| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹189.9 CrAccepted-AOC PLOT NO 16 OPP METRO PILLAR NO 190 PASCHIM VIHAR EXTENSION ROHTAK ROAD DELHI 110 063 | ₹189.9 Cr | L-1 | Accepted-AOC Being L-1 |
| 2 | L-2₹212.1 CrRejected-Finance PLOT NO 65 SECTOR 18 OPP HIPA SARHAUL GURUGRAM 122 001 | ₹212.1 Cr | L-2 | Rejected-Finance Other than L-1 |
| 3 | Rejected-Technical | - | - | Rejected-Technical Not eligible being contract cancelled |
Tender Value
₹121.5 Cr
EMD Value
₹15 L
Closing Date
13 Sept 2021, 6:00 pmClosed
Chief Engineer Udhampur Zone
Military Engineer Services Chief Engineer Udhampur Zone, Garhi-182121
COMPLETION OF INCOMPLETE/BALANCE WORKS FOR CONSTRUCTION OF 650 BEDDED HOSPITAL ALONGWITH OTM ACCN INCL LIFT, CENTRAL AC PLANT, HOT WATER SUPPLY, FIRE HYDRANT, SPRINKLER SYSTEM, FIRE ALARM SYSTEM AND EXTERNAL SERVICES FOR COMMAND HOSPITAL (NC) AT UDHA
2021_MES_446882_1
87869-A/E8
Open Tender
Civil Works
820 days
Udhampur
As per NIT
11 documents required · 11 mandatory
₹3,000
GE P CH Udhampur
₹15 L
Yes
6 Nov 2021
1 Jun 2021
15 Sept 2021
1 Jun 2021
13 Sept 2021
25 Aug 2021
Amount
Sch 'A' Part - I (Building Works) Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Construction of balance works for main hospital building incl Admin block,auditorium,basement, porches, ramps, stair case,fire escape stair case, lift wells etc. complete all as specified and shown on drawings. Note:- 1. The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 948 to 1009 2. The Go ahead approvals in principle accorded on cancelled contract shall remain in this contract too. The detail of AIPs alongwith details of works are enclosed as Appendix G to the Particular Specifications. The contractor shall consider these changes while quoting his lumpsum considering the effect of changes based on the details attached under this item. This provision is deemed to be included in the rate quoted by the contractor.
Construction of balance works for block of MNS Officer Mess for 52 officers including stair case complete all as specified and as shown on drawings. Note:The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1010 to 1014
Construction of balance works for block of JCO's Mess and Club for 32 JCO's including stair case complete all as specified and as shown on drawings. Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1015 to 1018
Construction of block of Cook House and Dining Hall for 40 Trainees complete all as specified and as shown on drawing.
Construction of balance works for block of Cook House and Dining Hall for single Hav/ORs for 151 to 250 men complete all as specified and as shown on drawing. Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1019 to 1021
Construction of block of SM barrack for 40 Havs and 75 ORs incl stair case complete all as specified and as shown on drawing.
Construction of balance works for block of SM barrack for 40 Havs and 75 ORs incl stair case complete all as specified and as shown on drawing. Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1022 to 1029
Construction of balance works for block of SM barrack for 40 ORs (Trainees) incl stair case complete all as specified and as shown on drawing. Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1030 to 1034
Construction of balance works for block of single living accn for 4 JCO's incl scooter shed and stair case complete all as specified and as shown on drawing (Block - I). Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1035, 1036, 1039 to 1041
Construction of balance works for block of single living accn for 4 JCO's incl scooter shed and stair case complete all as specified and as shown on drawing (Block - 2). Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1037, 1038, 1042 to 1044
Construction of balance works for block of four servant quarters incl stair case complete all as specified and as shown on drawing. Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1045 to 1049
Construction of balance works for block of four single living quarters for Major (Trainee Officers) incl stair case complete all as specified and as shown on drawing. Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1050 to 1052
Construction of block of three single living servant quarter and two garrages for Major (Trainee Officers) incl garrages and stair case complete all as specified and as shown on drawing.
Construction of balance works for block of eight single living quarters for Capt and below (MNS Officers) incl garage and stair case complete all as specified and as shown on drawing (Block-I). Note:-The details of balace work are as per Appendix-H enclosed at Srl Page Nos. 1053 to 1055 & 1059 to 1061
Construction of balance works for block of eight single living quarters for Capt and below (MNS Officers) incl garage and stair case complete all as specified and as shown on drawing (Block-2). Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos.1056 to 1058 & 1062 to 1065
Construction of balance works for block of twelve single living servant quarters for MNS Officers incl stair case complete all as specified and as shown on drawing (Block - I). Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1066, 1067, 1070 & 1071
Construction of balance works for block of twelve single living servant quarters for MNS Officers incl stair case complete all as specified and as shown on drawing (Block-2). Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1068, 1069 & 1073 to 1075
Construction of balance works for block of single married quarter for Major General (Commandent) incl servant quarter and garage complete all as specified and as shown on drawing. Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1076 to 1081
Construction of balance works for block of four married quarters for Major to Brig incl servant quarter, garages and stair case complete all as specified and as shown on drawing (Block-I). Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1082 to 1084 & 1088 to 1090
Construction of balance works for block of four married quarters for Major to Brig incl servant quarter, garages and stair case complete all as specified and as shown on drawing (Block - 2). Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1085 to 1087 & 1091 to 1095
Construction of balance works for block of six married quarters for JCO's incl scooter shed, garage and stair case complete all as specified and as shown on drawing. Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1096 to 1100
Construction of balance works for block of six married quarters for ORs incl scooter shed and stair case complete all as specified and as shown on drawing (Block-I). Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1101 to 1103 & 1107 to 1109
Construction of balance works for block of six married quarters for ORs incl scooter shed and stair case complete all as specified and as shown on drawing (Block-2). Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1104 to 1106 & 1110 to 1112
Construction of balance works for block of five married quarters for ORs incl scooter shed and stair case complete all as specified and as shown on drawing. Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1113 to 1119
Construction of block of four married quarters (type-II) for Non Combats incl stair case complete all as specified and as shown on drawing.
Construction of block of nine Guest Suits complete all as specified and as shown on drawing.
Construction of block of Guard house and Armoury complete all as specified and as shown on drawing.
Construction of block of welfare amenities incl stair case complete all as specified and as shown on drawing.
Construction of balance works for block of family welfare centre complete all as specified and as shown on drawing. Note:-The details of balace work are as per Appendix-H enclosed at Srl Page Nos. 1120 to 1123
Construction of block of religious institute complete all as specified and as shown on drawing.
Construction of block of senitry post complete all as specified and as shown on drawing.
Construction of balance works for block of garrage for Car/Gypsy five bays and four bays for lorry 3 ton including apron complete all as specified and as shown on drawing. Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1124 to 1125
Construction of block of garrage for Car/Gypsy five bays incl apron for MNS Officer Mess complete all as specified and shown on drgs.
Construction of balance works for block of garrage for one Ton and Ambulance 12 bays including apron for MNS Officer Mess complete all as specified and as shown on drawing. Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1126 to 1127
Construction of balance works for block of repair bays (two Nos) with inspection pit (one No) incl apron complete all as specified and as shown on drawing. Note:-The details of balace work are as per Appendix-H enclosed at Srl Page Nos. 1128 to 1130
Construction of block of MT store, Driver change room & technical office complete all as specified and as shown on drawing.
Construction of balance works for block for housing incinerator incl accessories complete all as specified and as shown on drawing. Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1131 to 1133
Construction of single ramp complete all as specified and as shown on drawing.
Construction of block of Petrol and lubricant store complete all as specified and as shown on drawing.
Construction of washing platform for all vehicles complete all as specified and as shown on drawing.
Construction of balance works for block of AC plant room complete all as specified and as shown on drawing. Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1134 to 1137
Construction of balance works for platform for single transformer of size 3000 x2500mm, 1200mm high from NGL, with brick construction including steps, XPM fencing fixed on angle iron posts up to 1200mm height with gate and locking arrangement, painting etc. complete all as specified and shown on drawing. Note:-The details of balance works are as per Appendix 'H' enclosed at Srl Page Nos. 1138 to 1139
Construction of under ground RCC sump 3 lakh litres capacity with monholes, vent pipe, puddle plates, rungs and other details complete all as specified and shown on drawings. Note :- Inlet, outlet and over flow pipes with valves and duck foot bend etc shall be measured and paid for separately.
Construction of balance works for Gate Complex-I comprising of two ornamental steel gates 5.40m wide, two wicket gates 1.2m wide, guard rooms, security rooms, surmounted with side pillars, domes, arches, insignia of brass metal letters, sign board etc complete all as specified and shown on drawings. Note:-The details of balace work are as per Appendix-H enclosed at Srl Page Nos. 1140 to 1141
Construction of Gate Complex-II comprising of one ornamental steel gates 5.40m wide, two wicket gates 1.2m wide, guard rooms, security rooms, surmounted with side pillars, domes, arches, insignia of brass metal letters, sign board etc complete all as specified and shown on drawings.
Total Amount of Sch 'A' Part - II (Sec A) (Internal Eletcrification)
Sch 'A' Part - II (SEC-B ) (INTERNAL ELECTRIC SUPPLY ) Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Supplying, installation, testing and commissioning of L.T. panel fully compartmentalized cubical type sheet clad floor/wall mounted totally enclosed , painted after seven tank process, extensible on both sides, switch board suitable for use on 1-Phase/3-phase,50 Hz system having required fault capacity, housed with incoming and outgoing, Copper bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.(MNS officer's Mess) NCOMER : 1 No.100 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Fixed magnetic releases. BUS BARS : 200 Amps. TP&N copper bus bars (25 KA Ics). OUT GOINGS 6 Nos. 25A 4P, MCB (10KA). Space for 2 Nos.25A 4P, MCB
All as per Srl item 49 above but following mountings. (Servant quarters for Capt & Below of 12) INCOMER : 1 No.40 Amps. 4P MCB(10 KA). BUS BARS : 63 Amps. TP&N copper bus bars. OUT GOING Space for 12 Nos. Single phase electronic meters 13 Nos 6A DP MCB (10KA)
All as per Srl item 49 above but following mountings.(single accn for Captain and below of 8 T/S) INCOMER : 1 No.80 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Fixed magnetic releases. BUS BARS : 200 Amps. TP&N copper bus bars (25 KA Ics). OUT GOING Space for 8 Nos. Single phase electronic meters 8 Nos 25A DP MCB (10KA) 1 Nos. 6A DP, MCB ( 10KA)
All as per Srl item 49 hereinbefore but following mountings. (Single JCO) INCOMER : 1 No.40 Amps. 4P MCB(10 KA). BUS BARS : 63 Amps. TP&N copper bus bars. OUT GOINGS :- Space for 4 Nos. Single phase electronic meters 4 Nos 20A DP MCB (10KA) 1 Nos. 16A DP, MCB ( 10KA) 1 Nos. 6A DP, MCB ( 10KA)
All as per Srl item 49 hereinbefore but following mountings.(SM barracks for 150 Hav& 230 OR's). INCOMER : 1 No.125 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Fixed magnetic releases. BUS BARS : 200 Amps. TP&N copper bus bars (25 KA Ics). OUT GOING 8 Nos 25A 4P, MCB (10KA)
All as per Srl item 49 hereinbefore but following mountings.(single Accn for Major and md accn for non combats). INCOMER : 1 No.40 Amps. 4P MCB(10 KA). BUS BARS : 100 Amps. TP&N copper bus bars. OUT GOINGS :- Space for 4 Nos. Single phase electronic meters 4 Nos 25A DP, MCB (10KA) 1 Nos. 6A DP, MCB ( 10KA)
All as per Srl item 49 hereinbefore but following mountings.(servant quarters and garage for Major). INCOMER : 1 No.25 Amps. DP MCB(10 KA). BUS BARS : 63 Amps. SP&N copper bus bars. OUT GOINGS :- Space for 3 Nos. Single phase electronic meters 4 Nos. 6A DP, MCB ( 10KA).
All as per Srl item 49 hereinbefore but following mountings.(MD accn for JCO). INCOMER : 1 No.63 Amps. 4P MCB(10 KA). BUS BARS : 100 Amps. TP&N copper bus bars. OUT GOINGS :- Space for 6 Nos. three phase electronic meters 6 Nos. 25A 4P, MCB ( 10KA). 1 Nos. 6A DP, MCB ( 10KA)
All as per Srl item 49 hereinbefore but following mountings.(MD accn for ORS). INCOMER :1 No.63 Amps. 4P MCB(10 KA) BUS BARS : 100 Amps. TP&N copper bus bars OUT GOINGS :- Space for 6 Nos. Single phase electronic meters 6 Nos. 25A DP, MCB ( 10KA). 1 Nos. 6A DP, MCB ( 10KA)
All as per Srl item 49 hereinbefore but following mountings.(welfare amenity). INCOMER : 1 No.100 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Fixed magnetic releases. BUS BARS : 200 Amps. TP&N copper bus bars (25 KA Ics). OUT GOINGS :- 4 Nos. 25A 4P, MCB ( 10KA). 4 Nos. 16A 4P, MCB ( 10KA) Space for 2Nos. 25A 4P, MCB
All as per Srl item 49 hereinbefore but following mountings.(servant quarters for block of 4). INCOMER : 1 No.100 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Fixed magnetic releases. BUS BARS : 200 Amps. TP&N copper bus bars (25 KA Ics). OUT GOINGS :- Space for 4 Nos. Single phase electronic meters 5 Nos. 6A DP, MCB ( 10KA)
Hospital Building All as per Srl item 49 hereinbefore but following mountings. (Major to Brigadier). INCOMER : 1 No.100 Amps. 4P MCCB(25 KA Ics) with Adjustable thermal & Fixed magnetic releases. BUS BARS : 200 Amps. TP&N copper bus bars (25 KA Ics). OUT GOINGS :- Space for 4 Nos. three phase electronic meters 4 Nos. 25A 4P, MCB ( 10KA) 1 Nos. 6A DP, MCB ( 10KA)
Supply only 1000 mm wide and 6mm thick corrugated insulation rubber matting suitable for 1100 volts grade.
welding work on outer surfaces of two continuous 'C' class MS pipes of size 100mm bore dia to make functional & leak proof joints including testing on completion complete all as specified and directed.
welding work on outer surfaces of two continuous 'C' class MS pipes of size 80mm bore dia to make functional & leak proof joints including testing on completion complete all as specified and directed.
welding work on outer surfaces of two continuous 'C' class MS pipes of size 65mm bore dia to make functional & leak proof joints including testing on completion complete all as specified and directed.
Point wiring with 1.5 sqmm copper conductor cable (multistranded, PVC insulated, FRLS unsheathed type) by drawing the main conductors (phase & neutral) + one earth wire of size 1.5 sqmm copper conductor in the existing concealed type 25mm dia PVC conduit & fixing the hylam sheet covers on existing steel sunken boxes including mounting of switches, sockets, regulators etc on the switch boards after making all electrical connections for the light/fan points or 3 pin 5 Amp socket outlets (the light/fan points or 3 pin 5 Amp socket outlets shall be fixed on same board but wiring shall be done independentally for each point) (For OTM Accn), complete all as specified and directed.
Point wiring with 1.5 sqmm copper conductor cable (multistranded, PVC insulated, FRLS unsheathed type) by drawing the main conductors (phase & neutral) + one earth wire of size 1.5 sqmm copper conductor in the existing concealed type 25/40mm dia stove enamelled steel conduit & fixing the inner & outer cover plates on existing GI flush boxes including mounting of modular switches, sockets, regulators etc on the modular switch boards after making all electrical connections for the light/fan points or 3 pin 5 Amp socket outlets (the light/fan points or 3 pin 5 Amp socket outlets shall be fixed on same board but wiring shall be done independentally for each point) (For Main Hospital Bldg), complete all as specified and directed.
BLANK
Fixing only MS outer/ cover plate at the existing TPN DB 4 ways with 200 Amps, 415 volts rated bus bars, complete all as specified and directed.
Fixing only MS outer/ cover plate at the existing TPN DB 8 ways with 200 Amps, 415 volts rated bus bars, complete all as specified and directed.
Fixing only MS outer/ cover plate at the existing TPN DB 12 ways with 200 Amps, 415 volts rated bus bars, complete all as specified and directed.
Fixing only MS outer/ cover plate at the TPN DB 6 ways with 200 Amps, 415 volts rated bus bars, complete all as specified and directed.
To make functional the existing copper earthing by tracing out of existing copper earth plate electrode of size 600x600x3.15mm thick (buried directly in ground not less than 2.25 meters deep below the ground level), earthing leads of 20x3mm copper strip, 40mm GI medium grade protection pipe upto 7.5m length, GI medium grade watering pipe 20mm dia, funnel, wire mesh etc and including making of fresh/new earth pits (using PCC 1:2:4 type B-1), earth pits shall be covered with CI cover comple all as shown in plate No. 3 of SSR Part-1 connected to existing earthing test points all as specified or indicated including testing on completion, complete all as specified and directed.
Testing and commissioning of existing 1.1 KV XLPE armoured/PVC insulated, PVC sheathed copper conductor cable laid over existing cable trays of size 4 core x 6 sqmm, complete all as specified and directed.
Testing and commissioning of existing 1.1 KV XLPE armoured/PVC insulated, PVC sheathed copper conductor cable laid over existing cable trays of size 4 core x 10 sqmm, complete all as specified and directed.
Testing and commissioning of existing 1.1 KV XLPE armoured/PVC insulated, PVC sheathed copper conductor cable laid over existing cable trays of size 4 core x 10 sqmm, complete all as specified and directed.
Point wiring with 1.5 sqmm copper conductor cable (multistranded, PVC insulated, FRLS unsheathed type) by drawing the main conductors (phase & neutral) + one earth wire of size 1.5 sqmm copper conductor in the existing concealed type 25/40mm dia stove enamelled steel conduit & fixing the inner & outer cover plates on existing GI flush boxes including mounting of modular switches, sockets, regulators etc on the modular switch boards after making all electrical connections independent for two light points controlled by one switch on the same switch circuit, complete all as specified & directed. (For Main Hospital Bldg)"
Point wiring with 1.5 sqmm copper conductor cable (multistranded, PVC insulated, FRLS unsheathed type) by drawing the main conductors (phase & neutral) + one earth wire of size 1.5 sqmm copper conductor in the existing concealed type 25/40mm dia stove enamelled steel conduit & fixing the inner & outer cover plates on existing GI flush boxes including mounting of modular switches, sockets, regulators etc on the modular switch boards after making all electrical connections independent for three light points controlled by one switch on the same switch circuit. complete all as specified & directed. (For Main Hospital Bldg)"
Point wiring with 1.5 sqmm copper conductor cable (multistranded, PVC insulated, FRLS unsheathed type) by drawing the main conductors (phase & neutral) + one earth wire of size 1.5 sqmm copper conductor in the existing concealed type 25/40mm dia stove enamelled steel conduit & fixing the inner & outer cover plates on existing GI flush boxes including mounting of modular switches, sockets, regulators etc on the modular switch boards after making all electrical connections independent for four light points controlled by one switch on the same switch circuit. (For Main Hospital Bldg)"
Point wiring with 1.5 sqmm copper conductor cable (multistranded, PVC insulated, FRLS unsheathed type) by drawing the main conductors (phase & neutral) + one earth wire of size 1.5 sqmm copper conductor in the existing concealed type 25/40mm dia stove enamelled steel conduit & fixing the inner & outer cover plates on existing GI flush boxes including mounting of modular switches, sockets, regulators etc on the modular switch boards after making all electrical connections independent for five light points controlled by one switch on the same switch circuit. (For Main Hospital Bldg)"
Point wiring with 1.5 sqmm copper conductor cable (multistranded, PVC insulated, FRLS unsheathed type) by drawing the main conductors (phase & neutral) + one earth wire of size 1.5 sqmm copper conductor in the existing concealed type 25/40mm dia stove enamelled steel conduit & fixing the inner & outer cover plates on existing GI flush boxes including mounting of modular switches, sockets, regulators etc on the modular switch boards after making all electrical connections independent for six light points controlled by one switch on the same switch circuit. (For Main Hospital Bldg)"
Point wiring with 1.5 sqmm copper conductor cable (multistranded, PVC insulated, FRLS unsheathed type) by drawing the main conductors (phase & neutral) + one earth wire of size 1.5 sqmm copper conductor in the existing concealed type 25/40mm dia stove enamelled steel conduit & fixing the inner & outer cover plates on existing GI flush boxes including mounting of modular switches, sockets, regulators etc on the modular switch boards after making all electrical connections independent for seven light points controlled by one switch on the same switch circuit. (For Main Hospital Bldg)"
Point wiring with 1.5 sqmm copper conductor cable (multistranded, PVC insulated, FRLS unsheathed type) by drawing the main conductors (phase & neutral) + one earth wire of size 1.5 sqmm copper conductor in the existing concealed type 25/40mm dia stove enamelled steel conduit & fixing the inner & outer cover plates on existing GI flush boxes including mounting of modular switches, sockets, regulators etc on the modular switch boards after making all electrical connections independent for Eight light points controlled by one switch on the same switch circuit. (For Main Hospital Bldg)"
Point wiring with 1.5 sqmm copper conductor cable (multistranded, PVC insulated, FRLS unsheathed type) by drawing the main conductors (phase & neutral) + one earth wire of size 1.5 sqmm copper conductor in the existing concealed type 25/40mm dia stove enamelled steel conduit & fixing the inner & outer cover plates on existing GI flush boxes including mounting of modular switches, sockets, regulators etc on the modular switch boards after making all electrical connections independent for Nine light points controlled by one switch on the same switch circuit. (For Main Hospital Bldg)"
Point wiring with 1.5 sqmm copper conductor cable (multistranded, PVC insulated, FRLS unsheathed type) by drawing the main conductors (phase & neutral) + one earth wire of size 1.5 sqmm copper conductor in the existing concealed type 25/40mm dia stove enamelled steel conduit & fixing the inner & outer cover plates on existing GI flush boxes including mounting of modular switches, sockets, regulators etc on the modular switch boards after making all electrical connections independent for Ten light points controlled by one switch on the same switch circuit. (For Main Hospital Bldg)"
Point wiring with 1.5 sqmm copper conductor cable (multistranded, PVC insulated, FRLS unsheathed type) by drawing the main conductors (phase & neutral) + one earth wire of size 1.5 sqmm copper conductor in the existing concealed type 25/40mm dia stove enamelled steel conduit & fixing the inner & outer cover plates on existing GI flush boxes including mounting of modular switches, sockets, regulators etc on the modular switch boards after making all electrical connections independent for Eleven light points controlled by one switch on the same switch circuit. (For Main Hospital Bldg)"
Point wiring with 1.5 sqmm copper conductor cable (multistranded, PVC insulated, FRLS unsheathed type) by drawing the main conductors (phase & neutral) + one earth wire of size 1.5 sqmm copper conductor in the existing concealed type 25/40mm dia stove enamelled steel conduit & fixing the inner & outer cover plates on existing GI flush boxes including mounting of modular switches, sockets, regulators etc on the modular switch boards after making all electrical connections independent for one light points controlled by two way switch. (For Main Hospital Bldg)"
Point wiring with 4.00 sqmm copper conductor cable (multistranded, PVC insulated, FRLS unsheathed type) by drawing the main conductors (phase & neutral) + one earth wire of size 4.00 sqmm copper conductor in the existing concealed type 25/40mm dia stove enamelled steel conduit & fixing the inner & outer cover plates on existing GI flush boxes including mounting of modular switches, sockets, regulators etc on the modular switch boards after making all electrical connections independent for 3 pin socket outlet 15/20 Amp. (For Main Hospital Bldg)"
Earthing Maintenance free earthing of make Electrolytic Earthing comprising of type 'K' copper 2.4 mm wall thickness, hollow tube 12 feet long, 2.125 inches outer diameter completely filled with non hazardous metallic salts (Tettafill) to achieve an earth resistance of less than 1 ohms and connected to earthing test point all as specified or indicated including testing on completion.
RISING MAINS, CABLE TRAY & LT CABLES(for Sub mains /Main) Compact Sandwich Rising mains Supply, Fixing ,inspection, handling, shifting, assembling, installation in correct assigned position of compact Sandwich construction copper rising mains (distribution bus trunking) and making proper connections, testing and commissioning 4 pole raising mains of copper bus bars with tap off connection points at every 1000mm intervals, expansion joints, fire barriers incl necessary support and louvers for ventilation, fabricated including 2 nos.of 50x6mm copper earthing conductor through out the length of the rising mains ( phase sequence should be matched with the incoming breaker provided at LT Panel ). Thrust pad shall be provided for each rising main for necessary support to rising main and to prevent the bus bar expansion in downward direction with end cover to close the end of rising main and to provode extra supports to bus bars at end, of following rating :-
(a) Compact Sandwich Copper Rising mains Distribution Bus Trunking, rating 400A with short circuit withstand of 35 KA –1 sec,enclosure of GI Powder Coated RAL 7032 of sheet thickness 1.6mm ,with plug in point provison for each floor ,Class F insulation of three layer of polyester and one layer of glass mica IP – 54 protection ,one spring hanger/rigid hanger at each floor, temp rise of 55 Deg over an ambient of 40 Deg temperature. For RM-7,9,10,11,12
(b) Compact Sandwich Copper Rising mains Distribution Bus Trunking, rating 630A with short circuit withstand of 40 KA –1 sec,enclosure of GI Powder Coated RAL 7032 of sheet thickness 1.6mm ,with plug in point provison for each floor ,Class F insulation of three layer of polyester and one layer of glass mica IP – 54 protection ,one spring hanger/rigid hanger at each floor, temp rise of 55 Deg over an ambient of 40 Deg temperature. For RM-4,6,8
(c) Compact Sandwich Copper Rising mains Distribution Bus Trunking, rating 800A with short circuit withstand of 50 KA –1 sec,enclosure of GI Powder Coated RAL 7032 of sheet thickness 1.6mm ,with plug in point provison for each floor ,Class F insulation of three layer of polyester and one layer of glass mica IP – 54 protection ,one spring hanger/rigid hanger at each floor, temp rise of 55 Deg over an ambient of 40 Deg temperature. For RM-3,4,6,8
(d) Compact Sandwich Copper Rising mains Distribution Bus Trunking, rating 1600A with short circuit withstand of 50 KA –1 sec,enclosure of GI Powder Coated RAL 7032 of sheet thickness 1.6mm ,with plug in point provison for each floor ,Class F insulation of three layer of polyester and ond one layer of glass mica IP – 54 protection ,one spring hanger/rigid hanger at each floor, temp rise of 55 Deg over an ambient of 40 Deg temperature. For RM-1
Supply, Fixing ,inspection, handling, shifting, assembling, installation in correct assigned position and including making proper connections, testing and commissioning MCCB Adopter Boxes fabricated out of 16 gauge CRCA sheet steel in cubical formation, dust and vermin proof and coupled with Rising mains. Boxes shall be treated with anticorrossive process before powder coating as per specifications, 2 nos. earthing terminals shall be provided. Boxes shall be suitable for connecting of rising mains at top and aluminuum cables at bottom, of following rating :-
(a) 400 Amp TPN End Feed unit complete with provision of 400 amps , TPN, MCCB of 35 KA (Ics)
(b) 630 Amp TPN End Feed unit complete with provision of 630 amps,TPN, MCCB of 40 KA (Ics)
(c) 800 Amp TPN End Feed unit complete with provision of 800 amps,4P, MCCB of 50 kA (Ics)
(d) 1600 Amp TPN End Feed unit complete with provision of 1600 amps,4P, ACB ,MDO,Microprocessor (with O/L,S/C,INST. E/F) Releases of 50 kA (Ics)
Supply, Fixing ,inspection, handling, shifting, assembling, installation in correct assigned position and including making proper connections, testing and commissioning Tap off Boxes fabricated out of 16 gauge CRCA sheet steel in cubical formation, dust and vermin proof and mounted on the Rising mains. Boxes shall be treated with anticorrossive process before powder coating as per specifications, 2 nos. earthing terminals, including providing of following MCCB's as required with all accessories and adequate space shall be provided for cables terminations, of following rating:-
(a) Tap off /Plug in box complete with 63A Amp, TPN, MCCB of 25 KA (Ics)
(b) Tap off /Plug in box complete with 100A Amp, TPN, MCCB of 25 KA (Ics)
(c) Tap off /Plug in box complete with 125A Amp, TPN, MCCB of 25 KA (Ics)
(d) Tap off /Plug in box complete with 160A Amp, TPN, MCCB of 25 KA (Ics)
(e) Tap off /Plug in box complete with 200A Amp, TPN, MCCB of 25 KA (Ics)
(f) Tap off /Plug in box complete with 250A Amp, TPN, MCCB of 35 KA (Ics)
(g) Tap off /Plug in box complete with 300A Amp, TPN, MCCB of 35 KA (Ics)
(h) Tap off /Plug in box complete with 400A Amp, TPN, MCCB of 35 KA (Ics)
(k) Tap off /Plug in box complete with 630A Amp, TPN, MCCB of 35 KA (Ics)
Perforated type GI cable trays for supporting LT sub main cables fabricated from perforated 2mm thick MS CRCA sheet duly galvanised with extention coupler plates duly galvanised, with bolts washer and nuts. knock out hole cable connections as per approved design. including supporting steel, fish plates, fixing accessories, nut bolts, down rods, dash fastners complete as required. as per specifications, for following sizes :-
(a) 150mm wide x 40mm x 40mm.
(b) 300mm wide x 40mm x 40mm.
(c) 450mm wide x 40mm x 40mm.
(d) 600mm wide x 40mm x 40mm.
(e) 750mm wide x 40mm x 40mm.
(f) 1000mm wide x 40mm x 40mm.
Supply, laying, testing and commissioning of 1.1 KV XLPE armoured / PVC insulated, PVC sheathed aluminium/copper conductor cables confirming to IS: 1554 part 1-1976 with latest amendment laid over existing Cable tray including clamping the cables to support, complete all as specified, of following sizes :-
(a) 3.5 core x 35 sq.mm XLPE armoured, aluminium conductor cable
(b) 3.5c x 50 sq.mm XLPE armoured, aluminium conductor cable
(c) 3.5 core x 70 sq.mm XLPE armoured, aluminium conductor cable
(d) 3.5 core x 95 sq.mm XLPE armoured, aluminium conductor cable
(e) 3.5 core x 120 sq.mm XLPE armoured, aluminium conductor cable
(f) 3.5 core x 150 sq.mm XLPE armoured, aluminium conductor cable
(g) 3.5 core x 185 sq.mm XLPE armoured, aluminium conductor cable
(h) 3.5 core x 240 sq.mm XLPE armoured, aluminium conductor cable
(j) 3.5 core x 300 sq.mm XLPE armoured, aluminium conductor cable
(k) 3.5 core x 400 sq.mm XLPE armoured, aluminium conductor cable
(l) 4 core x 6 sq.mm armoured copper cable
(m) 4 core x 10 sq.mm armoured copper cable
(n) 4 core x 16 sq.mm armoured copper cable
(o) 2 core x 10 sq.mm armoured copper cable
Cable end termination of 1.1 KV XLPE / PVC insulated, aluminium / copper conductor armoured cables, including supplying and fixing of crimping aluminum/ copper lugs, double compression heavy duty glands with earthing facility at both ends of cables,including taping of cable leads with insulation tape etc ,complete all as specified, of following sizes :-
(a) 4 core x 25 sq.mm XLPE armoured, aluminium conductor cable
(b) 3.5 core x 35 sq.mm XLPE armoured, aluminium conductor cable
(c) 3.5 core x 50 sq.mm XLPE armoured, aluminium conductor cable
(d) 3.5 core x 70 sq.mm XLPE armoured, aluminium conductor cable
(e) 3.5 core x 95 sq.mm XLPE armoured, aluminium conductor cable
(f) 3.5 core x 120 sq.mm XLPE armoured, aluminium conductor cable
(g) 3.5 core x 150 sq.mm XLPE armoured, aluminium conductor cable
(h) 3.5 core x 185 sq.mm XLPE armoured, aluminium conductor cable
(j) 3.5 core x 240 sq.mm XLPE armoured, aluminium conductor cable
(k) 3.5 core x 300 sq.mm XLPE armoured, aluminium conductor cable
(l) 3.5 core x 400 sq.mm XLPE armoured, aluminium conductor cable
(m) 4 core x 6 sq.mm armoured copper cable
(n) 4 core x 10 sq.mm armoured copper cable
(o) 4 core x 16 sq.mm armoured copper cable
(p) 2 core x 10 sq.mm armoured copper cable
Supplying and drawing in existing conduit Wiring for TV outlet with coaxial cable double screened, aluminium. foiled, tinned copper ATC braid having an impedance of 75 Ohms and signal losses not more then 6 db etc as reqd.
OUTGOINGS : 6 Nos. 40A 4P, MCB (10KA). Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.40A 4P, MCB
OUTGOINGS : 3 Nos. 25A 4P, MCB (10KA).TYPE-D. 3 Nos. 40A 4P, MCB (10KA).TYPE-D. Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b)Spare Space only for 2 Nos.40A 4P, MCB.
OUTGOINGS : 4 Nos. 25A 4P, MCB (10KA).TYPE-D. 1 No. 40A 4P, MCB (10KA).TYPE-D. Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b)Spare Space only for 2 Nos.25A 4P, MCB.
OUTGOINGS : 9 Nos. 25A 4P, MCB (10KA).TYPE-D, 1 No. 40A 4P, MCB (10KA).TYPE-D, 1 No. 63A 4P, MCB (10KA).TYPE-D. Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b)Spare Space only for 2 Nos.25A 4P, MCB.
OUTGOINGS : 1 No. 25A 4P, MCB (10KA).TYPE-D, 6 Nos. 40A 4P, MCB (10KA).TYPE-D. Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b)Spare Space only for 2 Nos.40A 4P, MCB.
OUTGOINGS : 2 Nos. 25A 4P, MCB (10KA).TYPE-D, 3 Nos. 40A 4P, MCB (10KA).TYPE-D. Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.25A 4P, MCB.
OUTGOINGS : 14 Nos. 25A 4P, MCB (10KA).TYPE-D, 2 Nos. 40A 4P, MCB (10KA).TYPE-D, 1 No. 63A 4P, MCCB (25KA). Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.25A 4P, MCB.
OUTGOINGS : 5 Nos. 25A 4P, MCB (10KA).TYPE-D, 4 Nos. 40A 4P, MCB (10KA).TYPE-D, Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b)Spare Space only for 2 Nos.25A 4P, MCB.
OUTGOINGS : 1 No. 63A 4P, MCCB (25KA). 2 Nos. 100A 4P, MCCB (25KA). 1 No 125A 4P, MCCB (25KA). 1 No 160A 4P, MCCB (25KA). Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.100A 4P, MCCB.
OUTGOINGS : 1 No. 20A 4P, MCB (10KA).TYPE-D, 1 No. 25A 4P, MCB (10KA).TYPE-D, 6 Nos. 32A 4P, MCB (10KA).TYPE-D, 2 Nos. 40A 4P, MCB (10KA).TYPE-D, 1 No. 63A 4P, MCB (10KA).TYPE-D. Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.25A 4P, MCB
OUTGOINGS : 1 No. 25A 4P, MCB (10KA). TYPE-D, 6 Nos. 40A 4P, MCB (10KA).TYPE-D. Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.40A 4P, MCB.
OUTGOINGS : 6 Nos. 25A 4P, MCB (10KA). TYPE-D, 3 Nos. 40A 4P, MCB (10KA).TYPE-D. Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b)Spare Space only for 2 Nos.25A 4P, MCB
OUTGOINGS : 2 Nos. 25A 4P, MCB (10KA).TYPE-D, 4 Nos. 40A 4P, MCB (10KA).TYPE-D. Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.40A 4P, MCB.
OUTGOINGS : 7 Nos. 25A 4P, MCB (10KA).TYPE-D, 2 Nos. 40A 4P, MCB (10KA).TYPE-D, 2 Nos. 63A 4P, MCCB (25KA).TYPE-D, 1 No. 100A 4P, MCCB (25KA). Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.25A 4P, MCB.
OUTGOINGS : 1 No. 25A 4P, MCB (10KA).TYPE-D, 5 Nos. 40A 4P, MCB (10KA).TYPE-D. Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.40A 4P, MCB.
OUTGOINGS : 6No. 25A 4P, MCB (10KA).TYPE-D, 2 Nos. 40A 4P, MCB (10KA).TYPE-D. Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.25A 4P, MCB.
OUTGOINGS : 1No. 25A 4P, MCB (10KA).TYPE-D, 4Nos. 40A 4P, MCB (10KA).TYPE-D. Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.40A 4P, MCB.
OUTGOINGS : 5Nos. 25A 4P, MCB (10KA).TYPE-D, 1No. 40A 4P, MCB (10KA).TYPE-D. Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.25A 4P, MCB.
OUTGOINGS : 5Nos. 25A 4P, MCB (10KA).TYPE-D, 1No. 40A 4P, MCB (10KA).TYPE-D. Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.40A 4P, MCB.
OUTGOINGS : 4Nos. 25A 4P, MCB (10KA).TYPE-D, 2Nos. 32A 4P, MCB (10KA).TYPE-D. 1No. 40A 4P, MCB (10KA).TYPE-D, 2Nos. 63A 4P, MCB (10KA).TYPE-D. 1No. 63A 4P, MCCB (25KA). Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.25A 4P, MCB.
OUTGOINGS : 3Nos. 25A 4P, MCB (10KA). 2Nos. 40A 4P, MCB (10KA). Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.40A 4P, MCB.
OUTGOINGS : 3 Nos. 20A 4P, MCB (10KA).TYPE-D, 2 Nos. 32A 4P, MCB (10KA).TYPE-D, 4 Nos. 40A 4P, MCB (10KA).TYPE-D, 1 No. 63A 4P, MCCB (10KA).TYPE-D. Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.25A 4P, MCB.
OUTGOINGS : 2 Nos. 25A 4P, MCB (10KA), 3 Nos. 32A 4P, MCB (10KA), 2 Nos. 40A 4P, MCB (10KA), 3 Nos. 63A 4P, MCCB (25KA) Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.25A 4P, MCB.
OUTGOINGS : 1 No. 20A 4P, MCB (10KA).TYPE-D, 5 Nos. 25A 4P, MCB (10KA).TYPE-D, 2 Nos. 32A 4P, MCB (10KA).TYPE-D, 3 Nos. 40A 4P, MCB (10KA).TYPE-D. Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.25A 4P, MCB..
OUTGOINGS : 11 Nos. 40A DP, MCB (10KA).TYPE-D, Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.25A DP, MCB..
OUTGOINGS : 5 Nos. 40A, 4P, MCB (10KA).TYPE-D, Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.40A 4P, MCB..
OUTGOINGS : 6 Nos. 25A, 4P, MCB (10KA).TYPE-D, 1 No. 40A, 4P, MCB (10KA).TYPE-D, 3 Nos. 63A, 4P, MCB (10KA).TYPE-D, 2 Nos. 63A, 4P, MCCB (25KA). Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.25A 4P, MCB.
OUTGOINGS : 2 Nos. 25A, 4P, MCB (10KA).TYPE-D, 4 Nos. 40A, 4P, MCB (10KA).TYPE-D, Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.40A 4P, MCB.
OUTGOINGS : 8 Nos. 25A, 4P, MCB (10KA).TYPE-D, 2 Nos. 63A, 4P, MCCB (10KA).TYPE-D, Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.25A 4P, MCB.
OUTGOINGS : 5 Nos. 40A, 4P, MCB (10KA).TYPE-D, Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.40A 4P, MCB.
OUTGOINGS : 1 No. 20A, 4P, MCB (10KA).TYPE-D, 5 Nos. 25A, 4P, MCB (10KA).TYPE-D, 2 Nos. 40A, 4P, MCB (10KA).TYPE-D. Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.40A 4P, MCB.
OUTGOINGS : 4 Nos. 25A, 4P, MCB (10KA).TYPE-D, 1 No. 40A, 4P, MCB (10KA).TYPE-D, Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.25A 4P, MCB.
OUTGOINGS : 8 Nos. 63A, 4P, MCCB (25KA lcs). Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.63A 4P, MCCB.
OUTGOINGS : 11 Nos. 25A, 4P, MCB (10KA ).TYPE-D 2 Nos. 40A, 4P, MCB (10KA ).TYPE-D Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.25A 4P, MCB.
OUTGOINGS : 4 Nos. 40A, 4P, MCB (10KA ).TYPE-D Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.40A 4P, MCB.
OUTGOINGS : 4 Nos. 25A, 4P, MCB (10KA ).TYPE-D 1 No. 40A, 4P, MCB (10KA ).TYPE-D Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.25A 4P, MCB.
OUTGOINGS : 4 Nos. 40A, 4P, MCB (10KA ).TYPE-D Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.40A 4P, MCB.
OUTGOINGS : 6 Nos. 25A, 4P, MCB (10KA ).TYPE-D 3 Nos. 40A, 4P, MCB (10KA ).TYPE-D Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.25A 4P, MCB.
OUTGOINGS : 1 No. 25A, 4P, MCB (10KA ).TYPE-D 5 Nos. 40A, 4P, MCB (10KA ).TYPE-D Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.40A 4P, MCB.
OUTGOINGS : 1 No. 16A, 4P, MCB (10KA ).TYPE-D 3 Nos. 25A, 4P, MCB (10KA ).TYPE-D 3 Nos. 40A, 4P, MCB (10KA ).TYPE-D Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.25A 4P, MCB.
OUTGOINGS : 4 No. 40A, 4P, MCB (10KA ).TYPE-D 1 Nos. 63A, 4P, MCB (10KA ).TYPE-D Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.40A 4P, MCB.
OUTGOINGS : 4 Nos. 25A, 4P, MCB (10KA ).TYPE-D 2 Nos. 40A, 4P, MCB (10KA ).TYPE-D 2 Nos. 63A, 4P, MCCB (10KA ). Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos.25A 4P, MCB.
OUTGOINGS : 4 Nos. 40A, 4P, MCB (10KA ).TYPE-D Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos. 40A 4P, MCB.
OUTGOINGS : 3 Nos. 25A, 4P, MCB (10KA ).TYPE-D 2 Nos. 40A, 4P, MCB (10KA ).TYPE-D 1 Nos. 63A, 4P, MCCB (25KA (lcs) ) Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos. 25A 4P, MCB.
OUTGOINGS : 4 Nos. 40A, 4P, MCB (10KA ).TYPE-D Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos. 40A 4P, MCB.
OUTGOINGS : 5 Nos. 25A, 4P, MCB (10KA ).TYPE-D 4 Nos. 40A, 4P, MCB (10KA ).TYPE-D 1 No. 63A, 4P, MCCB (25KA (lcs)) Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos. 25A 4P, MCB.
OUTGOINGS : 6 Nos. 40A, 4P, MCB (10KA ).TYPE-D Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos. 40A 4P, MCB.
OUTGOINGS : 3 Nos. 25A, 4P, MCB (10KA ).TYPE-D 4 Nos. 40A, 4P, MCB (10KA ).TYPE-D Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos. 25A 4P, MCB.
OUTGOINGS : 1 Nos. 25A, 4P, MCB (10KA ).TYPE-D 4 Nos. 40A, 4P, MCB (10KA ).TYPE-D Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos. 40A 4P, MCB.
OUTGOINGS : 2 Nos. 63A, 4P, MCCB (25KA (lcs)) 1No. 63A, DP, MCB (10KA ).TYPE-D Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos. 63A DP, MCB. (c) Spare Space only for 1 Nos. 63A 4P, MCCB.
OUTGOINGS : 2 Nos. 40A, 4P, MCCB (25KA (lcs)) 1No. 63A, DP, MCB (10KA ).TYPE-D Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos. 63A DP, MCB. (c) Spare Space only for 1 Nos. 63A 4P, MCCB.
OUTGOINGS : 1 Nos. 40A, 4P, MCCB (25KA (lcs)) 1 No. 40A, DP, MCB (10KA ).TYPE-D Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos. 40A DP, MCB. (c) Spare Space only for 1 Nos. 63A 4P, MCCB.
OUTGOINGS : 2 Nos. 25A, 4P, MCB (10KA ).TYPE-D 2 Nos. 40A, 4P, MCB (10KA ).TYPE-D 16 Nos. 16A, DP, RCBO (100mA ) 15 Nos. 25A, DP, RCBO (100mA ) 2 Nos. 16A, DP, MCB (10KA ).TYPE-D 2 Nos. 25A, DP, MCB (10KA ).TYPE-D 2 Nos. 32A, DP, MCB (10KA ) Note :- (a) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreader Terminals Links for all outgoing MCCB for cable connection. (b) Spare Space only for 2 Nos. 40A DP, MCB. (c) Spare Space only for 1 Nos. 63A 4P, MCCB.
Refrifgerator electric driven, single phase, capacity 300/310 litres, frost free, AC, 230 volts all as specified of approved make as directed by GE .
Refrifgerator electric driven, single phase capacity 180 litres, frost free AC, 230 volts all as specified of approved make as directed by GE .
Water cooler, electric driven, single phase, 230 volts AC, having storage capacity 80 Ltr and cooling capacity 40 ltr per hour and connecting to existing water supply line with G.I. pipe of suitable dia complete all as specified of approved make as directed by GE.
Water cooler, electric driven, single phase, 230 volts AC, having storage capacity 180 Ltr and cooling capacity 150 ltr per hour and connecting to existing water supply line with G.I. pipe of suitable dia complete all as specified of approved make as directed by GE.
Water cooler, electric driven, single phase, 230 volts AC, having storage capacity 120 Ltr and cooling capacity 60 ltr per hour and connecting to existing water supply line with G.I. pipe of suitable dia complete all as specified of approved make as directed by GE.
Deep freezer, hard top, 320 ltr capacity, double door, AC 230 volts complete all as specified of approved make as directed by GE.
Voltage stablizers, auto operation, single phase,naturally air cooled, indoor type, designed for input voltage variation 170 to 250 v and out put stablized 230v with accuracy of +/- 2.5%, of capacity 1 KVA, connecting to existing electric point and equipment complete all as specified of approved make as decided by GE.
Voltage stablizers, auto operation, single phase,naturally air cooled, indoor type, designed for input voltage variation 170 to 250 v and out put stablized 230v with accuracy of +/- 2.5%, of capacity 2 KVA, connecting to existing electric point and equipment complete all as specified of approved make as decided by GE.
Voltage stablizers, auto operation, single phase,naturally air cooled, indoor type, designed for input voltage variation 170 to 250 v and out put stablized 230v with accuracy of +/- 2.5%, of capacity 3 KVA, connecting to existing electric point and equipment complete all as specified of approved make as decided by GE.
Voltage stablizers, auto operation, single phase,naturally air cooled, indoor type, designed for input voltage variation 170 to 250 v and out put stablized 230v with accuracy of +/- 2.5%, of capacity 5 KVA, connecting to existing electric point and equipment complete all as specified of approved make as decided by GE.
Split type air conditioner 1.5 Ton capacity, single phase, air cooled complete in all respects
Total Amount of Sch 'A' Part - III (Internal Water Supply)
Total Amount of Sch 'A' Part - IV (Plumbing Works)
Total Amount of Sch 'A' Part - V (Site clearnace, Terrace cutting and Earth Work for basement & services)
Total Amount of Sch 'A' Part - VI (Sewage Disposal Work)
Total Amount of Sch 'A' Part - VII (Area Drainage Work)
Total Amount of Sch 'A' Part - VIII (Protective Work)
Total Amount of Sch 'A' Part - IX (Road, Path, Culvert and Hard Standing Work)
Total Amount of Sch 'A' Part - X (Security Fencing, Boundary Wall 7 Gate)
Total Amount of Sch 'A' Part - XI (Basket Ball, Foot Ball and Volley Ball Ground)
Total Amount of Sch 'A' Part - XII (Sec A) (External Electrification)
PART- XII(SEC-B) : LIST OF WORKS AND PRICES FOR EXTERNAL ELECTRIFICATION Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Testing and commissioning of existing 1.1 KV XLPE insulated, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor laid in trenches or ducts or passing through road crossings, pipes, fixed on wall/poles of size 3-½ core x 35 sqmm complete all as specified & directed.
Testing and commissioning of existing 1.1 KV XLPE insulated, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor laid in trenches or ducts or passing through road crossings, pipes, fixed on wall/poles of size 3-½ core x 50 sqmm complete all as specified & directed.
Testing and commissioning of existing 1.1 KV XLPE insulated, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor laid in trenches or ducts or passing through road crossings, pipes, fixed on wall/poles of size 3-½ core x 70 sqmm complete all as specified & directed.
Testing and commissioning of existing 1.1 KV XLPE insulated, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor laid in trenches or ducts or passing through road crossings, pipes, fixed on wall/poles of size 3-½ core x 120 sqmm complete all as specified & directed.
Testing and commissioning of existing 1.1 KV XLPE insulated, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor laid in trenches or ducts or passing through road crossings, pipes, fixed on wall/poles of size 3-½ core x 185 sqmm complete all as specified & directed.
Testing and commissioning of existing 1.1 KV XLPE insulated, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor laid in trenches or ducts or passing through road crossings, pipes, fixed on wall/poles of size 3-½ core x 240 sqmm complete all as specified & directed.
Testing and commissioning of existing 1.1 KV XLPE insulated, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor laid in trenches or ducts or passing through road crossings, pipes, fixed on wall/poles of size 3-½ core x 300 sqmm complete all as specified & directed.
Testing and commissioning of existing 1.1 KV XLPE insulated, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor laid in trenches or ducts or passing through road crossings, pipes, fixed on wall/poles of size 3-½ core x 400 sqmm complete all as specified & directed.
Testing and commissioning of existing 1.1 KV XLPE insulated, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor laid in trenches or ducts or passing through road crossings, pipes, fixed on wall/poles of size 3.5 core x 630 sqmm complete all as specified & directed.
Supplying, installing, testing and commissioning in correct alignment position, effecting proper connections, of continuous rating 500KVA outdoor type, oil filled, off load tap changer, step down transformer with the following specifications conforming to IS-2026 (Part-I to III) No load voltage Ratio : 11/0.433 KV No. of phases / Freq. : 3 Phase/50 Hz. Type : Core type, double copper wound Cooling : ONAN Vector Group : DYN 11 Temperature rise (Oil winding) : 50/55 Deg. Taps Changer :- OFF LOAD TYPE Taps on HV for HV Variation : -7.5% to +7.5% in : steps of 2.5% each (off circuit type) Termination Box (HV) : Air filled cable box suitable for 11KV 3x95 Sq.mm. XLPE cables. Termination box (LV) : Air filled cable box suitable for 1.1KV 2 run of 3.5x300 sq.mm. Al. Cond. XLPE Cable, PVC insulated . The transformer shall be supplied with following fittings: (a) Oil Conservator with drain valve. (b) Magnetic oil level indicator. (c) Dehydrating Silica gel breather with oil seal.
(d) First filling of filtered oil as per IS-335 including make up fill during installation of transformer plus 10% extra oil. (e) Off circuit switch. (f) Lifting lugs (g) Earthing terminals - 2 Nos. for body earthing and one additional for neutral for broughtout on a bushing. (h) Pocket Thermometer. (i) Air release hole with plug (j) Top filter valve - 1 No. (k) Radiator with top and bottom shut off valves. (l) Inspection cover. (m) 100mm dial magnetic oil level gauge with max pointer and low level alarm contacts. (n) Rating and Diagram plate. (o) 4 Nos Bi-directional Plain / Flanged Rollers. (p) 150mm dia winding temperature indicator with max pointer. (q) 150mm dia oil temperature indicator with max pointer. (r) Disconnecting facility for HV cable box. (s) Jacking lugs (t) Bottom drain cum filter valve
Supply, installation, testing, commissioning main LT feeder pillar-5 of following sizes and fabricated out of 3.15 mm thick CRCA sheet metal enclosed, outdoor type feeder pillar construction, having cubicle compartmentised type design distribution Feeder pillar with water proof dust and vermin proof hinged and lockable doors including rain protection cover on top and complete with interconnections, with copper bus bar/PVC insulated copper conductor unsheathed cable of suitable size for incoming and outgoing ACB/MCB/MCCB etc, tapes, bonding to earth and power coated painting complete as required and as per technical specification. The LT feeder pillar shall consist of ACB as incoming and MCCB/MCB as outgoing. Note: This panel shall be a FRONT and REAR operated, withcable entry from the bottom. The fault with standing capacity shall be 25 KA. Earth bus shall be part of the Main LT Feeder Pillar.Degree of protection of IP-57 INCOMING One number 800 Amps, 4 pole ACB, MDO micro processor (with O/L, S/C, INST E/F release at 50 KA (Ics) INDICATING PANEL The Indicating panel of incoming panel shall be provided with thefollowings : (a) Intelligent panel meter-Quasar (96mm square) covering 25 electric parameters with RS 485 port. (b) 3 number phase indicating lamp, each lamp shall have one toggle switch back up with HRC fuses. (c) Red/Green ON/OFF indicating lights for incoming and outgoing ACBS/MCCBs..
BUS BARS 1 Set of 1000Amps TPN Copper Bus bars of suitable length and of suitable cross section. Bus bar shall be insulated by heat shrinkable sleaves & clip on shrouds for joints. Bus bar shall be designed to with stand a fault level of 25 KA at 433 volts. OUTGOING 2 Nos. of 100 Amps TP+IN, MCCB of 25KA service breaking capacity and 100Amp (Adjustable thermal & adjustable magnetic setting) trip setting and heavy duty solid Isolating Neutral link as required and heavy duty solid Isolating Neutral link. 2 Nos. of 200 Amps TP+IN, MCCB of 35KA service breaking capacity and 200Amp (Adjustable thermal & adjustable magnetic setting) trip setting and heavy duty solid Isolating Neutral link as required and heavy duty solid Isolating Neutral link. (i) MCCB, 04 pole, 10 KA (Ics), 25 Amp, 415 volts-01 No. (ii) MCCB, 04 pole, 10 KA (Ics), 40 Amp, 415 volts - 04 Nos. (iii) MCCB, 04 pole, 15 KA (Ics), 63 Amp, 415 volts - 02 Nos.. Spare Space only for 2 Nos-20A DP MCB, 2 Nos-25A 4P MCB & 2 Nos 63A/200A TP MCCB
Note :- (i) The LT Feeder Pillar shall be as shown in schematic drawing & GA drawing. (ii) All MCCB's shall be provided with rotary operated mechanism and pad locking arrangement and incoming ACB shall have ON & OFF lamp indication (iii) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreaders Copper Terminal links (H/D) for All Outgoing MCCB For Cable Connection. (iv) Engraved Al-Plates shall be provided for each Feeder. (v) Main feeder pillar shall be treated with all anti corrosive process before painted and the shade colour of paint shall be as approved. (vi) PCC work in foundation as recommended by manufacturer.
(d) 3 Nos. phase indicating lamps; each lamp shall have one toggle switch backed up with HRC fuse. (e) Space for Electronic Energy meter of suitable capacity & CT's (f) Red/Green ON/OFF indicating lights for incomer MCCB & ON indication lights for outgoing MCCBS/MCBs. BUS BAR 1 Set of 300Amps TPN Copper Bus Bars of suitable length and of suitable cross section. Bus bar shall be insulated by heat shrinkable sleaves & clip on shrouds for joints. Bus bar shall be designed to with stand a fault level of 25 KA at 415 volts. OUTGOING 4 Nos. of 63 Amps, TP+IN, MCCB of 10KA and 63 Amp (Fixed thermal & fixed magnetic setting) trip setting and heavy duty solid Isolating Neutral link. 3 Nos, 40 Amps, 04 pole, MCCB, 10 KA (Ics). Notes: (i) The LT Feeder Pillar shall be as shown in schematic drawing & GA drawing. (ii) All MCCB's shall be provided with rotary operated mechanism and pad locking arrangement and incoming MCCB shall have ON, lamp indication. (iii) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreaders Copper Terminal links (H/D) for All Outgoing MCCB For Cable Connection. (iv) Engraved Al-Plates shall be provided for each Feeder. (v) Feeder pillar shall be treated with all anti corrosive process before painted and the shade colour of paint shall be set approved. (vi) PCC work in foundation as recommended by manufacturers
BUS BAR :1 Set of 800Amps TPN Copper Bus Bars of suitable length and of suitable cross section. Bus bar shall be insulated by heat shrinkable sleaves & clip on shrouds for joints. Bus bar shall be designed to with stand a fault level of 25 KA at 415 volts. OUTGOING 1 No. of 63 Amps, TP+IN, MCCB of 25 KA (Ics) and 63 Amp (Fixed thermal & fixed magnetic setting) trip setting and heavy duty solid Isolating Neutral link. 4 No. of 100 Amps, TP+IN, MCCB of 25 KA (Ics) and 100 Amp (Adjustable thermal & fixed magnetic setting) trip setting and heavy duty solid Isolating Neutral link. 2 Nos. of 125 Amps, TP+IN, MCCB of 25 KA (Ics) and 125 Amp (Adjustable thermal & fixed magnetic setting) trip setting and heavy duty solid Isolating Neutral link. 5 Nos MCCB, 40 Amp, 4 Pole, 10KA (Ics) Notes: (i) The LT Feeder Pillar shall be as shown in schematic drawing & GA drawing. (ii) All MCCB's shall be provided with rotary operated mechanism and pad locking arrangement and incoming MCCB shall have ON, lamp indication. (iii) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreaders Copper Terminal links (H/D) for All Outgoing MCCB For Cable Connection. (iv) Engraved Al-Plates shall be provided for each Feeder. (v) Feeder pillar shall be treated with all anti corrosive process before painted and the shade colour of paint shall be set approved. (vi) PCC work in foundation as recommended by manufacturers.
(e) Space for Electronic En meter of suitable capacity & CT's (f) Red/ Green ON/OFF indicating lights for incomer MCCB & ON indication lights for outgoing MCCBS/MCBs. BUS BAR :1 Set of 200Amps TPN Copper Bus Bars of suitable length and of suitable cross section. Bus bar shall be insulated by heat shrinkable sleaves & clip on shrouds for joints. Bus bar shall be designed to with stand a fault level of 25 KA at 415 volts. OUTGOING 4 Nos. of 63 Amps, TP+IN, MCCB of 15 KA (lcs) and 63 Amp (Fixed thermal & fixed magnetic setting) trip setting and heavy duty solid Isolating Neutral link. 1No-6A,DP, MCB 10KA Spare Space only for 1 No-25 Amps, DP, MCB & 1 No 63A TP MCCB. Notes: (i) The LT Feeder Pillar shall be as shown in schematic drawing & GA drawing. (ii) All MCCB's shall be provided with rotary operated mechanism and pad locking arrangement and incoming MCCB shall have ON, lamp indication (iii) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreaders Copper Terminal links (H/D) for All Outgoing MCCB For Cable Connection. (iv) Engraved Al-Plates shall be provided for each Feeder. (v) Feeder pillar shall be treated with all anti corrosive process before painted and the shade colour of paint shall be set approved. (vi) PCC work in foundation as recommended by manufacturers.
BUS BAR: 1 Set of 300Amps TPN Copper Bus Bars of suitable length and of suitable cross section. Bus bar shall be insulated by heat shrinkable sleaves & clip on shrouds for joints. Bus bar shall be designed to with stand a fault level of 25 KA at 415 volts OUTGOING 4 Nos. of 100 Amps, TP+IN, MCCB of 25 KA (Ics) and 100 Amp (Adjustable thermal & fixed magnetic setting) trip setting and heavy duty solid Isolating Neutral link. 2 Nos, 25 Amps, 04 pole, 16 KA (Ics), MCCB 1 No - 40 Amps, 04 pole, MCCB, 10 KA (Ics) Spare Space only for 2 Nos-40 Amps, 04 pole, MCCB Notes: (i) The LT Feeder Pillar shall be as shown in schematic drawing & GA drawing. (ii) All MCCB's shall be provided with rotary operated mechanism and pad locking arrangement and incoming MCCB shall have ON, lamp indication. (iii) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreaders Copper Terminal links (H/D) for All Outgoing MCCB For Cable Connection. (iv) Engraved Al-Plates shall be provided for each Feeder. (v) Feeder pillar shall be treated with all anti corrosive process before painted and the shade colour of paint shall be set approved. (vi) PCC work in foundation as recommended by manufacturers.
(e) Space for Electronic Energy meter of suitable capacity & CT's (f) Red/ Green ON/OFF indicating lights for incomer MCCB & ON in dication lights for outgoing MCCBS/MCBs. BUS BAR: 1 Set of 300Amps TPN Copper Bus Bars of suitable length and of suitable cross section. Bus bar shall be insulated by heat shrinkable sleaves & clip on shrouds for joints. Bus bar shall be designed to with stand a fault level of 25 KA at 415 volts. OUTGOING 4 Nos. of 63 Amaps, TP+IN, MCCB of 10 KA (Ics) and 63 Amp (Fixed thermal & fixed magnetic setting) trip setting and heavy duty solid Isolating Neutral link. 1 No. of 100 Amps, TP+IN, MCCB of 25 KA (Ics) and 100 Amp (Adjustable thermal & fixed magnetic setting) trip setting and heavy duty solid Isolating Neutral link.(for S/L) Spare Space only for 2 No 63A TP MCCB. Notes: (i) The LT Feeder Pillar shall be as shown in schematic drawing & GA drawing. (ii) All MCCB's shall be provided with rotary operated mechanism and pad locking arrangement and incoming MCCB shall have ON,lamp indication. (iii) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreaders Copper Terminal links (H/D) for All Outgoing MCCB For Cable Connection. (iv) Engraved Al-Plates shall be provided for each Feeder. (v) Feeder pillar shall be treated with all anti corrosive process before painted and the shade colour of paint shall be set approved. (vi) PCC work in foundation as recommended by manufacturers.
(e) Space for Electronic Energy meter of suitable capacity & CT's (f) Red/Green ON/OFF indicating lights for incomer MCCB & ON indication lights for outgoing MCCBS/MCBs. BUS BAR 1 Set of 200Amps TPN Copper Bus Bars of suitable length and of sulable cross section. Bus bar shall be insulated by heat shrinkable seaves & clip on shrouds for joints. Bus bar shall be designed to with stand a fault level of 25 KA at 415 volts. OUTGOING 03 Nos-40 Amps, 04 pole, 10 KA (Ics), MCCB. Spare Space only for 4 Nos-25A DP MCB, 1No-40A 4P MCB & 1 No 63A TP MCCB. Notes: (i) The LT Feeder Pillar shall be as shown in schematic drawing & GA drawing. (ii) All MCCB's shall be provided with rotary operated mechanism and pad locking arrangement and incoming MCCB shall have ON, lamp indication. (iii) All MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreaders Copper Terminal links (H/D) for All Outgoing MCCB For Cable Connection (iv) Engraved Al-Plates shall be provided for each Feeder. (v) Feeder pillar shall be treated with all anti corrosive process before painted and the shade colour of paint shall be set approved. (vi) PCC work in foundation as recommended by manufacturers.
Supplying, installation, testing and commissioning of L.T. panel for main power house fully compartmentalized cubical type fabricated out of 2mm thick CRCA sheet, floor/wall mounted totally enclosed, powder coated painting, painted after seven tank process, extensible on both sides, switch board suitable for use on 1 Phase/3-phase, 50 Hz system having required fault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/Sqmm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required. INCOMING 1 No x 1600 amps,4P, ACB MDO, Microprocessor (with O/L,S/C.INST. EF) Releases of 50 kA (Ics) for incommer -1 1 No x 1600 amps,4P, ACB MDO, Microprocessor (with O/L,S/C,INST. E/F) Releases of 50 kA (Ics) for incommer-2 1 No x 1600 amps,4P, ACB MDO, Microprocessor (with O/L,S/C,INST. EF) Releases of 50 kA (Ics) for Bus Coupler INDICATING PANEL (a) The Indicating panel of each incomer ACB shall be provided with the following: (b) Provide L&T make Intelligent panel meter- Quasar ( 96mm x 96mm) covering 25 electrical parameters with RS 485 port for all incomming and outgoing ACBs. (c) 3 Nos. phase indicating lamps; each lamp shall have one toggle switch backed up with HRC fuse. (d) Space for Electronic Energy meter of suitable capacity & CT's (e) Red/ Green ON / OFF indicating lights for both incomers and Bus coupler ACBS & ON indication lights for outgoing ACBs /MCCBs (f) Mechanically interlocking shall be provided with two Incomers and the Bus coupler ACBs
BUS BARS: 1 Set of 2000Amps TPN Copper Bus bars of suitable length and of suitable cross section. Bus bar shall be insulated by heat shrinkable sleeves & clip on shrouds for joints. Bus bar shall be designed to with stand a fault level of 50 KA at 433 volts. OUTGOING (i) 1 No- 1250 Amps, 3 pole and neutral, ACB, MDO, Microprocessor (with O/L,S/C,INST. E/F) Releases of 50 KA (Ics) (ii) 2 Nos. of 100 Amps, 3 pole and neutral, MCCB of 25 KA (Ics) service breaking capacity and 100 Amp (Adjustable thermal & adjustable magnetic setting)) trip setting as required. (iii) 01 No - 630 Amps, 04 pole, MCCB, 35 KA (Ics) micro processor type. (iv) 01 No 400 Amps, 04 pole, MCCB, 35 KA (Ics), micro processor type. (v) 01 No - 300 Amps, 04 pole, MCCB, 25 KA (Ics), micro processor type. (vi) 01 No - 200 Amps, 04 pole, MCCB, 25 KA (Ics), micro processor type. Notes: (1) The LT Panel shall be as shown in schematic drawing & GA drawing. (ii) All ACB/ MCCB's shall be provided with rotary operated mechanism. (iii) All ACB / MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreaders Copper Terminal links (H/D) for All Outgoing AC B/MCCB For Cable Connection., REAR (iv) This panel shall be a FRONT and REAR operated, with cable entry from the Top and bottom. The fault with standing capacity shall be 50 KA. Earth bus shall be part of the LT panel). (v) Engraved Al-Plates shall be provided for each Feeder. (vi) LT panel shall be treated with all anti corrosive process before painted and the shade colour of paint shall be set approved. (vii) PCC work in foundation as recommended by manufacturers.
Supplying, installation, testing and commissioning of L.T. panel for main sub station room fully compartmentalized cubical type fabricated out of 2mm thick CRCA sheet, floor/wall mounted totally enclosed powder coated painting, painted after seven tank process, extensible on both sides, switch board suitable for use on 1 Phase/3-phase, 50 Hz system having required ault capacity, housed with incoming and outgoing, copper bus bars with current rating of 0.8 Amp/Sqmm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required. INCOMING: 1 No x 800 amps,4P, ACB,MDO, Microprocessor (with O/L,S/C,INST. E/F) Releases of 50 kA (Ics) for incomer INDICATING PANEL (a) The Indicating panel of each incomer ACB shall be provided with the following: (b) Provide L&T make Intelligent panel meter- Quasar (96mm x 96 mm) covering 25 electrical parameters with RS 485 port for all incomming and outgoing ACBs. (c) 3 Nos. phase indicating lamps; each lamp shall have one toggleswitch backed up with HRC fuse. (d) Space for Electronic Energy meter of suitable capacity & CT's (e) Red/ Green ON/OFF indicating lights for both incomers and Bus coupler ACBS & ON indication lights for outgoing ACBS /MCCBs BUS BARS: 1 Set of 1000Amps TPN Copper Bus bars of suitable length and of suitable cross section. Bus bar shall be insulated by heat shrinkable sleaves & clip on shrouds for joints. Bus bar shall be designed to with stand a fault level of 50 KA at 430 volts
OUTGOING 3 Nos. of 100 Amps ,4P, MCCB of 25 KA (Ics) service breaking capacity and 100 Amp (Adjustable thermal & adjustable magnetic setting) trip setting as required. 1 No. of 160 Amps 4P, MCCB of 25 KA (Ics) service breaking capacity and 160 Amp (Adjustable thermal & adjustable magnetic setting) trip setting as required. 1 No. of 200 Amps 4P, MCCB of 25 KA (Ics) service breaking capacity and 200 Amp (Adjustable thermal & adjustable magnetic setting) trip setting as required. 1 No. of 250 Amps ,4P, MCCB of 25 KA (Ics) service breaking capacity and 250 Amp (Adjustable thermal & adjustable magnetic setting) trip setting as required. Notes: (i) The LT Panel shall be as shown in schematic drawing & GA drawing. (ii) All ACB/ MCCB's shall be provided with rotary operated mechanism. (iii) All ACB / MCCB's shall have heavy duty solid neutral link & 3 Nos. Spreaders Copper Terminal links (H/D) for All Outgoing AC B/MCCB For Cable Connection., (iv) This panel shall be a FRONT and REAR operated, with cable entry from the Top and bottom. The fault with standing capacity shall be 50 KA. Earth bus shall be part of the LT panel). (v) Engraved Al-Plates shall be provided for each Feeder. (vi) LT panel shall be treated with all anti corrosive process before painted and the shade colour of paint shall be set approved. (vii) PCC work in foundation as recommended by manufacturers.
Rubber insulating corrugated matt of size 2000mm x 1000mm, 15mm thickness suitable for 1100 volts grade conforming to IS complete.
Sch 'A' Part - XIII (EXTERNAL WATER SUPPLY AND SOLAR WATER HEATING SYSTEM) Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Ductile iron pressure pipes with spigot and socketed type, centrifugally cast, K-9 (as per IS-8329), in any length, laid in trenches complete all as specified, for
(a) 80mm nominal bore
(b) 100mm nominal bore Note : Earth work, fittings and joints shall be measured and paid for separately.
Rubber gasket joint for Spigot and Socket pipes and fittings complete all as specified, for
(a) 80mm bore
(b) 100mm bore
Lead joint for Spigot and Socket pipes and fittings complete all as specified, for
(a) 80mm bore
(b) 100mm bore
(c) 150mm bore
Jointing with rubber or fibre board gasket for Flanged Pipes and fitting incl nuts, bolts, washers etc complete all as specified, for
(a) 100mm bore
(b) 150mm bore
Tubes, 'medium grade', galvanised iron, with all fittings and fixed complete to walls and ceilings or laid in floors complete all as specified, of following bores:-
(a) 20mm nominal bore
(b) 25mm nominal bore
(c) 40mm nominal bore
(d) 50mm nominal bore
(e) 80mm nominal bore
(f) 100mm nominal bore
(g) 150mm nominal bore
Gun metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed complete, for pipes of :-
(a) 25mm bore
(b) 32mm bore
(c) 40mm bore
(d) 50mm bore
Construction of masonry valve pit of size 1050 x 1050 x 1200mm (internal dimensions) including excavation and earth work in any type of soil, PCC 1:4:8, type D-2 in foundation, brick masonry in CM 1:4, 15mm thick plaster in CM 1:6 and flush pointing the hidden surfaces as the work proceeds, angle iron 35 x 35 x 6mm frame, MS sheet 10 SWG in cover including painting, locking arrangement etc., complete all as specified and shown on drawing.
All as per Srl item 307 above but of size 750x750x750mm
Centrifugally Cast (Spun) ductile iron pressure pipes with socket & spigot ends confirming to IS: 8329/2000 for water supply lines (external works) in standard lengths classification K 7 suitable for Push-on-joint (Rubber Gasket D jointing) with cement mortar lining inside the pipes and outside zinc coating as per IS: 8329/2000, laid in trenches complete all as specified, of following bores:-
(a) 100mm bore
(b) 150mm bore Note : Earth work, fittings and joints shall be measured and paid for separately.
D.I specials of Class K-12 as per IS: 9523 for pipes upto 150mm bore complete all as specified.
Rubber gasket SBR (Tyton) joint for Spigot and Socket pipes and fittings complete all as specified, for
(a) 100mm bore
(b) 150mm bore
C.I. double acting air valve of approved quality with bolts, nuts, rubber insertions etc. complete (the tail pieces, tapers etc. if required will be paid separately) suitable for 150mm bore and 80mm dia inlet connection complete all as specified.
Butterfly valve class-I, P.N. 1.6, conforming to IS 13095-1991 complete with flanges, bolts, nuts, gasket etc. as per specifications complete in all respect hydraulically tested to 20kg/sqcm, suitable for
(a) 80mm bore
(b) 100mm bore
(c) 150mm bore.
Cast iron double flanged horizontal type with gunmetal seat non-return valve confirming to class - I of IS : 5312 including nuts, bolts, 1.5 mm thick compressed asbestos gasket including painting complete all as specified, for
(a) 80mm bore.
(b) 150mm bore.
Supply, Installation, testing & commissioning of horizontal monobloc pumping set with C.I. body and bronze impeller, shaft of carbon steel and C.I. Base & head, mechanical seal, connected to a TEFC induction motor suitable for 400/440 volts, 3 phase, 50 cycles, A.C. supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads as required, M.S fabricated base plate, suction and dilevery pipe including headers, bolted to cement concrete foundations complete. Recycle Water Supply Capacity/Flow Rate - 800 LPM, Head-40m, Capacity not less than 7.5 WHP complete
Supply, Installation, testing & commissioning of horizontal monobloc pumping set with C.I. body and bronze impeller, shaft of carbon steel and C.I. Base & head, mechanical seal, connected to a TEFC induction motor suitable for 400/440 volts, 3 phase 50 cycles A.C. supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads as required, M.S fabricated base plate, section and dilevery pipe including headers, bolted to cement concrete foundations complete. Recycle Water Supply Capacity/Flow Rate - 200 LPM, Head-20m, Capacity not less than 2 WHP complete.
Supplying, installing, testing and commissioning of Solar water heating system at 60o/70oC consisting of solar Flat Plate collectors (Cu-Cu) with ultrasonic welded fins including structural supporting frames, Heat Exchanger Stainless steel-304 hot water storage tank of 3mm thickness (minimum) of required capacity with installation over MS/Civil supports, electric panel for power back up, isolation valves, GI piping, insulation with aluminium cladding, on-line Pressure/Re-circulation pump and any other necessary works required to provide staisfactory functioning complete all as specified fixed on floor or roof with fixing arrangements as per manufactures instructions and connecting to cold water supply but excluding cold water tank and pipe line, for following capacities:-
(a) 200litres
(b) 300litres
(c) 500litres
(d) 1000litres
Providing orange colour safety foot rest of minimum 6mm thick plastic encapsulated as per IS:10910 on 12mm dia steel bar conforming to IS:1786 having minimum cross section 23mm x25mm and over all minimum length 263mm and width 165mm with minimum 112mm space between protruded legs having 2mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length 138mm as per standard drawing and suitable to withstand the bend test and chemical resistance test as per specifications and having manufacturer's permanent identification mark visible even after fixing, including fixing in manholes with 30x20x15cm cement concrete block 1:3:6, type C-1, using graded stone aggregate 20mm complete as per design. (for sewage disposal)
Supplying, fixing, testing and commissioning of Non-clog type Submersible single stage pump with bronze impellar, SS shaft suitable for solids handling upto 40 mm size, coupled to submersible including electric motor, panel and necessary cabling complete with pressure gauge on each pump outlet with low level cut off, level controller for automatic operation in the sump, pump capacity 7.5Lps (450 lpm) at 10 m head (for Sewage disposal and drainage disposal in Basement toilets) (One working + one stand by)
Puddle flanges fabricated out of 600mm long G.I. pipe welded around with 6mm thick MS plate and MS flange at one end of suitable size and properly fixed in RCC wall, slab etc of OHT/UGT etc, complete for following bore of pipes :-
(a) 65mm bore
(b) 80mm bore
(c) 100mm bore
(d) 150mm bore
Total Amount of Sch 'A' Part - XIV (Demolition of Buildings/ Structures)
PART- XV : LIST OF WORKS AND PRICES FOR SHADOWLESS, LANDSCAPE AND STREET LIGHTING SYSTEM SCHEDULE `A' PART-XV is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signified this fact only. Bidder shall insert their rates in Green field under Col-6.
1X36W fluorescent tube rod/ light/ lamp suitable for existing FTL Fitting complete all as specified and directed. Make :- Crompton /Bajaj /Havells /Phillips
4X18W fluorescent tube rod/ light/ lamp suitable for existing tube light Fitting complete all as specified and directed. Make :- Crompton /Bajaj /Havells /Phillips
2X36W CFL light/ lamp suitable for existing tube light Fitting complete all as specified and directed. Make :- Crompton /Bajaj /Havells /Phillips
Decorative Pole 8m with twin Filia bracket made out of G.I , primered and painted PU factory finish. The pipe should be of diameter 140mm with base plate dimension 300X300X20mm.The pipe shall have cross section thickness of 4.2 mm with tolereance +/- 5% . The column shall have extra 200mm below the ground level along with the base plate for hiding the nuts and bolts for aesthetic apperance and shall be provided with flush door at the bottom with proper strengthening to the cutout of the door opening. A junction/ looping box with Heavy duty 3 phase connector shall be suitable into the pole.
Decorative Pole 8m with single Filia bracket made out of G.I , primered and painted PU factory finish. The pipe should be of diameter 140mm with base plate dimension 300X300X20mm.The pipe shall have cross section thickness of 4.2 mm with tolereance +/- 5% . The column shall have extra 200mm below the ground level along with the base plate for hiding the nuts and bolts for aesthetic apperance and shall be provided with flush door at the bottom with proper strengthening to the cutout of the door opening. A junction/ looping box with Heavy duty 3 phase connector shall be suitable into the pole.
Supplying, laying, jointing and testing in trenches/ducts or fixed to wall/poles or passed through pipe, 1100 volts grade, armoured, heavy duty LT XLPE Cable with stranded aluminium conductor of nominal cross section area 50 Sqmm 3.5 Core, complete all as specified.
All as per Srl item 345 above but cross section area 16 Sqmm 4 core complete all as specified.
All as per Srl item 345 above but cross section area 25 Sqmm 4 core complete all as specified.
All as per Srl item 345 above but cross section area 10 Sqmm 4 Core complete all as specified.
All as per Srl item 345 above but cross section area 10 Sqmm 2 Core complete all as specified.
All as per Srl item 345 above but cross section area 6 Sqmm 2 Core complete all as specified.
LT feeder piller box, out door type, with canopy having slant of 600, water, dust and vermin proof, made of 14SWG CRCA sheet and angleiron 50x50x6mm frame, powder coated inside and out side having thickness 50 micron (min) in light gray shade or seisems gray shade, duly wired with copper wiring and having electronic grade copper bar. The panel shall be front and back openable with locking arrangement, painted in two coats with dray paint over one coat of red Oxide zinc chrome primer, mounted on angle iron 50x50x6mm legs grooted in PCC foundations, 100 Amp Copper bas bars, mounted on DMC insulators, bakelite terminal blocks for outgoing connections in the cable along and shall be consisting by providing of following accessories:-
(a) Copper bus bar chamber 200 Amp, TPN - 01 No. (b) Incoming MCCB, 100 Amp, 4 Pole and 25KA - 01 No. (c) Out going MCCB TP 63 Amp - 02 Nos. (d) Out going MCB SPN 40 Amp - 04 Nos. (e) Voltmeter 0 to 500 Volts square type - 01 Nos. (f) Phase indicating lamp - 01 Set of three. (g) Complete internal wiring of incoming, out going MCCB/MCB with suitable size of single core unseathed copper cable with lugs - 01 job.
LT feeder piller box, out door type, with canopy having slant of 600, water, dust and vermin proof, made of 14SWG CRCA sheet and angleiron 50x50x6mm frame, powder coated inside and out side having thickness 50 micron (min) in light gray shade or seisems gray shade, duly wired with copper wiring and having electronic grade copper bar. The panel shall be front and back openable with locking arrangement, painted in two coats with dray paint over one coat of red Oxide zinc chrome primer, mounted on angle iron 50x50x6mm legs grooted in PCC foundations, 100 Amp Copper bas bars, mounted on DMC insulators, bakelite terminal blocks for outgoing connections in the cable along and shall be consisting by providing of following accessories:-
(a) Copper bus bar of suitable size, 100 Amps colour coated with heat strinkable sleeves - 04 Nos. (b) Incoming MCCB, 63 Amp, 4 Pole and 25KA - 01 No. (c) Out going MCB SPN 40 Amp - 04 Nos. (d) Voltmeter 0 to 500 Volts square type - 01 Nos. (e) Phase indicating lamp - 01 Set of three. (f) Complete internal wiring of incoming, out going MCCB/MCB with suitable size of single core unseathed copper cable with lugs - 01 job.
Copper bus bar chamber, 4 strips, 100 Amp with CRCA sheet 1.6mm and MS angle Iron 45x45x6mm frame of size 1000x600x300mm size with front opening door having 1 incoming and 4 outgoing cable hole (20mm dia) with rubber bushes/glands including 4 Nos angle iron legs grouted in PCC foundation complete all as directed.
GI Pipe, light grade, 40mm dia for protection of cable at road/drain crossing etc. including all fittings, laid in trenches, under floor or ducts.
2X13W CFL light/ lamp suitable for existing tube light Fitting complete all as specified and directed. Make :- Crompton /Bajaj /Havells /Phillips
Decorative Pole 4m (ATG) made out of G.I , primered and painted PU factory finish. The pipe should be of diameter 114mm with base plate dimension 300X300X20mm.The pipe shall have cross section thickness of 4.2 mm with tolereance +/- 5% . The column shall have extra 200mm below the ground level along with the base plate for hiding the nuts and bolts for aesthetic apperance and shall be provided with flush door at the bottom with proper strengthening to the cutout of the door opening. A junction/ looping box with Heavy duty 3 phase connector shall be suited into the pole erected to truely vertical position complete all as specified.
2X18W CFL light/ lamp suitable for existing tube light Fitting complete all as specified and directed. Make :- Crompton /Bajaj /Havells /Phillips
Decorative Pole 6m (ATG) with "T" mounting bracket made out of G.I , primered and painted PU factory finish. The pipe should be of diameter 114mm with base plate dimension 300X300X20mm.The pipe shall have cross section thickness of 4.2 mm with tolereance +/- 5% . The column shall have extra 200mm below the ground level along with the base plate for hiding the nuts and bolts for aesthetic apperance and shall be provided with flush door at the bottom with proper strengthening to the cutout of the door opening. A junction/ looping box with Heavy duty 3 phase connector shall be suited into the pole erected to truely vertical position complete all as specified.
1X18W CFL light/ lamp suitable for existing tube light Fitting complete all as specified and directed. Make :- Crompton /Bajaj /Havells /Phillips
GI Nuts & bolts including washers of suitable size for fastening of GI perforated LT cable trays joints complete all as specified and directed.
Torch light 1x70w CDMT- the column is comprised of a cylinder of 2 m which is cadium plated and a light conductor of 3 m made of opaline acrylic. The Sealsafe® optical compartment (IP 66 according to IEC-EN 60598), fitted with an Aluminium reflector, situated at the bottom of the light conductor. At the top of the cylinder, another reflector, made from Aluminium, reflects the light towards the ground.The Impact resistance of PMMA is IK 08(according to IEC-EN 62262) and the empty weight of the luminaire should not be less than 57 Kgs.The lamp and the control gear - on a removable plate - are accessed via a hatch incl making connections and testing complete.
BLANK
BLANK
welding work on outer surfaces of two continuous 'C' class MS pipes of size 150mm bore dia to make functional & leak proof joints including testing on completion complete all as specified and directed.
MCB, SP, 6 Amp, 240 V, 'C' curve complete all as specified.
PCC 1:3:6, type C-2, using 40mm graded crushed stone aggregate for foundation filling and mass concrete of poles etc.
Dry sand cushioning to under ground cable, provided with a layer 8cms thick before laying the cable and 15cms thick after laying and stretching the cable complete all as specified.
Sub class 'B' bricks, well burnt, as in cable protection cover, laid dry, flat, over sand cushioning with width equal to the length of brick, transversally along the length the cable complete all as specified.
L T feeder piller box made out of CRCA sheet 3.15mm thick and 50x50x6mm angle iron base frame with 4 Nos legs, out door type, including & providing following accessories:- (a) Copper bus bar chamber 100 Amp, TPN - 01 No. (b) Incoming MCCB, 63 Amp, 4 Pole and 25KA (lcs) - 01 No. (c) Out going MCB SPN 40 Amp - 04 Nos. (d) Voltmeter 0 to 500 Volts square type - 01 Nos. (e) Phase indicating lamp - 01 Set of three. (f) Complete internal wiring of incoming, out going MCCB/MCB with suitable size of single core unseathed copper cable with lugs - 01 job.
EARTHING WORK FOR LIGHTNING, RECYCLE WATER SUPPLY, VARIOUS TREATMENT PLANTS, INCINERATOR, MECHANICAL, LAUNDRY AND AC.
Earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6.00mm thick burried directly in ground (earth plate not less than 2.25m deep below normal ground level)with top edge of the plate not less than 1.5m below normal ground level connected to and including GI earth wire 4.00 mm dia by means of steel bolts, nuts, check nuts and washers, PCC 1:2:4 type B-1 in pit, angle iron 25x25x3mm frame work with precast RCC 1:2:4 type B-1 cover reinforced with 8mm dia TMT bars @ 150mm C/C both ways and 12mm dia MS fabricated handle,light grade GI watering pipe 20mm bore with funnel, wire mesh and medium grade GI protection pipe 15mm bore upto 5m length for drawing in earth lead wire, salt, charcoal, including excavation and earth work in any type of soil, removal of surplus soil to a distance not exc. 50m complete all as shown in electrical plate No.3 of MES Schedule 2009 (Part-l) and connected to main control board all as specified including testing on completion.
All as per Srl item 373 above but GI earth strip 32x6mm without protection pipe
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or fixed to poles or any other indicated situation or on cable tray for loop earthing etc. as required with 20x3.15mm Galvanised iron strip.
All as per Srl item 375 above but G.I wire 4mm dia
Supplying, laying, jointing and testing in trenches/ducts or fixed to wall/poles or passed through pipe, 1100 volts grade, armoured, heavy duty LT XLPE Cable with stranded aluminium conductor of nominal cross section area 16 Sqmm 2 Core, complete all as specified.
Supplying, laying, jointing and testing in trenches/ducts or fixed to wall/poles or passed through pipe, 1100 volts grade, armoured, heavy duty LT XLPE Cable with stranded aluminium conductor of nominal cross section area 6 Sqmm 4 Core, complete all as specified.
RCC M-25 (design mix), using 20 mm graded crushed stone aggregate as in foundations, including rafts, footings, foundation beam; plinth beams; bases of columns, etc.; basement slabs, under-reamed piles and mass concrete, complete all as specified and as directed by Engr-in-Charge.
TMT mild steel bars, 16 mm dia and over, as in reinforcement, cut to length, bent to shape required including cranking, bending spirally or hooping for columns, hooking ends and binding with and including MS wire (annealed not less than 0.9mm dia) , complete all as specified and as directed by Engr-in-Charge.
All as per serial item No. 380 here in before but 10 mm dia.
All as per serial item No. 380 here in before but 8 mm dia.
Mild steel screw bolts (machine made) with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, 20mm dia x 600 mm, complete all as specified and directed.
Use and waste of formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams, sides and soffits (if any) of foundation and plinth beams; and similar work; vertical or to batter, to obtain rough finished flat surfaces of concrete complete all as specified and as directed.
PART- XVI : LIST OF WORKS AND PRICES FOR RECYCLE WATER SUPPLY Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
High density polyethylene pipes (HDPE) and fittings of pressure rating 10kg/sqcm PE 100 grade conforming to IS: 4984 including jointing, laid in trenches complete, for following bores :-
(a) 25mm bore
(b) 32mm bore
(c) 40mm bore
(d) 50mm bore
Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed, for pipes of :-
(a) 25mm bore
(b) 40mm bore
(c) 50mm bore
Construction of masonry valve pit of size 1050 x 1050 x 1200mm (internal dimensions) including excavation and earth work in any type of soil, PCC 1:4:8, type D-2 in foundation, type C-1, brick masonry in CM 1:4, 15mm thick plaster in CM 1:6 and flush pointing the hidden surfaces as the work proceeds, angle iron 35 x 35 x 6mm frame, MS sheet 10 SWG in cover including painting, locking arrangement etc., complete all as specified and shown on drawing.
All as per Srl item 395 above but of size 750x750x750mm
Reinforced concrete pipes, class NP2, laid and jointed complete with collars (for encasing of HDPE pipe), bore of pipe.
SFRC (Steel Fibre Reinforced Concrete) Cover and frame (Light duty LD-2.5 grade designation) 610x450mm internal diameter conforming to I.S 12592. (for Butterfly Valve chamber), complete all as specified.
Un plasticized (UPVC) class-III pipes and fittings of pressure rating 6 Kgs / cm2 conforming to IS: 4985 including jointing and laid in trenches complete, of following sizes :-
(a) 75mm outer dia
(b) 90mm outer dia
(c) 110mm outer dia
(d) 160mm outer dia
Puddle flanges fabricated out of 600mm long GI/MS pipe welded with 6mm thick M S plates along with flanges of suitable size and properly fixed in walls and top slabs of UGT complete, of following sizes :-
(a) 65mm dia
(b) 80mm dia
(c) 100mm dia
(d) 150mm dia
Gunmetal garden hydrant (pop-up sprinkler) fixed on irrigation pipe line complete, for 25mm dia
Butterfly valve confirming to type P.N. 1.6 of IS 13095-1991 complete with flanges, bolts, nuts, gasket etc. complete in all respect hydraulically tested to 20kg/sqcm, complete all as specified, of following sizes :-
(a) 65mm diameter Class - I
(b) 80mm diameter Class - I
(c) 100mm diameter Class - I
(d) 150mm diameter Class - I
Cast iron double flanged horizontal type with gunmetal seat non-return valve confirming to class - I of IS : 5312 including nuts, bolts, 1.5 mm thick compressed asbestos gasket including painting complete of following sizes :-
(a) 65mm diameter Class - I
(b) 80mm diameter Class - I
C.I 'Y' strainer with flanged end of approved make and making connection to pipe complete in all respects, of following sizes :- (a) 65mm dia nominal bore
Supply, Installation, testing & commissioning of Horizontal monoblock pumping set with C.I. body and bronze impeller, shaft of carbon steel and C.I. Base & head, mechanical seal, connected to a TEFC induction motor suitable for 400/440 volts, 3 phase 50 cycles A.C. supply with 150 mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads as required, M.S fabricated base plate, section and dilevery pipe including headers, bolted to cement concrete foundations complete. Recycle Water Supply Capacity/Flow Rate - 800 LPM, Head-20m, Capacity not less than 5 WHP complete
ELECTRIC PANNEL Supply, installation, testing and commissioning of panel suitable for 415 V, 3 phase, 4 wires, 50 Hz power distribution system, floor/wall mounting, sheet metal enclosed, dust and vermin proof with Copper busbars separate earth bus bars throughout the length of the panel, incoming and outgoing feeder accommodated in a modular multitier arrangement. The painting shall done as per relevant IS codes/as specified in the specifications. Adequate size cable alley shall be provided for each cable bending and termination. Bus bars shall be provided with heat shrinkable colour coded PVC sleeves, inlcuding necessary suitable size Cables, etc. complete. The panels shall be suitable for cable entry from top/Bottom. The minimum fault rupturing of all incoming and outgoing switches/breakers shall be as specified. The panels shall be fabricated after the approval of fabrication drawings and shall be comprising by providing the followings:- Incoming: One (1) No. 200 Amp, 25 KA (Ics), TPN, MCCB with adjustable thermo magnetic release as incomer. One (1) No. (0-500V) digital type voltmeter. One (1) No. (0-200A) digital type Ammeter with suitable C.T.’s for metering. One (1) No. earth leakage relay with multiple trip setting with CBCT.
Sch 'A' Part - XVII (ETP, WTP, CSP AND STP)
Effluent Treatment Plant capacity 0.3MLD as per drawings and all as specified herein after :- (a) Diffused Aeration System. Construction, supply, installation of diffused aeration system complete with diffuser membranes made of EPDM rubber extruded membrane, with diffusers evenly spaced and adequately supported for equalization tank - 01 Job (b) Effluent Transfer Pumps Horizontal single stage open impeller suitable for solids upto 10 mm coupled to a horizontal TEFC electric motor and mounted on a MS fabricated base plate , with pressure gauge on each pump outlet, automatic duty switchover after each operation complete. Pump Capacity 8.33 lps (500 lpm) at 10 m head - 02 Set (c) Tube settler with flash mixing Tank Self supporting ETP unit comprising of mixing tank for flash mixer, mixed solution tank and the main tube settler unit as per manufacturer’s design fabricated from 6 mm MS plates strengthened with MS structural members, painted inside with epoxy paint - 01 Set
(d) Chemical Dosing Pumps Chemical dosing metering pumps mounted on 100 lit MSEP/PVC containers with lids complete with suction and delivery piping, injection assembly, complete with connection with solution making and storage tanks for continuous supply of chemicals. Dosing pump capacity as per manufacturer’s design. For Lime , Alum , poly-electrolyte and dosing for Neutrilization - 03 Set (e)Solution making and storage tanks MSEP/HDPE self supporting solution making tanks each of 200 ltr capacity provided with water connection and agitation for proper mixing of the chemicals - 03 Set (f) Flash Mixer Electrical vertical flash mixer for mixing and preparing dosing solution installed in the flash mixer tank on the ETP - 01 Set (g) Sludge Transfer Pumps Horizontal, centrifugal type with TEFC electric motor and mounted on a MS fabricated base plate, with pressure gauge on each pump outlet, automatic duty switchover after each operation complete in all respects Pump Capacity 2 Cum/hour at 10 m head - 02 Nos
WATER SOFTENING PLANT Supplying, installation, testing and commissioning of water softener fabricated from MS plate as per IS:2825 (shell & thick dished ends) complete with initial charge of resins. GI class 'C' face piping, CI butterfly valves, pressure gauge, hydraulic brine injector, accessories, painting inside with epoxy paint and outside with two coats of red oxide primer and two or more coats of synthetic enamel paint, regeneration capacity complete with resins of approved quality comprising of following parameters:- (a) Inlet (TDS) - 700-1000 PPM (Approx.) (b) Inlet (Hardness) - 400-1000 PPM (Approx.) (c) Outlet (Hardness) - Commercially Zero Capacity - 55000 LPH (55 Cum/hour) Regeneration Period - 12 hrs. OBR - 550 Cum Operating Pressure - 3.0kg/Sq.cm Test pressure - 5.5 Kg/Sq.cm Suggested Resin Quantity - 8370 Lit. Suggested Height - 2600 mm Suggested dia - 2400 mm Brain Tank - 1 No. (100 lit. capacity)
CENTRAL SEWAGE TREATMENT PLANT Supply, installation, testing & commissioning of Central Sewage Treatment Plant capacity 1MLD as per drawings and all as specified here in after :-
(a) Coarse Bar Screen Fabrication, Supply & Installation of coarse bar screen in MSEP of suitable size for 1.0 MLD and capable of holding particles upto 20 mm.- 02 Nos
(b) Fine Bar Screen Fabrication, Supply & Installation of fine bar screen in MSEP of suitable size for 1.0 MLD and capable of holding particles upto 6 mm.- 02 Nos
(c) Main Sewage Pumps Submersible single stage open impeller suitable for solids upto 40 mm size coupled to submersible electric motor complete with pressure gauge on each pump outlet complete with low level cut off, level controller to operate 2nd pump if 1st pump fails to meet the demand, automatic duty switch over after each operation in the STP.complete in all respects Pump Capacity 52 Cum per hour at 9 m head (Two working + one stand by)- 03 Nos
(d) Air Blower for the FAB Reactor Electrically operated twin lobe air blowers and TEFC electric induction motor mounted on a common MS base plate with belt drive, belt protection guard, suction silencer and all accessories and supports. Blower capacity 500 cum/hr (each), 12.5 HP- 02 Nos
(e) Attached Growth bio reactor Manufacture, supply, installation of Attached Growth Bio Reactor (AGBR) suitable for 95% BOD removal efficiency, provided with PVC media, with specific surface area not less than 350 sq.m/cu.m . Media may be structured or floating type. The reactor should be complete with supports, as per specifications and as directed by GE. - 02 Nos
(f) Diffused aeration System Supply, installation of diffused aeration system complete with diffuser membranes made of EPDM rubber extruded membrane, with diffusers evenly spaced and adequately supported for following tanks. Pipe grid shall be separately measured as per piping rates, complete all as per specifications and as directed by GE.- 01 Set ( i) Aeration units (ii) Main Equalization tank ( iii) Sludge Holding Tank (iv) Treated Water Tank
(g) Clarifier mechanism Manufacture, supply, installation, testing and commissioning of clarifier mechanism complete with scrapper mechanism for scrapping sludge at the bottom.- 01 Set For Clarifier of main STP
For Clarifier of main STP (h) Main Filter MS fabricated /FRP multilayer filter vertical , pressure type dished ends fitted with internal distribution pipe on top, collector pipes and arms at bottom, inlet and outlet header complete with initial charge of filter media, face piping, accessories, working pressure 2.4 kg/sqcm ( Test pressure 3.75 kg/sq.cm. The vessel shall be painted with two coats of red oxide zinc chrome primer and two coats of paint. Capacity 60,000 liter per hour Filtarion velocity 10,000 liter per hour /sqm - 01 No
(i) Activated carbon filter MS fabricated /FRP multilayer filter vertical , pressure type dished ends fitted with internal distribution pipe on top, collector pipes and arms at bottom, inlet and outlet header complete with initial charge of filter media, face piping, accessories, Working Pressure 2.4 kg/sqcm ( Test pressure 3.75 kg/sq.cm. The vessel shall be painted with two coats of red oxide zinc chrome primer and two coats of paint. Capacity 60,000liter per hour . Filteration velocity. 10,000 liter per hour /sqm. - 01 No
(j) Chlorination Pumps Chemical dosing metering pumps mounted on 90 lit PVC containers with lids complete with suction and delivery piping, injection assembly, one set of buckets and containers for making solution for each pump complete in all respects. capacity as per manufacturer’s design. For Chlorine dosing of final effluent - 02 Nos.
(k) Instrumentation Magnetic type flow meter giving reading in liter per minute/liter per hour. (a) On Main STP inlet - 01 No (b) Level Controllers - 03 Nos
Float type suitable to work in sewage water without cleaning (l) Piping Supply, erection, jointing and testing MS pipes for waste water lines with necessary fittings, specials & supports as per technical specifications, etc. all pipes above ground shall be complete with two coats of red oxide zinc chrome primer and enamel paint , shade shall be as specified. - 01Job
(m) Valves Supply, Fixing and testing CI Butterfly valves for waste water lines with necessary fittings, specials & supports as per technical specifications, etc. complete all as specified and as directed by GE. - 01 Job
(n) Filter press Design, supply & installation of filter press in cast iron frame and polypropelene plates of size 24”x24” (min) with 32 plates with electric driven hydraulic power pack system complete in every respect required for efficient operation. - 01 Set
(o) Filter Press Feed Pumps Horizontal single stage open impeller suitable for solids upto 65 mm coupled to a horizontal TEFC electric motor and mounted on a MS fabricated base plate, with pressure gauge on each pump outlet, automatic duty switchover after each operation complete in all respects. Pump Capacity 5 Cum/hour at 10 m head - 01 Set
COLD STORAGE PLANT Supplying, instalation , testing and commissioning of pre fabricated cold storage plant electrically driven with suitable cooling/freezing units with control panel and all other accessories complete for temperature range minus 6 Deg C to 6 Deg C for 1.25 TR capacity details as under :- (a) Room Dimension (Mt.) (2.39X2.39X2.4) (b) Room Temperature (+) 4° C (c) Ambient Temp. (45° C) (d) Material to be stored. (Pharma Products) (e) Product Incoming Rate (300 Kgs/Day) (f) Product Entry Temp. (20-22 Degree Celcius) (g) Pull down time (12 hours) (h) Insulation (i) Walls and Ceiling (60 mm PUF with prepainted CRCA sheet). (ii) Floor (60mm PUF Panels). (j) Sliding Door size (0.9 x 1.9 m) (k) Refrigeration unit (R-134A 15,000 BTUH (1.25 TR.
Supplying, instalation , testing and commissioning of pre fabricated cold storage plant electrically driven with suitable cooling / freezing units with control panel and all other accessories complete for temperature (+) 4o C for 5 TR capacity details as under :- (a) Ambient Temp. ( 45 Degree Celcius) (b) Material to be stored (F&V Products) (c) Product Incoming Rate (1000 Kgs/Day) (d) Product Entry Temp. (20-22 Degree Celcius) (e) Pull down time ( 24 hours) (f) Insulation (i) Walls and Ceilling (60 mm PUF with Prepainted CRCA sheet as external finish and as intrnal finish) (ii) Floor (60 mm PUF Panels) (g) Sliding Door size (0.9 x 1.9 Meter) (h) Refrigeration unit (R-134A 60,000 BTUH (5 TR.))
Supplying, instalation , testing and commissioning of pre fabricated cold storage plant electrically driven with suitable cooling / freezing units with control panel and all other accessories complete for temperature range 2o C to 4o C for 4 body mortury cabinet details as under :- (a) Dimension (mm) (2110x2400x1785 high) (b) Interior finish (0.55 pre painted GI sheet) (c) Exterior finish (0.55 pre painted GI sheet) (d) Front finish & trims ( 0.50 Stainless steel) (e) Door & Door Frame - (FRP Door (45mm thick PUF) (f) Foamed Panel (i) Insulation thickness 80 (mm) (ii) Insulation material (Rigid Polyurethane foam (CFC free), Denisity 40 Kg/m3) (iii) Locking machanism (Cam-Locks embedded in foam) (g) Standard Accessories (i) Lamp (Vapor proof incandescent lamp, 40 W) (ii) Temperature indicator cum controller (Electronic with Digital display)
(iii) Carriage assembly (Three piece, telescopic action, GI powder coated) (iv) Mortuary Tray (One piece stain less steel tray with tubular edge and handles). (h) Refrigerating system (Roof Top Mounting Unitary) (i) Capacity (BTU/H) (6000) (ii) Power supply (230 V/1 HP/50 HZ) (iii) Compressor Power (KW) (1.25) (iv) Total Unit Power Consumptions (KW) (1.75) (v) Operating conditions (4 Deg C Room Temperature @ 35 Deg C Ambient) (vi)Over all Dimensions (mm) of Ref. Unit (1140 (L x 900 (W)x415 (H)) Note : Cables for electric connections to the equipments mentioned above shall be measured under respective items of External Electrification.
Supply, installation, testing and commissioning of LT panel board for effluent treatment plant, out door type, cubical, floor mounted, factory made, totally enclosed, made out of CRCA sheet not less than 16 SWG mounted on angle iron 50x50x6 mm with MS plate suitable for bottom cable entries with cable glands of brass of suitable size weather proof with front and back open including adjustable type locking arrangement and powder coated painted internally and externally providing and consisting of the following fitments/accessories :-
(a) Bus bar chamber 3 phase, 4 wire, 440 volts, 50c/s consisting of copper bus bar of capacity 100 Amps (all the four bus bar to be of the same size including neutral) for incoming/outgoing feeder and fixing on insulators with PVC coloured sleeves - 01 Set.
(b) MCCB, 4 pole, 63 Amp, 415 volts, 25 KA (Ics) - 01 No. (incoming).
(c) MCCB, 4 pole, 25 Amp, 415 volts, 10 KA (Ics) - 01 No. (outgoing).
(d) MCB DP 25 Amps, 230 volts, 10 KA (Ics) - 03 Nos.
(e) MCB DP 16 Amps, 230 volts, 10 KA (Ics) - 03 Nos.
(f) DOL starter for upto 3 HP motor - 04 Nos.
(j) Internal wiring connection in colour coding with suitable copper cable/lugs with end terminal - 01 Job.
(k) Indicator lamp LED type in RBY colour set of 3 - 01 Set.
Supply, installation, testing and commissioning of LT panel board for sewage treatment plant, out door type, cubical, floor mounted, factory made, totally enclosed, made out of CRCA sheet not less than 16 SWG mounted on angle iron 50x50x6 mm with MS plate suitable for bottom cable entries with cable glands of brass of suitable size weather proof with front and back open including adjustable type locking arrangement and powder coated painted internally and externally providing and consisting of the following fitments/accessories :-
(a) Bus bar chamber 3 phase, 4 wire, 440 volts, 50c/s consisting of copper bus bar of capacity 250 Amps (all the four bus bar to be of the same size including neutral) for incoming/outgoing feeder and fixing on insulators with PVC coloured sleeves - 01 Set.
(b) MCCB, 4 pole, 200 Amp, 415 volts, 25 KA (Ics) - 01 No. (incoming).
(c) MCCB, 4 pole, 40 Amp, 415 volts, 10 KA (Ics) - 03 No. (outgoing).
(d) MCCB, 4 pole, 63 Amp, 415 volts, 10 KA (Ics) - 02 No. (outgoing).
(e) MCB DP 25 Amps, 230 volts, 10 KA (Ics) - 04 Nos.
(f) DOL starter for upto 6 HP motor - 04 Nos.
(g) Star Delta starter for 12.5 HP motor - 02 Nos.
(k) Internal wiring connection in colour coding with suitable copper cable/lugs with end terminal - 01 Job.
(l) Indicator lamp LED type in RBY colour set of 3 - 01 Set.
Sch 'A' PART-XVIII : INCINERATOR Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Supply, Installation, commissioning and testing oil fired incinerator of suitable capacity for hospital waste / bio-medical waste 60Kg/hr. confirming to design and emission parameters mentioned in the Gazette and Guidelines of August 2003 of Central/State polution control board. The incinerator system shall comprise of following accessories/fitments:-
(a) Main Incinerator with. i). Refractory lined Primary and Secondary Chamber. ii). Refractory lined main charging door and ash cleaning door.
(b) (i). 1 No. fully automatic oil burner for primary chamber. (ii). 1 No. fully automatic oil burner for secondary chamber.
(c) Centrifugal forced draft combustion air fan with motor.
(d) Auto-loading device in the form Double Flap Damper Valve (DFDV) mechanism with outer gate manual and inner damper motorized.
(e) Suitable flow measurement device on the Primary & Secondary air ducting.
(f) Emergency stack / vent.
(g) High pressure venturi scrubber of Stainless Steel (SS316 L).
(h) Cyclonic type droplet separator cum recirculation tank with built in caustic solution tank in MSRL construction.
(i) I.D. Fan with MSRL casing & SS 316 L impeller with motor.
(j) Recirculation Pump (SS 316) with Motor along with piping & valves.
(k) Overhead HDPE Water tank of suitable capacity along with water piping between tank and scrubber.
(l) Interconnecting ducting within the battery limits.
(m) Instruments, valves, dampers and fittings within battery limits.
(n) PLC based Control Panel with necessary instruments.
(o) Data recording device in the form of a Printer.
(p) Oil tank along with oil piping, valves & strainers between tank & burner.
(q) Operating tools & tackles like rake, hoe, shovel, two teeth scrapper.
(r) Portable stack monitoring device for CO, CO2 & O2.
(s) Self supported Mild steel rubber lined chimney of 200 mm top dia and 30m height.
Supply, installation, testing and commissioning of LT panel board of sewage treatment plant, indoor type, cubical, floor mounted, factory made, totally enclosed, made out of CRCA sheet not less than 16 SWG mounted on angle iron 50x50x6mm with MS plate suitable for bottom cable entries with cable glands of brass of suitable size weather proof with front and back open including adjustable type locking arrangement and powder coated painted internally and externally providing and consisting of the following fitments/accessories :-
(a) Bus bar chanber 3 phase, 4 wire, 440 volts, 50 c/s consisting of copper bus bar of capacity 150 amps (all the four bus bar to be of the same size including neutral) for incoming / outgoing feeder and fixing on insulators with PVC coloured sleeves - 01 set.
(b) MCCB, 4 pole, 100 Amp, 415 volts, 25 KA (Ics) - 01 No. (incoming).
(c) MCCB, 4 pole, 40 Amp, 415 volts, 10 KA (Ics) - 02 Nos (outgoing).
(d) MCB DP 30 Amps, 230 volts, 10 KA (Ics) - 02 Nos.
(g) Internal wiring connection in colour coding with suitable copper cable/lugs with end terminal - 01 Job.
(h) Indicator lamp LED type in RBY colour set of 3 -01 set.
Sch 'A' PART-XIX : MECHANICAL LAUNDRY Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Testing and commissioning of existing WASHER EXTRACTOR of capacity 30 Kg, make- Fabcare, including proper installation of the extractor at the platform, making electrical connections through electrical cable conductors, complete all as specified and directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning of existing WASHER EXTRACTOR of capacity 100 Kg, make- Fabcare, including proper installation of the extractor at the platform, making electrical connections through electrical cable conductors, complete all as specified and directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning of existing TUMBLE DRYER of capacity 30 Kg, make- Fabcare, including proper installation of the dryer at the platform, making electrical connections through electrical cable conductors, complete all as specified and directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning of existing TUMBLE DRYER of capacity 100 Kg, make- Fabcare, including proper installation of the dryer at the platform, making electrical connections through electrical cable conductors, complete all as specified and directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning of existing FLAT BED PRESS of size 1580mm (width) X 1100mm (depth) X 1220mm (high), make- Fabcare, including proper installation of the PRESS at the platform and making electrical & all other necessary connections, complete all as specified and directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning of existing UTILITY LAUNDRY PRESS of size 1455mm (width) X 1100mm (depth) X 1220mm (high), make- Fabcare, including proper installation of the PRESS at the platform and making electrical & other necessary connections all as specified, complete all as specified and directed. (Note ; All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning of existing VACCUM FINISHING TABLE- suction 1HP motor, make- Fabcare, including proper installation of the vaccum table at the platform and making electrical & other necessary connections complete all as specified and directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
SUPPLY, INSTALLATION AND COMMISSIONING OF IRONER SIZE 800 Dia, 3000mm, 1 Roll Simple chain drive mechanism with single motor - Heating roll made of high quality stainless steel - Large contact area of 300 degree to maximize heat exchange - Patented automatic belt tensioning system eliminates manual adjustment - Variable speed frequency inverter control - Gradual speed increment between rolls to improve ironing quality by stretching effect - Heat isolation panel on feeding side - simple control with ON/OFF button and speed adjustment - Heating roll and guide shaft drive simultaneously - Float type steam trap reduces steam consumption Maximum Ironing Width - 3000 mm Diameter of Roll - 800 mm Ironing Speed - 1-10 m /min Steam Pressure - 0.3 - 0.55 Mpa Main Motor - 1.1 Kw Frequency Inverter - 1.5 kw
SUPPLY, INSTALLATION AND COMMISSIONING OF AIR COMPRESSOR (7.5 HP ) Double Stage Tank Cap 220 liter 8 Kg/ cm² . All Performance parameters are as per JIS standards - Duplex compressor mounted on base frame - Low noise and vibration levels - Easy installation - Continuous and heavy duty operation - cost of efficiency.
SUPPLY, INSTALLATION AND COMMISSIONING OF STEAM BOILER(2 X 400 KGS)
(a) STEAM GENERATION PLANT HSD Fired Coil type Steam Boilers Reverse flame type capable of generating 400 kg/hr of steam from and at 100 deg celcius with max. safety valve set off pressure of 10.54 Kg/Sqcm including all accessories/Safeties, SIBR Kind
(b) BOILER ROOM AUXILLARIES Day Tanks of (i) 2000 lits feedwater tank fabricated out of 6mm thick MS sheet with all fittings and gauge glass
(ii) 990 lits Fuel Oil tanks fabricated out of 5 mm thick MS sheet with all fittings like level gauge glass
(c) (i) FLUE GAS DUCTING Flue duct ( Bare Size)fabricated out of 5mm thick MS Sheet, for 200 mm dia
(c) (ii) FLUE GAS DUCTING Flue duct ( Bare Size)fabricated out of 5mm thick MS Sheet, for 250 mm dia
(iii) Water pump suitable for above softening plantwater @ 50liter per meter @ 30 m head
(e) Steam Pressure reducing station complete with valves,gauges,safety valve,bypass valves & flanking valves,IBR, as under :-
(i) Steam piping from Boilers to Individual headers (IBR)
(ii) One set of Fuel oil piping from the Oil tank to both boilers inclusive of Valves/NRV
(iii) All boiler drain/Blow down piping to the pit
(g) INSULATION:- Hot insulation to all equipment complete with 50 mm thick 100/Cum insulation & aluminium cladding of 24 gauge, for
(i) Steam piping
(ii) Steam Headers
(iii) Flue gas Ducting within Boiler house
(h) MISCELLANEOUS
(i) Structural steel work for making platform pipe supports, hanger and blow down chamber including cutting,bending,welding of structural steel with I Beams, TEE beams,Channels, Angles & Painting with one coat primers and two coats of approved paint
(ii) Structural steel work for soft water tank
(iii) Structural steel work for Day Oil tank
Note : Cost of IBR approval along with initial steam drawings, obtaining clearance and Hydro test , initial Approval and final steam test shall be deemed to include in the rate quoted.
Supply, Installation, Testing & Commissioning of steam, cold water, drainage pipeline including electric cabling, connection, electric panels, starters etc., all Inclusive to make the plant and machinery functional as per manufacture instructions and design / drawings and standard engineering practice
Cable Connection PVC insulated unsheathed copper conductor cable of size 25 sqmm, single core, 1100 volts fixed on walls/poles or laid in ducts/trenches or passed through pipes complete all as specified.
All as per Srl Item No 526 but of size 16 sqmm single core.
Gay supported Main Chimney complete with base, cylindrical top sections, base plate, cowl on top of 525 mm dia 30 m height
Polishing softener of 1600 liter per hour with brine tank, frontal piping and control valves
Steam header High Pressure header (IBR) comprising of following:- (i) 250 mm dia & 3000 mm long seamless tube (ii) 2 Nos lintel flange nozzles. (iii) 1 No outlet flange (iv) Drain flange nozzles (v) Flanged ends and Blind flanged. (vi) Set of Bellow seal valves on steam line
Steam Pressure reducing station complete with valves gauges saftey valve, bypass valves & flanking valves IBR, as under:- PR Station PRS-2 for steam press @ 4bar for 300 kg
SCH 'A' PART-XX : NURSE CALL AND PUBLIC ADDRESS SYSTEM FOR FIRE FIGHTING (System should confirm to UL 1069 (Under Writers Laboratories), CSA (Canadian Standards Association), NEC(National Electrical Code) Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
CORRIDOR LAMP/ROOM CONTROLLERS/ZONE LAMPS Corridor Lamps (2-lamp style) shall be provided as indicated on the plans and drawings. (a) Corridor Lamps shall utilize LED's for high visibility, long life and low maintenance. CorridorLamps utilizing incandescent lamps shall not be acceptable. (b) The corridor lamp shall make use of multiple colors and programmable flash rates and patterns to indicate pending calls, service requirements and staff presence. (c). Corridor Lamps shall serve as the hub for all room wiring. All field wire connections shall be accomplished using modular connectors. (d) Any Corridor Lamp shall be able to function as a Zone Lamp that shall visually annunciate calls from assigned room/stations without the use of a Zone Lampcontroller such as a duty station. (e) The Corridor Lamp shall be equipped with a heart-beat LED (visible to service personnel) to indicate that the unit is functioning properly. (f) The Corridor Lamp shall accommodate a paper label to indicate the room number.
ROOM STATION : Room stations non audio shall be equipped with followings as shown on drawings:- (i) DIN style receptacle(s) for call cord. (ii) Reset Button to cancel pending calls. Reset button shall be able to cancel calls from other stations in the room if desired (iii) Red LED(s) to indicate call placement from one or both of the call points.(iv) Removing a call cord shall place a Cord Out call. (iv) Removing a call cord shall place a Cord Out call. (v) Cord Out calls may be cancelled locally using the cancel Button. No Dummy Plugs shall be required. (vi) Room stations shall employ modular connectors. It shall be possible to service Room Stations without removing power from the system.
Pull Cord Station for WC:- Pull cord sub-stations shall be water resistant with a PVC (poly-vinyl chloride) pull-cord, membrance resetbutton and coveredcall assurance LED. Unit may utilize remote cancel button for ease of nurse cancel when pull cord station I mounted in inaccessiblelocation (e.g. ceiling).
CALL CORD:-Standard Call Cords shall be pendant type with a single easy to activate call button, DIN style, male plug and sheet clip. Cable shall be minimum of10'/300cm. One standard call cord shall be provided for each bed with an additional 10% provided as spares.
Public Address System for Fire Fighting Supplying, installing, testing and commissioning of Public Address (PA) System for the entire hospital consisting of the following :- Make : BOSCH/AHUJA or equivalent of make as approved by Accepting Officer.
(a) Mounting rack for amplifiers and monitors (shall be like table top )
(d) Amplifier with 480W RMS output
(e) Single CD Player, with dual cassette deck, AM/FM Tuner.
(g) 6W Ceiling Ring Speakers complete with built in LMT, grill, mounting clamps etc
(h) 6W Wall mounted box type speakers with built-in LMT, grill, mounting clamps etc. for Basement
(j) 6Watt cone type speakers for outdoor application with built in LMT.
(k) Car Calling console with Microphone Desk mounted.
FRLS PVC insulated flexible copper conductor, single core 3 x 1.5 sqmm cable, drawing in existing surface/recessed PVC/steel conduit complete all as specified.
All as per Srl item 550 above but of size 3 x 2.5 sqmm.
Copper flexible cable 2 core 24/0.20mm with terminations, and connectors complete in all respect.
Supply, fixing, laying testing and commissioning of PVC insulated copper conductor CAT 6 cable suitable for nurse call sysytem. Make : Rauland Borg
-------------Blank-------------
-------------Blank-------------
-------------Blank-------------
-------------Blank-------------
-------------Blank-------------
SCH 'A' PART-XXI : MEDICAL GAS PIPE LINE SYSTEM Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Testing and commissioning of existing medical gases supply control station for the entire hospital consisting of Oxygen Manifold 20+20 cylinders with NRVs, tail pipes etc W/O cylinder (Indegenious) complete all as specified and directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning of existing medical gases supply control station for the entire hospital consisting of Emergency Oxygen System Manifold of 8+8 cylinders w/o cylinder (Indegenious) complete all as specified and directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning of existing medical gases supply control station for the entire hospital consisting of Fully Automatic Oxygen Control Panel (Imported) complete all as specified and directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning of existing medical gases supply control station for the entire hospital consisting of Nitrous Oxide Manifold 4+4 cylinders with NRVs, tail pipes etc w/o cylinders (Indegenious) complete all as specified and directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning of existing medical gases supply control station for the entire hospital consisting of Emergency N2O Manifold of 1+1 cylinder with regulator (Indegenious) complete all as specified and directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning of existing medical gases supply control station for the entire hospital consisting of Fully Automatic Nitrous Oxide Controls, complete all as specified and directed.. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning of existing medical gases supply control station for the entire hospital consisting of Oil Less Compressor System (compressors in triplex, skid mounted with facility for single point connection) complete all as specified and directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning of existing medical gases supply control station for the entire hospital consisting of Vaccum System (Duplex pump System, skid mounted with facility for single point connection), complete all as specified and directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning of existing Horizontal Bed Head Panel, length-1.8 mtr, made of extruded aluminium having twin horizontal rail to mount accessories & having provision for gas outlets (as per the outlet list) and seperate segregated channel for high voltage 6 Nos electrical sockets and a channel for low voltage-Nurse call/Monitor Cabling/ telephone cabling etc. and other items as per detailed specifications, complete all as specified & directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning of existing Vertical Bed Head Panel - (for Triagex 3 beds & 12 Beded ICU) V, length-2.5 mtr, made of extruded aluminium having twin vertical rail to mount accessories & having provision for gas outlets (as per the outlet list) and seperate segregated channel for high voltage 12 Nos electrical sockets and a channel for low voltage-Nurse call/Monitor Cabling/ telephone cabling etc. and other items as per detailed specifications, complete all as specified & directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning in all technical aspects of the existing Copper Piping of size 76.1mm OD x 1.5mm thick laid on wall surfaces or over the MS fabricated structures for the medical gas system of the entire hospital bldg,complete all as specified & directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning in all technical aspects of the existing Copper Piping of size 42mm OD x 1.2mm thick laid on wall surfaces or over the MS fabricated structures for the medical gas system of the entire hospital bldg, complete all as specified & directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning in all technical aspects of the existing Copper Piping of size 28mm OD x 0.9mm thick laid on wall surfaces or over the MS fabricated structures for the medical gas system of the entire hospital bldg, complete all as specified & directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning in all technical aspects of the existing Copper Piping of size 22mm OD x 0.9mm thick laid on wall surfaces or over the MS fabricated structures for the medical gas system of the entire hospital bldg, complete all as specified & directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning in all technical aspects of the existing Copper Piping of size 15mm OD x 0.9mm thick laid on wall surfaces or over the MS fabricated structures for the medical gas system of the entire hospital bldg, complete all as specified & directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning in all technical aspects of the existing Copper Piping of size 12mm OD x 0.7mm thick laid on wall surfaces or over the MS fabricated structures for the medical gas system of the entire hospital bldg, complete all as specified & directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning in all technical aspects of the existing 2 Gas Valve Box installed for the medical gas system of the entire hospital bldg, complete all as specified & directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Testing and commissioning in all technical aspects of the existing 3 Gas Valve Box installed for the medical gas system of the entire hospital bldg, complete all as specified & directed. (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate) "
Supplying, installing, testing and commissioning of medical gases supply control station for the entire hospital consisting and providing the following all as specified.
(A) Oxygen System
(a) Oxygen Gas Oultet point
(b) Oxygen Flow meters with humdiifer bottle
(B) NITROUS OXIDE SYSTEM
(a) Gas Outlets Point for N2O
(C) COMPRESSED AIR SYSTEM
(a) Gas Oultet point for Air 4 Bar
(b) Gas Outlet point for Air 7 Bar
(D) Vaccum system
(a) Gas Outlet point for Vaccum
(E) VACCUM ACCESSORIES
(a) ward vaccum unit with one regulator one collection bottle complete all as specified.
(b) Theatre vaccum unit mounted on the trolley with 1 vaccum regulator & 2 collection bottles ( 2 units for each major and minor OT)
(F) ALARM SYSTEM
(a) For 5 services ( o2, N2O, M. Air(4) S. Air ( 7) Vac)
(b) For 4 services ( O2, N2O, C.Air(4), Vac)
(c) For 3 services ( O2, C. air ( 4) Vac)
(d) For 2 services ( O2, Vac)
Central Main Alarm in the Plant Room
Slave Main Alarm with computerized cabling
Horizontal Bed Head Panel Length -1.8 mtr, made of extruded aluminium having twin horizontal rail to mount accessoires & having provision for gas outlets (as per the outlet list) and separate segregated channel for high voltage 6 no. Electrical Sockets and a channel for low voltage-Nurse Call / Monitor cabling/ telephone cable etc. and other items as per detailed specifications.
Vertical Bed Head Panel - (for Triagex 3 beds & 12 Beded ICU) V. Length - 2.5 mtr made , made of extruded aluminium having twin vertical rail to mount accessories & having provision for gas outlets (as per the outlet list) and separate segregated channel for high voltage 12 no. Electrical Sockets and a channel for low voltage-Nurse Call / Monitor cabling/ telephone cabling etc. and other items as per detailed specifications.
Matching Probes for Outlets
(b) Nitrous Oxide
(c) M. Air - 4 bar
(d) S. Air - 7 bar
(e) Vacuum
Copper Piping (with third party inspection certificate) of following sizes:-
(a) 108mm OD x 2.0 mm thick
(b) 76.1mm OD x 1.5 mm thick
(c) 42mm OD x 1.2 mm thick
(d) 28mm OD x 0.9 mm thick
(e) 22mm OD x 0.9 mm thick
(f) 15mm OD x 0.9 mm thick
(g) 12mm OD x 0.7 mm thick
Valave Box
Rigid Retractable ceiling mount type pendant for OT provision for - 2xO2, 1x N2O, 1x Air (4), 1x Air (7) and 2 x Vac, 1x AGSS outlets, 6 x electrical sockets
Multi Movement and Multiarm (800+1000mm arm with 330º movement) ceiling mount type pendant for major OT, and provision for the lifting of the Anaesthesia machine and head with provision for 3xO2, 1x N2O, 1x Air (4), 1x Air (7) and 3 x Vac, 10 x electrical sockets, monitor jacks, grounds and one tray and another tray (bottom) with drawer.
H.P. Antistatic Rubber tube (100 mtrs, for O2- white, 50mtr N2O-Blue, 150 mtr Air - Black and 200 mtr for Vacuum - Yellow.
Electrical Control Panel (input panel ) for both Vacuum Pumps and Compressors for the Manifold Room and cabling for all alarms
Liquid Tank Capacity 5000 Ltr with foundation work & copper piping for liquid tank & other accessories
PART- XXII : LIST OF WORKS AND PRICES FOR LIGHTNING PROTECTION SYSTEM Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Supply, installation, testing and commissioning of Advance Lightning Protection complete with the lightning Air Terminal- Configured as a Spheroid consisting and comprising of separate electrically isolated 4 panels surrounding an Earthed Central Finial. The Insulation material used to electrically isolate the panels shall comprise of a base polymer which provides high Ozone & UV resistance with di-electric strenght of 24-38 KV/mm tested as per NFC 17-102 & IEC 60-1:1989. The ESE terminal shall not contain any electronic circuits or any moving parts for its operation. The ESE terminal shall be tested & certified by CPRI (Central Power Research Institute, Govt of India) for the impluse current of 45 KA (8/20 micro sec) with 5 positive & 5 negative impulse. The ESE terminal shall be approved by DGMS (Director General of a protection radius of 79m with the Level 1 (High) protection & to be mounted as per design and shall be provided with following accessories/fitments.
(a) Model: Stormaster 60 - 79m (Protection radius 79m with Level 1 / High protection)
(b) Upper Termination Kit
(c) Lower Termination Kit
(d) FRP Mast (2m)
(e) Inline coupling
(f) Guy wire kit
(g) GI Mast (3m)
Supply only advance maintenance free chemical gel single pole earthing system of 1 number of "J K CHEMRODE" - 10 feet length, 50mm dia, 1.5mm thick electrolytic grade Copper tube duly filled with conducting natural minerals with the permanent sealings at both ends with the lead terminal at the top along with 1 set of Part (5Kgs) + 2 set (5 Kgs) LPI GRIP (Ground Resistance improvement Powder) - Part 1 (mixture of calcium carbonate & sodium sulphate) + Part 2 (Copper sulphate) along with heavy duty polyplastic Chember.
Supply and fixing of specially designed lightning current High Voltage Sheilded Cable (HVSC) 7 layer cable consisting of Inner Core, Concentric Conductor (copper), Inner binding tape, Insulation material, Metallic screen, Outer binding tape, Outer sheath with the nominal cross sectional area of 50 sq.mm & overall diameter of 37mm with the insulation resistance of 1830 M Ohm-km, tested for 200 KV as per termination & connected to the earth pit with the lower terminal kit to safely route the lightning current.
Supply only Test Link joint Kit in IP55 weather proof enclosure of suitable dimension.
PART- XXIII : LIST OF WORKS AND PRICES FOR UPS AND DESK COMPUTER Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Supplying, installation, testing and commissioning of SU20K3/3X 20KVA SmartOnline 3-Phase Intelligent, True Online UPS System to save valuable space and simplify runtime scalability. Power and battery components are combined into a single, small-footprint module (the smallest in its class). A robust internal battery runtime capability can be easily extended by installing additional modular internal battery packs through the convenient front panel access door. SU20K3/3X SmartOnline 3-Phase Intelligent, True On-Line UPS System provides mission-critical equipment with the highest level of power protection available. Large capacity 20,000 VA/16,000 watt power module continually converts incoming AC power into filtered DC power, and then resynthesizes it back into AC power with a pure sine wave. Perfectly regulated, continuous sine wave output with zero transfer time offers compatibility with all equipment types. SmartOnline models provide some of the highest levels of isolation from THD (total harmonic distortion)—<3%—allowing equipment to perform at its peak. A 3:1 crest factor safely supports a variety of equipment, even those with wildly-fluctuating power demands.
An accessory slot accepts an optional internal SNMP card (model # SNMPWEBCARD) for remote shutdowns, reboots and more. A Battery Start Switch allows cold restart of UPS during a prolonged blackout to utilize its batteries for periodic system access or data retrieval. An Emergency Power Off button turns UPS output OFF and disables Bypass output. Built-in Emergency Power Off (EPO) interface supports remote emergency shutdown in large facilities. Front panel combination LCD/LED display alerts users to a variety of UPS operational modes and conditions
Supplying, installation, testing and commissioning of SU30K33INT 30KVA SmartOnline 3-Phase Intelligent, True Online UPS System to save valuable space and simplify runtime scalability. Power and battery components are combined into a single, small-footprint module (the smallest in its class). A robust internal battery runtime capability can be easily extended by installing additional modular internal battery packs through the convenient front panel access door. SU30K33INT SmartOnline 3-Phase Intelligent, True On-Line UPS System provides mission-critical equipment with the highest level of power protection available. Large capacity 30,000 VA/24,000 watt power module continually converts incoming AC power into filtered DC power, and then resynthesizes it back into AC power with a pure sine wave. Perfectly regulated, continuous sine wave output with zero transfer time offers compatibility with all equipment types. SmartOnline models provide some of the highest levels of isolation from THD (total harmonic distortion)—<3%—allowing equipment to perform at its peak. A 3:1 crest factor safely supports a variety of equipment, even those with wildly-fluctuating power demands.
An accessory slot accepts an optional internal SNMP card (model # SNMPWEBCARD) for remote shutdowns, reboots and more. A Battery Start Switch allows cold restart of UPS during a prolonged blackout to utilize its batteries for periodic system access or data retrieval. An Emergency Power Off button turns UPS output OFF and disables Bypass output. Built-in Emergency Power Off (EPO) interface supports remote emergency shutdown in large facilities. Front panel combination LCD/LED display alerts users to a variety of UPS operational modes and conditions.
Supplying, installing, testing and commissioning of desk computer completewith processor,UPS, Monitor & Printer etc. preloaded with latest window operating system as under:-
(a) Desk Computer Dual Core 2.6 GHz Intel G31 Chip set mother Board 1 GB DDR-II RAM 320 GB Hard Disk DVD RW Key Board, Optical Mouse 18.5" LCD with internal speakers
(b) UPS-600 VA with internal battery
(c) Printer -Laser Jet Printer
PART- XXIV: LIST OF WORKS AND PRICES FOR FIRE FIGHTING WORK Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Painting job on outer surface of the existing class 'C' MS pipe of size 150 mm bore dia with one coat of red oxide primer and two coats of post office red colour complete all as specified and directed. (for Fire Hydrant/ Wet Riser System)
Painting job on outer surface of the existing class 'C' MS pipe of size 80 mm bore dia with one coat of red oxide primer and two coats of post office red colour complete all as specified and directed . (for Fire Hydrant / Wet Riser System) "
Testing & commissioning of the existing 'C' class MS pipe of size 150 mm bore dia fixed or fitted on wall surfaces or suspended from celing with necessary specials such bends, reducers orifice plates etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Fire Hydrant / Wet Riser System). (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class MS pipe of size 80 mm bore dia fixed or fitted on wall surfaces or suspended from celing with necessary specials such bends, reducers orifice plates etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Fire Hydrant / Wet Riser System). (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class MS pipe of size 150 mm bore dia laid in underground trenches with necessary specials such bends, reducers orifice plates etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Fire Hydrant / Wet Riser System- Undergtound). (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class MS pipe of size 80 mm bore dia laid in underground trenches with necessary specials such bends, reducers orifice plates etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed . (for Fire Hydrant / Wet Riser System- Underground). (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Painting job on outer surface of the existing class 'C' MS pipe of size 150mm bore dia with one coat of red oxide primer and two coats of synthetic enamelled paint of colour as approved by the GE complete all as specified and directed. (for Fire Sprinkler System) "
Painting job on outer surface of the existing class 'C' MS pipe of size 100mm bore dia with one coat of red oxide primer and two coats of synthetic enamelled paint of colour as approved by the GE complete all as specified and directed. (for Fire Sprinkler System) "
Painting job on outer surface of the existing class 'C' MS pipe of size 80mm bore dia with one coat of red oxide primer and two coats of synthetic enamelled paint of colour as approved by the GE complete all as specified and directed. (for Fire Sprinkler System) "
Painting job on outer surface of the existing class 'C' MS pipe of size 65mm bore dia with one coat of red oxide primer and two coats of synthetic enamelled paint of colour as approved by the GE complete all as specified and directed. (for Fire Sprinkler System) "
Painting job on outer surface of the existing class 'C' MS pipe of size 50mm bore dia with one coat of red oxide primer and two coats of synthetic enamelled paint of colour as approved by the GE complete all as specified and directed. (for Fire Sprinkler System) "
Painting job on outer surface of the existing class 'C' MS pipe of size 40mm bore dia with one coat of red oxide primer and two coats of synthetic enamelled paint of colour as approved by the GE complete all as specified and directed. (for Fire Sprinkler System) "
Painting job on outer surface of the existing class 'C' MS pipe of size 32mm bore dia with one coat of red oxide primer and two coats of synthetic enamelled paint of colour as approved by the GE complete all as specified and directed. (for Fire Sprinkler System) "
Painting job on outer surface of the existing class 'C' MS pipe of size 25mm bore dia with one coat of red oxide primer and two coats of synthetic enamelled paint of colour as approved by the GE complete all as specified and directed. (for Fire Sprinkler System) "
Testing & commissioning of the existing 'C' class MS pipe of size 150 mm bore dia suspended from beams, RCC roof slabs with necessary specials such bends, reducers orifice plates etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Fire Sprinkler System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class MS pipe of size 100 mm bore dia suspended from beams, RCC roof slabs with necessary specials such bends, reducers orifice plates etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Fire Sprinkler System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class MS pipe of size 80 mm bore dia suspended from beams, RCC roof slabs with necessary specials such bends, reducers orifice plates etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Fire Sprinkler System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class MS pipe of size 65 mm bore dia suspended from beams, RCC roof slabs with necessary specials such bends, reducers orifice plates etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Fire Sprinkler System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class MS pipe of size 50 mm bore dia suspended from beams, RCC roof slabs with necessary specials such bends, reducers orifice plates etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Fire Sprinkler System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class MS pipe of size 40 mm bore dia suspended from beams, RCC roof slabs with necessary specials such bends, reducers orifice plates etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Fire Sprinkler System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class MS pipe of size 32 mm bore dia suspended from beams, RCC roof slabs with necessary specials such bends, reducers orifice plates etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Fire Sprinkler System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class MS pipe of size 25 mm bore dia suspended from beams, RCC roof slabs with necessary specials such bends, reducers orifice plates etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Fire Sprinkler System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 15mm dia nominal bore quartzoid bulb type upright sprinklers with temperature rating of 68 deg C conventional type suspended with ceiling, wall beam clamps, fasteners ceiling rosette (in case of false ceiling) complete all as specified and directed. (for Fire Sprinkler System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing SS Flexible Pipe fixed to connect the sprinklers with MS pipe lines complete all as specified and directed. (for Fire Sprinkler System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing roof slab mounted Intelligent addressable Optical Based smoke and heat detector with facility of numbering in base (UL listed) complete all as specified and directed. (for Fire Alarm System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 2 Core X 1.5 sqmm multistranded armoured copper cable fixed to celing/ roof slab by means of clamping for wiring of detectors and devices complete all as specified and directed. (for Fire Alarm System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
A: FIRE HYDRANT SYSTEM: Supply, Erection and Commissioning of Diesel engine driven main fire hydrant pump horizontal mounted centrifugal pump located at ground floor level, capable of delivering 2280 liters of water / minute at an head of 70m and giving a jet pressure not less than 3,5 kg / sq.cm at the top most hydrant, suitable for automatic opeation, mounted on a common base frame inlcuding pressure gauge, pressure switch suitable diesel tank of required litres storage capacity and coupled to diesel engine of adequate HP. It shall be fitted on a common base frame wih antivibrating pads including all other auxillaries such as batteries, exhaust pipe necessary valves,. "Y" strainer for coolling water inlcuding cooling system and civil work etc. complete.
Supply, Erection, Testing and Commissioning of electrical motor driven end suction back pullout centifugal/fire hydrant pump with bronze impellors, cast iron body, capable of delivering (2280 litres of water per minute at an head of 70m and giving a jet pressure not less than 3.5kg / sq.cm at the top most hydrant, and coupled to adequate HP electrical motor mounted on a common base frame with pressure gauge pressure switch etc as required including inter connecting wires, cables and civil work etc complete
Supply, Erection, Testing and commissioning of jockey pump located at ground floorlevel capable of delivering 180 litres of water / minute at than 3.5 kg / sqcm at the top most hydrant, complete with adequate HP. pressure not less Electircal driven monoblock type pump wtih squirrel cage motor with bronze impellors, pressure gauge, pressure switch and civil work etc. complete.
Supply, Erection and commissioning of 'C' class MS pipe (as per IS 1239) for fire hydrant/ wet riser system. The pipes shall be fitted on walls or suspended for from ceiling with necessary specials, such as bends. Reducers, orifice plates, if any tees, flanges, CI Tapers etc. The rates shall include the cost of consumables for cutting and welding, painting with a coat of red oxide and two coats of post office red colour
(a) Blank
(b) Blank
(c) 150 mm dia
(d) 100 mm dia
(e) 80 mm dia
Supply, Erection and commissioning of 'C' class MS pipes (as per IS 1239) for fire hydrant / wet riser system. The pipes shall be finex for underground with necessary specials, such as bends. Reducers, orifice plates, if any tees, flanges, CI Tapers etc. The rates shall include the cost of consumables for cutting and welding, with anticorrosive bitumastic paint and wrappping with polythene sheet based pipe kote of 4mm thickness for Under ground piping
(a) 150mm dia
(b) 100mm dia
(c) Blank
Supply, erection, testing and commissioning of 'FIRE HOSE CABINET" fhc) OF SIZE (APPROX) 750 mmX 600 mmX 450 mm with hinged door shutter and frame and fabricated out of 14 SWG sheet steel fitted with 4mm thick toughned glass in the front including finishing with powder coat/spray painting complete
Supply, erection, testing and commissioning of 'FIRE HOSE CABINET" fhc) OF SIZE (APPROX) 1200 mm X 600 mm X 2100 mm with hinged door shutter and frame and fabricated out of 14 SWG sheet steel fitted with 4mm thick toughned glass in the front including finishing with powder coat/spray painting complete.
(a) 63mm dia instantaneous pattern oblique single headed yard hydrant valve
(b) 63mm dia instantaneous pattern oblique single headed internal hydrant valve.
(c) 15 mtr 63mm dia controlled CP Hose with gun metal female instantaneous coupling as required.
(d) 15 mtr 63mm dia controlled RRL Hose with gun metal female instantaneous coupling as required.
(e) One branch pipe and nozzle with valve
(f) 19mm dia bore reinforced rubber of length 36.5m fitted with 6.35mm dia nozzle with a ball valve. The hose reel shall be recessed swinging type with rell drum hose provided with necessary couplings.
(g) One no 25mm dia ball valve
(h) Drawal out connection of gun metal with adequate pipe of MS
(j) Cabinet of MS for the drawl out connection
Supplying, erection, testing and commissioning of air release valve fitted on the top most point of the wet riser with riser with drain connection. The rate shall be inclusive of accessoires. 25mm dia ball valve and Air release valve.
Supply, erection, testing and commissioning of fire brigade inlet connection of the system confiming to IS 5290, of
Fire Brigade Inlet Connection Cabinet of appropriate size as required of ms construction with 4 mm thick glass on front
Supply, erection, testing and commissioning of sluice valves class PN-1, conforming to IS-14846, hand wheel operated, stainless steel stem with gunmetal parts, flanges drilled to IS-1538, non rising stem with body test pressure 15 Kg/cm² and seat test pressure 10 Kg/Cm2 complete, for following bore of pipes :
(a) 300mm dia.
(b) 200 mm dia
(c) 150mm dia
(d) 100mm dia
(e) 80mm dia
Supply, erection, testing and commissioning of slim seal type Non Return valves with Cl body & cast steel disc and tested to 10kg/ sqcm including a set of suitable Gl washers, rubber gaskets etc complete), for
(a) 150mm dia
(b) 100mm dia
(c) 80 mm dia.
Supply, erection testing & commissioning of pot strainer / Y strainer including rubber insertion, bolts, nuts, Gl flanges, etc complete for following bore of pipes:
(a) 150mm dia
(b) 100mm dia
Supply, erection testing and commissioniong of Air cushion tank of 200mm dia & 1000mm height with drain connection. The rate shall be inlcusive of accessoires. 25mm dia Air release valve and ball valve
Autostart panel for the Diesel engine complete auto / manual switch, indication lamps protective fuses with battery charges, suitable of working on 230 C, AC single phase, enclosure being vermin & dust proof suitable for auto-operation of diesel engine main fire hydrant pump centrifugal type capable to deliver 2850 Lpm at 70m head.
MS brackets fabricated out of angle / flats of required size with 6mm / 8mm GI U clamps with Gl washers and nuts etc for supporting GI / MS fire hydrant pipes running in fire dud pipes & ground floor ceiling level. The work shall also include making hole grouting the same in RCC slabs / masonry walls concrete and making good the same cement
12mm/15mm dia full threaded GI rods with necessary washers and nuts etc. for supporting GI MS fire hydrant pipes running in fire duct / terrace ground / basement floor ceiling level
12mm/15mm dia anchor fasteners for suspending Gl rods / brackets etc
1100V Grade Cables, PVC insulated armoured, copper/aluminium conductor, 1100V grade power cables, laid in trenches/ducts or passed through pipes etc, of following sizes :
(a) 4 core x 16 sq. mm Aluminium
(b) 4 core x 10 sqmm Aluminium
(c) 2 core x 1.5sq. mm copper
(d) Blank
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required, with following sizes of conductor:
(a) 25 x 3 mm Gl strip
(b) 50 x 6mm Gl Strip.
Gunmental / Cl foot valve spring operated type, tested to 2 kg / sq.cm, of following sizes :
Pressure Switch for Auto operation of fire pumps of approved make with fittings.
Pressure gauage of approved make 0-10 kgs, 4" dial with fittings complete
Earthing complete with galvanised steel earth plate 600mmx600mmx6mm thick burried directly in ground (earth plate not less than electrode 2.25m deep below normal ground level)with top edge of the plate not less than 1.5m below normal ground level connected to and including Gl earth strip 32x6mm by means of steel bolts, nuts, check nuts and washers, PCC 1:2:4 type B-1 in pit, angle iron 25x25x3mm frame work with precast RCC 1:2:4 type B-1 cover reinforced with 8mm dia TMT bars @ 150mm C/C both ways and 12 mm dia MS fabricated handle, light grade Gl watering pipe 20 mm bore with funnel, wire mesh, and connecting to test point, salt, charcoal, etc. including excavation and earth work in any type of soil, removal of surplus spoil to a distance not exc. 50m complete all as shown in electrical plate No. 3 of MES Schedule 2009 (Pt-I) and connected to main control board all as specified including testing on completion.
100 mm dia exhaust pipe from engine to ground floor level with flexible joint, silencer & fittings etc and insulating the exhaust pipe with 50 mm thick rock wool insulation and cladded with 22 gauge Aluminium sheet in an approved manner.
B: SPRINKLER SYSTEM Supply, erection, jointing, testing & commissioning of 'C' Class MS pipes (as per IS 1239). The pipes being suspended from beams, RCC roof slabs with necessary specials such as tees, bends, flanges redcuers etc., complete.Rate quoted shall also include for painting of pipe with one coat of primer & two coats of synthetic enamel paint of approved colour & make, of size :
(a) 150 mm dia
(b) 100 mm dia
(c) 80 mm dia
(d) 65 mm dia
(e) 50 mm dia
(f) 40 mm dia
(g) 32 mm dia
(h) 25 mm dia
Supply, erection, testing and commissioning of slim seal type butterfly valves with Shperoidal graphite iron disc (SG iron), with nitrile rubber seal and tested to 10kg/sq.cm including a set of suitable GI flange, as per BS 10 Table - 1, bolts, nuts Gl washer, neoperene rubber gaskets etc., complete. (intervalve make), of size
(a) 150 mm dia
(b) 200 mm dia
Supply.erection, testing and commissioning of 15mm dia nominal bore quartzoid bulb type sprinklers with temperature rating of 68 deg C conventional type the shall also include suspending arrangement with ceiling, wall arrangement with ceiling, wall beam clamps, fasteners ceiling rosette (incase of false ceiling) etc.,complete, of
(a) Concealed type
(b) Upright type
(c) Sidewall type
(d) Pendant type
Supply, Erection, testing & comissioning of SS Flexible Pipe of suitable dia and length required for connecting.
Providing and fixing of 12mm / 15mm dia anchor fasteners for suspending Gl rods / brackets etc
Flow switch installed on the sprinkler main distribution line connected to the main sprinkler annunciation panel located in the ground floor suitable for 100mm bore pipe.
Cast iron double flanged horrizontal type with gun metal seat non-return valve conforming to class 1 of IS-5312 incl nuts, bolts, gasket etc complete for 150mm dia pipe.
FIRE BUCKETS & STAND :
(a) Fire Bucket 9 Itrs with round bottom & Stand (Steel Stand with provision of 2 bucket fixing)
(b) Fire Bucket 9 Its. With round bottom & stand (Steel stand with provision of 4 buckets fixing)
(c) Fire beater
(d) Ceiling hook
(e) Fire gong
HFC 227 EA/HCFC Blend A Modular 10 kg capacity
Aerosole
FIRE DOOR
(a) One hr rating
(b) Two hr rating
D: FIRE ALARM SYSTEM Supply,installation, testing and commissioning of following:
(a) Blank
(b) Blank
Supply, installation, testing and commissioning of following Detectors & devices
(a) Intelligent addressable Optical Based smoke and heat detector with facility of numbering in the base( UL Listed)
Intelligent addressable Manual Pull Station and shall be resettable type.( UL Listed)
Duct detector( UL Listed)
Fault isolation module similar.
Intelligent addressable Control Module with following application.
Intelligent addressable input/monitor Module
Response Indicator
ELECTRONIC HOOTER
Power Supply unit with 12 V 7 Ah battery and with charger circuit for sounders.
2 Core X 1.5 Sq.mm multistrand armoured copper cable with all accessories and 2 complete in all aspects, the cable shall be having cable pointers at every 1 Meter. These cables shall be used for the wiring of detectors and devices.
Stove enamelled back steel conduit having wall thickness not less than 1.6mm, concealed type, including of all fittings such as elbows, tees, bends, reducers etc. as required, of 25mm dia.
LED lit laser etched fire exit sign complete with maintenance free battery of atleat1.5 hr duration with chrome finish, of
(a) Single side
(b) Double side
Gas Detector sensitron
Gas Detector Panel
Supply,installation, testing and commissioning of following:
(a) Intelligent addressable Micro processor based fire alarm control panel with02 loop capacity Networkable and expandable, with dual stage alarm facilities like hooter, fire / fault indicators, audio-visual signals, auto learn features, flexibility in shared zone mode or stand alone system, PC networking connectivity as RS232/RS485, communication facility, suitable for connect other systems. shall be interfaced to Graphic Software, having inbuilt power supply.
(b) Graphic Display Software with PC for the same shall be atleast of PIV capacity and of specified make only
Material and labour for Brick work using old site sub class B bricks built in cement mortar 1:6
Material and labour for PCC work 1:5:10 type E2 using 40mm graded stone agregates
Supply and fix bronze ball valve 50mm dia
Supply and fix CI sight glass 50mm dia
Supply , Errection, Testing and commissioning of slim seal type Non return valves with CI body and cast steel disc and tested to 10kg/sqcm including a set of suitable GI washers , rubber gasket etc complete of size 300 mm dia
SCH 'A' PART- XXV : AIR CONDITIONING WORK Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Testing & commissioning of the existing 'C' class black MS pipe of size 125 mm bore dia laid or fixed at wall surfaces or suspended in ceiling/RCC slabs with necessary fittings, supports & insulation etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Chilled Water Piping System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class black MS pipe of size 150 mm bore dia laid or fixed at wall surfaces or suspended in ceiling/RCC slabs with necessary fittings, supports & insulation etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Chilled Water Piping System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class black MS pipe of size 100 mm bore dia laid or fixed at wall surfaces or suspended in ceiling/RCC slabs with necessary fittings, supports & insulation etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Chilled Water Piping System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class black MS pipe of size 65 mm bore dia laid or fixed at wall surfaces or suspended in ceiling/RCC slabs with necessary fittings, supports & insulation etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Chilled Water Piping System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class black MS pipe of size 80 mm bore dia laid or fixed at wall surfaces or suspended in ceiling/RCC slabs with necessary fittings, supports & insulation etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directe. (for Chilled Water Piping System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class black MS pipe of size 50 mm bore dia laid or fixed at wall surfaces or suspended in ceiling/RCC slabs with necessary fittings, supports & insulation etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Chilled Water Piping System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class black MS pipe of size 40 mm bore dia laid or fixed at wall surfaces or suspended in ceiling/RCC slabs with necessary fittings, supports & insulation etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed (for Chilled Water Piping System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class black MS pipe of size 32 mm bore dia laid or fixed at wall surfaces or suspended in ceiling/RCC slabs with necessary fittings, supports & insulation etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Chilled Water Piping System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class black MS pipe of size 25 mm bore dia laid or fixed at wall surfaces or suspended in ceiling/RCC slabs with necessary fittings, supports & insulation etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Chilled Water Piping System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing GI sheet metal ducting (Rectangular), fabricated with 0.63mm (24 Gauge) sheet, testing shall be done in all technical aspects complete all as specified and directed by Engr-in-Charge, Qty- 7779.30 Sqm. (for GI Ducting) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing GI sheet metal ducting (Rectangular), fabricated with 0.80mm (22 Gauge) sheet, testing shall be done in all technical aspects complete all as specified and directed by Engr-in-Charge, Qty- 7882.51 (for GI Ducting) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing GI sheet metal ducting (Rectangular), fabricated with 1.00mm (20 Gauge) sheet, testing shall be done in all technical aspects complete all as specified and directed . (for GI Ducting) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing aluminium sheet metal ducting (Rectangular), fabricated with 0.80mm (22 Gauge) sheet, testing shall be done in all technical aspects complete all as specified and directed (for Aluminium Ducting) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing aluminium sheet metal ducting (Rectangular), fabricated with 1.00mm (20 Gauge) sheet, testing shall be done in all technical aspects complete all as specified and directed (for Aluminum Ducting) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing aluminium powder coated supply air diffuser with damper complete all as specified and directed. (for Grill) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing aluminium powder coated return air diffuser without damper complete all as specified and directed (for Grill) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Removal of existing old damaged/ defective EPS insulation from the existing class 'C' MS pipe line of size 400 mm bore dia laid in underground trenches and supply & fixing new EPS insulation on the same pipe line after complete removal of old damaged insulation including excavation in trenches upto 1.5m depth, returning-filling & removal of surplus soil at a distance not less than 50m away from the excacation point complete all as specified and directed. (for Chilled Water Piping System) "
Removal of existing old damaged/ defective EPS insulation from the existing class 'C' MS pipe line of size 350 mm bore dia laid in underground trenches and supply & fixing new EPS insulation on the same pipe line after complete removal of old damaged insulation including excavation in trenches upto 1.5m depth, returning-filling & removal of surplus soil at at distance not less than 50m away complete all as specified and directed. (for Chilled Water Piping System) "
Testing & commissioning of the existing 'C' class black MS pipe of size 400 mm bore dia laid in underground trenches with necessary fittings, supports & insulation etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Chilled Water Piping System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class black MS pipe of size 350 mm bore dia laid in underground trenches with necessary fittings, supports & insulation etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Chilled Water Piping System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class black MS pipe of size 250 mm bore dia laid in underground trenches with necessary fittings, supports & insulation etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Chilled Water Piping System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class black MS pipe of size 200 mm bore dia laid in underground trenches with necessary fittings, supports & insulation etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Chilled Water Piping System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class black MS pipe of size 150 mm bore dia laid in underground trenches with necessary fittings, supports & insulation etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Chilled Water Piping System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class black MS pipe of size 125 mm bore dia laid in underground trenches with necessary fittings, supports & insulation etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Chilled Water Piping System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class black MS pipe of size 100 mm bore dia laid in underground trenches with necessary fittings, supports & insulation etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Chilled Water Piping System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class black MS pipe of size 80 mm bore dia laid in underground trenches with necessary fittings, supports & insulation etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Chilled Water Piping System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class black MS pipe of size 65 mm bore dia laid in underground trenches with necessary fittings, supports & insulation etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Chilled Water Piping System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class black MS pipe of size 50 mm bore dia laid in underground trenches with necessary fittings, supports & insulation etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Chilled Water Piping System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class black MS pipe of size 40 mm bore dia laid in underground trenches with necessary fittings, supports & insulation etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Chilled Water Piping System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Testing & commissioning of the existing 'C' class black MS pipe of size 32 mm bore dia laid in underground trenches with necessary fittings, supports & insulation etc, testing shall be done in all technical aspects such as water leakages, pressure bearing capacity upto the bench mark & water hammer effects complete all as specified and directed. (for Chilled Water Piping System) (Note : All testing equipments shall be arranged by the contractor and cost of the same shall be included in the quoted item rate)"
Water Chilling Unit Supplying, fixing, testing and commissioning hermatically sealed water cooled centrifugal chilling unit 750 TR capacity complete with open/hermatically sealed compressor with motor condenser, chiller, controls, microprocessor based control panel, VFD panel with ACB, digital voltmeter & ammeter for incoming supply & load interconnecting refrigerant piping, base frame, concerete base for mounting the unit complete all as per specified with following features. Chilled water in : 12.2O C Chilled water out : 6.6O C Chiller F.F. : 0.0005 750 TR (Actual)
Pump Set Supplying, fixing, testing and commissioning horizontal split casing type water circulating pump sets complete with motor, base plate foundation etc. complete all as specified with following features/fixtures :-
(a) Chilled water pump, horizontal split casing type, 1800 USGPM at 40m. head (one standby).
(b) Condenser water pumps, horizontal split casing type, 2850 USGPM at 27m. head (one standby).
Secondary Chilled Water Pumps & Variable Speed Pumping System Supplying, fixing, testing and commissioning of secondary variable speed pumping system consisting of 2 Nos. secondary pumps, 1 No. dedicated microprocessor based pump controller with parallel pumping software duly downloaded, 2 Nos. adjustable frequency drives and multiple differential pressure sensor/ transmitters as necessary complete all as specified. Secondary chilled water pumps 3600USGPM at 30m. head. (one standby) Note:- The entire system alongwith secondary pumps must be sourced from single manufacturer only for unit responsibility. The system shall be complete in all respects and suitable for rating described hereinafter and as per specification.
Cooling Tower Supplying, fixing, testing and commissioning FRP induced draft type cooling tower complete with FRP basin, FRP body, fan, distribution pipes, overflow pipe, ladder including foundation etc. complete all as specified suitable for 750 TR.
Airhandling Unit Supplying, fixing, testing and commissioning of horizontal double skin floor mounted type airhandling units complete with fan, fan motor, drive, cooling coil, prefilters, microvee filter & HEPA filters, heaters, humidifier, mixing box, strip heaters, HRW canvass connection, fresh air damper with louvers & bird screen, including foundation, vibration isolator pads complete all as specified, of :-
(a) 20,000 cfm, 8 row coil
(b) 6,500 cfm, 8 row coil
(c) 6,000 cfm, 8 row coil
(d) 4,500 cfm, 8 row coil
(e) 4,000 cfm, 8 row coil
(f) 3,500 cfm, 8 row coil
(g) 2,500 cfm, 8 row coil
Airhandling Unit Supplying, fixing, testing and commissioning of horizontal double skin floor mounted type airhandling unit complete with fan, fan motor, drive cooling coil prefilters, microvee filter fresh air damper with louvers & bird screen, including foundation, vibration isolator pads complete all as specified, of :-
(a) 20,000 cfm, 6 row coil
(b) 18,000 cfm, 6 row coil
(c) 16,000 cfm, 6 row coil
(d) 15,000 cfm, 6 row coil
(e) 13,000 cfm, 6 row coil
(f) 10,000 cfm, 6 row coil
(g) 9,000 cfm, 6 row coil
(h) 8,000 cfm, 6 row coil
Unitary Airhandling Units Supplying, fixing, testing and commissioning of double skin ceiling mounted unitary type airhandling unit complete with fan, fan motor drive, cooling coil, filters, canvass connections, 2 way throttling valve with snap acting thermostat etc. complete all as specified, of :-
(a) 6,000 cfm, 6 row coil cooling
(b) 5,000 cfm, 6 row coil cooling
(c) 4,000 cfm, 4 row coil cooling
(d) 3,000 cfm, 4 row coil cooling
(e) 2,000 cfm, 4 row coil cooling
Blank
Air Purifier Supplying, fixing, testing and commissioning of Photo hydro ionization cell based on advanced oxidation technology with broad spectrum UV tube duly enclosed in hydrated catalytic matrix cell with the capability to produce friendly oxidizers like hydro peroxides, super oxide ions, ozonide ions & hydroxide ions, duly encased in poly tube to prevent glass or mercury leakage into the atmosphere, the cell will have built in fiber optic device as remote indication of this operation complete all as specified, of :-
Packaged Type Airwasher Supplying, fixing, testing and commissioning packaged type airwashers of G.I. construction fabricated from 16 gauge G.I. sheet body, blower housing, centrifugal forward curved blower with motor, drive set, acetate paper cooling pad of 90% effeciency with stainless steel sump and body, pump, water connection, Aluminum filters, canvas connection, mounting base of angle iron/chennel etc. blower & motor mounted on common rail using cushy foot mounting and M.S. frame for supports etc. complete all as specified, of :-
(a) 40,000 cfm, 50 mm static pressure
(b) 30,000 cfm, 50 mm static pressure
Axial Flow Fan Supplying, fixing, testing and commissioning axial flow type exhaust fan complete with fan and motor, drive set, mounting frame, mounting accessories canvass connection, gravity damper of G.I. at fan outlet and electric control panel with cabling and earthing complete all as specified (Fan to be suspended from ceiling/ installed on wall with M.S. supports of and mounting accessories etc. and Fan should be interlocked with fire panel of 3,000 cfm, 20 mmwg S.P. each
Propeller Type Fan Supplying, fixing, testing and commissioning of propeller type fan for fresh air supply and exhaust complete all as specified of 5000 cfm, 610 mm dia each
Exhaust Scrubber Supplying, fixing, testing and commissioning of centrifugal exhaust scrubber of 18 gauge sheet steel duly powder coated inner & outer construction with fan and motor and drive (both fan and motor shall be mounted on a common frame using cushy foot mounting) with side suction and front discharge including vibration isolator, water tank with float valve, pump, distributor, nozzels, eleminator, piping & valve from tank to pump to distributor, and M.S. frame for supports etc. complete all as specified for 50,000 cfm, 65 mmwg static pressure
Air Curtain Supplying, fixing, testing and commissioning of air curtains with decorative casing, fan, motor, remote etc. complete all as specified of 1500 mm length each
Inline Fans Supplying and fixing inline fans of G.I. construction complete with centrifugal fan with motor, canvass connection at inlet and outlet complete with electric panel with MCB and relays, cabling and earthing complete all as specified, of :-
(a) 1600 cfm, 20 mm S.P.
(b) 1000 cfm, 20 mm S.P.
(c) 800 cfm, 20 mm S.P.
Hot Water Boiler Supplying, fixing, testing and commissioning of Horizontal fire tube boiler operative. All accessories, including automatic burner pre heaters interconnecting H.P. flexible/ copper piping. Fuel pumping and blower with damper & auto electric sequance control/ operational panel complete all as specified of 10,00,000 Kcal / Hr (1176 Kw) Each
Heat Exchanger Supplying, fixing, testing and commissioning of plate type heat exchanger of 600000 kcal capacity with stainless steel plates of variable surface with nitril rubber gasket, carbon steel frame, etc. complete in all respect and all as specified.
Condenser Water Piping Supplying, fixing, testing and commissioning `C' class mild steel - black steel pipes in condensor water piping system with all necessary fittings incl bends, tees, reducers, flanges, supports etc. complete all as specified, for
(a) 600 mm dia
(b) 300 mm dia
Butterfly Valves class 1, PN-1.6 conforming to IS-13095 of 1991 complete with flanges, bolts, nuts, gasket etc. As per specifications, hydroulically tested to 20 kg/cm2 complete in all respects, suitable for
(a) 600 mm dia pipe
(b) 300 mm dia pipe
Cast iron balancing Valves confirmation to IS, class 1 incl nuts, bolts, gasket etc complete suitable for 300 mm dia pipe
Cast iron double flanged horrizontal type with gun metal seat Non Return Valves confirming to class 1 of IS-5312 incl nuts, bolts, gasket etc complete suitable for 300 mm dia pipe
Pot Strainers incl rubber insertion, bolts, nuts, G.I. Flanges etc complete, suitable for following bore of pipes :-
(a) 600 mm dia
(b) 300 mm dia
Water flow switch (incl for chilled water supply)
Pressure gauge (incl for chilled water supply)
Thermometer (incl for chilled water supply)
Flexible Pipe Connection of suitable length for 300 mm bore pipe complete
Chilled Water Piping Supplying, fixing, testing and commissioning `C' class mild steel black steel pipes with all necessary fittings, supports & insulation etc. complete all as specified, of
(a) Blank
(b) Blank
(c) Blank
(d) 125 mm dia
(e) 150 mm dia
(f) 100 mm dia
(g) 65 mm dia
(h) 80 mm dia
(j) 50 mm dia
(k) 40 mm dia
(l) 32 mm dia
(m) 25 mm dia
Butterfly Valves Class 1, PN-1.6 conforming to IS-13095 of 1991 complete with flanges, bolts, nuts, gasket etc. As per specifications, hydroulically tested to 20 kg/cm2 complete in all respects, suitable for
(a) 350 mm dia pipe
(b) 250 mm dia pipe
(c) Blank
(d) 150 mm dia pipe
(e) 65 mm dia pipe
(f) 50 mm dia pipe
Ball Valves suitable for pipes of dia
(a) 40 mm with strainer
(b) 40 mm without strainer
(c) 32 mm with strainer
(d) 32 mm without strainer
(e) Blank
(f) Blank
Cast iron balancing Valves confirming to IS, class 1 incl nuts, bolts, gasket etc complete, suitable for following dia pipes:-
(a) Blank
(c) Blank
(d) Blank
Cast iron doubleflangged horrizontal type with gun metal seat non-return valve conforming to class 1 of IS-5312 incl nuts, bolts, gasket etc complete, suitable for following dia pipes :-
(a) Blank
Pot Strainer, of size
(a) Blank
Air purge valve (15 mm)
Flexible Pipe for Connection of suitbale and required length of following bores :-
(a) Blank
Expansion Tank Supplying, fixing, testing and commissioning expansion tank fabricated from 3 mm thick M.S. sheet having 50 mm thick polyurethen foam insulation covered with 26 gauge Aluminium sheet with main hole cover drain, over flow, quick fill, normal water supply connections complete in all respect and all as specified of 4000 litres capacity.
Drain Piping Supplying, fixing, testing and commissioning G.I. drain piping complete with fittings, supports valves and 15 mm thick polyurethen foam insulation complete all as specified, for following dia :-
Ducting Supplying, fixing, testing and commissioning steel metal ducting complete with supports, dampers, etc. all as specified. (i) G.I. Sheet Metal Ducting (Rectangular), fabricated with
(a) 0.63 mm (24 Gauge)
(b) 0.80 mm (22 Gauge)
(c) 1.00 mm (20 Gauge)
(d) 1.25 mm (18 Gauge)
(ii) Aluminium Ducting (Rectangular), fabricated with
(a) 0.80 mm (22 Gauge)
(b) 1.00 mm (20 Gauge)
Insulation Supplying and fixing of glass wool insulation on ducts complete all as specified of 25 mm thickness.
Supplying and fixing of UV/fire/water, thermal protective, canvas coating on duct insulation by wrapping canvas cloth dipped in star bond 30-36, complete all as specified.
Duct Acoustic Lining Supplying and fixing of duct acoustic lining with bonded glass insulation of density 32 kg/m3 covered with 26 gauge perforated aluminium sheet with nuts and bolts complete all as specified of 25 mm thickness.
Grills Supplying, fixing, testing and commissioning Aluminium powder coated supply and return air grilles/diffusers complete all as specified, for
(a) Aluminium supply air diffuser with damper.
(b) Aluminium return air diffuser without damper.
(c) Aluminium return air grilles without damper.
Fresh/Return Air Grilles
(a) Fresh/Exhaust air damper with louvers, bird screen and damper.
(b) Double louvered fresh air grill with damper (for airwasher).
Fire Damper Supplying and fixing galvanised sheet fire dampers complete with damper electric actuator, smoke/heat detector, interlocking arrangement with blower motor complete all as specified. (Opening of fire damper in wall/ partition to be cut and later made good to a fire rating of similar capacity as of damper without any extra cost to Govt), for
(a) Fire dampers
(b) Actuator assembly
Volume Control Damper Supplying and fixing G.I. volume control damper with blades, adjustable lever, frame etc. complete all as specified.
(B) Bus Coupler : 01 No. 2000 Amp capacity triple pole metal clad bus coupler panel extensible panel provided with under mentioned equipments:- (i) Electrolytic copper bus bar 2000 Amps for phases and 1250 Amps for neutral - 01 Set (ii) ACB 1600 Amps trip free withdrawable type manual operated with mechanical ON/OFF indicator, auxiliary switches and safety features - 01 No. (iii) Red and Green indicating lamps to indicate ON/OFF position - 01 Set (iv) Electricial/ Mechanical inter lock - 01 Set. (v) Cable boxes/side frame - 01 Set. (C) Out Going 1(a) 02 Nos 1250 Amps capacity triple pole metal clad outgoing feeder control panel extensible pattern each provided with following equipments/ accessories :- (i) Electrolytic copper bus bar 2000 Amps for phases and 1250 Amps for neutral - 01 Set (ii) ACB 1250 Amps trip free withdrawable type manual operated with mechanical ON/OFF indicator, auxiliary switches and safety features - 01 No. (iii) CT's of ratio 1250/05 Amps of suitable VA burden and accuracy for protection and metering - 01 Set. (iv) Static trip devices for over current and earth fault - 01 Set. (v) Under voltage release - 01 No. (vi) Red and Green indicating lamps to indicate ON/OFF position - 01 Set
Power Cabling Supplying and fixing PVC sheathed Aluminium cables with for various equipments through walls/ceiling/cable tray with appropriate clamps & fixing arrangements including M.S. perforated cable tray complete all as specified of
(a) 31/2 C - 400 sqmm
(b) 31/2 C - 240 sqmm
(c) 4 C - 6 sqmm
(d) 4 C - 4 sqmm
Control Consol Supplying, fixing, testing and commissioning desk type control consol floor mounted paneled type fabricated from 2.0 mm CRCA sheet with indication lamp, ON/OFF/FAULT lamps alarm relays and internal wiring.
Control Cabling Supplying, fixing and terminations of multicore PVC control cabling of copper 1.5 sqmm upto control consol panel board through walls/ceiling/cable tray with appropriate clamps and fixing arrangements complete all as specified.
Earthing Conductor Double earthing continuity conductors of G.I. between panel boards and equipments as required of size.
(a) 32 x 6 mm (Strip)
(b) 8 SWG (wire)
(c) 10 SWG (wire)
Supply and fixing rotational moulded polyethylene water storage tank (cylintrical vertical with closed top), hoisted and fixed in position all as specified in SSR Part-I for 1000 litre capacity incl and providing brass float valve of suitable dia of inlet pipe with polythene float and fly nut complete screwed for iron pipe complete all as specified. Note : Tank to be hoisted on roof of existing pump house building and all inlet, outlet, washout and over flow pipes shall be measured under respective parts of Sch 'A'.
Supplying, fixing, testing and commissioning underground 'C' class mild steel black steel pipes with necessary fittings and insulation (expandable polystyrens thermcol) etc complete all as specified.
(a) 400 mm dia
(b) 350 mm dia
(c) 250 mm dia
(d) 200 mm dia
(e) 150 mm dia
(f) 125 mm dia
(g) 100 mm dia
(h) 80 mm dia
(j) 65 mm dia
(k) 50 mm dia
(l) 40 mm dia
(m) 32 mm dia
M&L for brick work using sub class B bricks in cement mortar 1:6 for brick pillar of UG chiller pipe line
M&L for PCC work 1:5:10 type E2 using 40 mm graded aggregate for brick pillar of UG chiller pipe line
M&L for Ball valve of 15 mm dia for drain pipe
M&L for Ball valve of 32 mm dia for drain pipe
M&L for 2 way motorised Ball valve of 200 mm dia
M&L for 2 way motorised Ball valve of 100 mm dia
M&L for 2 way motorised Ball valve of 80 mm dia
M&L for 2 way motorised Ball valve of 65 mm dia
M&L for 2 way motorised Ball valve of 50 mm dia
M&L for 2 way motorised Ball valve of 40 mm dia
M&L for 2 way motorised Ball valve of 32 mm dia
M&L for strainer of size 100 mm dia made of cast iron flanged type
M&L for strainer of size 80 mm dia made of cast iron flanged type
M&L for strainer of size 65 mm dia made of cast iron flanged type
M&L for strainer of size 50 mm dia made of cast iron flanged type
M&L for strainer of size 40 mm dia made of cast iron flanged type
M&L for strainer of size 32 mm dia made of cast iron flanged type
M&L for strainer of size 15 mm dia made of cast iron flanged type
M&L for additional accessories to hot water boiler for air conditioning work
Supply, fixing, testing and commissioning day tanks of 990 liters fuel oil tanks fabricated out of 5mm thick MS sheet with all fittings like level gauge glass
Supply, fixing, testing and commissioning of fuel duct (bare size) fabricated out of 5mm thick MS sheet for 250 mm dia
Supply, fixing, testing of Gay supported chimney of top dia 675mm, 30 meter height made out of MS sheet.
Supply, fixing of softner of 1200 liters per hour for Hot water boiler
Supply, fixing, testing and commissioning of water pump suitable for softening plant of cap 1200 liters per Hr @ 50 liters per minute @ 30 m head.
Air Handling Unit Supplying, fixing, testing and commissioning of horizontal double skin floor mounted type air handling unit complete with fan, fan motor drive, cooling coil, prefilters, microvee filter fresh air damper with louvers & bird screen, including foundation, vibration isolator pads complete all as specified of :- (a) 24000 cfm, 6 row coil
Unitary Air Handling Unit Supplying, fixing, testing and commissioning of double skin ceiling mounted unitary type air handling unit complete with fan, fan motor, drive, cooling coil, filters, canvas connections, 2 way throttling valve with snap acting thermostat etc. complete all as specified of :- (a) 7000 cfm, 6 row coil
Butterfly valves class 1, PN-1.6, gear operated, conforming to IS-13095 of 1991 complete with flangs, bolts, nuts, gasket wtc, as per specifications, hydraulically tested to 20 Kg/Sqcm complete in all respects, suitable for (a) 400 mm dia
Butterfly valves class 1, PN-1.6, gear operated, conforming to IS-13095 of 1991 complete with flangs, bolts, nuts, gasket wtc, as per specifications, hydraulically tested to 20 Kg/cmm2 complete in all respects, suitable for
(a) 100 mm dia
(b) 80 mm dia
(c) 40 mm dia
Cast iron balancing valves conforming to IS, class 1 incl nuts, bolts, gasket etc complete suitable for following dia pipes :-
(a) 100 mm dia
(b) 80 mm dia
Pot Stariner of size :- 400 mm
Air Pulge Valve (25mm)
Providing and fixing rubber expension bellows with control rods/ spacers in pipe connection to equipment of size 400 mm
SCH 'A' PART- XXVI : COMMUNICATION SYSTEM Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Rigid galvanised steel conduit, consealed type, welded, exclusive of junction & terminal boxes, but inclusive of all fittings such as tees bends elbows, reducers, bell mouth tube ends and all fixing accessories such as couplers lock nuts, saddles pipe, hook, etc., of 20mm dia bore for Intercom, musical system, TV Cable system, PA system & Computer system.
Dismentalling & taking down of existing wall/surface mounted steel conduit of size 20mm dia alongwith flexible copper cable inclusive all fittings such as tees, bends, elbows, reducers, bell mouth tube ends & all accessories such as couplers, lock nuts, saddles pipe, hook etc and refixing the existing steel conduit alongwith copper flexible cable on the same wall/surface as consealed type and making good the damaged surfaces occured due to chiseling & grooving work done during refixing of steel conduit in existing wall surfaces complete all as specified and directed.
All as per item ser No 970 above but of 25mm dia bore.
Junction box with cover any number or types of outlets, as ordered for rigid galvanised steel conduit of size 20mm dia.
All as per item ser No 972 above but for 25mm dia steel conduit.
Perforated type GI trays for holding galvanised steel conduit of following sizes fabricated from perforated 2mm thick Mild Steel galvanised CRCA Sheet with expansion coupler, GI plates with bolts,nuts & washers,knock out hole, supporting fish platesand accessories, down rods-fasterners complete all as required at site.
(a) 150mm widex40mmx40mm
(b) 300mm widex40mmx40mm
SCH 'A' PART- XXVII : SIGNAGES WORKS
Composite Signage Ceiling hung : Composite signage, false ceiling suspended type, having 2 or 3 assorted pictograms/ text about department/ clinic/ ward type along with direction arrows on either side of the floor depiction in figure as well words, on either face readable from both sides, made up of 0.8mm thick standard modular aluminium graphic arc double surface panels. The Aluminium panel shall be secured with five Abs supporting strips (Polka Model PL-317) in size, for 1500mm over all length, two of which shall be at the end. A pair of Arc hidden aluminium extruded cum slotted rails fixed to a double sided aluminium extruded fixing rail to full length of panel shall be clipped on to the Abs Supporting strip at two designed points having built in clipping device. The ends of the united pair of Arc hidden rails shall be plugged with Arc double surface end cover on either end Text letters/ pictograms duly electonic plotter cut in coloured vinyl shall be pasted on to the powder coated surface of the aluminium panel. The signage unit shall be suspended from ceiling with custom designed stainless steel suspension rods as per fixing detail. The Composite Signage Ceiling hung shall have different depiction in accordance to their situation at each floor as per distribution as under :- (a) Basement Floor - 05 Nos. (b) Ground Floor - 07 Nos. (c) First Floor - 07 Nos. (d) Second Floor - 07 Nos (e) Third Floor - 06 Nos (f) Fourth Floor - 06 Nos
Department Sign Ceiling. Department Sign close to ceiling level either mounted on wall above door height or suspended from false ceiling, having requisite Department/ Clinic/ Ward's Inscription. The DSC shall of standard Aluminium profile (Illusion modle C-150) of size 600mm x150mm with Abs side cap on either end. The DSC unit shall either be screwed to wall surface or suspended from false ceiling. The exposed surface of the profile shall have removable 0.6mm thick polycarbonate film covering to enable the user to insert the requisite Department/ linic/ Ward's inscription. The distribution of DSC shall be as under :- (a) Basement Floor - 06 Nos. (b) Ground Floor - 35 Nos. (c) First Floor - 21 Nos. (d) Second Floor - 13 Nos. (e) Third Floor - 09 Nos. (f) Fourth Floor - 08 Nos.
Wall Bracket Sign. Wall Bracket Sign shall be made of 0.8mm thick standard modular aluminium graphic arc double surface panels 200mm wide, secured with two Abs Supporting strips (Polka model PL-253) in size. A pair of Arc hidden aluminium extruded cum slotted rails anchored to a double sided aluminium extruded fixing rail to full width of panel shall be clipped to the Abs Supporting strip at two designed points having self built in clipping device. The ends of the united pair of Arc hidden shall be plugged with Arc double surface end cover on exposed end, supported to standard extruded aluminium wall rail to form the bracket. The wall rail shall be fixed to wall surface with aluminium screws and rawl plugs. Text letters/ Pictograms duly electronic plotter cut in coloured vinyl shall be pasted on the powder coated surface of the aluminium panel on either face. Wall Bracket Sign shall be of following type :-
(a) Air Handling Unit - 41 Nos.
(b) Dining - 41 Nos.
(c) Dirty Utility - 35 Nos.
(e) Electric Room - 26 Nos.
(f) Female Toilet - 31 Nos
(g) His - 05 Nos.
(h) Janitor Closet - 10 Nos
(j) Male Toilet - 30 Nos
(k) Officer's Toilet - 11 Nos
(l) Pantry - 32 Nos.
(m) Wet Riser - 05 Nos
(n) Stairs - 35 Nos
(o) Stores - 56 Nos
(p) Soiled Linen - 29 Nos
(q) Sluice Room - 06 Nos
(r) Toilet - 44 Nos.
(s) UPS - 08 Nos
Floor Polka Sign. Floor Polka Sign suspended from ceiling made up of 0.8mm thick standard modular aluminium graphic arc double surface panels secured with two Abs supporting stips (Polka Model PL-317) in size at either end of its 300mm lengths. A pair of Arc hidden aluminium extruded cum slotted rails anchored to a double sided aluminium extruded fixing rail to full length of panel shall be clipped to the Abs supporting strip at two designed points having self built in clipping device. The ends of the united pair of Arc hidden rails shall be plugged with Arc double surface end cover on either end. Floor reference duly electronic plotter cut in coloured vinyl shall be paster on to the powder coated surface of the aluminium panel. FPS Shall be 2 on each floor in the Lifts Lobby along side Hospital street.
Floor Directory Sign. Floor directory Signage unit on wall surface. The unit shall comprise of flat sign series of Aluminium anodised extruded top flat panel 124mm wide & subsequent number of flat panels 62mm wide on required basis (model 2124 and 2062 respectively), edge progile (model 2303) on either side. The unit shall measure 600x124 mm +62mm x number of panels required on each floor. Number of flat panels shall be 13 at Ground Floor, and 5 at basement floor. Each of the flat panel shall be provided with 4 numbers 31mm low height plastic holders (model 2502) for sliding in edge profile. The edge profile shall be provided with plastic pole cap on top and bottom end (model 2559 for left side and 2560 for the right side). The unit thus formed shall be fixed on 12mm thick MDF board duco painted of shape as per drawing, which in turn shall be fixed to wall surface using wood screws and rawl plugs.
Door Plate Sign. Door Plate Sign shall be laser cut 3 mm thick ACP pasted over 3mm thick coloured acrylic measuring 120x180mm. The ACP shall have CNC router cut pictogram/ words as per facility use. The Plate shall be fixed on door shutter with 4-12mm dia black powder coated steel studs. In case of DPS/B, DPS/Ba, DPS/W&DPS/Wa the size of plate shall be 120x120mm. Door Plate Sign shall be of following type :-
(a) Air Handling Unit - 40 Nos
(b) Bath - 43 Nos.
(c) Bath Assist - 26 Nos.
(d) Change/ Dress - 10 Nos.
(e) Dining - 42 Nos.
(f) Dirty utility - 35 Nos.
(g) Electric Room - 24 Nos.
(h) Female Toilet - 31 Nos.
(j) His - 05 Nos.
(k) Janitor Closet - 35 Nos.
(l) Male Toilet - 30 Nos.
(m) Officer's Toilet - 11 Nos.
(n) Pantry 49 Nos.
(o) Wet Riser - 05 Nos.
(p) Stairs - 05 Nos.
(q) Stores - 56 Nos.
(r) Shaft - 05 Nos.
(s) Soiled Linen - 29 Nos.
(t) Sluice Room - 05 Nos.
(u) Under ground sump - 05 Nos.
(v) Toilet - 244 Nos.
(w) Telephone - 03 Nos.
(x) Wet Riser - 05 Nos.
(y) UPS - 08 Nos.
(z) Water Closet - 141 Nos.
(aa) Water Closet Assist - 39 Nos.
Wall Plate Sign. Wall plate signage shall be laser cut 3mm thick ACP pasted over 3mm thick coloured acrylic measuring 120x180mm. The ACP shall have CNC router cut pictogram/ words as per facility use. The plate shall be fixed on wall with 4-12mm dia black powder coated steel studs with screws and rawl plugs. Wall plate sign shall be of following type :- (a) Drinking Water (Cooler) - 28 Nos. (b) Reception - 27 Nos. (c) Receipt / Issue - 02 Nos. (d) Shops - 05 Nos. (e) Trollery Bay - 39 Nos. (f) Waiting - 58 Nos.
Room Use Plate. Room use plate of size 250x60mm of aluminium extruded profile with Abs side caps, "ILLUSION" Model C-060 having removable 0.6mm thick polycarbonate film cover. The sign plate shall be screwed on to wall surface by the side of rooms door.
Room Number Plate. Room Number Plate of size 120x80mm of aluminium extruded profile with Abs side caps, "ILLUSION" model C-060 having removable 0.6mm thick poly carbonate film cover. The sign plate shall be screwed on to wall surface by the side of door and over BUP
Fire Safety Signs. Self Contained Rechargeable Emergency Exit/Egress Light Sign (Surface mounted). The signage shall conform to IS-9583-1981 and to meet the technical conditions such as Battery duration+/-10%, Red LED "ON" indicates charging, Equipped with push Test Switch, 22 SWG CRCA white powder coated housing, and input-230v, 50 Hz. The signage shall be maintainable for 3 hours with backup of 1x11 CFL. SLA Rechargeable Battery 10 to 12 hours. Self contained Rechargeable Emergency LED Exit/Egress Edgelit Lights Signage.
Parking Warning Signs. Warning sign measuring 200x200mm shall be of CNC router cut 3mm Aluminium anodised sheet duly powder coated with vinyl cut pictogram of three types on one side. The sign shall be fixed on wall surface in the basement parking areas.
Indoor signs for evacuation / fire / lift / stairs / ramps. Vinyalized SAFETY GRADE - VG - Q1++1 mm aluminium based Hi - grade luminescent glow in the dark signs to be installed in the interiors with more than 10 hours glow capacity duly cut to size and individually printed as per the different govt, standards with specific text / graphics / language colour combinations size and code as directed by GE, duly installed with mirror screws and supporting powder coated aluminium / PVC based signs hangers as required at site for fixing double sided signs of different height and width as under :-
(a) 8 inch height and 20 inch width, size / code : EV-01 820.
(b) 6 inch height and 12 inch width, size / code : EVST-02 612.
(c) 8 inch height and 8 inch width, size / code : LT-03 88.
(d) 6 inch height and 8 inch width, size / code : FF-04 68.
(e) 6 inch height and 6 inch width, size / code : FL-05 66.
(f) 4 inch height and 11 inch width, size / code : BG-06 411.
(g) 6 inch height and 16 inch width, size / code : EVSTS-07 616.
(h) 6 inch height and 16 inch width, size / code : EVSTD-08 616.
PART- XXVIII : LIST OF WORKS AND PRICES FOR OT WORKS Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Twin plate X-ray viewing screen designed to provide a high level of control luminance without flicker, size 1000mm x 700mm x 95mm deep, indigenous, complete all as specified. Make : MPS / APEX ENG / MANJOT
Writing Board with magneting system of size 1000mm x 700mm x 60mm deep made of G.P sheet flushed with the wall system complete all as specified (Indegenous). Make : MPS / APEX ENG / MANJOT
Storage unit size 1666mm x 865mm x 350mm having two shelves, made of zinc passivated steel with 5mm thick glass door & mounted flush with the theatre wall (Indegenous). Make : MPS / APEX ENG / MANJOT.
Recess mounted bottom opening, clear room luminaire (peripheral light) with dimming, each having 2x36W CFL, Electronic ballast (size 2'x1') complete all as specified (Indegenous). Make : MPS / APEX ENG / MANJOT.
PART- XXIX : LIST OF WORKS AND PRICES FOR LIFT WORKS Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Testing & commissioning of 20 passengers Gearless lift with machine room to serve Basement, Ground+4th upper floors with AC variable voltage & variable frequency (VVVF) drive complete with all accessories, full collective duplex (adjacent) controlled operation, side opening power doors with door drive (electric motor driven mechanism) sliding stainless steel doors, Automatic Rescue device system and built in intercom system without hand se & infra red curtain, all as specified herein under :- (i) Type and capacity of Lift : 20 Passengers.-1360 kgs (ii) Speed: 1.0 M/sec (iii) Type of Drive: V3F(variable voltage & variable frequency (iv) Machine room : Top (v) Travel - 21.750 Mtrs (Approx) (vi)Serving : Basement, ground to 4th Floor( Floor designations will be-1, 0,1,2,3,4) (vii) No of stop : 6 (viii) Available well size: 2250mm(W) x 3050mm(D) (After plaster in plum) (ix) Power supply: 415 Volts, 3 phase, AC, 50 Hz (x) Auxiliary : Single phase 220 volt 50 C/s AC (xi) Car size (inside): 1300mm (W)x 2400mm(D)x2200mm(H) (xii) Pit depth : 1600 mm (xiii) Head room : 5000 mm (xiv) Car enclosure: Car ceiling : SS hairline finish ceiling with fan(CT002), Car panels : SS hairline finish panels, Car Flooring : Aluminium chequered plate flooring, Car Illumination : CFL light (xv) No of entrance Front opening in all landings (xvi) Car entrance : Centre opening, power doors in stainless steel hairline finish. (xvii) Door safety : Full height infra red curtain (xviii) Landing Entrance: Centre opening, power doors in stainless steel hairline finish for car & landing at all floors.
(xix) Clear opening : 1200mm(W) x 2000mm (high) (xx) Control : Full collective duplex (adjacent) (xxi) Indicator: (a) Car: KDS300 COP-Partial height with seven segment Red indicator and round surface mounted butttons. (b) Landing : KDS300LCI-seven segment Red indicator and round surface mounted buttons FEATURE (a) Direction and position indicator in car . (b) Emergency Alarm. (c) Facia Plate (d) 2 phase fire man drive (e) Two way hands free press & speak intercom (f) Full height Infra red safety curtains with criss cross beams (g) Pit ladder (h) Emergency light with rechargeable battery (j) Adjustable guide shoes (k) Micro movement LED base buttons (l) + 10% To - 10 % volt fluct base button (m) Mirror on rear side (half height) (n) Over speed governer (o) Load weighing device (p) Automatic phase reversal (q) Manual rescue Operation. (r) Pressure limit& in doors (s) Car door lock (t) Automatic rescue device/automatic landing device to be operated with maintenance free batteries for safe landing as specified. "
Testing and commissioning of 26 passengers Gearless lifts with machine room to serve Basement, Ground+4th upper floors with AC variable voltage & variable frequency (VVVF) drive complete with all standard accessories, full collective duplex (Adjacent) controlled operation, side opening power doors with door drive (Electric motor driven mechanism) sliding stainless steel doors, Automatic Rescue device system and built in intercom system without hand set & infra red curtain, all as specified herein under :- (i) Type and capacity of Lift : 26 Passengers.-1768 kgs (ii) Speed: 1.0 M/sec (iii) Type of Drive,: V3F (variable voltage & variable frequency) (iv) Machine room c: Top (v) Travel - 21.750 Mtrs (Approx) (vi)Serving : Basement, ground to 4th Floor( Floor designations will be-1, 0,1,2,3,4) (vii) No of stop : 6 (viii)Available well size :2250mm(W) x 3050mm(D) (After plaster in plum) (ix) Power supply: 415 Volts, 3 phase, AC, 50 Hz (x) Auxiliary : Single phase 220 volt 50 C/s AC (xi) Car size (inside): 1300mm (W)x 2400mm(D)x2200mm(H) (xii) Pit depth : 1600 mm (xiii) Head room : 5000 mm (xiv) Car enclosure: Car ceiling : SS hairline finish ceiling with fan(CT002), Car panels : SS hairline finish panels, Car Flooring : Aluminium chequered plate flooring, Car Illumination : CFL light (xv) No of entrance Front opening in all landings (xvi) Car entrance : Side opening, power doors in stainless steel hairline finish. (xvii) Door safety : Full height infra red curtain (xviii) Landing Entrance: Side opening, power doors in stainless steel hairline finish for car & landing at all floors.
xix) Clear opening : 1200mm(W) x 2000mm (high) (xx) Control : Full collective duplex (adjacent) (xxi) Indicator: (a) Car: KDS300 COP-Partial height with seven segment Red indicator and round surface mounted butttons. (b) Landing : KDS300LCI-seven segment Red indicator and round surface mounted buttons FEATURE (a) Direction and position indicator in car . (b) Emergency Alarm. (c) Facia Plate (d )2 phase fire man drive (e) Two way hands free press & speak intercom (f) Full height Infra red safety curtains with criss cross beams (g)Pit ladder (h) Emergency light with rechargeable battery (j) Adjustable guide shoes (k) Micro movement LED base buttons (l) + 10% To - 10 % volt fluct base button (m)Mirror on rear side (half height) (n) Over speed governer (o) Load weighing device (p) Automatic phase reversal (q) Manual rescue Operation. (r) Pressure limit& in doors (s) Car door lock (t) Automatic rescue device/automatic landing device to be operated with maintenance free batteries for safe landing as specified. "
Total Amount of Sch 'A' Part - XXX (DEVIATION ORDER FOR CERTAIN CHANGES IN ONE BLOCK OF 05 AND TWO BLOCKS OF 06 MD QTRS FOR ORS ACCN AGAINST SCH 'A' PART-I SI ITEM NOS 18 & 19 (DUE TO REDUCTION OF PLINTH AREA) Notes:- (i) Go ahead approvals/approvals in principle for the changes/works has bee accorded during currency of previous cancelled contract. These changes shall be measured and paid for seperately under this schedule.
Total Amount of Sch 'A' Part -XXXI (DEVIATION ORDER FOR CERTAIN CHANGES IN ONE BLOCK OF 06 MD QTRS FOR JCOs ACCN AGAINST SCH 'A' PART-I SI ITEM NO 17 (DUE TO REDUCTION OF PLINTH AREA) Notes:- (i) Go ahead approvals/approvals in principle for the changes/works has bee accorded during currency of previous cancelled contract. These changes shall be measured and paid for seperately under this schedule.
PROVISIONAL SUM FOR CERTAIN BUILDING WORK Provide Provisional Sum of Rs 825000.00 for construction of block for housing ETP, sewage cum Pump house and water softening pumps with accessories/fitments etc. Notes:- (i) The work of provisional sum shall be carried out by the contractor only after written order of GE. The work order shall be placed by the GE duly priced on SSR 2004 Part-II rates. (ii) Building work shall be executed as per the work order placed by GE based on the drawings provided during currency of work. Measurements for entire work executed under provisional sum shall be recorded in MB and shall be form basis for making payment. (iii) Internal/external services and earthwork shall be measured under respective items of Sch 'A'/BOQ.
Schedule of Credit (for demolished buildings) Deduct Schedule of credit worth Rs. 411801.17 (Minus) as listed in Schedule 'A' Part - XXXII Note : Tenderers will not quote against this item being a firm amount at present. Contract Sum will be worked out after deducting the credit schedule amount during acceptance of tender.
Schedule of Credit for material lying at site Deduct Schedule of credit worth Rs. 170845733.90 (Minus) as listed in Schedule 'A' Part - XXXIII (Sec-A) Note : Tenderers will not quote against this item being a firm amount at present. Contract Sum will be worked out after deducting the credit schedule amount during acceptance of tender.
Schedule of Credit for material lying at site Deduct Schedule of credit worth Rs. 8355078.40 (Minus) as listed in Schedule 'A' Part - XXXIII (Sec-B) Note : Tenderers will not quote against this item being a firm amount at present. Contract Sum will be worked out after deducting the credit schedule amount during acceptance of tender.
Varindera Constructions Limited
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.12 MB
Download all tender documents and submit your bid