Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.7 LAccepted-AOC | L1 | Accepted-AOC Accepted being L1 | |
| 2 | L2₹16.4 L+₹74,175 (4.73%)Rejected-Finance C O S 1 ESS GEE COMPLEX NEAR J K BANK SONAWAR BAZAR B B CANTT SRINAGAR 190004 J K | SRINAGAR | SRINAGAR | JAMMU AND KASHMIR | 190004 | L2 | Rejected-Finance Rejected being L2 | |
| 3 | L3₹16.9 L+₹1.2 L (7.57%)Rejected-Finance HOUSE NO 251 E BLOCK ADARSH NAGAR BALLABHGARH FARIDABAD 121004 HARYANA | FARIDABAD | FARIDABAD | HARYANA | 121004 | L3 | Rejected-Finance Rejected being L3 | |
| 4 | L4₹17.1 L+₹1.4 L (9.12%)Rejected-Finance KHUNMOH SRINAGAR PIN 191104 J K | SRINAGAR | SRINAGAR | J K | 191104 | L4 | Rejected-Finance Rejected being L4 | |
| 5 | L5₹17.4 L+₹1.7 L (10.9%)Rejected-Finance | L5 | Rejected-Finance Rejected being L5 |
Tender Value
₹19 L
EMD Value
₹38,000
Closing Date
5 Apr 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE HQ 134 WORK ENGRS
HQ 134 WORK ENGRS PIN-914134 C/O 56 APO
PROVN OF 02x63 KVA GENR SET AT LASSIPORA UNDER GE 861 EWS
2021_MES_423073_2
134 WE-81/2020-21
Open Tender
Civil Works
Item Rate
180 days
SRINAGAR
PLEASE SEE TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE 861 EWS
₹38,000
Yes
15 May 2021
15 Mar 2021
7 Apr 2021
15 Mar 2021
5 Apr 2021
17 Mar 2021
60 days
Amount
Supply, installation,testing and commissioning diesel engine driven generating set water cooled of capacity 63 KVA, 415 volts, 3 phase, 4 wire, 0.8 power factor at NTP with relay panel and switch gear for automatic starting on main failure, control panel having meters and sound proof canopy as per CPCB norms of approved make as per OEM and with necessary foundation as recommended by OEM, mounted on common base plate with flexible coupling, with and including of acoustic insulated chamber to maintain noise level as per CPCB norms for capacity of 63 KVA DG set complete in built with all accessories and totally enclosed type with silencer pipe protected with asbestos rope from engine to outside the building, 0.5 mtr and independently supported AVM pads, battery starter type foundation as per manufacturers design (Including foudation of DG set as per manifacturer size and specification ) (A) Prime Mover Vertical diesel engine of suitable capacity 63 KVA at NTP, water cooled type closed, circuit as per BS-649 or IS-10001/IS-10002, direct injection type turbo Charged , battery starting system having rated speed 1500 RPM. The DG set shall be capable of running 24 hours continuously with 10% over loading for one hour in every 12 hours run as per BS- 5514/BS-649. Engine shall be equipped with all standard fittings as per manufacture’s recommendation & mounted common plate through flexible coupling.
(i) RPM cum hour meter (ii) Battery charging ammeter. (iii) Ignition key and starting with button switch. (iv) Lubricating oil pressure gauge. (v) Mechanical / electric governor controlling. (vi) Oil temperature gauge (vii) Safety control with tripping facility for the following (a) Low lubricant oil pressure (b) Over speed (c ) High water temprature (viii) Starting equipment comprising of following:- (a) Battery as per manufacturer recommended Make :- Exide/Luminus/Amron. (b) Battery, charging alternator with inbuilt regulator. (c) Battery leads of copper cable of suitable size brass thimbles and terminals.
(B) Alternator: - Alternators rating 63 KVA, 3 phase, 50 Hz, 415 Volts, 4 wire supply at NTP 0.8 power factor running @ 1500 RPM self excited, self regulated, mounted on strong steel fabricated steel frame suitable for mounting on a permanent foundation to be coupled with above engine. The alternator shall be conforming to BS-2613 or IS-4722/13364. (C) Control Panel: Alternator control panel in built with internal copper wiring for 63 KVA alternator, 415 Volts, 3 Phase, 4 wire, 50 Hz fabricated out of 2mm thick MS sheet painted externally and internally with two coats of synthetic enamel paint over one coat of primer all as per manufacturer design including provision of following accessories: -
Excavation in trenches, not exceeding 1.5 mtr wide and not exceeding 1.5 metre in depth for laying of cables including getting out soft/loose soil complete all as specified and directed by Engr-in-Charge.
M&L Sub Class 'B' brick covering protection to the eletric cable laid dry flat transversally along the length of cable on sand cushioning with width equal to length of brick complete all as specified and directed by Engr-in-Charge.
S&F for river sand cushioning to underground cables 8cm thick before laying cable and 15cm thick after laying and streching the cable, complete all as specified and directed by Engr-in-Charge. Note :- For payment purpose punned thickness shall be measured
Returning filling in (soil) including spreading levelling, watering and well ramming in layers not exc 25cm thick complete all as specified and directed by Engineer -in-charge.
Removal of excavated soil to a distance n.exc 50 m and depositing where directed at a level not exc 1.5 mtr above the ground level/starting point compalete all as specified and directed by Engineer -in-charge.
S&F for XLPE UG cable, 1100 volts grade, PVC insulated, heavy duty, armoured, multistranded aluminium conductor cable of size 70 Sqmm 3.5 core in trenches, fixing on wall, under road crossing protection pipe etc complete all as specified and directed by Engr-in-Charge. Note:- Earth work, sand cushioning and brick shall be measured and paid separately)
S&F for XLPE UG cable, 1100 volts grade, PVC insulated, heavy duty, armoured, multistranded aluminium conductor cable of size 50 Sqmm 3.5 core in trenches, fixing on wall, under road crossing protection pipe etc complete all as specified and directed by Engr-in-Charge. Note:- Earth work, sand cushioning and brick shall be measured and paid separately)
M & L Earthing complete with GI earth plate electrode 600x600x6 mm burried directly in ground not less than 2.25 mtr deep below normal ground level with top edge of earth plate not less than 1.25 Mtr below normal ground level connected to the GI strip 25x4 mm size by means of bolts ,nuts,check nuts and washers of galvanised iron and 25 x 4 mm GI strip procted by provision of GI light grade pipe 40 mm bore incl provision of concrete pit in PCC1:2:4 type B-1 , using 20 mm graded stone aggregates with 40 mm thick cover of RCC (1:2:4) reinforced with and 6mm dia bar handle, excavation and earth work in any type of soil ,charcoal dust and salt light grade GI watering pipe 20 mm bore with funnel and wiremash and medium grade GI protection pipe 40 mm up to 5 Mtr long and GI strip upto main earthing of pole complete all as shown in electrical plate No 3 of MES Sch 2009 Part-I all as specified and directed . (i) Main earthing strip from earth plate electrode to test point upto length of 7.5 meters length shall deem to be included in the unit rate quoted against this item . (ii) On testing after completion if the desired resistenance is not obtained the contrator shall redo the earthing without any extra cost to the department .
M/S A.N CONSTRUCTIONs
national engineering
M/S HAFIZ AND SONS
NAJAR ENTERPRISES
M/S ASHRAF CONSTRUCTIONS
FG CONSTRUCTION
M/S TRADE LINK
ALCO ENGINEERSPVT LTD
M/S SUHEEL CONSTRUCTIONS
M/S Sky Engineers
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .