermometer pocket g) Two earthing terminals on tank body to facilitate fixing of 32X6 mm GI earth strips. h) One no Thermometer Dial type vapour pressure type having range 0-120 degree centigrade with maximium temprature indicator and resettling device to maximium temprature including needles of temprature gauge. max reading painted terminal. j) Rating plate with terminal plate. k) Oil level gauge. l) Oil drain filter valve m) Oil filling port on top cover with plate n) Air release valve/plug o) 4 nos plain solid cast steel detachable rollers. p) Extra bushing for neutral out side the cable box and providing independent earthing for neutral. q) First fill transformer oil confirming to revelant IS and tested up to 60 KV dielectric strength.
Supply, installation, commissioning and testing of Polycarbonate ASTA CPRI approved OEM made LT Panel outdoor type, floor Mounted (Minimum Size 800mmX1000mmX170mm), the Panel shall be made of modular Polycarbonate Thermoplastic enclosures and shall be UV resistant, anti-acid, anti corrosive and FR material ( Make of Enclosures Hensel, ABB, Schneider, siemens), the manufacturer of panel shall submit a copy of CPRI Test report in Polycarbonate only also share panel assembled by OEM, channel partner or sister concern assembly will not be accepted. Degree of ingress protection IP 65 in accordance with IEC 60529 and the gasket shall be internally embedded made of polyurethane. The Panel Shall be mounted on angle legs of size 40mm x 40mm legs with Ground clearance 450mm duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, legs grouted in PCC(1:2:4) Type B-1 (using 20 mm graded stone aggregate) complete including all provision of opening for incomming/outgoing cables, and they shall submit a copy of TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel as per following. a). 1. In accordance with IEC 60 439-1 (IS8623) at ASTA ( CPRI Bhopal Laboratory ) and IEC 61 439-2 for power switchgear and controlgear assembly. The type test report as per CPRI ( in accordance with IEC 60 439-1 ) should consist with following: i) Degree of protection of system, (ii) Temperature Rise Limit iii) Dielectric Properties, (iv) Short Circuit Withstand Strength v) Effectiveness of protective circuit, (vi) Clearance and creepage distance, (vii) Mechanical Operation
b) Glow wire test at 9600C in accordance with IEC 60 695-2-11 UL subject 94, should be flame retardant and self-extinguishing in nature, so that fire should not be spread all over in the event of fire due to short circuit. c) Degree of protection against mechanical load IK 08 (5 Joule) ) in accordance with IEC 62262
Supply, installation, commissioning and testing 0f Polycarbonate ASTA CPRI approved OEM made LT Panel outdoor type Floor Mounting (Minimum Size 750mmx900mmx170mm). The Panel shall be made of modular Polycarbonate shall be UV resistance, anti-acid, anti corrosive and FR material. (Make of Enclosures Hensel, ABB, Schneider, siemens). The manufacturer of panel shall submit a copy of CPRI test report in polycarbonate only also share panel assembled by OEM, channel partner or sister concern assembly will not be accepted. Degree of ingress protection IP 65 in accordance with IEC 60529 and the gasket shall be internally embedded made of polyurethane. The Panel Shall be mounted on angle legs of size 40mm x 40mm legs with Ground clearance 450mm duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, legs grouted in PCC(1:2:4) Type B-1 (using 20 mm graded stone aggregate) complete including all provision of opening for incomming/outgoing cables and they shall submit a copy of TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel as per following :- a). 1. In accordance with IEC 60 439-1 (IS8623) at ASTA ( CPRI Bhopal Laboratory ) and IEC 61 439-2 for power switchgear and controlgear assembly. The type test report as per CPRI ( in accordance with IEC 60 439-1 ) shall consist with following: i) Degree of protection of system ii) Temperature Rise Limit iii) Dielectric Properties iv) Short Circuit Withstand Strength v) Effectiveness of protective circuit vi) Clearance and creepage distance vii) Mechanical Operation
b) Glow wire test at 9600C in accordance with IEC 60 695-2-11 UL subject 94, should be flame retardant and self-extinguishing in nature, so that fire should not be spread all over in the event of fire due to short circuit
OUTGOINGS: (i) 63 Amp, 4 pole MCCB, 16 KA with Fixed Thermal and Magnetic Setting - 03 No (2 nos for Block 1 and 2 + one spare) (ii) 40 Amp, 4 pole MCCB, 10 KA with Fixed Thermal and Magnetic Setting - 01 No (For stilt parking) NOTES: (i) Contractor shall submit the test reports in respect of IP Test Report and verification of short circuit withstand test report issued by CPRI in respect of the Polycarbonate LT Panel. (ii) Contractor shall submit the test reports and drawings for approval from Accepting Officer before sample approval and placing order to firm.MAKE OF MCCB/MCB :- LEGRAND / ABB / L&T / SCHNEIDER/ HAGER/ PANASONIC
Supply, installation, commissioning and testing of Polycarbonate ASTA CPRI approved OEM made Meter Panel Indoor type wall Mounted (Minimum Size 750 mmx900mmx170mm), the Meter Panel shall be made of modular Polycarbonate thermoplastic enclosures shall be UV resistance, anti-acid, anti corrosive and FR material. (Make of Enclosures Hensel, ABB, Schneider, Siemens). The manufacturer of panel shall submit a copy of CPRI test report in polycarbonate only also share panel assembled by OEM, channel partner or sister concern assembly will not be accepted. Degrss of ingress protection IP 65 in accordance with IEC 60529 and the gasket shall be internally embedded made of polyurethane. The Meter Panel shall be with M&L for 8 Nos of single Phase meter with provisions of Meters in panel. The Meters in Transpartant Enclouser and MCB's under Flap cover. Contractor shall submit a copy of TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel as per following. a). 1. In accordance with IEC 60 439-1 (IS8623) at ASTA ( CPRI Bhopal Laboratory ) and IEC 61 439-2 for power switchgear and controlgear assembly. The type test report as per CPRI ( in accordance with IEC 60 439-1 ) should consist with following: i) Degree of protection of system ii) Temperature Rise Limit iii) Dielectric Properties iv) Short Circuit Withstand Strength v) Effectiveness of protective circuit vi) Clearance and creepage distance vii) Mechanical Operation
b) Glow wire test at 9600C in accordance with IEC 60 695-2-11 UL subject 94, should be flame retardant and self-extinguishing in nature, so that fire should not be spread all over in the event of fire due to short circuit c)Degree of protection against mechanical load IK 08 (5 Joule) ) in accordance with IEC 62262 d)Rated insulation voltage should be 690Vac / IEC 1000 Vdc as per IEC 60664. e) UV-resistance in accordance with IEC 61 439-1, Clause 10.2.4: The material is examined for UV resistance. INCOMER:- (i) 160 Amp, 4 pole MCCB, 36 KA with Fixed Thermal and Megnatic Setting - 01 No (ii) Set of LED type indicating lamps - 01 Set (iii) TPN+E Copper electrolytic grade bus bar of capacity 200 Amps for phases & 160 Amps for neutral.and auxillary busbar to support main busbar. duly supported on SMC/DMC, busbar supports and insulated with colour coded heat shrinkable sleeve. OUTGOINGS: (i) M&L for single phase Meters - 7 +1 Nos ( One No Spare ) (ii) MCB DP 40 A 10KA C-Curve - 8 Nos NOTES: (i) Contractor shall submit the test reports and drawings for approval from Accepting Officer before sample approval and placing order to firm. MAKE OF MCCB/MCB :- LEGRAND / ABB / L&T / SCHNEIDER/ HAGER/ Panasonic
Supply and installation in repairs, commissioning and testing Polycarbonate ASTA CPRI approved OEM made Meter Panel Indoor type wall Mounted (Minimum Size 750 mmx750mmx170mm), The Meter Panel shall be made of modular Polycarbonate thermoplastic enclosures shall be UV resistance, anti-acid, anti corrosive and FR material. (Make of Enclosures Hensel, ABB, Schneider, Siemens) The manufacturer of panel shall submit a copy of CPRI TEST REPORT IN POLYCARBONATE only also share panel assembled by OEM, channel partner or sister concern assembly will not be accepted. Degree of ingress protection IP 65 in accordance with IEC 60529 and the gasket shall be internally embedded made of polyurethane. The Meter Panel shall be with M&L for 6 Nos single Phase meter with provisions of Meters. The Meters in Transpartant Enclouser and MCB's under Flap cover. They shall submit a copy of TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel as per following. a). 1. In accordance with IEC 60 439-1 (IS8623) at ASTA ( CPRI Bhopal Laboratory ) and IEC 61 439-2 for power switchgear and controlgear assembly. The type test report as per CPRI ( in accordance with IEC 60 439-1 ) should consist with following: i) Degree of protection of system, (ii) Temperature Rise Limit iii) Dielectric Properties, (iv) Short Circuit Withstand Strength v) Effectiveness of protective circuit vi) Clearance and creepage distance vii) Mechanical Operation
b). Glow wire test at 9600C in accordance with IEC 60 695-2-11 UL subject 94, should be flame retardant and self-extinguishing in nature, so that fire should not be spread all over in the event of fire due to short circuit c).Degree of protection against mechanical load IK 08 (5 Joule) ) in accordance with IEC 62262 d).Rated insulation voltage should be 690Vac / IEC 1000 Vdc as per IEC 60664. e). UV-resistance in accordance with IEC 61 439-1, Clause 10.2.4: The material is examined for UV resistance. INCOMER:- (i) 125 Amp, 4 pole MCCB, 36 KA with Fixed Thermal and Megnatic Setting - 01 No (ii) Set of LED type indicating lamps - 01 Set (iii) TPN+E Copper electrolytic grade bus bar of capacity 160 Amps for phases & 125 Amps for neutral.and auxillary busbar to support main busbar. duly supported on SMC/DMC, busbar supports and insulated with colour coded heat shrinkable sleeve. OUTGOINGS: (i) M&L for single Phase Meters - 6 ( 5 +One No Spare ) (ii) MCB DP 40 A 10KA C-Curve - 6 Nos NOTES: (i) Contractor shall submit the test reports and drawings for approval from Accepting Officer before sample approval and placing order to firm MAKE OF MCCB/MCB :- LEGRAND / ABB / L&T / SCHNEIDER/ HAGER
External water supply
M&L for construction of valve pit chamber of size 900mm x 900mm x 900mm (internal size) suitable for valves with PCC (1:4:8) type D 2 using 40 mm graded crushed stone aggregate for foundation and brick masonry wall in cement mortar (1:6), PCC (1:3:6) type C 1 using 20 mm graded crushed stone aggregate for coping rendering in CM (1:4)15mm thick including Provn of mild steel sheet cover minimum 3 mm thick on 40mm x 40mm x 6mm angle iron frame work with two coats of synthetic enamel black paint over a coat of red oxide primer and locking arrangement including necessary excavation earth work all as specified and directed by Engr -in-Charge.
Cutting hard standing/road not exceeding 1.5m deep and making good with and including PCC (1:3:6) type C2 (using 40mm graded crushed stone aggregate) and removal of debris to a distance not exceeding 50 m and making the damaged areas uniform as per existing complete all as specified and directed.
DG SET
Supply, installation, testing and commissioning of silent Diesel Engine driven generating set 415 volts, 3 phase 4 wire, engine as per IS:10002 and Alternator as per IS: 13364 complete including relay panel and switch gears for automatic starting on main failure (AMF Panel), control panel having meter and sound proof canopy as per CPCB norms 4+ Compliant of capacity 15 KVA, Factory assembled, shrinkpacked, Kirloskar make,Engine Model 3R550TC 4G1 or equivalent model of approved make canopised disel generator set Air Cooled diesel engine directly coupled to Kirloskar Green make alternator (Brushless), both mounted on a common base frame complete with standard control panel, fuel tank, battery leads, first fill of Engine oil, coolant and all standard accessories built into the canopy, Service manual along with cat part list and price list-03 sets as specified and directed by Engr-in- Charge,
DG Set shall be equipped with : (i) Disel Engine complete with all accessories comply with the IS 10002/BS 5514/ISO 3046 latest edition, turbo charged multi cylinder V type in line type with mechanical fuel injection system, the engine with all accessories shall be enclosed in a enclosure to make it work silently (Within permissible noise level)
(ii) An alternator directly coupled to the engine through coupling complete with all accessories shall comply with BS 2613/IS 4722/IEC 34 latest edition. The alternator shall be continuosly rated duty suitable for 415V, 3 Phase, 50 Hz. Power development having brush less, synchronous, self excited, self regulating system, the rotor shall be dynamically balanced to minimize vibration, the alternator shall be fitted with shaft mounted centrifugal fan, alternator regulator shall be directly coupled to the engine and shall be complete with the excitation system, automatic voltage regulation of +/- 1%, voltage adjusting potentiometer and under/over speed protection, terminal box suitable for termination of 50/25 Sq mm 3.5/4 Core XLPE cable, one spare set of terminal shall also be available for connection, (iii) Automatic voltage regulator
(iv) Complete starting arrangement, including battery with battery chargers, one number of 12 V batteries complete with all leads, terminals and stand shall be provided. The battery shall have sufficient capacity to give 10 Nos successive starting impulse to the disel engine, the battery charger shall be completed with transformer, suitable rating (415V, 3 Ph, 50 HZ/230V, 1 Ph, 50 HZ) rectifier circuit , DC Ammeter & Voltmeter, Charger shall be provided with output voltmeter & Ammeter.
(v) The engine and alternator shall be mounted on a common heavy duty, rigid fabricated steel base frame constructed with ISMC of suitable sections, adequate number of anti-vibration mounting pads shall be fixed on the common base frame on which engine and alternator mounted to isolate the vibration from passing on to the common base frame or the foundation of the DG set.
(vi) Fuel Tank of appropriate capacity shall be provided on a suitably fabricated steel platform. The tank shall be completed with level indicator marked in litres, filling inlet with removable screen, an outlet, a drain plug , an air vent , an air breather and necesscary piping. The tank shall be painted with oil resistant paint. The fuel piping shall be carried out to connect the DG set. (vii) Engine Cooling and lubrication system. (viii) Engine air filtering system. (ix) Exhaust silencer package. (x) Set of GI pipes, valves, strainers, unloading hose pipes as required for fuel transfer system from storage area to fuel tank including electrically driven fuel pump. (xi) All lubricants , consumable, touch up paints etc for first filing, testing & commissioning at site. The fuel oil for first testing / commissioning shall also be provided by the contractor Make : Kirloskar /Sudhir/Greves Cotton/Jackson
NOTE : The Pre-commissioning test of above DG set shall have to be carried out in presence of IEM or any other officer as detailed by the CWE. The expenditure for testing including cost of fuel consumed/equipment required for testing shall be born by the contractor and which shall be deemed to be included in unit rate quoted. No extra payment shall be paid for this account. The testing shall be carried out for 12 hours continously with one hour 10% overload in 12 hours. The drawing shall be approved by the CWE before procurement.
Cutting hard standing/road not exceeding 1.5m deep and making good with and including PCC (1:3:6) type C2 (using 40mm graded crushed stone aggregate) and removal of debris to a distance not exceeding 50 m and making the damaged areas uniform as per existing complete all as specified and directed.
Supply, installation, testing & commissioning of Passenger lift machine room less electrically operated with modular microprocessor based controls, complete with power driven automatic center opening with 18 SWG stainless steel (SS) moon rock finish sliding car doors and landing doors having stainless steel (SS) car enclosure suitable to carry 13 passenger lifts (884 kg) at speed of 1.5 M/Sec to serve upto 4 floors (G+3), full collective operation with all standard features mentioned below and human interface device (HID) and along with (ARD) automatic resucue device confirming to NBC 2016, IS 14665 (Part-1): 2000 and IS 14665 (Part-2/Sec 1 &2) & (Part-3/Sec 1 &2) : 2000( latest edition and amendment up to date) complete all as specified and as per following technical specification of Make: KONE / OTIS / SCHEINDER / MITSUBISHI.
(l)Electric light: LED light fittings with all accessories. (m)Fan : Cross flow Pressure fan, 400 mm sweep-01 No. (n)Car Entrance: Automatic centre opening in stainless steel hairline finish. (o)Door Opening: Center opening doors 800mm W x 2000mm H with provision of emergency key opening at all landings. SS car door finish with 2 hr. fire resistance door duly supported by valid test certificate issued by NABL accredited or Independent test laboratory. Car door lock compatible. (p)Door Operation: Automatic power operation with adjustable door opening and closing timings. Variable speed high-traffic door operator. (q)Monitoring: Pulse 24/7 belt integrity monitoring system and Automated rescue operation. (r)Indicators: Hall position indcators for car & landing Direction and position indicator with stainless steel fixtures at all floor. (s) Over Head available/Required for 1 m/s: ( car height + 1900) 4100mm (t) Pit available/Required for 1 m/s :1600mm deep (u) Levelling accuracy ± 5mm independent of load in the car. (v) Guide Rails: Tounge & Groove Guide Rails (w)Brake: Braking of the lift will be done by electronically varying the voltage and the frequency of motor feeding current (variable Voltage and Variable frequency control) i.e., VVVF control.
The following shall also be provided in addition to above standard features:- (i) Anti Nuisance car call protection. (ii) Automatic car return device (homelanding). (iii) Independent service ( for Simplex only). (iv) Overlaoding Device. (v) Nudging. (vi) Emenrgency fireman's service. (vii) Audio's car call button. (viii) Emergency Car light unit. (ix) High performance contact free infrared curtain door protection. (x) Door time protection. (xi) Emergency Alarm button. (xii) Extra door time of lobby & parking. (xiii) Door open close button. (xiv) Manual rescue operation . (xv) Belt inspection device 7 auto fan cut off.
ADDITIONAL DEVICE Automatic rescue,infra red sensor,overload warning indicator and floor announcing system with music/ariival chime HUMAN INTERFACE DEVICE (i) Hall button with micro stroke push buttons combained with 16 signals digital LED display position indicator. (ii) Full height car operating panel with micro stroke call push button located on side panel. (iii) Door open door closed on car operating panel. (iv) 2 way inter communication system in cabin (v) Dot matrix position indicator. (vi) Battery operated alarm well & emergency light. (vii) Fireman witch at main lobby. (viii) Manual rescue operation (ix) Call register indicator in all landings. (x) Attendant operation in car panel. (xi) Diffused Lighting fixture/LED Lighting (xii) Lighting for car operating panel with door open/close button
SAFETY FEATURES Motor overheat protection , phase failure and reversal protection and features as per ISI / IS code /NBC Provision.Every lift installation shall necessarily be provided with the safety features in accordance with IS 14665(Part-4/Sec-4):2001. Note:- (i) Contractor shall note that the defects liability period for lift shall be three years from the cerftified date of completion as certified by AGE(I). During the said defects liability period, the lift shall be kept functioned serviceable all the time and all consumable items shall also be provided by contractor for runnig of the lift without any additional cost to the department. (ii) The lift shall be inspected and commissioned by the lift inspector and it shall be the responsibility of the contractor to get the lift inspected & commissioned without any extra cost to the department. Cost of the above provisions shall be deemed in the rates quated by contractor. (iii) All dimensions given above are recommended dimensions . In the event of any variations mutually agreed between manufacturer and purchaser are permitted. However, variation in car inside dimensions shall be within the maximum area limits specified in 1S 14665 (Part 3/Sec 1).
(iv) Dimensions of pit depth and overhead may differ in practice as per individual manufacturer’s design depending upon load, speed and drive. However, the pit depth and overhead shall be such as to confirm to the requirements of bottom clearance and top clearance of IS 14665 (Part 2/Sec 1). (v) Contractor to obtain permission and approval prior to commencement of work and lift license from state govt authority. (vi) Item cost includes required scaffolding & structural steel brackets for erecting lift as per above specification, obtaining required all necessary permissions of Lift inspector to erect and complete the elevator work, Laisons to operate the elevators including all necessary charges, payments for the same etc complete. (vii) Contractor to verify all above required dimension at site prior to procurement of lift. In the event of any variation the commercially available standard size lift with respect to load and category shall be submitted to the dept for approval. (viii) Contractor shall submit GA drawing along with other relevant details to Engr-in-Charge for approval from Accepting Officer prior to procurement of lift.
M & L for vertical type sheet steel enclosure distribution boards, double door factory made 3 phase, 415 volts, 4 way, with 200 amps rated copper bus bar of suitable size and PVC insulated copper jumpers from the MCCB to the out going circuits (one incoming MCCB and 12 outgoing MCBs circuits) comprising of 3 phase 4 wire of suitable rating including MCCB 63 amps, 25 KA, TP, 415 volts, 50 Hz = 01 No. and 12 Nos MCBs 40 Amps, complete all as specified and directed.
PHASE III: Commence after completion of work of Phase II
Manning and operation of Lift 08 Passenger at Domestic Area Amritsar in 3 shifts round the clock, each shift shall consist of 8 hours duration (6:00 AM to 2:00 PM, 2:00PM to10:00PM and 10:00 PM to 6:00 AM alongwith required T&P and ladders) by engaging required staff one Lift Operator per shift for proper and efficient running and satisfactory performance of installation including operating DG Set as required complete all as specified and directed Note: (i) The contractor shall employ adequate No of operators ITI qualified with minimum two years experience for operation of installation and necessary T & P shall be provided. (ii) The area upto 25 metre around the installation including DG Set shall be maintained by cleaning including grass cutting etc all as directed by Engineer-in-charge. The unit rates quoted by contractor shall deem to include this aspect also. Nothing extra shall be admissible on this account. In case area is not cleared by contractor around the installation recovery @Rs. 3000/- per month/per installation shall be made from contractor. (ii) The unit rates quoted by the contractor shall including cleaning of lifts. DG Set and including of repairs for operation of lifts. (iii) Contractor shall also be responsible for proper maintenance and operation of lift,maintain log sheet of lift and DG Set for proper operation.
PHASE IV: Commence after completion of work of Phase III
Manning and operation of Lift 08 Passenger at Domestic Area Amritsar in 3 shifts round the clock, each shift shall consist of 8 hours duration (6:00 AM to 2:00 PM, 2:00PM to10:00PM and 10:00 PM to 6:00 AM alongwith required T&P and ladders) by engaging required staff one Lift Operator per shift for proper and efficient running and satisfactory performance of installation including operating DG Set as required complete all as specified and directed Note: (i) The contractor shall employ adequate No of operators ITI qualified with minimum two years experience for operation of installation and necessary T & P shall be provided. (ii) The area upto 25 metre around the installation including DG Set shall be maintained by cleaning including grass cutting etc all as directed by Engineer-in-charge. The unit rates quoted by contractor shall deem to include this aspect also. Nothing extra shall be admissible on this account. In case area is not cleared by contractor around the installation recovery @Rs. 3000/- per month/per installation shall be made from contractor. (ii) The unit rates quoted by the contractor shall including cleaning of lifts. DG Set and including of repairs for operation of lifts. (iii) Contractor shall also be responsible for proper maintenance and operation of lift,maintain log sheet of lift and DG Set for proper operation.
PHASE V: Commence after completion of work of Phase IV
Manning and operation of Lift 08 Passenger at Domestic Area Amritsar in 3 shifts round the clock, each shift shall consist of 8 hours duration (6:00 AM to 2:00 PM, 2:00PM to10:00PM and 10:00 PM to 6:00 AM alongwith required T&P and ladders) by engaging required staff one Lift Operator per shift for proper and efficient running and satisfactory performance of installation including operating DG Set as required complete all as specified and directed Note: (i) The contractor shall employ adequate No of operators ITI qualified with minimum two years experience for operation of installation and necessary T & P shall be provided. (ii) The area upto 25 metre around the installation including DG Set shall be maintained by cleaning including grass cutting etc all as directed by Engineer-in-charge. The unit rates quoted by contractor shall deem to include this aspect also. Nothing extra shall be admissible on this account. In case area is not cleared by contractor around the installation recovery @Rs. 3000/- per month/per installation shall be made from contractor. (ii) The unit rates quoted by the contractor shall including cleaning of lifts. DG Set and including of repairs for operation of lifts. (iii) Contractor shall also be responsible for proper maintenance and operation of lift,maintain log sheet of lift and DG Set for proper operation.
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
technical_845748.pdf
techsummary_845748.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.65 MB
BOQ_845748.xls
BOQ • 0.62 MB
Binder1.pdf
Additional Documents • 13.98 MB
tenderdoct02.pdf
Tender Documents • 21.50 MB
Download all tender documents and submit your bid