Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹20.7 LAdmitted-Finance | -40.99% | ₹20.7 L | L1 | Admitted-Finance |
| 2 | L2₹22.0 LAdmitted-Finance | -37.50% | ₹22.0 L | L2 | Admitted-Finance |
| 3 | L3₹24.7 LAdmitted-Finance 272 VIKAS KUNJ VIKAS PURI NEW DELHI 110018 | WEST | DELHI | 110018 | -29.62% | ₹24.7 L | L3 | Admitted-Finance |
| 4 | L4₹27.3 LAdmitted-Finance NONE | -22.23% | ₹27.3 L | L4 | Admitted-Finance |
Tender Value
₹35.2 L
EMD Value
₹70,310
Closing Date
5 Mar 2026, 3:00 pmClosed
Er. CHANDER SINGH RAWAT
The Executive Engineer (E), West Electrical Division (M-131N), PWD, 41 Rama Road, Zakhira New Delhi-15, Telephone No. 25459518, e-mail ID [email protected]
Comprehensive maintenance of street lighting on PWD roads under West Electrical Division dg. 2025-26. (SH- Replacement of damaged/malfunctional/ dim LED light at various roads under WR-1 as per as and etc (FULL NAME OF WORK MENTIONED IN NIT)
2026_PWD_287709_1
84/EE(E)/West Elect Div(M-131N)/PWD/2025-26
Open Tender
Electrical Works
90 days
Work
Please refer Tender documents.
13 documents required · 13 mandatory
₹0
₹70,310
Yes
6 Mar 2026
25 Feb 2026
5 Mar 2026
25 Feb 2026
5 Mar 2026
25 Feb 2026
LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥120 <135 lm/Watt) Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -5 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K/6500°K(As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). ( As and when required basis.)
Supplying, installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -5 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection,EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirementdeg, suitable tilt able fitting, life time (LED,Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).( As and when required basis.)
Supplying and drawing following sizes of PVC Insulated and PVC Round Sheathed Aluminium Conductor flexible cable for Voltage Grade 1100 Volts as per IS: 694:1990. (Internal Wire) including removing of fitting and reinstallation of fitting back with help of tower wagon.
Supplying of following size XLPE insulated and PVC sheathed aluminium conductor armoured power cable of 1.1 KV grade as required.
4 x 16 Sqmm
4 x 25 Sqmm
3 x 10 Sqmm
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Dismantling and Taking out of existing octagonal/Swaged poles along with street light fittings upto 12/10/8 mtr length from Cement concrete foundation by the help of crane of suitable capacity and with manual labour i/c loading and carriage/ transportation by suitable truck from various sites upto distance of 20 Kms of PWD Roads to PWD Sub Division office at Rama Road JE(E) store and storage at safe place i/c. unloading etc. as reqd i/c taking permission from traffic police if required. if any mishappening will occur during entire work only the agency will be the responsible. (As and when required basis.)
Installation of octagonal/Swaged poles along with street light fittings inplace of damaged pole upto 12/10/8 mtr length from Cement concrete foundation by the help of crane of suitable capacity and with manual labour i/c loading and carriage/ transportation by suitable truck from PWD Sub Division office at Rama Road JE(E) store to various sites upto distance of 25 Kms of PWD Roads. if any mishappening will occur during entire work only the agency will be the responsible.(Note- Foundation bolt should be welded properly) (As and when required basis.)
Supplying and fixing of 40 Amp terminal block suitable for 25sq.mm conductor -4 nos. & shorting links – 5nos. on DIN channel i/c pdg. and fixing DIN channel of suitable length – 2 nos. on the existing laminated sheet. a) Supplying and fixing 6 Amp, SPMCB, ‘C’ Characteristics Curve - 2 No. Earth stud-2Nos. welded at suitable height two nos. washers, springs washers & nuts. b) Cable support clamp suitable for 4 Nos of 4x25 sqmm cable. c) The nuts and bolts shall be welded..
Dismantling of following size of semi high mast/high mast pole including dismantling of all accessories like LEF fitting, ring, rope, gear box and supplied all dismantle accessories at JE store Rama Road (Approx 30 Km from all site) and pole layed near by available space and as directed by Engineer-in-charge. (As and when required basis.)
Reinstallation of following size semi high mast/high mast pole including fixing of all accessories like LED fitting, Gear box, Rope, Internal wire, ring etc. on suitable location as directed by Engineer-in-charge and with proper repairing of gear box etc as required.(As and when required basis.)
Supplying & Fixing of following size Aluminium thimble with proper connection and PVC Tape etc as required.
Supplying and coating composite electric insulation suitable of 8/10/12 Mtr Street light pole upto 2 mtr. height from base after cleaning of street light pole ( like internet wire, banners, polythene etc.) for 1 KVA to 11 KVA to avoid the current leakage. It is in nature of highly hydrophobic and is having excellent water repellant helps to avert the leakage currents, resulting into reduction in contamination flashovers also having excellent U.V. radiation resistance coupled with tracking resistance which makes its use beneficial for outdoor exposure and in extreme weather conditions i/c coating Binder for electric insulation suitable for 1 KVA to 11 KVA load for make proper proportion solution with minimum 4 coats of painting etc. complete as required. a) Di-Electric strength 122 KV/mm. b) Stable up to 200 0 C c) Excellent resistance to UV radiation (suitable for outdoor exposure). d) Tough and Scratch resistant (excellent puncture resistant) e) Excellent Corrosion Resistance Technical specification PERAMETER/PROPERTY VALUE CHARASTRICTICS PHYSICAL APPRIENCE :- LIQUID SOLID CONTAINTS 50.00 :- ±2.00 %w/v Specific Gravity :- (25 0C) :- 1.060 ±0.050 SOLVENT SYSTEM :- Alcohols & Esters % NCO :- 6.00 ±1. 00
Supplying & fixing of weather proof hot press moulded SMC distributions boxes of 250 x 200 x 105 (mm) deep with front opening with hinged type door having locking arrangement mounted on wall / pole with the help of clamp etc i/c providing & fixing of 2 no 6 A to 32 A ratings , SP MCB, “C” curve, 10 KA breaking capacity, channel and 2 nos 20 mm x 3 mm thick copper strip i/c 4 nos DMC / SMC support for fixing the strip , 3 nos hole in each strip, making hole for cable entry & making hole of suitable size in existing pole to draw wire for connection of existing fitting with tower wagon at suitable height etc complete as required.
Fabricating, Supplying & Fixing wire mesh protection frame work made out of 40 mm x 6 mm thick angle & "T" strengthened with intermediate members of MS flat iron of size 30 mm x 5 mm thick welded at a distance of 30 cm horizontally & vertically and duly welded with wire mesh of size 75 mm x 25 mm made with 6 SWG wire mash of size 75 mm x 25 mm made with 6 SWG wire on all sides and top i/c providing and fixing of double door gate with double locking arrangement ( Two Nos. sliding bolts and One No go down lock) having 0.5 mtr. long legs of 40 mm x 40 mm x 6 mm thick angle iron, duly grouted in cement concrete foundation ration 1:2:4 (1 cement: 2 coarse sand : 4 graded stone aggregate), up to suitable depth painting with one coat of red oxide & Two coats of synthetic enamel paint of approval colour and shade etc. complete as reqd.
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.65 MB
BOQ_381346.xls
BOQ • 0.55 MB
Download all tender documents and submit your bid