Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.7 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹28.0 L+₹1.7 L (6.61%)Rejected-Finance 361 D SHAKTI NAGAR NEAR KHAN DAIRY INDIRA NAGAR LUCKNOW 226016 | LUCKNOW | LUCKNOW | UTTAR PRADESH | 226016 | L2 | Rejected-Finance Being L2 | |
| 3 | L3₹29.3 L+₹3.0 L (11.6%)Rejected-Finance | L3 | Rejected-Finance Being L3 | |
| 4 | L4₹30.4 L+₹4.1 L (15.7%)Rejected-Finance | L4 | Rejected-Finance Being L4 | |
| 5 | L5₹30.7 L+₹4.5 L (17.1%)Rejected-Finance 307 SADAR BAZAR LUCKNOW UP 226002 | LUCKNOW | UTTAR PRADESH | 226002 | L5 | Rejected-Finance Being L5 |
Tender Value
₹38 L
EMD Value
₹76,000
Closing Date
24 Jun 2023, 6:00 pmClosed
GE E/M Lucknow
Garrison Engineer E/M, 36 LBS Marg, Lucknow Cantt, Lucknow (U.P.) PIN 226002
REPAIR/MAINT OF DISTR PANEL INCL LT SWITCH GEAR, EARTHING, TIMER PANEL, LT POLES, POLE BOX, STREET LIGHTS, LT DISTRIBUTION NETWORK AND CONNECTED ITEMS AT GGS MARG, AFMSD AND VARIOUS LOCATIONS AND ADJOINING AREA UNDER GE E/M LUCKNOW
2023_MES_599649_1
GE/EM/LKO/EXT(ELECT)/T-14 OF 2023-2024
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Lucknow
As per NIT
8 documents required · 8 mandatory
₹500
GE E/M Lucknow
₹76,000
Yes
12 Aug 2023
30 May 2023
26 Jun 2023
30 May 2023
24 Jun 2023
19 Jun 2023
Amount
Supply and fixing bollard light 1 mtr long 15 - 20 watt LED Bollard light having epoxy powder coated pressure die cast aluminium housing Light optic /Diffuser - High impact polycarbonate/Optic colour temprature 5700K CRi>70,THD<10% PF >.90 surge protection 4KV inbuilt ,Rated voltage and frequency 240 Volt,50 Hz street furniture with touch if aesthetic innovative design with uniformly lit diffuser at the upper portion acts a beacon of path guidance in a landsscape IP 65 environmental complete with foundation work nut,bolt and washer etc complete all as specified and directed.
Supply and fixing in replacement of 60 W LED Street light fitting having epoxy powder coated pressure die cast aluminium housing front cover with polycarbonate lens with silicon gasket, with elegantly designed heat sink for efficient thermal management, sturdiness & excellent corrosion resistant.IP lens for better distribution and toughened glass fixed to housing with screws , street light should have IP 66 protection and impact resistance of IK 07 , Lumen efficiency of LED not less than 110>_ lumen per watt system efficency ,power factor >0.95, THD<10% at Full load CRI> 70% ,Street light should have built in potted DriverTHD, open circuit protection , over voltage protection , surge voltage protection 5KV in built & 10KV SPD , and provided with company LOGO ingraved on housing of the Street light complete including taking down of old UNSV fittings complete all as specified and directed. Note :-The contractor should take approval of techincal specification of luminaries and driver from department before procurement .
Supply and fixing in replacement of 90 W LED Street light fitting having epoxy powder coated pressure die cast aluminium housing front cover with polycarbonate lens with silicon gasket, with elegantly designed heat sink for efficient thermal management, sturdiness & excellent corrosion resistant.IP lens for better distribution and toughened glass fixed to housing with screws , street light should have IP 66 protection and impact resistance of IK 07 , Lumen efficiency of LED not less than 110>_ lumen per watt system efficency ,power factor >0.95, THD<10% at Full load CRI> 70% ,Street light should have built in potted Driver THD, open circuit protection , over voltage protection , surge voltage protection 5KV in built & 10KV SPD , and provided with company LOGO ingraved on housing of the Street light complete including taking down of old UNSV fittings complete all as specified and directed. Note :-The contractor should take approval of techincal specification of luminaries and driver from department before procurement.
Supply and fixing in replacement of 45 W LED Street light fitting having epoxy powder coated pressure die cast aluminium housing front cover with polycarbonate lens, with elegantly designed heat sink for efficient thermal management, sturdiness & excellent corrosion resistant.IP lens for better distribution . street light should have IP 66 protection and impact resistance of IK 07 , Lumen efficiency of LED not less than 100>_ lumen per watt system efficency ,power factor >0.95, THD<10% at Full load CRI> 70% ,Street light should have built in potted IP 66 electronic LED driver with APFC, lower THD, open circuit protection , over voltage protection , surge voltage protection 5KV in built & 10KV SPD , and provided with company LOGO ingraved on housing of the Street light complete including taking down of old UNSV fittings complete all as specified and directed. Note :-The contractor should take approval of techincal specification of luminaries and driver from department before procurement .
Supply and fixing in replacement of 120 W LED flood light fitting having epoxy powder coated pressure die cast aluminium housing front cover with polycarbonate lens with silicon gasket, with elegantly designed heat sink for efficient thermal management, sturdiness & excellent corrosion resistant.IP lens for better distribution and toughened glass fixed to housing with screws , flood light should have IP 66 protection and impact resistance of IK 07 , Lumen efficiency of LED not less than 110>_ lumen per watt system efficency ,power factor >0.95, THD<10% at Full load CRI> 70% ,Street light should have built in potted IP 66 electronic LED potted driver with open circuit protection , over voltage protection , surge voltage protection 5KV in built & 10KV SPD and provided with company LOGO ingraved on housing of the flood light complete including taking down of old UNSV fittings complete all as specified and directed. Note :-The contractor should take approval of techincal specification of luminaries and driver from department before procurement
Supply and fixing bollard light 60 cm long 10 - 12 watt LED Bollard light having epoxy powder coated pressure die cast aluminium housing Light optic /Diffuser - High impact polycarbonate/Optic colour temprature 5700K CRi>70,THD<10% PF >.90 surge protection 4KV inbuilt ,Rated voltage and frequency 240 Volt,50 Hz street furniture with touch if aesthetic innovative design with uniformly lit diffuser at the upper portion acts a beacon of path guidance in a landsscape IP 65 environmental complete with foundation work nut, bolt and washer etc including taking down old and unsv existing fitting, complete all as specified and directed.
S&F Post top energy saving 240V,50Hz AC, environmental friendly, aesthetically designed electronic constant current,IK07, having epoxy powder coated pressure die cast aluminium housing Top cover spun Al sheet powder coated,front cover Clear acrylic diffuser with indirect symmetrical light distributio, IP-65 luminaire with high power LED as light source of capacity 40 Watt, 5700K PF >0.9, THD<10% and light efficiency 85>_ ,CRI > 70,Surge protection 5KV incl dismentling taking down unsv fitting any type complete all as specified and directed.
Supply and fixing security light Bracket made out of galvanised steel light grade pipe of 40mm dia 1.5 mtr long bend to an angle of 120 degree with 02 Nos clamp made out of 50mm x 5mm flat iron and 06 sets of nuts, bolts and washers painting with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed. Note - including taking down old and unsv.
Supply and fixing street light junction box of size 200mm x 140mm x 95mm outdoor type, weather proof, factory made out of PVC SMC sheet 1.8mm thick with front side hinged opening having locking arrangement with nuts & bolts & arrangement for incoming and out going cable/wire complete comprising with the followings :- (a) Bus bar with four aluminium strips, 100 Amps capacity insulated with insulators, including colour coding, including PVC cable of suitable size from bus bar to MCB (b) MCB SPN 5 to 30 Amps - 01 No (c) 02 Nos Clamps made out of 25mm x 3mm flat iron duly welded with nuts & bolts complete all as specified and directed. Note - including taking down old and unsv.
M&L for 15mm dia galvanised iron, light grade, ISI marked, complete with all fittings fixed to pole with fixing arrangement including clamps, nut and bolts of suitable size complete all as specified and directed.
S&F PVC insulated, PVC sheathed twin core 1100 volts grade, 4 sqmm aluminium stranded conductor from OH conductor or from junction box to street/security light complete all as specified and directed.
S&F 1100 volts grade heavy duty twin core cable PVC insulated with stranded aluminium conductor of size 6 sqmm and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension GI wire from pole to pole complete all as specified and directed.
Supply and installed steel tubular swaged pole type 410 SP - 31 (9 mtr long) complete with MS base plate of size 300x300x6mm thick at bottom, welded at the centre with through hole of 14mm dia at a height of 300mm above the coping finial cap and painted with two coats of aluminium paint over a coat of red oxide primer with writing number including excavation upto required depth, PCC type C-2 1:3:6 (using 40mm graded stone aggregate) at bottom, PCC type B-1 1:2:4 (20mm graded stone aggregate) for mass filling and pole coping (60x60x30cm) and rendering of coping with 5mm thick in 1:3 cement mortar including taking down old and unsv existing pole, complete all as specified and directed.
M & L for PCC 1:4:8 type D2 using stone aggregate of 40mm nominal size in foundation concrete for pole/strut complete all as specified and directed.
M & L for PCC 1:3:6 type C2 using stone aggregate of 40mm nominal size in foundation concrete for stays complete all as specified and directed.
M & L for PCC 1:3:6 type C1 using stone aggregate of 20mm nominal size in foundation concrete for coping of poles complete all as specified and directed.
Supply and errection in of 05 mtr continuously tapered hot dip galvanised Octagonal cross sectional pole with single dipping method having bottom 130 mm A/F and top 70 mm A/F 3 mm thick confirming to ASTM A 572 Gr with yield 450 mpa cut and folded to form an octagonal section and welded in accordance with AWS for wind loading as per IS 875 part 3 1987.Poles shall be provided with base plate of size 225x225x12 mm which shall be free from any lamination or incursion with no cutting or welding on the pole after hot dip galvanising with single arm 1000 mm long bracket tilted to 150 degree from horizontal toward vertices suitable for mounting on the octagonal pole, of company recommendation and one no TPN Connecton 3 phase 4 wire 100 Amps, and one number MCB SP 6 Amps. A triangular flat MS plat of 6mm thick duly coated with GI shall be welded between cap of the octagonal pole and bracket. Welding work shall be done 250mm on bracket and 150 mm on pole's cap including all RCC work type (1:2:4) type B-1 as per pole manufacturer's drawing and earth work all as per requirement including taking down old and unsv existing pole complete all as specified and directed.
Supply and errection in of 07 mtr continuously tapered hot dip galvanised Octagonal cross sectional pole with single dipping method having bottom 130 mm A/F and top 70 mm A/F 3 mm thick confirming to ASTM A 572 Gr with yield 450 mpa cut and folded to form an octagonal section and welded in accordance with AWS for wind loading as per IS 875 part 3 1987.Poles shall be provided with base plate of size 225x225x12 mm which shall be free from any lamination or incursion with no cutting or welding on the pole after hot dip galvanising with single arm 1000 mm long bracket tilted to 150 degree from horizontal toward vertices suitable for mounting on the octagonal pole, of company recommendation and one no TPN Connecton 3 phase 4 wire 100 Amps, and one number MCB SP 6 Amps. A triangular flat MS plat of 6mm thick duly coated with GI shall be welded between cap of the octagonal pole and bracket. Welding work shall be done 250mm on bracket and 150 mm on pole's cap including all RCC work type (1:2:4) type B-1 as per pole manufacturer's drawing and earth work all as per requirement including taking down old and unsv existing pole complete all as specified and directed.
Shifting/Removing and refixing of LT pole 9 mtr from one place to another places of entier Cantt area , including necessary excavation and earth work , PCC 1:4:8 type D2 in foundations below pole, PCC 1:3:6 type C2 around poles and PCC 1:3:6 type C1 as in plinth block all RCC work type (1:2:4) type B-1 as per existing RCC of octagonal pole 5/7 mtr and required nut bolt as per site requirement, disposal of surplus soil to a distance not exceeding 50 m and depositing where complete all as specified and directed.
S&F LED lamp 10 watt, CDL, B-22 cap, (Pin type), 230V, PF-0.95 (min) incl dismentling taking out unsv CFL, complete all as specified and directed.
S&F GI Pipe light grade 40 mm with all fitting such as clamp nuts bolt washer etc laid in trenches / under road / path /bollard light, Post top lantern fittings etc complete all as specified and directed.
All as per item No 21 above but 50 mm
All as per item No 21 above but 80 mm
M&L for painting of steel tublar/rail pole 09/11 meter long with silver aluminium paint of two coat after preparing surface & Marking number on pole with black paint complete all as specified and directed.
M&L for earthing complet with galvanised steel earth plate electrode 600x600x6mm thick burried directly in ground earth pit not less than 2.25m in deep below ground level with top edge of the plote not less than 1.5m deep below normal ground level connected to and incl 32x6mm dia galvanised strip as earth strip by means of bolts, nuts, checknuts and washers of galvanised iron or steel all as specified in electrical plate No 5 of SSR (1991) part-I incl 15mm bore GI pipe for protection upto 5 mtr length and PCC 1:2:4 type B-1 as in pit excavation and earth work in any type of soil charcoal common salt and 20mm bore galvanised medium grade steel tubing for watering with one end fixed with cast iron fixing and wiremesh and testing on complete all as specified and directed.
Supply and fix single automatic street light switch suitable for 3KW load complete with two numbers infrared sensor based NATURE SWITCH for automatic switching of street/security lights with one number two pole power contractor 40 Amps (Type MU40-2P,Cs90119) with coil voltage 220/240 V and incoming MCBs single pole - 01 No, out going MCBs single pole - 01 No of rating 32 Amps & circuit wiring with single core multistranded of size 10 sq mm lighting switch operation should be based on natural light lux level, Required lluminance level for switching ON is < 30 Lux. The sensor (one service and one stand by) should also have part night operation facility for 4,5,6---------11&12 hours. The sensor along with suitable power contractor (S), incoming and out going MCBs should be enclosed in a pole/wall mountable enclouser made of Rust proof, Electric shock proof,termite proof and FR grade confirming to IP66 including taking down old and unsv existing street light switch complete all as specified and directed.
Supply, installing, testing and commissioning of factory made , tested , CPRI approved powder coated LT Panel board ,cubical (Not less than 1400mmx1200mmx500mm) compartmentalized , out door type double door , plate form mounted, suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with insulated aluminium bus bars four pole installed on porcelain/SMC insulator. The panel shall be dust and vermin proof IP-54 class protection and outer shell made of of 3.15 mm CRCA MS sheet, inner shell made of 2.0 mm thick CRCA MS sheet , 50x50x6mm thick MS angle iron frame work, duly coated with zink metal coating,front and rear opening type, with apron for cable entry closing locking arrangement including internal wiring with PVC insulated solid, copper conductor FRLS cable, IS-694 marked, 1100 volts grade of appropriate size ( but not less than 2.5 Sqmm) and comprising of the following :- (a) Incoming :- (i) MCCB 4 pole , 400 Amps,50 Hz,415 Volts, 36 KA, with thermal magnetic release Adjustable type - 01 Nos (ii) Digital VAF+PF meter with RS 485 CL1 -01No (iii) CTs ratio 400/5 A ,class 1, ISI marked -01 sets of three (iv) Indicating lamp- 01 set of three (v) Four Pole , Aluminium bus bar 600 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Outgoing (i) MCCB 4 pole , 200 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release - 05 Nos (II) MCCB 4 pole , 100 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release - 02. (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level.
All as per item No 27 above but comprising with following:- (a) Incoming :- (i) MCCB 4 pole , 315 Amps,50 Hz,415 Volts, 36 KA, with thermal magnetic release adjustable type - 01 Nos (ii) Digital VAF+PF meter with RS 485 CL1 -01No (iii) CTs ratio 400/5 A ,class 1, ISI marked -01 sets of three (iv) Indicating lamp- 01 set of three (v) Four Pole , Aluminium bus bar 600 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Outgoing (i) MCCB 4 pole , 200 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release adjustable type - 02 Nos (ii) MCCB 4 pole 100 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release adjustable type - 02 Nos (iii) MCCB 4 pole 125 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release adjustable type - 01 Nos
All as per item No 27 above but comprising with following:- (a) Incoming :- (i) MCCB 4 pole , 315 Amps,50 Hz,415 Volts, 36 KA, with thermal magnetic release adjustable type - 01 Nos (ii) Digital VAF+PF meter with RS 485 CL1 -01No (iii) CTs ratio 400/5 A ,class 1, ISI marked -01 sets of three (iv) Indicating lamp- 01 set of three (v) Four Pole , Aluminium bus bar 600 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Outgoing (i) MCCB 4 pole , 125 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release adjustable type - 03 Nos (ii) MCCB 4 pole 63 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release adjustable type - 03 Nos .
All as per item No 27 above but comprising with following:- (a) Incoming :- (i) MCCB 4 pole , 250 Amps,50 Hz,415 Volts, 36 KA, with thermal magnetic release adjustable type - 01 Nos (ii) Digital VAF+PF meter with RS 485 CL1 -01No (iii) CTs ratio 400/5 A ,class 1, ISI marked -01 sets of three (iv) Indicating lamp- 01 set of three (v) Four Pole , Aluminium bus bar 600 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Outgoing (i) MCCB 4 pole , 125 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release adjustable type - 05 Nos
Eco Creations
MTR GROUP & COMPANY
Prime power system
M/s Vatsh Raj and co
Diamond Electric Co.
OM NAMAH SHIVAY ENTERPRISES
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .