| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.2 LAccepted-AOC | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹19.8 L+₹28,115.31 (1.44%)Rejected-Finance | L2 | Rejected-Finance HIGHER THEN L1 BIDDER | |
| 3 | L3₹19.9 L+₹38,973.99 (2.00%)Rejected-Finance | L3 | Rejected-Finance HIGHER THEN L1 BIDDER |
Tender Value
₹20.5 L
EMD Value
₹41,000
Closing Date
21 Apr 2023, 6:00 pmClosed
CWE
HQ 136 WORKS ENGINEERS PIN - 914136 C/O 99 APO
REPAIR/REPLACEMENT AND IMPROVEMENT OF OVER HEAD CONDUCTOR,UG CABLE AND ALLIED EXTERNAL ELECTRIFICATION WORKS AND STREET LIGHT /SECURITY LIGHT AND ALLIED WORKS AT LEBONG AND JALAPAHAR UNDER AGE(I) DARJEELING
2023_MES_579116_2
CWE/136-WE/60 OF 2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Darjeeling
Class E, Category b(ii)
9 documents required · 9 mandatory
₹500
AGE (I) Darjeeling
₹41,000
8 May 2023
30 Mar 2023
22 Apr 2023
30 Mar 2023
21 Apr 2023
8 Apr 2023
30 Mar 2023 - 4 Apr 2023
Amount
Disconnecting the electric supply, taking down the old u/s Disc insulator and Supply & Fixing Disc insulator single disc 11 KV grade porcelain vitreous brown or green 145mm high and 255 mm dia complete all as as directed. .
Disconnecting the electric supply, taking down the old u/s pin type insulator and Supply & Fixing pin type insulator 11 KV grade porcelain vitreous brown or green insulator including one galvanised iron washer and one nut 150mm high and 150 mm dia including taking out old unserviceable one complete all as as directed.
M&L for Cable jointing kit for 11 KV (earthed) grade cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 Sqmm including taking out old u/s one complete all as directed.
All as per item No 3.00 here- in- before but size 120 to 185 Sqmm complete all as directed.
M&L for Cable jointing kit for Eleven KV (earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 Sqmm including taking out old u/s one complete all as as directed.
All as per item No 5 here- in- before but size 120 to 185 Sqmm complete all as directed. Note: Earth work shall be measured and paid separately.
M&L for Cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 Sqmm including taking out old u/s one complete all as directed
All as per item No 07 here- in- before but size 120 to 185 Sqmm complete all as directed. Note: Earth work shall be measured and paid separately.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in hard/ dense soil for foundation of poles, structures, stay rods, laying of underground cable etc complete all as as directed.
Excavation in trenches not exc. 1.5M wide and exc.1.5M & upto 3.0M tin depth for foundation of stay/ pole and etc and getting out in hard/dense soil complete all as specified and as directed.
Returning, filling in soils including spreading, leveling, watering and well ramming in layers each not exceeding 25cm thick complete all as as directed.
Removing excavated soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as as directed.
M&L for sand cushioning for protection of PVC cable with approved sand of uniform thickness, laid dry, by filling in trenches and punning to proper required cover all as directed.
M&L for laying un-reinforced precast concrete cable cover, class HV , type 1 with , size 300 mmX180mmX 40mm complete all as directed.
M/L for cement concrete in foundation (1:4;8) type D2 using 40 mm graded broken stone aggregate for base of foundation complete as specified
M/L for cement concrete in foundation (1:3;6) type C2 using 40 mm graded broken stone aggregate including form work complete as specified
PCC (1:2:4) type B1 (using 20mm graded stone aggregate) as in coping including necessary formwork complete all as specified and as directed.
Supply and lay GI tubing 100 mm dia, light grade for cable protection at road crossing / on poles and tubing sealed at both ends after laying the cables complete all as directed.
Supply and lay GI tubing 80 mm dia, light grade for cable protection at road crossing / on poles and tubing sealed at both ends after laying the cables complete all as directed.
Supply, lay, connect test and commissioning of 3 core, 95 Sqmm, 11000 Volts grade(Earthed) XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminum conductor laid in trench/under ground/wall/surafce/tunnel/duct including taking out unserviceable burnt out cable complete all as directed.
Supply, lay, connect test and commissioning of 3 core, 120 Sqmm, 11000 Volts grade (Earthed)XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminum conductor laid in trench/under ground/wall/surface/tunnel/duct including taking out unserviceable burnt out cable complete all as directed.
M&L for Supply, test, erection & commissioning of Steel tubalar swaged poles staying in a truely vertical position till the foundations are properly set with the help crane complete with cast iron base plate, finial taper plug, bolts, nuts & screws including drilling of holes to poles for clamps & hooks for running of earth wire/Strip complete all as specified type 410 SP-55,11 mtrs HT poles complete all as as directed. . Note:-(i)Crane charges for erection shall be deemed to be including in quoted rate. (ii) Earth work,PCC,coping shall be measured and paid separately. (iii) The rates include staying the poles in atruely vertical position till the foundations are properly set. (iv)The rates include cast iron base plate,nuts,bolts,screws,painting of steel tubular poles,drilling of holes in steel tubular poles for fixing of clamps,hooks for continuous earth wire/strip.
Supply, test, install & commissioning of HT 11 KV outdoor type gang operated air break switch triple pole mechanically operated suitable for horizontal or vertical mounting(suitable for existing one) on insulator and steel frame with operating mechanism worked from ground level for current rating up to 400 Amps and connecting up with jumpers, testing and commissioning including dismantling/disconnecting & taking down the old unserviceable one complete all as as directed.
M&L stay assembly comprising of MS stay plate 6 mm thick and of size 300 x 300 mm and 20 mm dia MS stay rod, 2150 mm long including thimbles GI stay strand 7/3.15 mm dia of required length complete all as shown on electrical plate No.1 on page No.495 of MES Part-I 2009 including necessary excavation PCC 1:3:6 Type C2 (using 40mm graded stone aggregate), loop insulator as specified in and including taking down old unserviceable one complete all as as directed.
M&L for loop type insulator, vitreous porcelain, white, brown or green, large size with overall dimensions 90 x 140mm size, clearance of hole 25.5 mm complete all as specified and as directed.
M&L of cross arms i.e bracing supporting clamps back plates, nuts, bolts and washers complete including one under coat and one finishing coat with synthetic enamel paint over a coat of red oxide primer & including taking down old unserviceable complete all as directed. .
M&L ACSR jumpers in HT/LT over head line upto 10 mm dia as that of existing size including binding wire, nuts & bolts washers complete all as as directed.
M&L of danger notice plate of 1.6mm thick mild steel sheet vitreous enameled white, with letters, figures and convention skull and bones in signal red colour and fixed with MS clamps bolts and nuts of approved size for HT 11 KV of size 25 x 20 cm complete
M&L for Cradles, hexagonal/rectangular fabricated with galvanised steel 4mm dia & including taking down old unserviceable complete all as specified and directed .
M&L for ACSR conductor, steel reinforced for LT / ht over head lines on poles including streching tightining of poles insulator with binding wire of suitable size with insulator/streching of ACSR conductor including disconnecting/taking out old existing unsv ACSR conductors complete all as specified and directed.
Cutting anxious green growth / vegetation growth for cleaning out the area around transformer/ all other installations and four pole structure yards at ground level by cutting out roots, un wanted plants bushes and removal of the same by surface excavation not exceeding 30 cm deep average 15 cm complete.
Surface excavation not exc 30 cm deep and averaging 15cm deep and getting out HARD / DENSE soil
M&Lfor shingle filling in floors or pavings of Gauge 90 to 40 mm, deposited, spread and levelled in layers not exc. 150mm thick, watered and rammed to a True Surface, complete all as specified and as directed.
M&L for Galvanised iron strip 32 x 6mm buried in ground for Earthing connection purpose complete all as specified and directed
Preparation of old painted surface removing of rust from any kind of steel surface, clamps etc for of any description and repainting by 1st quality Synthetic enamelled paint one coat over a coat of red oxide zinc chromate primer complete all as specified and directed.
Preparation of old painted surface of brick/stone/plaster surface and painting by one coat of 1st quality Synthetic enamelled paint, over a coat of priming paint plaster coat complete all as specified and directed.
M&L PCC 1:3:6, type C-1 (using 20 mm graded crushed stone aggregate) in foundations, filling and mass concrete complete all as specified and directed.
M&L for Disconnecting the electric supply and Servicing of 11 KV AB switches upto 400Amps by disconnecting,overhauling,greasing and re-assembling same in its original existing postion, testing & commissioning including complete all as as directed. Note: Male/female contacts shall be measured and paid separately under relevant items.
Supply only Male contacts suitable for 11 KV Air Break switch including taking down old u/s item complete all as as directed. .
Supply only Female contacts suitable for 11 KV Air Break switch including taking down old u/s item complete all as as directed.
Disconnecting the electric supply and taking down the broken unserviceable post top insulator and S&F post top porcelain insulator vitrous brown with GI clamp nuts bolts etc suitable for 11000 Volts grade working pressure complete all as as directed.
M&L for Replacement of air breather with filled silica gel suitable for any make of tranformer rating up to 400 KVA mounted on plinth/pole including taking out old u/s one complete all as as directed.
Supply and filling of transformer oil in transformer plinth / pole mounted including testing insulation and vescocity of oil all as specified and directed .
M&L for Dehydration including filtration cleaning of transformer oil in transformer indoor/ outdoor type by centrifusion / machine having minimum capacity 1000 to 30000 ltrs/ hrs including testing insulation and vescocity of oil before and after dehydration complete all as directed. .
M&L for Shifting of the any make of transformer rating up to 400 KVA mounted on plinth/pole from existing location to new location and existing transformer vice versa, including removing and reconnections of HT/LT side, jumper / cable connection, control cable connection of both transformers including testing and commission complete all as as directed. . Note:- (i) The rate quoted is deemed to be inclusive of necessary crane / vehicle charges for shifting and installation of the transformer.
Dismantling HT pole of any height by taking out from PCC foundation complete and shifting to other location as directed including fixing the pole in true vertical position including excavation and earth work, PCC 1:4:8 type D2 (using 40mm graded stone aggregate) as base concrete and PCC 1:3:6 type C2 (using 20mm graded stone aggregate) in both foundation and coping of poles all as specified in Part I-2009 and applying two coats of aluminium paint to pole surface complete all as directed.
Inspection of defective 11kv HT cable(laid in UG/trench/tunnel/wall/surface) to locate the fault using cable fault Locator machine(by surge generators mounted on Van) (fault either by Short/Moisture/earth fault or any type) including complete all as as directed.
M&L for cleaning/Painting the HT poles of OH lines and HT Four poles/two poles and single pole structure complete with cross arms any height and any description thoroughly with necessary cleaning agent including scrapping up of old corroded paint dirt/dust/rust carefully and applying two coats of synthetic aluminum paint including marking and colour washing of pole coping details as are under :-
Two poles with cross Arms
Four Poles with cross Arms
Single HT 11mtr Pole with cross Arms
M&L for Spray painting of upto 400 KVA transformer pole mounted / plinth mounted at site and applying two coat of synthetic enameled Smoke grey paint after removing all dust & rust and paint shall confirm to IS 2032 including marking or transformer capacity with stencil letter with black or white paint and Font and Size of letter shall be as directed. , complete all as specified and directed.
Maintenance of earthings of installations like cleaning of earth pits, treatment of earthing by puring salt water, replacement of perished wire mesh, unserviceable funnel etc all as directed.
Restreching/Restringing, tightening and repair to overhead line ACSR conductor of any size on LT poles including necessary Aluminium binding wire connectors PVC sleeves for jumper, fixing of insulators and prunning of tree complete all as specified and directed.
Dismantling and taking out existing Expulsion fuse unit single pole 11 KV channel mounted complete including supply and fix for new Expulsion fuse unit single pole 11 KV, above 50 & 100 amp channel mounted complete.
Cutting and trimming trees branches any girth and any size touching to overhead lines and cleaning the distance 1.5 mtr length both side of OH line with in a span of 50 mtrs each disposing the same, clearing the site all as directed.
Taking out and Relaying of HT 11 KV cable of size 95 sq mm to 150 Sqmm 3 core after carrying out necessary Repair such as joining with Epoxy joint and laid with sand Cushioning and brick protection and making connection By using Lugs all as specified and directed . Note: (a) Earth work , sand Cushioning, brick protection, Joints shall be measured and paid separately under Relevent Item) (b) Retrived serviceable bricks/ PCC cover shall be reused under relevent item)
Relaying of serviceable bricks / pcc cover of any size retrived during taking out of HT cable complete all as directed
Supply and fixing cable route indicator for HT UG Cable of 11000 Volts bolted with 40 x 6 mm flat iron member of height 0.60 mtr, and 80 mm dia CI plate embedded in PCC 1 : 3 : 6 type C2 of size 20 x 20 x 30 cm block complete all as specified and directed.
Supply of Rubber mat ISI marked of size 1mX2mX20mm
Replacment / Renewal of Silica gel for filling in existing air breather by removing old one
Arresting leakage of transformer fins by brazing / welding etc, after removing of oil from inside of transformer and refilling of oil by opening top cover of transformer of capacity upto 500KVA
M&L in replacement of GOD operating GI pipe 25mm dia upto 7.5 mtr long with clamp, nut, bolts, washers and necessary operating handle, complete, all as specified and directed.
Supply & Replace MCCB along with both side spreader link and nut bolts of appropriate size (Conforms to IEC:60947-II/IS:13947-II) in exisitng LT Panel box/Feeder Pillar boxes (KIOSK),in MCCB DBs of capacity 315-400 Amps, 4 pole, 25 KA capacity 315-400 Amps, 4 pole, 25 KA, 415 Volt including disconnecting/taking out existing old unsv/burned MCCB complete all as specified and directed.
All as per item No-64 here in before but of capacity 200 Amps, 4 pole, 25 KA
All as per item No-64 here in before but of capacity 160 Amps, 4 pole, 16KA
Supplying, erecting and fixing steel tubular swaged poles with cast iron base plate of size 300mm x 300mm x 6mm, finial taper plug, bolts, nuts & screws for type 410 SP-31 (9.0 mtrs long) including painting with two coats of aluminium paint over one coat of red oxide primer on all exposed surfaces and tarring with black bituminous paints to embedded portion in PCC and providing 3 Nos of 30cm wide circular bands with black & yellow paint starting from plinth level at a gap of 30 cm in between 2 bands and numbering of poles, in yellow paint over black painted back ground at a height of 2m from bottom of pole with 5 cm large bold letters 2" (inch) wide including taking down old unserviceable PCC poles of any type complete all as specified and directed. Note: Excavation, earth work, PCC in foundation and coping shall be measured and paid separately under relevant item of this schedule.
M&L for attending, repair and rectification of external LT electric supply complaints on up to 1100 Volts grade, over head/underground system alongwith necessary T&P, safety devices as per site requirement for the following type of complaints complete all as specified and directed:-
Replacement of worn out jumpers, jointing and tightening with new ACSR conductor. Note:- Single phase/two wire or 3 phase/4 wire system will be considered as one job for payment purpose.
Disconnecting from over head conductor/ conductor on panel/ FPB, cutting worn out portion of LT cables of any type and size, carry out repairs including taking out cables from under ground loop line and rejoining the same to restore electric supply. Note :- (i) LT Jointing Kits, Cable protection Pipe if required at site will be measured and paid separately. (ii) Quoted rate is deemed to be inclusive of lugs/ sockets and cutting and removing the pole coping and inserting the cable alongwith protection pipes.
Taking down old unsv Street light / flood loght fittings in any position of any capacity for Repair by replacement of unsv spares ( SPD / Driver / Mcpcb etc ) and re-fixing the same in existing locatin. Note:- Spares for repair of street light fittings will be measured and paid under respective items.
Notes: (a) The contractor will be allotted complaints at MES complaint cell on daily basis on all working days and sufficient resources will be deployed by him/her for completion of day to day complaint within 24 Hrs from the time of reporting. (b) The contractor will intimate MES authority well in advance if electric shutdown is required during rectification of complaints. (e) The quoted rate is deemed to be inclusive of transportation and other expenses required for the resource deployment at the complaint site around scattered Military station.
Restreching/Restringing, tightening and repair to overhead line ACSR conductor of any size on LT poles including necessary Aluminium binding wire connectors PVC sleeves for jumper, fixing of insulators and prunning of tree complete all as specified and directed. Notes: (i) The distance between pole to pole in one span (contains 2/4/6 runs) i.e one span will only be considered for payment purpose. (ii) No Extra conductor will be measured for binding to insulators / jumpering etc.
M&L for painting the existing LT steel poles of 9.0 Mtr long including cross arms, clamps, street light junction boxes etc with 1 coats of aluminium paint including throughly cleaning the existing surface, writing of pole numbers in yellow circle 15 cm with black paint on poles. Painting the poles up to 1.5 Mtr height with alternate bands 30 cm height (3 Nos black and 2 Nos Yellow) from ground level, complete all as specified and directed.
Cutting unaxious green growth shrubs,branches and grass by manual labour or by machine at all Installation premisses/around and along the boundary / fencing along the pipe line , along the cable route etc. and removing rubbish from the site of work complete all as specified and directed.
Supply, fixing, connecting and testing post top light fitting in spherical shape polycarbonate PMMA clear diffuser and IP65 protection, new generation energy saving and environmental friendly long life aesthetically desinged aluminium decorative luminaires with high power LED as light source of capacity 1X35/40 watts, fixed to Pole/Wall in any position including taking down old existing street light fitting of any type and capacity complete all as specified and directed.
Supply only LED Driver of similer wattage with operating voltage input ac 85- 300 volt , pf> .95 as per IS 15885 with inbuilt surge protection of minimum 5 kv and BIS crtified suitable for 60 watts LEDstreet light fittings of any make complete all as specified and directed.
Supply only LED Driver of similer wattage with operating voltage input ac 85- 300 volt , pf> .95 as per IS 15885 with inbuilt surge protection of minimum 5 kv and BIS certified suitable for 70/72 watts LEDstreet light fittings of any make complete all as specified and directed.
Supply only LED Driver of similer wattage with operating voltage input ac 85- 300 volt , pf> .95 as per IS 15885 with inbuilt surge protection of minimum 5 kv and BIS crtified suitable for 90 watts LEDstreet light fittings of any make complete all as specified and directed.
S&F LT line rigid PVC Spacers spiral type, two lines, Phase to phase distance 300 mm, spacer rod dia 13 mm, spiral hole dia 5-6 mm and spiral length 250 mm.
Dismantling of damage / broken coping of steel pole of any size anf and removing the debries from site complete all as specified and directed.
Dismantling LT steel tubuler pole of any height by taking out from PCC foundation complete and shifting to other location as directed including fixing the pole in true vertical position including excavation and earth work, PCC 1:4:8 type D2 (using 40mm graded stone aggregate) as base concrete and PCC 1:3:6 type C2 (using 20mm graded stone aggregate) in both foundation and coping of poles all as specified in Part I-2009 and applying two coats of aluminium paint to pole surface complete all as directed.
S&F On-Load changeover switch (In sheet steel enclosure), AC 21 (Side Handle), 4 pole of capacity 200 Amps, 415 Volts, 50 Hz, Conforms to HSN Code : 8536 complete all as specified and directed.
S&F On-Load changeover switch (In sheet steel enclosure), AC 23 (Side Handle), 4 pole of capacity 100 Amps, 415 Volts, 50 Hz, Conforming to relevant IS complete all as specified and directed.
S&F On-Load changeover switch (In sheet steel enclosure), AC 23 (Side Handle), 4 pole of capacity 63 Amps, 415 Volts, 50 Hz, Conforming to relevant IS complete all as specified and directed.
S&F in relacement of 40mm dia steel tubes (light grade) galvanised with fittings, laid in trenches/wall/pole for protection of underground cable when crossing the road complete all as directed.
S&F in relacement of 20mm dia steel tubes (light grade) galvanised with fittings, laid in trenches/wall/pole for protection of underground cable when crossing the road complete all as directed.
S&F in relacement of 15mm dia steel tubes (light grade) galvanised with fittings, laid in trenches/wall/pole for protection of underground cable when crossing the road complete all as directed.
Supply & fix in Replacement street light fitting LED type not less than 90 watts with Pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having TOP Opening seperate driver compartment with IP66 protection and including driver unit etc and taking down old unsv any size/watt of security light all as directed .
S&F bldg security light fitting LED not less than 30 Watt for Energy saving and environmental friendly long life made up of pressure die cast aluminium housing with acrylic cover as diffuser with IP-66 protection and Impact resistance of IK07 including driver unit etc and taking down old unsv any size/watt of bldg security light all as directed .
Supply & Fix in Replacement LED Garden light fitting not less than 10 Watts, IP65 rated inverted pyramid tripod type and including driver unit etc and taking down old unsv any size/watt of garden light all as directed .
Supply & Fix in Replacement LED Decorative Post top lartan light fitting not less than 40 Watts,IP65 protection and including driver unit etc and taking down old unsv any size/watt of Post top lantern light all as directed .
Supply & Fix in Replacement LED Flood light (not less than 70 watt) fitting ,IP65 protection and including driver unit etc and taking down old unsv any size/watt of flood light all as directed .
Supply and fix in replacement of FRP looping box of size not less than 155x210x95 mm (HWD) with fuse/6 amps MCB provision and suitable connector for single phase connections loop in and out 10 to 16 sqmm 2 core aluminium armoured cable branch out 1.5 sqmm single core copper pvc insulated cable enclosed in thermoplastic /polycarbonate enclosure which should be shock proof safe IP 66/67 thermoplastic metric size glands ,GI clamps made out of GI flat of size 25mmX 3mm channel including making connections, takng down of old FRP box all as specified and directed .
Supply and fix in replacement of driver unit suitable for street light 90 Watt including making connections as directed .
Dismantling/uprooting of steel poles of any size and shapecomplete all as specified and as directed..
M&L for Multistandarded Copper Conductor cable of 3 Core 1.5 Sq mm size drawn through steel tubular poles for interconnection of cable looping box to Street Light Fitting, Post Top Lantern & etc taking down old unsv cable all as directed.
Dismanting and taking down the existing defective street light fitting of any type and any capacity LED street light from steel tubular pole ,opening the street light fitting ,checking the serviceability , remove the cable carbon and replcaement of 3 core 1.5 sqmm size multi stranded copper conductor including taking down old unserviceable 3 core 1.5 sqmm size copper conductor complete all as directed by Engr-in - charge( Note- 3 core 1.5 sqmm size multistranded copper conductor etc will be measured and paid separately in respective item of schedule A here in after.)
Note 1:- (Applicable for all parts/items) : The biidders/contractors are advised to read tender document, all drawings & all corrigendum/ amendments and general condition of contracts before entry/quoting the rates. Note 2:- Attention to bidder is hereby invited to upload revised BOQ if published during their bid submission. Uploading of incorrect/ pre-revised BOQ shall be treated as non bonafide and rejected.
GEETA CONSTRUCTION
Darjeeling Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .