Loading…
Loading…
Tender Value
₹13.2 L
EMD Value
₹26,500
Closing Date
5 Oct 2026, 6:00 pm
CWE, HQ 138 WE
CWE, HQ 138 WE
PROVN OF THREE STANDALONE CENTRAL HEATING SYSTEM FOR RR BN UNDER GE 865 EWS
2026_MES_789286_1
138WE/L-104/2026-27
Open Tender
Civil Works
Item Rate
180 days
GE 865 EWS
As per Tender Documents
6 documents required · 6 mandatory
₹500
GE 865 EWS
₹26,500
Yes
14 Sept 2026
14 Sept 2026
12 Oct 2026
14 Sept 2026
5 Oct 2026
28 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing and commissioning of ductable type stand alone oil-fired kerosene/ HSD based heating system complete with stainless steel heat exchanger chamber consisting of furnace fabricated out of high temperature resistance stainless steel, automatic burner assembly control panel with sequence controller, photocell for flame failure. HT Transformer electrode fan assembly with motor temperature controller stainless steel reflector, built in fuel oil piping exhaust chimney all housed in powder coated casing suitable for operation on 50 Hz single phase 230 Volt AC supply capacity 75,000 Kilo Cal/hr including fuel container of suitable capacity with following :-
(a) Heat Output - 75000 Kilo Cal/Hr.
(b) Hot Air Temp - 40 degree Celcius
(c) Temperature Rise - 90 degree Celcius Max
(d) Fuel Consumption - 5.2 - 5.6 Ltr/Hr
(e) Thermal Efficiency - minimum 80%
(f) Electrical Supply - 220 Volts 50 Hz
(g) Temperature Control - Automatic
(h) Fuel - Kerosene/ Diesel | 3 | Each Job | - | - |
| 2 | Design, supply, fixing and testing ducting for hot air blower to room with complete insulation of the duct, complete all as specified and/or as directed by Engr-in-Charge. | 30 | Sqm | - | - |
| 3 | S&F sheet metal enclosure for DBs double door when MCB's to be used single pole & neutral 240 Volts 4 Ways, complete all as specified and/or as directed by Engr-in-Charge. | 3 | Each | - | - |
| 4 | S&F MCB SPN 40 Amp 240 Volts AC ISI marked, complete all as specified and/or as directed by Engr-in-Charge. | 3 | Each | - | - |
| 5 | S&F MCB SP 6-32 Amps. 240 Volts 50 Hz, complete all as specified and/or as directed by Engr-in-Charge. | 3 | Each | - | - |
| 6 | M&L for submain wiring along with earth wire with the sizes of FR PVC insulated copper conductor, single core cable in surface/recessed as required in PVC casing caping wire size 2 x 4.0 sqmm + 1 x 4 sqmm earth wire, complete all as specified and/or as directed by Engr-in-Charge. | 30 | RM | - | - |
| 7 | S&F sheet metal enclosure with 20 Amp 240 V socket plug top and MCBs single pole and neutral enclosure with two pin and earth plug and socket with one single pole 20 Amp MCB, complete all as specified and/or as directed by Engr-in-Charge. | 3 | Each | - | - |
| 8 | M&L for earthing complete with galvanised steel earth plate electrode 60 cm X 60 cm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of the plate not less than 1.5 meter below normal ground level, connected to and including 4 mm dia GI wire as earthing lead, by means of bolts, nuts, check nuts and washers of galvanised iron all as shown in electrical plate No 3 of MES SSR Part I and testing on completion including excavation and earth work in any type of soil, PCC (1:3:6) type C1 chamber, MS frame and cover 6 mm thick in cement concrete (1:2:4) type B1 reinforced with welded steel wire fabric or XPM (weight not less than 4 Kg per Sqm) with cast iron frame, funnel with wire mesh, GI watering pipe 20mm dia medium grade and lugs, complete all as specified and/or as directed by Engr-in-Charge. | 3 | Each | - | - |
| 9 | S&F tubes light grade of size 40 mm bore galvanised with all fittings and fixed complete to walls and ceiling or laid in floors, complete all as specified and/or as directed by Engr-in-Charge. | 10 | RM | - | - |
| 10 | Supply and laying in trenches or passing through pipe or fixed on surface XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade of size 16 sqmm 2 core, complete all as specified and/or as directed by Engr-in-Charge. | 170 | RM | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.33 MB
TenderL104202627.pdf
Tender Documents • 1.07 MB
BOQ_884769.xls
BOQ • 1.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .