| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.7 LAccepted-AOC | L1 | Accepted-AOC L1 BIDDER | |
| 2 | L2₹21.8 L+₹2.5 L (12.8%)Rejected-Finance B 235 MULLA COLONY B SECTOR KAROND BERASIA ROAD BHOPAL | BHOPAL | MADHYA PRADESH | 462001 | L2 | Rejected-Finance NOT LOWEST BIDDER | |
| 3 | L3₹22.2 L+₹2.8 L (14.7%)Rejected-Finance 84 A VIJAY NAGAR COLONY LALGHATI PO NAYAPURA BHOPAL 462032 | 462032 | L3 | Rejected-Finance NOT LOWEST BIDDER | |
| 4 | L4₹23.8 L+₹4.4 L (22.9%)Rejected-Finance CIVIL LINE MATATILA ROAD TALBEHAT DISTT LALITPUR U P | TALBEHAT | LALITPUR | U P | L4 | Rejected-Finance NOT LOWEST BIDDER | |
| 5 | L5₹23.9 L+₹4.6 L (23.5%)Rejected-Finance LIG 10 VIVEK NAGAR NAVIBAGH BHOPAL MADHYA PRADESH 462038 | BHOPAL | MADHYA PRADESH | 462038 | L5 | Rejected-Finance NOT LOWEST BIDDER |
Tender Value
Refer Docs
EMD Value
₹58,200
Closing Date
3 Jan 2024, 6:00 pmClosed
Shri Ankit Goyal, IDSE
GE Dronachal, Dronachal Top, Neori Hills, Bhopal 462038
SPECIAL REPAIR TO CONVERSION OF OH LT LINE TO UG CABLE AT DRONACHAL BHOPAL AND SPECIAL REPAIR REPLACEMENT OF UNSV BER SUMMER APPLIANCES AT DRONACHAL BHOPAL
2023_MES_632651_1
8817/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Bhopal
Class-D, Category b (i) and as per NIT documents
6 documents required · 6 mandatory
₹500
Garrison Engineer Dronachal
₹58,200
Yes
19 Apr 2024
14 Dec 2023
5 Jan 2024
14 Dec 2023
3 Jan 2024
28 Dec 2023
15 Dec 2023 - 22 Dec 2023
Amount
Supply installation, testing and commissioning LT Feeder piller board out door type cubicle panel boardsuitable for 3 phase,4 wire 415 volt 50 hz factory febricated approved CPRI powder coated made out of 3.15 mm thick CRCA sheet and MS angle iron sectiom 40X40X6mm frame with front and back openable double door system with locking arragement louver and air vent gaket for netural flow of air with conopy, inner compartment made out of 2 mm the CRCA sheet duly compartmentalized for each MCCB of incoming and outgoing with lockable arragement with alluminium bus bar three phase and neutral of capacity of 400 amp marked red, yelllow, black and blue inslulators, made of high strength insulated material suitable 1100 voltage all controll PVC wires shall be with 2.5 sq mm multistrand copper conductor and shall be properly bunched, tied, frerruled for proper indication , fixed on PCC foundation complete all as specified and directed with following accessories:-
Supply installation, testing and commissioning LT Feeder piller board out door type cubicle panel boardsuitable for 3 phase,4 wire 415 volt 50 hz factory febricated approved CPRI powder coated made out of 3.15 mm thick CRCA sheet and MS angle iron sectiom 40X40X6mm frame with front and back openable double door system with locking arragement louver and air vent gaket for netural flow of air with conopy, inner compartment made out of 2 mm the CRCA sheet duly compartmentalized for each MCCB of incoming and outgoing with lockable arragement with alluminium bus bar three phase and neutral of capacity of 400 amp marked red, yelllow, black and blue inslulators, made of high strength insulated material suitable 1100 voltage all controll PVC wires shall be with 2.5 sq mm multistrand copper conductor and shall be properly bunched, tied, frerruled for proper indication , fixed on PCC foundation complete all as specified and directed with following accessories:-
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded,galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sq mm 4 core complete all as specified and directed by the Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm 3½ core complete all as specified and directed by the Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4 core complete all as specified and directed by the Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 3½ core complete all as specified and directed by the Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 185 sq mm 3½ core complete all as specified and directed by the Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sq mm 3½ core complete all as specified and directed by the Engineer-in-Charge.
Excavation in trench by mechanical means (Hydraulic excavator) means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5m, complete all as specified and directed by the Engineer-in-Charge.
M & L for sand cushioning to PVC/XLPE cables with river sand and punning to provide required cover to UG cables, complete all as specified and directed. Note:- For the purpose of payment only punned thickness will be measured.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in any type soil.
Removing excavated surplus soil (hard rock) obtained from excavation to a distance not exceeding 50 mtr and deposting where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed by the Engineer-in-Charge
Sub class 'B' old size well burnt brick laid flate in trenches as protection to LT cable complete all as specified and directed by the Engineer-in-Charge.
Supply and lay for tubes 'medium grade ' with all galvanised fittings laid in trenches/on ground complete of dia 100 mm.
Supply and lay for tubes 'medium grade ' with all galvanised fittings laid in trenches/on ground complete of dia 50 mm.
Supply and lay for tubes 'medium grade ' with all galvanised fittings laid in trenches/on ground complete of dia 25 mm.
Earthing complete with galvanized steel earth plate, electrode 60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to GI strip 25X4 mm as earthing lead covered with 40mm bore GI pipe light grade by means of bolts, nuts, check nuts and washers of galvanised iron or steel, connected to earthing test point, earth plate electrode surrounded by mixer of common salt and charcoal dust, including 20 mm dia GI watering pipe 'medium grade', funnel with wire mesh, earthing chamber with cement concrete (1:3:6) type C-1, RCC chamber cover 80 mm thick (1:2:4) type B-1, excavating & earth work all as shown in electrical plate No. 3 of SSR (Part-I) and testing on completion complete all as specified and directed. Note:- Length upto 7.5m of GI strip is inclusive in unit rate.
Taking down old insulator any type and make - from existing over head line and poles/stay after dismantling electrically complete all as specified and directed by the Engineer-in-Charge.
Dismantling cross-arms of M.S. channel or angle sections etc. and taking down complete all as specified and directed by the Engineer-in-Charge.
Dismantling/Taking down old LT, over head line of ACSR from PCC/Steel pole. (Note :- Dismentaling of MS work and insulators shall be removed and paid seperatly)
Dismantling/Taking down old guard wire and stay wire of galvanised iron wire from LT over head line PCC/Steel pole. (Note :- Dismentaling of MS work and insulatores shall be removed and paid seperatly)
Supply & fix street light junction box of size 300 x200 x105 mm inner dimension made out of FRP sheet with weather proof hinged doors, locking arrangements horizontal / vertical operated with 6 amps MCB SP, along with provision of 04 Nos aluminium bus bar of capacity 40 Amps and including 25mm x3mm MS flat iron clamps duly painted with two coat of synthetic enamel paint over a coat of red oxide primer all as specified and directed including dismantling of existing unserviceble box.Make of Box Sintex/Hensel or equivalent
supply & fix weather proof PVC insulated multi stranded copper conductor 1.5 Sqmm flat / round, three core 1100 volts grade complete all as specified and directed.
Supply, install,testing and commissioning of 5 Star rated air cooled spilt type airconditioners electric driven( 250 Volts, single phase, 50 HZ supply) with Energy efficient Rotary Compressor, working on R-32 or superior enviornment-friendly refrigerant, cordless remote operated, comprising of indoor unit,wall mounted, material of construction of indoor unit ABS, Nominal cooling capacity 4500 KCal/Hr, Minimum Power consumption , Minimum room discharge airflow 700 CuM /Hr Guranteed cooling capacity(Min) 4275 KCal/Hr, outdoor unit, Material of Cabinet GI Sheet 1.0 mm thick powder coated,Copper tubing, electric connection (Between indoor and outdoor unit located upto a maximum distance of 10 Meters) and condensate water drainage arrangement etc complete of capacity 2 Ton complete all as specified and directed at site. Note :- The outdoor unit shall be fixed on wall with standard bracket or fixed on roof /floor with proper MS stand. The cost is deemed to be included in the quoted rates.
Supply, install,testing and commissioning of 5 Star rated air cooled spilt type airconditioners electric driven( 250 Volts, single phase, 50 HZ supply) with Energy efficient Rotary Compressor, working on R-32 or superior enviornment-friendly refrigerant, cordless remote operated, comprising of indoor unit,wall mounted, material of construction of indoor unit ABS, Nominal cooling capacity 4500 KCal/Hr, Minimum Power consumption , Minimnu room discharge airflow 700 CuM /Hr Guranteed cooling capacity(Min) 4275 KCal/Hr, outdoor unit, Material of Cabinet GI Sheet 1.0 mm thick powder coated,Copper tubing, electric connection (Between indoor and outdoor unit located upto a maximum distance of 10 Meters) and condensate water drainage arrangement etc complete of capacity 1.5 Ton complete all as specified and directed at site. Note :- The outdoor unit shall be fixed on wall with standard bracket or fixed on roof /floor with proper MS stand. The cost is deemed to be included in the quoted rates.
SAMEER ELECTRICAL SUPPLIER
POONAM ELECTRIC INDUSTRY
HARNAM SINGH ANIL SINGH
PRAGATI ELECTRICALS AND ELECTRONICS
M/S RAKESH TRADERS
HRK ENGINEERING CORPORATION
MODI CORPORATION
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .