Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance 428 SURAJ PALACE C A ROAD GANDHIBAG NAGPUR MAHARASHTRA 440002 | NAGPUR | MAHARASHTRA | 440002 | Admitted-Finance |
Tender Value
₹33.8 L
EMD Value
₹34,000
Closing Date
27 May 2024, 12:00 pmClosed
SE
EWC Agra
Increasing capacity 33, 11 Sub-Station Sulatanganj, Shamserganj, Chauraipur, Manchana, Aramsarai, Bhogaon Dehat and installation of additional 5 MVA Transformer at Bewar Sub station in Distt.- Mainpuri on Semi-Turnkey Basis.
2024_DVVNL_923430_1
EWCA/T-25 (2023-24)
Open Tender
Electrical Works
Fixed-rate
60 days
Mainpuri
As per tender specification
2 documents required · 2 mandatory
₹3,000
DVVNL
₹34,000
10 Jun 2024
26 Apr 2024
27 May 2024
26 Apr 2024
27 May 2024
26 Apr 2024
Amount
Carriage of 33 KV Bus Isolator, Lightening Arrestors, 33 KV VCB, Control Panel, CT, PT, 11 KV SWITCH GEARS of Incoming & Outgoing, 11 KV Cable, jointing kit, Pole, ACSR Dog Conductor, etc. from Center Store to Site
33 KV Bus Isolator
G.I. Structure for 33 KV Bus Isolator
33 KV Post Insulator
G.I. Structure for 33 KV Post Insulator
33 KV Lightening Arrestors
G.I. Structure for 33 KV Lightening Arrestors
33/11 KV Transformer 5 MVA
33/11 KV Transformer 10 MVA
90 Lbs. Rail pieces for T/F
33 KV Fuse Set
G.I. Structure for 33 KV Fuse Set
33 KV VCB 800A, 750 MVA with structure
33 KV Control Panel for single T/F
33 KV CT 400/200/1A
G.I. Structure of 33 KV CT
Plinth & foundation of 33 KV VCB.
11 KV SWITCH GEARS Incoming 600/300/5A, 350MVA, I /C
11 KV SWITCH GEARS Outgoing 200/100/5A, 350MVA
11KV 3 Core XLPE Cable 3 × 300 Sq.mm
11KV 3 Core XLPE Cable 3 × 185 Sq.mm
Laying and dressing of 11 KV , 3x300/185 Sq. mm. under ground cable in the trench as per Resspo norms. The work includes supplying of fine sand and bricks, refilling and ramming of the left out soil, closing the trench and leveling.
11KV Cable jointing kit. Heat Shrinkable 3x300 Sq.mm Indoor
11KV Cable jointing kit. Heat Shrinkable 3x300 Sq.mm Outdoor
11KV Cable jointing kit. Heat Shrinkable 3x185 Sq.mm. Indoor
11KV Cable jointing kit. Heat Shrinkable 3x185 Sq.mm. Outdoor
33 KV 1 Ph PT 33 KV/110 V
PCC Pole 8.5 Mtr. long
G.I. Nut, bolt with washer
GI Stay Rod 16x1800mm
11 KV Stay clamp
11 KV Stay Insulator
Stay wire 7/10 SWG
Concreting of Stay Road 16x1800mm
Concreting of support (0.268 Cub.M/Pole)
Supply & Laying of 4 x 2.5 mm² control cable through cable trench in SGR interlinking through proper connections Transformer control panel/ Protection board/Battery & Battery Charger/ buchholtz relay/ 33/11 KV Transformer junction box/ 33 KV VCB, CTs, PT etc. as per site conditions.
Supply & Laying of 2 x 2.5 mm² control cable through cable trench in SGR interlinking through proper connections Transformer control panel/ Protection board/Battery & Battery Charger/ buchholtz relay/ 33/11 KV Transformer junction box/ 33 KV VCB, CTs, PT etc. as per site conditions.
Outdoor Equipment (Earth Mat) of Sub-Station as per Resspo norms
Indoor Equipment (Earth Mat) of Sub-Station as per Resspo norms
ACSR Dog conductor
Pipe Earthing of Power Transformer by way of boring and lowering of “B” class G.I. pipe 50 mm. dia. into the ground up to the water level to the lower end of which a solid copper con approx 9 inches long and 750 gram in weight provided and screwed in connecting and bringing out continuous copper wire 8 SWG from the cone to the ground surface where it will be bolted to the G.I. Earth strip for Transformer neutral connection. The earth strip will be welded to the G.I. pipe. The work also includes cap and clamp for pouring water, the cost of all material with all labour and T&P etc. complete in all respect.
Chemical Pipe earthing
P.G. clamp
24 V Battery with Battery Charger Cabinet.
Fabrication and grouting of G.I. Channel 100x50x6 mm. in L shape & in proper size and alignment to provide support for the two separate Earthing strips for power transformer neutral including supply & fixing of two nos. flexible copper bonds for neutral Earthing. The work also includes painting of G.I. Channel with two coats of aluminium paint.
Fabrication and erection of cable support made of two pieces of G.I. 65x65x6 mm. 3.00mtr. long, joined to each other by means of 5 Nos. M.S. flat 50x6 mm. pieces of size 150 mm. long each by welding at equal intervals as per drawing and grouting in a block of size 300x300x700 mm complete with two coats of Aluminum paint. This includes providing of four nos. G.I. clamp made of G.I. flat for holding the cable including Nuts & bolts.
PLINTH OF 5 MVA, 33/11 KV TRANSFORMERS : Construction of plinth of size 3.46x4.46 Mtr. for 5 MVA Transformers having 0.5 Mtr. below ground level and 0.4 Mtr. above ground level. The work also includes laying of 2 Nos. 3.46 Mtrs. long each rail pieces complete with cutting welding & proper fitting etc. The plinth will be made as per drawing and shall be plastered/finished on top and sides of the plinth.
Protection board
Connecting T/F body and structure of 33 KV VCB, 33 KV CT, PT and 11 KV VCB, etc. to earthmat through G.I. flat
Sundry Stores (Connecting clamps for all equipment & T/F )
LED light 100 Watt complete with fitting and accessories
Barbed wire fencing with gate etc (switchyard)
Dismantling charges of Transformer and keeping it at safe place in Sub-Station
Dismantling & Carrige of 33 KV VCB with structure (Including cartage of dismantled material from site to concerning store of DVVNL)
Dismantling charges of yard fencing and keeping it safe place at Sub-Station
Dismantling charges of 02 No. 8.5 Mtr. Double Pole Structure and re-installation of fittings on new Double Pole Structure
Road restoration charges for pucca road crossing
M/s Manisha Trading Co.
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .